| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹2.6 CrAdmitted-Finance | +10.00% | ₹2.6 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.7 CrAdmitted-Finance KERALA KL | KANNUR | KERALA | 670511 | +12.00% | ₹2.7 Cr | L2 | Admitted-Finance |
Tender Value
₹2.4 Cr
EMD Value
₹1 L
Closing Date
6 Mar 2026, 11:30 amClosed
Superintending Engineer, PWD BCC Thrissur
Office of Superintending Engineer, PWD Building Center Circle, Thrissur
The work is proposed for the construction of First floor over the existing Ground floor. Civil, Electrical, AC, Lift and Electronics works included in this work.
2026_PWD_838339_1
WD/BLDG/TR/9995/2023_23_3_2/1
Open Tender
Civil Works - Buildings
540 days
Perumbavoor
Please refer Tender documents.
19 documents required · 19 mandatory
₹9,759
Yes
₹1 L
Yes
o/o Superintending Engineer, PWD BCC TSR
11 Mar 2026
21 Feb 2026
9 Mar 2026
21 Feb 2026
6 Mar 2026
21 Feb 2026
27 Feb 2026
Building Proper(Civil work)
15.2.1:Demolishing cement concrete manually / by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in-Charge.Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
15.7.4:Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar
26.30.1:Drilling suitable holes in reinforced or plain cement concrete with power driven drill machine to a minimum depth of 100mm upto 200mm in RCC beams, lintels, columns and slabs to introduce steel bars for sunshades/balconies including fixing the steel bars in position using epoxy resin anchor grout of approved make but excluding the cost of reinforcement, all complete as per direction of Engineer-In-Charge.Upto and including 12mm dia.
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
2.26.1:Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil
4.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
2.25:Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.2:Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
5.9.6:Centering and shuttering including strutting, etc. and removal of form for:Columns, Pillars, Piers, Abutments, Posts and Struts
5.9.5:Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
5.9.3:Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
5.9.19:Centering and shuttering including strutting, etc. and removal of form for:Weather shade, Chajjas, corbels etc., including edges
5.9.16.1:Centering and shuttering including strutting, etc. and removal of form for: Edges of slabs and breaks in floors and wallsUnder 20 cm wide
5.9.7:Centering and shuttering including strutting, etc. and removal of form for:Stairs, (excluding landings ) except spiral - staircases)
OD259457/2025-2026:Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Note:- Cement content considered in this item is @ 330 kg/ cum.Cement content optained as per mix deisgn shall be used by the contractor at site to obtain the rewquired strength.There will be no additional payment for excess cement used as per designed mix seperately as per circular No.CE/BL/GL 6541/2015 Dated 30/8/2017 of CE BLDS. All work upto plinth level
OD259450/2025-2026:Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer - in-charge. Cement content optained as per mix deisgn shall be used by the contractor at site to obtain the rewquired strength.There will be no additional payment for excess cement used as per designed mix seperately as per circular No.CE/BL/GL 6541/2015 Dated 30/8/2017 of CE BLDS. ..All work above plinth level upto floor V level
5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
5.22A.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more
50.6.1.5:Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure up to floor two level thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete
50.6.2.1:Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x15 cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 15cm in: CM 1:6 ( 1 cement :6 coarse sand) etc complete
13.1.1:12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand)
13.16.1:6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
13.7.1:12 mm cement plaster finished with a floating coat of neat cement of mix:1:3 ( 1 cement : 3 fine sand)
50.13.1:9 mm cement plastering of mix : 1:3 (1 cement : 3 fine sand ) including all cost of materials, labour charges etc complete
OD259451/2025-2026:Supplying and fixing Pressed steel single door of standard pattern with frame as per profile of IS 4351 of section 100x60mm using 18G ( TATA GALVANO) sheet and shutter made of section 75x30cm using 20G (1.00mm TATA GALVANO) sheet outer styles and horizontal members and then inserted with enclosed and stiffened sheet as per specification with Zincromate primer coat ,SS handle ,SS aldrop SS but hinges etc.including labour charges,conveyance etc Complete.
OD259449/2025-2026:Supplying and fixing pressed steel window using frame 80x60x1.2 mm and shutters 50x20x1.2 mm made out of Galvano steel sheets welded and assembled with 12 mm dia MS rod at 12 cm horizontally and 25x5mm flat-2 nos vertically per pannel as grill with3"hinges,2"SShooks,eye,stay,and MS handles and fitted with 9x9 mm Aluminium C channel as beading and then fitted wih 4mm thick float glass and finally applied with zincromate yellow primer including cost & conveyance, complete
21.18:Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and stopper etc to be paid separately)
21.12.2:Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0mm thick & 2100 mm long with S.S. screws etc. complete as per direction of Engineer -in-Charge.Powder coated minimum thickness 50 micron aluminium tubular handle bar
21.13:Providing and fixing Brass100 mm mortice latch and lock with 6 levers without pair of handles ( best make of approved quality ) for aluminum doors including necessary cutting and making good etc. complete
50.9.1.1:Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately), using good quality Anjili wood /jack wood
50.9.2.1:Providing and fixing paneled and glazed shutters for doors, windows and clerestory windows, 35 mm thick shutters including ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws, excluding panelling which will be paid for separately, all complete as per direction of Engineerin - charge using Anjili/ Jack wood
50.9.4.1:Providing and fixing paneling or paneling and glazing in paneled or paneled and glazed shutters for doors, windows and clerestory windows (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured) paneling for paneled or paneled and glazed shutters 25 mm to 40 mm thick using good quality Anjili/ Jack wood
50.9.5.1:Providing and fixing glazed shutters for doors, windows and clerestory windows using 4 mm thick float glass panes including ISI marked M.S pressed butt hinges bright finished of required size with necessary screws. Using Anjili wood/ jack wood 35 mm thick shutters.
