GE (I) DM Visakhapatnam
GE (I) DM Visakhapatnam
SERVICING MAINTENANCE AND CALL ON REPAIRS FOR 24 HRS AND OTHER ALLIED WORKS FOR 11 KV HT VCBS PANELS AT OLD DOCKYARD SUBSTATIONS AT NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) (DM) VISAKHAPATNAM
2026_MES_793892_1
8711/C/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Naval Dockyard Visakhapatnam
As per tender document
8 documents required · 8 mandatory
₹500
GE (I) DM Visakhapatnam
₹90,800
Yes
14 Oct 2026
14 Oct 2026
6 Nov 2026
14 Oct 2026
4 Nov 2026
28 Oct 2026
15 Oct 2026 - 26 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Attending day to day complaints and call on repair for 24 Hrs of HT Switchgear Vacuum Circuit breaker of capacity 630A to 1250A Schneider make with one Engineer , one electrician and one helper for all days including Holidays & Sundays for opening of covers, checking for any uncertainty and refixing the same to original position, re-connection of all existing cables, extended bus bars, after rectification & testing , closing the complaint by re-energising the feeder complete all as specified and as directed.
Note: Replacement of defective parts shall be measured and paid separately. | 35 | Job | - | - |
| 2 | Taking down HT Switch gear vaccum circuit breaker of capacity 630 Amps to 1200 Amps, 12kv/11KV, Schneider make HWX Model for carrying out following repairs, overhaluing, servicing, preventive maintenance and reflixing the same after carrying out repairs / overhauling complete all as specified and as directed.
(a) Tripping off the breaker, rackout the breaker complete from the panel along with trolly for servicing / inspection/ overhauling.
(b) Servicing / inspecting/ checking automatic safety shutter operation for service ability and replacement of spares if required.
(c ) Servicing /inspecting / checking of busbar spout and circuit spout connections for RYB Phases and replacement of spares if required.
(d) checking of breaker ma9in mechanism assembly, fixed contacts and cuurrent carrying parts of the breaker, trolley, insulated asembly etc.
(e) setting, reassembling, cleaning adjustment of fixed contacts main contact, acring contact and moving contact for proper setting of auxiliary contacts operatingg mechanism. | 20 | Each Job | - | - |
| 2.01 | (f) Servicing / inspecting / checking of secondary socketd / busbar earthing plugs / earthing sockets and replacement of spares if required.
(g) checking, setting and adjustment of rackin and rackout operation of the breakedr trolley.
(h) Decarbonising of busbar and connected items.
(j) Lubrication and greasing of all moving parts of the trolley, stopper bolt for proper operating.
Note:
(a) The rate quoted shall be deemed to be include for necessary T & P, Nuts, bolts, washers, gasket, insulation tape, HT Sleeve, monoplast compound to put in to the VCBs and paneles in serviceable condition, testing and commissioning
(b) Replacement of defective parts of the VCB Shall be measured and paid separately. | - | - | - | - |
| 3 | Maintenance, servicing, cleaning of vacuum circuit breaker unit of 11 KV VCB panel of capacity 630 Amps to 1250 Amps, taking out from panel, cleaning of all parts with CTC and clean cloth, removal of carbon deposited inside the moving contacts, greasing of all moving parts of the VCB, checking of complete operating mechanism for proper functioning, reporting for any defective parts, complete all as specified and as directed.
Note: Replacement of defective parts of the VCB shall be measured and paid separately. | 25 | Job | - | - |
| 4 | Supply and fix including dismantling taking out unserviceable Buffer (For Opening Spring ) For 630 Amps to 1250 Amps Schneider make 11 KV VCB. All as specified and directed.
Make : - Schneider only, Part No- MVIJ00098-01 . | 20 | Each | - | - |
| 5 | Supply and fix including dismantling taking out unserviceable Buffer (For Closing Spring ) For 630 Amps to 1250 Amps Schneider make 11 KV VCB all as specified and directed.
Make :- Schneider only, Part No- MVIJ00056-01 | 20 | Each | - | - |
| 6 | Supply and fix single (Read-Blue) phase busbar spout suitable for 630 Amps to 1250 Amps VCB make Schneider only Model No MEP-39-32185 complete all as specified and as directed. | 10 | Each | - | - |
| 7 | Supply and fix single (Y) phase busbar spout for 630 Amps to 1250 Amps VCB make Schneider only Model No MEP-39-32186 complete all as specified and as directed. | 6 | Each | - | - |
| 8 | Supply and fix CT Spout suitable for VCB 630 Amps to 1250 Amps complete all as specified and as directed.
Make :- Schneider only, Model No MEP-39-32187 | 18 | Each | - | - |
| 9 | Supply & fixing closing coil assembly 110 V DC to Schneider make 11KV VCB incl necessary connection testing complete including dismantling taking down unsv one complete all as specified and as directed.
Make :- Schneider only, Part No- ECO39SN134900FN | 12 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
8711Tender.pdf
Tender Documents • 0.97 MB
BOQ_890358.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .