Sh K K Soni AE (Civ) AGE I R and D Manali
AGE I R AND D MANALI PIN 175103 PH 01902255014
REPAIR/MAINT TO STREET LIGHTS AND FLOOD LIGHTS AND CONNECTED WORKS AT DGRE RDC MANALI AT AGE(I) R n D, MANALI.
2026_MES_772200_1
AGE(I)/MNL-39/2026-27
Open Tender
Electrical and Maintenance Works
120 days
Manali
As per NIT and tender documents
5 documents required · 5 mandatory
₹500
AGE I R AND D MANALI
₹19,000
Yes
15 Jun 2026
15 Jun 2026
20 Jul 2026
15 Jun 2026
13 Jul 2026
29 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Supply only XLPE insulated armoured cable (heavy duty) electric cable with aluminium stranded conductor 1100 volts grade of following size after taking down complete all as specified and directed by Engr-in-charge and directed as follows : | |||||
| 1.1 | 10 Sqmm x 2 Core | 200 | RM | - | - |
| 1.2 | 16 Sqmm x 2 Core | 250 | RM | - | - |
| 2 | Supply, installing, testing and commissioning factory made LT panel ( 415 Volts, 50 Hz , 3-phase, 4 wire supply ) CPRI approved and tested Street Light TIme switch Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system. The panel shall be dust and vermin proof, protection class ( IP-54 ) and made of 3.15 mm thick CRCA mild steel sheet and mild steel angle iron frame work ( made out of 40 mm X 40 mm X 6 mm thick ), front opening type with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FR cable of adequate size but not less than 1.5 sqmm complete. All steel metal works including frame shall be with anticorrosive coating with seven tank process and finally epoxy polyester powder coating of Siemens grey shade 7035 embedded in ground with and including masonry of blocks of PCC 1:2:4 type B1 of block size 30x30x30 cm in 1:4 CM incl rendering in cement mortar of 1:4 complete all as specified and directed. The scope of work also comprising of the following. Make of Panel Board:- Adlec/ Schneider / Universal Switch Gear Control/ Tricolite. | 1 | Each | - | - |
| 2.01 | INSTRUMENTS:-
(i) Red, Yellow, Blue Phase indicating light LED type- 01 Set.
(ii) Control MCB 6 A SP C Series - 1 Set.
INCOMING:-
(i) MCB 63 Amps, 4 Pole, 10 KA, 50 Hz, 415 Volts-01 No. Make: L&T/ Havells / Legrand
(ii) Power Contactor 3 Pole, 32 Amps. 50 Hz, 220 Volts- 01 No. Make: L&T/ Havells/ ABB or equivalent.
(iii) Automatic astronomical Timer Switch with battery backup of 100 hours, Programmable every 4 Hours current capacity 16 Amps 240/415 Volts, 50 Hz- 01 No. Make: L&T/ Havells or equivalent.
(iv) Auto Manual Selector Switch 6 A SP- 01 No. Make: L&T/Schneider/Kaycee.
(v) RED Phase indicating light LED type- 01 No.. Make: L&T/Vishnu/ Schneider/ C&S.
(vi) Outgoing Terminal 4 Way - 1 Set. Make: Master/FTC/Connectwell.
Panel wiring for control circuit with copper flexible 1.5 Sq mm & power wiring 10 Sqmm flexible.
Note: In Case of failure, manual system should also be provided. | - | - | - | - |
| 2.02 | The panel manufacturer should have following Govt. Approved Certificates:
1. Panel should be according to IEC-61439. CPRI Certification Degree of Protection IP-54 (IS/IEC : 61439 (Part-1), 2011 & IS/IEC : 61439 (Part-2) 2011)
2. Tempreature Rise (IS/IEC : 61439-1, 2011 & IS/IEC : 61439-2 2011)
3. CPRI Short Circuit IEC-61439-1 & 2 withstand strenght should be 70kArms for 1.0 Sec with intial peak of 154kApk
4. CPRI Certification IEC-61439-1 & 2 Rated current for short circuit not less than 6300 A with rated insulation voltage 660V
5. ISO 9001 CERTIFIED.
Contractor will get the copy of above certificates and submit to Engineer-in-charge/AGE(I) before erection of panel on ground. | - | - | - | - |
| 3 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required upto 35 sqmm complete all as specified and as directed by Engr-in-charge. | 330 | RM | - | - |
| 4Supplying and making straight through joint with cast resin compound including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. | |||||
| 4.01 | 16 Sqmm x 2 Core | 5 | Each | - | - |
| 5 | Arranging fault locating machine to locate the fault in underground electric power cable of any length & any type of 1.1 KV grade HT/ LT cables & pin point the fault, it also include testing of the cable after locating fault and cutting the cable at Fault to fix the joint including excavation and earth wotrk in any type of soil complete
Note : Cable joint shall be measured and paid separately under respective of Sch 'A'
(ii) If fault is not rectifed within 24 hours after receivng message , the contractor shall be charged penalty for Rs 500/- per Hours & the same has been deducted from his account during RAR. Record shall be maintained by JE and submit to AGE (I) for payment purpose. | 5 | Job | - | - |