9.48.1:Providing and fixing M.S. Grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. including priming coat with approved steel primer all complete.Fixed to steel windows by welding
9.53:Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
21.1.1.2:Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
21.3.1:Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness (weight not less than 10kg/sqm)
21.2.2:Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides
9.79.2:Providing and fixing special quality bright finished brass cupboard or ward robe locks with four levers of approved quality including necessary screws etc. complete.50 mm
9.114.2:Providing and fixing magnetic catcher of approved quality in cupboard/ward robe shutters, including fixing with necessary screws etc. complete.Double strip (horizontal type)
9.82:Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete.
9.95.3:Providing and fixing ISI marked aluminium butt hinges anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete:100x75x4 mm
10.17:Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar, bent to shape with hooked ends in R.C.C. slabs or beams during laying, including painting the exposed portion of loop, all as per standard design complete.
9.74.1:Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete:250x10 mm
9.75.1:Providing and fixing bright finished door latch with necessary screws etc. complete:300x16x5 mm
9.81.1:Providing and fixing bright finished brass handles with screws etc. complete:125 mm
9.119:Providing and fixing factory made P.V.C. door frame of size 50x47 mm with a wall thickness of 5 mm, made out of extruded 5 mm rigid PVC foam sheet, mitred at corners and joined with 2 Nos. of 150 mm long brackets of 15x15 mm M.S. square tube, the vertical door frame profiles to be reinforced with 19x19 mm M.S. square tube of 19 gauge, EPDM rubber gasket weather seal to be provided through out the frame. The door fame to be fixed to the wall using M.S. screws of 65/100 mm size, complete as per manufacturer's specification and direction of Engineer-in Charge.
9.120.1:Providing and fixing factory made panel PVC door shutter consisting of frame made out of M.S. tubes of 19 gauge thickness and sized of 19 mm x 19 mm for styles and 15x15 mm for top & bottom rails. M.S. frame shall have a coat of steel primers of approved make and manufacture. M.S. frame covered with 5 mm thick heat moulded PVC 'C' channel of size 30 mm thickness, 70 mm width out of whicj 50 mm shall be flat and 20 mm shall be tapered in 45 degree angle on both side forming styles and 5mm thick, 95 mm wide PVC sheet out of which75 mm shall be tapered in 45 degree on th inner side to form top and bottom rail and 115 mm wide PVC sheet out of which 75 mm shall be flat and 20 mm shall be tapered on both sides to form lock rail. Top, bottom and lock rails shall be provided both side of the panel. 10 mm (5 mmx2) thick, 20 mm wide cross PVC sheet be provided as gap insert for top rail & bottom rail. paneling of 5 mm thick both side PVC sheet to be fitted in the M.S. frame welded /sealed to the styles & rails with 7 mm (5 mm + 2 mm ) thick x 15 mm wide PVC sheet beading on inner side, and joined together with solvent cement adhesive. An additional 5 mm thick PVC strip of 20 mm width is to be stuck on the interior side of the 'C' Channel using PVC solvent adhesive etc. complete as per direction of Engineer -in-charge, manufacture's specification & drawing.30 mm thick plain PVC door shutters
13.43.1:Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
13.60.1:Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work
13.88:Removing white or colour wash by scrapping and sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
13.98.1:Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade:One or more coats on old work
13.99.1:Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :One or more coats on old work
13.61.1:Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work
11.41.2:Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm.
11.46.2:Providing and laying Vitrified tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete.Size of Tile 600x600 mm
11.40:Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer) of Ist quality conforming to IS: 15622 of approved make in all colours, shades, except white, Ivory, Grey Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigments etc., complete.
8.31:Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in- Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
10.28:Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
10.16.1:Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes
OD259452/2025-2026:Roofing with galvalume sheet 0.4 mm thick with overlap 150mm at ends and selfdrilling screw including plain washers and bitumen washers etc. complete
OD276634/2025-2026:Providing and fixing Square gutter with all necessary fittings clamps,bolts,nuts etc
50.18.9.19.2:Providing and fixing PVC pipes including fixing the pipe with clamps/clips at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 m dia 4 Kgf/cm2 - External work - Exposed on wall
50.18.9.22.1:Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110 mm dia Elbow
50.17.1.3:Supplying and fixing CP Towel rod 60cm or nearest available length including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
50.17.1.4:Supplying and fixing CP Health faucet good quality including cost of materials and labour charges etc. complete as per the direction of site engineer-in-charge.
50.18.7.1.1:Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 15mm dia 12kgf/cm2 -Internal work- Exposed on wall
OD275265/2025-2026:Providing and fixing stainless steel (Grade 304) letters of size 25cm height in malayalam/English letters, including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the letters with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the building and padippura with suitable arrangement as per approval of Engineer-in-charge including all cost for scaffolding and fixing. (as per approved estimate 11975/2023)
8.2.2.1:Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. Granite of any colour and shadeArea of slab upto 0.50 sqm
50.18.7.2.1:Providing and fixing PVC pipes, fittings including fixing the pipe with claps at 1.00 metre spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 20 mm dia 12Kgf/cm2 - Internal work - Exposed on wall
50.18.7.4.1:Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 32 mm dia 10Kgf/cm2- Internal work - Exposed on wall
50.18.8.7.1:Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work including cutting chases and making good the wall etc. 63 mm pipe 6 Kgf/cm2
17.2.1:Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required:W.C. pan with ISI marked white solid plastic seat and lid
17.7.1:Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require:White Vitreous China Wash basin size 630x450 mm with a pair of 15 mm C.P. brass pillar taps
17.11.2:Providing and fixing white vitreous china laboratory sink with C.I brackets, C.P. brass chain with rubber plug 40 mm C.P brass waste and 40 mm C.P. brass trap with necessary C.P. brass unions complete, including painting of fittings and brackets, cutting and making good the wall wherever required:Size 600x450x200 mm
26.22.1:Providing and fixing false ceiling at all heights with integral densified calcium silicate reinforced with fibre and natural filler false ceiling tiles of Size 595x595mm of approved texture, design and patterns as per CPWD Specification 2019, to be laid in true horizontal level suspended on inter-locking metal T-Grid of hot dipped galvanised iron section of 0.33mmthick (galvanized @ 120 grams per sqm including both sides)comprising of main-T runners of size 24x38 mm of length 3000 mm,cross - T of size 24x32 mm of length 1200 mm and secondaryintermediate cross-T of size 24x32 mm of length 600mm to formgrid module of size 600 x 600 mm, suspended from ceiling usinggalvanised mild steel items (galvanizing @ 80 grams per sqm) i.e. 12x50 mm long dash fasteners, 6 mm dia fully threaded hanger rod upto 1000 mm length and L-shape level adjuster of size 76x25x25x1.6 mm fixed with grid and Z cleat of size 25x37x25x1.6mm thick with precut hole on both 25mm flange to pierce into 12x50mm or even bigger size dash fastener if require, fixed with Glavanised iron perimeter wall angle or size 24x24x0.40 mm of length 3000 mm to be fixed on periphey wall / partition with the help of plastic rawl plugs at 450mm center to center and 40 mm long dry wall S.S screws. The workshall be carried out as per specifications, drawing and as per directionsof the Engineer-in-Charge.With 15 mm thick tegular edged light weight calcium silicate false ceiling tiles.
50.17.1.1:Supplying and fixing Stainless steel soap dish including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
18.51.1:Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore
18.52.1:Providing and fixing C.P brass stop cock ( concealed) of standard design and of approved make conforming to IS: 893115 mm nominal bore
50.18.8.3.1:Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 25 mm pipe 12 kgf/cm2
50.17.1.5:Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
50.18.9.9.1:Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
50.18.9.13.2:Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 25 mm dia 10 Kgf/cm2- External work - Exposed on wall
50.18.9.14.1:Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 32 mm dia 10 Kgf/cm2 - External work- Exposed on wall
50.18.9.17.1:Providing and fixing PVC pipes including fixing the pipe with clamps/ clip at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 63 mm dia 6 Kgf/cm2 - External work - Exposed on wall
50.18.9.21.3:Providing and fixing PVC moulded fittings / accessories for Rigid PVC pipes, including jointing with PVC solvent cement -75 mm dia Door Elbow
50.18.9.22.3:Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement-110 mm dia Door Elbow
50.18.9.22.4:Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes, including jointing with PVC solvent cement- 110 mm dia Bend
50.18.9.22.5:Providing and fixing PVC moulded fittings/ accessories for Rigid PVC pipes including jointing with PVC solvent cement 110x110x110 mm dia Tee
50.18.9.22.6:Providing and fixing PVC moulded fittings/accessories for Rigid PVC pipes, including jointing with PVC solvent cement - 110x110x110 mm dia Door tee
50.18.9.22.8:Providing and fixing PVC moulded fittings /accessories for Rigid PVC pipes, including jointing with PVC solvent cement -110 mm dia Vent cowl
OD259455/2025-2026:Supplying and fixing RCC Pre-cast Waste pit of size 75cm dia concrete ring including cost of materials,labour charges,conveyance etc. complete.
OD259458/2025-2026:Providing and fixing good quality RCC waste pit with Concrete rings of 70 cm dia 90 cm depth, 5 cm thick) including all cost for transportation and installation of tanks and rings as per the directions of departmental officers at site
16.91.2:Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.80 mm thick C.C. paver block of M-30 grade with approved color design and pattern.
4.1.5:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:3:6 (1 Cement : 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources)
26.29.1:Cleaning of reinforcement from rust from the reinforcing bars to give it a total rust free steel surface by using alkaline chemical rust remover of approved make with paint brush and removing loose particles after 24 hours of its application with wire brush and thoroughly washing with water and allowing it to dry, all complete as per direction of Engineer-In-Charge.Bars upto 12 mm diameter
14.1.1:Repairs to plaster of thickness 12 mm to 20 mm in patches of area 2.5 sq meters and under, including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete, including disposal of rubbish to the dumping ground within 50 meters lead:With cement mortar 1:4 ( 1 cement : fine sand)
OD276743/2025-2026:Engaging plumber....
OD276744/2025-2026:Engaging fitter for fitting..
Drain(Civil work)
15.2.2:Demolishing cement concrete manually / by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in-Charge.Nominal concrete 1:4:8 or leaner mix ( including equivalent design mix)
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
4.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
4.2.3A:Providing and laying cement concrete in retaining walls, return walls, walls ( any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts,buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor, etc. up to floor five level, excluding the cost of centering, shuttering and finishing: 1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)1:2:4 (1 Cement : 2 coarse sand (zone-III) including manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 25% : 4 graded stone aggregate 20 mm nominal size including Recycled Concrete Aggregate (RCA) upto 25%)).
4.20.2.3:Providing and laying in position ready mixed or site batched design mix cement concrete for plain cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana/Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering and finishing as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the minimum specified cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement. All works above plinth and upto floor V level :Concrete of M20 grade with minimum cement content of 270 kg /cum
5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
5.9.1:Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.2:Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
10.25.2:Item Shifted to Sub head 14 as item 14.73 Item Shifted to head 14 as item 14.74 Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
Steel Stair and ramp(Civil work)
10.25.1:Item Shifted to Sub head 14 as item 14.73 Item Shifted to head 14 as item 14.74 Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In stringers, treads,landings etc. of stair cases, including use of chequered plate wherever required, all complete
50.10.1:Steel work in built up G I tubular ( round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting,fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
50.10.2:Steel work for purlin/single section with G I pipes including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete
12.50:Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+0.05%), total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5x55mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
12.51.1:Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screwscomplete :Ridges plain (500-600 mm)
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
4.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
4.2.3A:Providing and laying cement concrete in retaining walls, return walls, walls ( any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts,buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor, etc. up to floor five level, excluding the cost of centering, shuttering and finishing: 1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)1:2:4 (1 Cement : 2 coarse sand (zone-III) including manufactured sand derived from Recycled Concrete Aggregate (RCA) upto 25% : 4 graded stone aggregate 20 mm nominal size including Recycled Concrete Aggregate (RCA) upto 25%)).
Inspection Chamber(Civil work)
2.8.1:Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
5.1.2:Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level:1:1:5:3 (1 cement 1.5 coarse sand :3 graded stone aggregate 20 mm nominal size derived from natural sources)
5.22.6:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
13.7.1:12 mm cement plaster finished with a floating coat of neat cement of mix:1:3 ( 1 cement : 3 fine sand)
4.1.3:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:2:4 (cement : 2 coarse sand (zone-III)derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
4.1.8:Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
50.6.1.4:Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 part I of 1979 for foundation and plinth with thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand ) etc complete
General Electrical Work for transformer installation(Electrical work)
OD310914/2025-2026:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 6 sq mm with factory made clamp
OD310915/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 4 C X6 sqmm
OD310921/2025-2026:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
OD310922/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 4x10 sqmm
OD310931/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 4x16 sqmm (clamped with 1mm thick saddle)
OD311393/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 4 C X16 sqmm
OD311408/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5 C X50 sqmm
OD312175/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x50 sqmm (clamped with 25x3mm MS flat clamp)
OD312184/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5 C X70 sqmm
OD312185/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x70 sqmm (clamped with 25x3mm MS flat clamp)
OD312282/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5 C X150 sqmm
OD312283/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x150 sqmm (clamped with 25/40x3mm MS flat clamp)
OD312371/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x185 sqmm (clamped with 25/40x3mm MS flat clamp)
OD312374/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5 C X185 sqmm
OD312411/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE copper conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x240 sqmm (clamped with 40x3mm MS flat clamp)
OD312491/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5 C X240 sqmm
OD312513/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE copper conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x300 sqmm (clamped with 40x3mm MS flat clamp)
OD312514/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE aluminium armoured power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size in the existing RCC/ HUME/ METAL pipe as required. 3.5 C X300 sqmm
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.12.10.4:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation77/63 mm or nearest size
90.12.10.6:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation110/94 mm or nearest size
90.12.10.8:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation125/109 mm or nearest size
9.1.23:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.26:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.30:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
9.1.1:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
OD264307/2025-2026:Supplying and providing earth clamps made out of copper strips of the following sizes including cutting and bending the flat exactly to the shape of the gland, drilling necessary holes for nut & bolt, tinning the points of contacts and giving connections to the main earthing system 32 x 3 mm for earthing glands of size 300 sq mm to 630 sq mm
OD281599/2025-2026:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size ofglands for the following sizes of cables as required.(150sq mm with 20 mm wide x 1.20mm thick clip)
OD281531/2025-2026:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required.(25 sq - 95sq mm with 20 mm wide x 1.20 mm thick clip)
OD281532/2025-2026:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size ofglands for the following sizes of cables as required.(185sq mm with 20 mm wide x 1.20mm thick clip)
OD285941/2025-2026:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size ofglands for the following sizes of cables as required.(240sq mm with 20 mm wide x 1.20mm thick clip)
OD264303/2025-2026:Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required. 1.5 sq mm - 16 sq mm with 12 mm wide x 1 mm thick clip
90.11.1.19:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.18:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
OD277487/2025-2026:Supplying and fixing 40 amps to 63 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
OD277504/2025-2026:Supply and fixing of Power Capacitor duty contactors for switching capacitor banks 20kVAR with AC Coil
OD277508/2025-2026:Supply and fixing of Power Capacitor duty contactors for switching capacitor banks11-15 kVAR with AC Coil
OD277558/2025-2026:Supply and fixing of Power Capacitor duty contactors for switching capacitor banks 10 kVAR with AC Coil
OD277624/2025-2026:Supply and fixing of Power Capacitor duty contactors for switching capacitor banks 5 kVAR with AC Coil
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
90.14.24.55:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.5 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel with block reactor.
90.14.24.58:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel with block reactor.
90.14.24.60:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.15 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel with block reactor.
90.14.24.61:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.20 KVAr, 3 phase, 520 V, Metalised Poly Propylene Heavy duty Cylindrical Gas filled Capacitor suitable for APFC panel with block reactor.
OD316077/2025-2026:supply and providing 8 stage 440 / 110 V 5A/1A , APFC controller
OD316105/2025-2026:Supply and providing Detuned Reactors 7% copper wound 440V 50Hz suitable for 20KVAr Capacitor
OD316106/2025-2026:Supply and providing Detuned Reactors 7% copper wound 440V 50Hz suitable for 15KVAr Capacitor
OD316107/2025-2026:Supply and providing Detuned Reactors 7% copper wound 440V 50Hz suitable for 5KVAr Capacitor
OD316108/2025-2026:Supply and providing Detuned Reactors 7% copper wound 440V 50Hz suitable for 10kVAr Capacitor
OD289349/2025-2026:Flush head Push Button with 1 NO Block
OD289350/2025-2026:Supply and fixing of Flush head Push Button with 1 NC Block and giving connection etc as required
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
OD312800/2025-2026:Providing and drawing 2.65 mm (12 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
OD312803/2025-2026:Providing and drawing 3.15 mm (10 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
OD264304/2025-2026:Painting letters or figures with enamel paint as identification mark to SB, DB, panel board etc as required
OD312813/2025-2026:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & shall conform to relevant IS .Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2mm CRCA sheet, powder coated (excluding base frame)
90.14.2.4:Supply and providing 5mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.2.2:Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD289347/2025-2026:Supplying and fixing 2 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
90.14.10.22:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.630A, 70 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.4:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
90.14.10.17:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.320A/400A, 50/55 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
2.2.14:Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 125 Amp, 36 KA
90.14.10.11:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.13:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.200A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.14:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.250A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
2.2.15:Providing and fixing following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 200 Amp, 36 KA
2.1.7:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.320 Amp TP&N
90.14.11.3:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 250A to 400A with CBCT.
90.14.11.11:MCCB AccessoriesSupply and fixing one number under voltage release for all voltage range up to 630A MCCB.
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
90.14.11.15:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A
90.14.11.14:MCCB AccessoriesSupply and fixing rotary handle, Direct type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
OD289536/2025-2026:Supply and fixing of spreader/terminal adapter kit extended terminal for 4 pole MCCB of rating UP TO 100A(8 pcs)
OD289537/2025-2026:Supply and fixing of spreader/terminal adapter kit extended terminal for 4 pole MCCB of rating 160A & 200A(8 pcs)
OD289538/2025-2026:Supply and fixing of Spreader terminal adapter kit extended terminal for 4P MCCB (630A) 8pc
OD289539/2025-2026:Supply and fixing of Spreader terminals adapter kit extended terminal for 4P MCCB (400A) 8pc
OD289540/2025-2026:Supply and fixing of Spreader terminals adapter kit extended terminal for 4P MCCB (125A) 8pc
OD289543/2025-2026:Supply and fixing of Spreader terminals adapter kit extended for 4P MCCB 250A
OD264316/2025-2026:Supply and fixing Multifunction meter to read: V, A, F, 3 phase accuracy class 1 and giving connection etc as required
OD264309/2025-2026:Supply and fixing 100/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT and giving connection etc as required
OD264305/2025-2026:Supply and fixing 100/5 A, 5 VA, accuracy class 5P 10, Protection CT (Tape wound) and giving connection etc as requied
OD264314/2025-2026:Supply and fixing Red ,Green ,Yellow colour LED type Indicator on existing panel.
OD312874/2025-2026:Supply and fixing Blue colour LED indicator, AC/DC, 22.5 mm cut out dia
OD264306/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required 1.5 copper wire 1 run.
OD316164/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required.10.00sq mm wire single run
OD316165/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required.6.00sq mm wire single run
OD264308/2025-2026:Supply and providing the 25x6 mm sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
OD264312/2025-2026:Supply and providing the 25 x 3mm sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
OD312885/2025-2026::Supply and providing Bus bar chamber, 100 x 40 mm aluminium anodised legend plates in the existing panel board as required
OD312886/2025-2026::Supply and providing Cable alley, 100 x 40 mm aluminum anodized legend plates in the existing panel board as required
OD312887/2025-2026:Supply and providing Earth, 40 x 20 mm with 8 mm hole aluminum anodized legend plates in the existing panel board as required
2.21:Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2 mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.8:Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
HT. WORKS(Electrical work)
OD289209/2025-2026:Supply, conveyance, installation, testing and commissioning of 315KVA USS , 11kv/433v,50hz,3phase,AN cooled,delta/star,with copper windings with tappings +5 to -5 in steps of 2.5%, class f insulation, outdoor type ,laser scribed core ,confirming to ECBC norms , copper interconnections , with 11KV,630A, VCB ,26.3KA for 3 sec, horizontal drawout fitted with manual spring charged etc complete with necessary multifunction meter ,11KV CT & PT ,master trip relay,push button ,provision for TOD meter ,annunciation panel with alarm,strip heater,thermostat etc complete enclosed in CRCA powder coated sheet conforming to IP 54 of minimum thickness 2mm and louvers enclosed with mesh to prevent entry of rats.
OD289234/2025-2026:Supply and laying of 1no: PVC insulated and PVC sheathed armoured aluminium power cable,11KV grade of the following sizes in the existing RCC/HUME/STONE WARE/GI/DWC pipe as required. 3 core 300 sqm stranded compact circular aluminium conductor,conductors screened with extruded semi conducting compound XLPE insulated , insulation screened with extruded semi conducting compound in combination with copper tape(0.3 KA for 1 sec.) cores laid up.inner sheath of PVC tape,galvanized steel flat strip armoured, and overall PVC sheathed cable conforming to IS:7098 part II 1985 with latest amendments
10.4.4:Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
10.5.4:Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
14.2:Excavation for cable trenches of depth upto 1.2 m in soft soil including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50 metres.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
90.12.9.13:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench200/174 mm or nearest size
OD264326/2025-2026:Supply of Class 2 (yellow) electrical insulating Gloves packaged in an individual container or package of sufficient strength to protect properly the gloves from damage, conforming to IS 13774/IEC 60903 suitable for working voltage upto 17 K V and shall be marked as per standard.
OD264318/2025-2026:Supply, Installation, Testing and Commissioing of 3 Phase, 4 wire, 110 V (L-L), -/1 A CT or -/5A CT, accuracy class 0.2S, HT TOD meter with terminal block and 20A fuse with HRC Link etc as required.
OD316161/2025-2026:Supply, installation, testing, and commissioning of numerical protection relay, Make: L&K, Model: MC12
5.8:Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
OD316376/2025-2026:Supply and providing plate earthing as per IS 3043:2018 with 1200x1200x12mm GI earth plate,50 mm GI(medium class) watering pipe,GI funnel with weld mesh,25x5 mm GI clamps,CI/MS cover plate with locking arrangements,charcoal/coke and salt etc including providing brick work masonry enclosure at the top (450x450x450mm inside)etc as required.
OD316152/2025-2026:Supplying and installation including all manner of supports/ suspenders, anchor bolts etc for cable trays made out of suitable size channel sections, slotted angles, flats, MS plates etc as required including painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.
Electrification for Store room(Electrical work)
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.11:Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.9:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.9 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.14:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
1.17.33:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 6 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
90.3.20.3:Supply & installation of light fittings on TW round block Supply, conveyance installation testing and commissioning the light fittings of following types made of CRCA with 0.5mm thickness complete with all accessories and lamps etc. directly on wall or ceiling with PVC round block neatly painted to suit the fitting and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS and giving connections as required.1200 mm 1X20W LED Lamp with box type fixture
90.3.18.1:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.25 mm dia with HG company fabricated clamps
OD313283/2025-2026:Supply ,installation,testing and commissioning of 4200 lumen LED, efficacy >=120 Lm/watt, IP 66 street light fitting with die-cast aluminium housing, polycarbonate cover complete with THD <10%, power factor >0.95, RoHS compliant, duly wired up for use on 230 V AC supply, IK >=7, with internal surge protection 4k above. Chip make Cree/Osram/lumilled/Nichea/Bridgelux.(LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
OD264353/2025-2026:Supply,conveyance,installation,testing and commissioning of 3000 lumen square/Round (2ft X 2ft) surface/recess fitting made of crca sheet of thickness 0.5mm, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea pre-wired fluorescent fitting complete with all accessories and fluorescent lamps etc. suspended from ceiling using 4 nos steel chain (16 SWG or nearest) of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.
OD264344/2025-2026:Supply and installation of 1800 lumen round/ square surface/recess mount fitting made of diecast aluminium, having efficacy not less than 100l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea
OD264357/2025-2026:Supply ,installation, testing and commissioning of 700lm pressure die cast housing Bulk head with IP65 protection & IK 08 having efficacy not less than 105lm/W and giving connection with 3 core flex wire as required.
OD313492/2025-2026:Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
OD264351/2025-2026: Supply, conveyance, installation , testing and commissioning of 300/305 mm sweep Light Duty Exhaust fan in metal frame working on 230 V A/C in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
90.3.8:Supplying and providing extra steel chain (16 SWG) 4 x 1.00 m long with 16/0.20 mm 3 core copper conductor flex wire conforming to relevant ISS or with the extended original wiring and giving connection etc. as required.
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
90.10.3.14:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator
OD288871/2025-2026:Supplying and fixing 4P sheet steel enclosure on surface/ recess along with 40 to 63 amps 415 volts "C" curve TPN MCB complete with connections, testing and commissioning and giving connection etc. as required.
90.11.1.10:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43)
2.3.3:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.15:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.14.1:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.10.4:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
OD264347/2025-2026:Supplying and fixing 40 A to 63 A, TP MCB (C curve), 10 kA breaking capacity, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. TP MCB
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
1.48:Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as required. (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)
1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
OD264349/2025-2026: Supplying and clamping the following sizes of corrugated pvc flexible conduit with necessary compression gland with locking ring and check nut at termination pointed using suitable size GI/painted MS saddles spacing not exceeding 60 cms on surface including making good the damages.20 mm dia .
OD264352/2025-2026:Supply and providing brass bolt and nut 25x3mm
OD264342/2025-2026:Supply and providing 2mm thick Elastomeric fire retardant insulating mat as per IS 15652/2006 to withstand 3.3 KV dielectric strength including painting in ground with suitable synthetic adhesive.
OD264345/2025-2026:Supply and installation of 6Kg ABC Fire Extinguisher cap filled with mono ammonium phosphate powder 50% confirms to IS 1409, stored pressure type, with pressure gauge, the discharge time 24 sec, controllable discharge mechanism, jet range 5 meters, average discharge is 90%, appliccable on A,B & C and electrically started fire, A rating-3A, B rating 21B, construction: deep drawn & co2 mig welded, EPDM rubber hose with both end aluminium clamped, internal coating-epoxy powder coating, external coating-pure polyster powder coating(UV resistant),brass forged valves with safety pin is of ss material, sheet metal thickness ISI approved.
OD316206/2025-2026:Supply and providing 4.5Kg CO2 fire extinguisher, filled with CO2 gas as per IS 15222, control discharge mechanism fitted with minimum 1.5 meter wire braided hose & flat horn with diffuser nozzle for dispersed discharge of CO2, discharge time 37 sec, average discharge is 95%, applicable on class B, C and electrcally started fire, external coating is of enamel spray painting, valve confirm to IS 3224 ISI marked, CO2 cylinder construction: hot spinning by seamless pipes & bearing ISI mark, body confirms to IS 7285 extinguishers to ISI marked. fire rating:89B
OD289534/2025-2026:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
OD314643/2025-2026:Providing and drawing 3.15 mm (10 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
OD314838/2025-2026:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
OD314890/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 4x25 sqmm (clamped with 1mm thick saddle)
OD264341/2025-2026:Charges for preparation of Electrical Drawing per A3 sheet first copy
OD264350/2025-2026:Copying charges of Electrical Drawing per A3 sheet additional copies
OD315093/2025-2026:Supply, installation, testing and commissioning of 6KVA UPS with Isolation Transformer having 60 minutes backup with tubular battery & rack having the following specifications . "a) 1 ph to 1 ph b) Input pf : 0.99 @ full load c) Output pf : unity d) Input voltage range : 140V -280V with cut off e) THD : ≤ 10% f) Overall Efficiency : ≥87% g) Ambient Temperature : 0-40°C h) Generator Compatibility. i) Pure sine wave. j) Battery over charge & under charge cut off. l) Bypass arrangement. m) EN/IEC 620401 for General Safety compatibility n) EN/IEC 620402 for Electromagnetic Compatibility. o) EN/IEC 620403 for Performance p) EN/IEC 620404 for Environmental Compatibility q) battery : exide / panasonic or equivalent "
SITC of LIFT(Electrical work)
Air conditioning system(Electrical work)
OD309448/2025-2026:Supply , Installation, Testing and Commissioning of 5 Star rated 2TR Air Cooled Hi Wall Invertor split type Air conditioners complete with Indoor unit(IDU), Out door unit (ODU), Copper evoporator coil and condensing coil , surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 Degree Celcius. Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS /International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature) with comprehensive maintenance contract up to the end of 5 years form date of commissioning including Stand, periodical services and gas topping etc. complete
OD264338/2025-2026:Supply, Conveyance & Installation of Voltage stabilizer suitable for split type 2.2 TR AC unit, capacity 20 A with voltage range of 175-275V and out put range of 210 - 240V (V Guard VG500) or its equivalent
OD264336/2025-2026:Supply and fixing of 25mm 10Kg/cm2 PVC drain water pipe line with necessary,supports,saddles,clamps -and fittings such as bends, tees etc
OD264335/2025-2026:Supply and providing the following size soft drawn copper pipe for extending the pipe between out door and indoor unit, including insulating the pipe using rubberized foam sleeve 10mm thick, brazing, leak testing etc.:- 3/8 inch (9.52 mm) and 5/8 inch (15.8 mm) 22 gauge
90.10.3.32:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator
90.6.5.13:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 4.00 sq mm
90.6.5.20:Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.4 core 4.00 sq mm
OD315265/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 4x6 sqmm (clamped with 1mm thick saddle)
Active Componets(Electronics Work)
OD289038/2025-2026:SITC of 4 MP IP vari focal Bullet Camera with following specification. Lens 2.7 mm to 13.5 mm vari focal, IP 67, compression techniques H.265/H.264/MJPEG, Min.Illumination Color:0.001Lux@(F1.2,AGC ON),0.014Lux@(F1.4,AGC ON),0LuxwithIR S/N Ratio 58dB or better.IR Distance :up to 50m WDR Upto120dB, TWDR (Off/Low/Middle/High), IR LED Control Auto,Manual,OFF,1~30fps, Network Port RJ45 10M,100M, Protocol TCP/IP, IPv4, IPv6, SSL, TLS, UDP, HTTP/HTTPS,HTTP-Base64,HTTP-Digest,DHCP, DNS, RTP, RTSPS, ICMP, RTCP, NTP, SMTP, IGMP, Multicast, System Compatibility ONVIF Profile S,G and T Approved Make :- CP Plus, Sparsh
OD289040/2025-2026:SITC of 4 MP IP Dome Camera with following specification 1/2.7 inch 4MP CMOS Image Sensor Minimum Illumination 0.001 [email protected] Shutter Auto/Manual 1/3 to1/100,000 s Lens - Fixed-focal, Max. Aperture F1. Mount M12 Lense: 3.6 mm fixed Lens, S/N Ratio 56 dB or better, Back Light Compensation BLC/ HLC/ WDR(120dB) IR Range of 50 Mtr. IR Control Auto, Manual Resolution 4MP (2688 X 1520/ 2560 X 1440), 3MP (2304 X 1296), 2MP (1920 X 1080), 1.3MP (1280 X 960) 720p (1280 X 720), D1 (704 X 576/ 704 X 480), VGA (640 X 480), CIF (352 X 288/ 352 X 240) Cyber Security AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, WSSE, account lockout, syslog, video encryption, IP/MAC filtering, HTTPS, trusted upgrade, trusted boot Ethernet RJ-45 (10/100 Base-T) Approved Make : Cp plus, Sparsh or STQC Approved equivalent make.
OD289041/2025-2026:SITC of 4 MP IP Bullet Camera with following specification 1/2.7 inch 4MP CMOS Image Sensor Minimum Illumination 0.001 [email protected] Shutter Auto/Manual 1/3 s to 1/100,000 s Lens - Fixed-focal, Max. Aperture F1. Mount M12, Lense 3.6 mm fixed Lens, S/N Ratio 56 dB or better, Back Light Compensation BLC/ HLC/ WDR(120dB) IR Range of 50 Mtr. IR Control Auto, Manual Resolution 4MP (2688 X 1520/ 2560 X 1440), 3MP (2304 X 1296), 2MP (1920 X 1080), 1.3MP (1280 X 960) 720p (1280 X 720), D1 (704 X 576/ 704 X 480), VGA (640 X 480), CIF (352 X 288/ 352 X 240) Cyber Security AES 256-bit Encryption, Configuration encryption, trusted execution, Digest, security logs, WSSE, account lockout, syslog, video encryption, IP/MAC filtering, HTTPS, trusted upgrade, trusted boot Ethernet RJ-45 (10/100 Base-T) Approved Make : Cp plus, Sparsh or STQC Approved equivalent make.
OD289039/2025-2026:Supply, Installation, Testing and Commissioning of L2+ 24 port 10/100/1000Mbps PoE+ Switch , PoE Power budget 250 Watts or above, with 48 Gbps throughput in full duplex mode having port based VLAN with 2 or more SFP uplink ports, rack mountable switch with minimum 3 years onsite warranty. Approved Make Netgear. Ruckus, Brocade,juniper, TP Link.
OD289129/2025-2026:SITC of 32 inch LED commercial Display suitable for 16x7 operation , resolution HD(1366X768) Aspect ratio 16:9, full HD Resolution, 350 nits brightness with wall Mount bracket, 2HDMI,2USB input , RJ45, 20W Audio out, Remote control, and all accessories and having 3 years warranty. Make: LG/Panasonic/Samsung
OD289130/2025-2026:Supply and installation of wireless mouse . Preferred make:- logitech or equivalent
OD289131/2025-2026:Supply Installaion Tesing and Commissioning of 1KVA UPS with one number of 12V, 100AH- tubular battery for necessary backup for the entire system with 3 years OEM warranty for UPS and batteries and with necessary electrification for charging the UPS and powering the rack and display. Approved Make for UPS : APC, Hykon, Igatech, Numeric and Battery Exide/Amaron
OD289260/2025-2026:SITC of STQc approved 16 channel NVR having 16 channel IP camera input, embedded linux operating system, video compression insta stream, H.265,H.264+, H264, MJPEG, 384 Mbps ,incoming/recording/outgoing bandwidth, 2SATA up to 20TB each, 2USB ports, 1HDMI/1 VGA video output port, Rj45, ONVIF, support Protocols HTTP, HTTPS, TCP/IP, IPv4, UDP, NTP, DHCP, DNS, SMTP, UPnP, DDNS, Alarm Server, Multicast,P2P, Auto Registration, iSCSI, ONVIF 23.12(Profile S, Profile T, Profile G), CGI, SDK . Preferred make :- CPPLUS/ Sparsh
OD289410/2025-2026:Supply, Installation, Testing and Commissioning of L2+ 24 port 10/100/1000Mbps Switch meets IEEE standards 802.3, 802.3u, 802.3ab, 802.3x, 802.1Q, 802.1p, 802.1D and 802.1ad, with 48 Gbps throughput in full duplex mode having port based VLAN with 2 or more SFP uplink ports, rack mountable switch with minimum 3 years onsite warranty. Approved Make:- TP Link, HP, Netgear. Ruckus, Brocade,juniper,Cisco, Digisol.
Passive componets (Electronics Work)
OD289046/2025-2026:Supply and fixing Cat-6 Angled Dual Information outlet with spring shutter front access on surface / in recess with metal back box as required for inter connection of nodes and switches including termination charges. Node numbers should be neatly written in I/O ports. Approved Make :- Molex/ Legrand/Actassi/Belden/Panduit.
OD289047/2025-2026:Supply and fixing Cat-6 Angled Information outlet with spring shutter front access on surface with PVC back box/ In recess with metal back box as required, for inter connection of nodes and switches including termination charges. Node numbers should be neatly written in I/O ports. Approved Make :- Molex/ Legrand/Actassi/Belden/Panduit.
OD289049/2025-2026:Supply and Installation of CAT 6 24 Port loaded Modular type Patch Panel with necessary numbering with permanent marker or by printed means including termination charges Approved make : Legrand/Molex/AMP
OD289135/2025-2026:Supply of of 6 TB Surveillance Hard Disk Drive/SSD for copying the recorded footage. preferred make:- SEAGATE/WD
OD289210/2025-2026:Supply and fixing of 19 inch 6U (450 mm depth) rack with covered wire manager, cooling fan 2 Nos, AC distribution box and all other accessories. Approved Make. Rittal,Netrack,Valrack
Cables and Conduits(Electronics Work)
OD289053/2025-2026:Supplying and drawn of 23 AWG LSZH UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable, Approved Make:- AMP, Molex, Actassi, Systimax.
OD289054/2025-2026:Supplying and drawn of 23 AWG UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required 3 run of Cable. Approved make:- AMP, Molex, Actassi, Systimax.
OD289067/2025-2026:Supply and Installation of UL Listed, ETL Listed and RoHS Complaint. CAT 6, 1Mtr standard factory crimped patch cord. Approved Make: Molex, Actassi, Belden, Panduit.
OD289072/2025-2026:Supply of 3 meter factory crimped UL Listed, ETL listed and RoHS compliant Cat6 patch cord having 0.5mm conductor thickness Approved Make :- Molex/Belden/Actassi/Honeywell.
OD289099/2025-2026:Supplying and drawn of 23 AWG UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required 2 run of Cable. Approved make:- AMP, Molex, Actassi, Systimax.
OD289208/2025-2026:Supply and laying of 10 meter HDMI 2.0 V Male to Male 4 K @ 30 Hz 18G Cable. approved make Logic GL-PR-H10MM-4K or equivalent
OD289263/2025-2026:Supplying and fixing of following sizes of medium class PVC conduit along with accessories on surface/ in recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm.Approved Make:-Precision, Toms, Balco
OD289264/2025-2026:Supplying and fixing of following sizes of medium class PVC Conduit along with accessories on surface/ in recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm Approved Make:/ Precision/ Modi/Balco/Toms
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
Tendernotice_1.pdf
PDF • 0.07 MB
2Affidavit.pdf
Tender Documents • 0.29 MB
1PRELIMINARYAGREEMENT.pdf
Tender Documents • 0.28 MB
3FormVI.pdf
Tender Documents • 0.19 MB
epay.pdf
Tender Documents • 0.07 MB
6GST.pdf
Tender Documents • 0.51 MB
7Integritypact.pdf
Tender Documents • 0.01 MB
8DeclarationElectrical.pdf
Tender Documents • 0.33 MB
9ElectricalUndertaking.pdf
Tender Documents • 0.27 MB
10ElectronicsUndertaking.pdf
Tender Documents • 0.34 MB
11ACUndertaking.pdf
Tender Documents • 0.34 MB
12LIFTUndertaking.pdf
Tender Documents • 0.34 MB
13Machinerydetails.pdf
Tender Documents • 0.26 MB
BOQ_1412264.xls
BOQ • 0.85 MB
viewsbdperumbavoor.pdf
Tender Documents • 5.84 MB
5Instructionstobidders.pdf
Tender Documents • 0.39 MB
Download all tender documents and submit your bid