| Sl No | Description | Qty | Unit | Blue Star Ltd. L1 | VERTIV ENERGY PRIVATE LIMITED L2 |
|---|---|---|---|---|---|
| 1.00 | DIESEL GENERATOR (Make: Kirloskar-KOEL)
400KVA DG set with acoustic enclosure with accessories inclusive of 6 Numbers of 12 V,180 AH lead acid batteries along with leads, day fuel tank, fuel piping from fuel tank to Engine, fuel tank to fuel storage tank, Residential silencer, Engine cold start kit, suitable size termination box (Cable / Bus duct) with extended Alternator terminal with bus bars including control switchgear & Exhaust System etc as installed at site. | 3 | Nos. | 9,298 ₹32,914.92 Lowest | 21,677.78 ₹76,739.34 |
| 2.00 | UPS SYSTEM (Make: Delta)
400 KVA double conversions online IGBT based UPS with active/ Passive filter as installed at site with isolation transformer as installed at site | 2 | Nos. | 18,824 ₹44,424.64 Lowest | 30,850.25 ₹72,806.59 |
| 3.00 | Battery Bank (AMRON Quanta)
12V VRLA 200AH (Min) battery bank with Battery Breaker suitable for the above UPS and Battery bank with copper cable of adequate rating from UPS to battery as installed at site (Each Bank includes 38 batteries of the mentioned model). | 4 | Nos. | 538 ₹2,539.36 | 361.3 ₹1,705.34 Lowest |
| 4.00 | UPS SYSTEM (for other load) (Make: Emerson)
2 x 20 KVA Parallel redundant double conversion IGBT based with active! Passive filter as installed at site with isolation transformer as installed at site | 2 | set | 3,227 ₹7,615.72 | 2,613.47 ₹6,167.79 Lowest |
| 5.00 | Battery Bank (AMRON Quanta)
12V SMF mono block 100AH (Min) battery bank with Battery Breaker as installed at site (Each Bank includes 34 batteries of the mentioned model). | 2 | set | 1,076 ₹2,539.36 | 982.73 ₹2,319.24 Lowest |
| 6.00 | DG AMF Synchronization cum auto load management panel including the followings as installed at site:
Incomer 3 nos800 Amps ,3P microprocessor based MCCB, 50KA with SCO/ L, neutral contactor 800 A, AC3 duties and earth fault protection.
2 nos 1250 Amps 4P microprocessor based MCCB, 50KA Bus coupler between DG 1 & DG 2 and DG-2 & DG-3 with SC, O/L & earth fault protection.
3 nos 1250 Amps 4P microprocessor based MCCB, 50KA outgoing SC, O/ L.
4 nos energy analyzer, indication lamps for on/off, trip, synchro lamp, RYB lamps, synchrony relays with synchroscope, load manager, PLC based priority selection, necessary control wirings, CT/PT, DG parameter display & as installed at site | 1 | Set | 6,973 ₹8,228.14 Lowest | 10,838.89 ₹12,789.89 |
| 7.00 | Main LT Panel
MAIN LT Panel including of followings as installed at site but not limited to:
A. INCOMER: - 2 Nos 1250 Amps and 2 nos of 1250Amps EDO TYPE ACB 50 kA, 4 pole, microprocessor release, and Motor wound spring charged closing mechanism. Each Incomer shall have one set of the following items:
B. BUS COUPLER :- ACB, 1250 Amps, 50 kA, microprocessor release, Motor wound spring charged closing mechanism, EDO type,
-01 No Indication Lamps, LED type, for breaker 'ON’, ’OFF’,’TRIP’ indication with SP MCB control fuses- 3 sets
Suitable arrangement, interconnection required for electrical and mechanical interlock among 2 Nos. Incomers and 1 No Bus coupler - 01 Set
Outgoing Feeders: -:-MCB, 630 Amps, 4 Pole, 36kA, microprocessor release
-3 Nos. MCCB, 400 Amps, 4Pole, 36 kA, microprocessor release
-5 Nos. MCCB, 160 Amps, 4 Pole, 25 kA
-3 Nos. MCCB, 100 Amps, 4Pole, 25 kA
-5 Nos MCCB, 63 Amps, 4Pole, 25 kA
-3 Nos. 32 Amps, 4 Pole, 25 kA
-1 Nos. Indicating lamps LED type, for breaker “ON“,“OFF“,“TRIP“ indicate on with SP MCB control fuses 14 Sets.( only for ACBs )As installed at site | 1 | set | 1,136 ₹1,340.48 Lowest | 3,612.96 ₹4,263.29 |
| 8.00 | APFC panel
300 kVAR automatic, manual Power Factor Correction Panel including followings & as installed at site:
Capacitors Type - MD -XL,500V, 3 ph, 50 Hz | 1 | set | 199 ₹234.82 Lowest | 1,734.22 ₹2,046.38 |
| 9.00 | PAC Panel
2 nos of PAC Panel, including the followings & as installed at site:
A. INCOMER: 1 Nos 400 Amps microprocessor based MCCB 36 kA 4 pole
B. Outgoing: 6 nos 100 Amps microprocessor MCCB 25 kA 4 pole
Outgoing Feeders: - 3 Nos CTs, 15 VA, class 1.0 and control circuit wiring with SP MCB control fuses. | 1 | Set | 199 ₹234.82 Lowest | 722.59 ₹852.66 |
| 10.00 | 3 Phase Transformer of 750 kVA (Make: United) | 1 | Nos. | 4,103.51 ₹4,842.14 Lowest | 13,006.67 ₹15,347.87 |
Tender Value
₹6.5 Cr
EMD Value
₹13 L
Closing Date
18 Mar 2024, 3:00 pmClosed
Commissioner,DoITC
IT Building Yojana Bhawan-Jaipur
Request for Proposal Document for Overall Maintenance and Operation of Non-IT Equipments installed at Datacentre RSDC P-1, P-2 and P-3, Jaipur
2024_DoIT_380227_1
F5.502(1415)/DoITC/2024/ ML-4235
Open Tender
Miscellaneous Services
Item Rate
1095 days
Jaipur
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,000
Yes
As Per RFP
₹13 L
Yes
Jaipur
12 Apr 2024
8 Feb 2024
18 Mar 2024
8 Feb 2024
18 Mar 2024
11 Mar 2024
12 Feb 2024
Amount
DIESEL GENERATOR (Make: Kirloskar-KOEL) 400KVA DG set with acoustic enclosure with accessories inclusive of 6 Numbers of 12 V,180 AH lead acid batteries along with leads, day fuel tank, fuel piping from fuel tank to Engine, fuel tank to fuel storage tank, Residential silencer, Engine cold start kit, suitable size termination box (Cable / Bus duct) with extended Alternator terminal with bus bars including control switchgear & Exhaust System etc as installed at site.
UPS SYSTEM (Make: Delta) 400 KVA double conversions online IGBT based UPS with active/ Passive filter as installed at site with isolation transformer as installed at site
Battery Bank (AMRON Quanta) 12V VRLA 200AH (Min) battery bank with Battery Breaker suitable for the above UPS and Battery bank with copper cable of adequate rating from UPS to battery as installed at site (Each Bank includes 38 batteries of the mentioned model).
UPS SYSTEM (for other load) (Make: Emerson) 2 x 20 KVA Parallel redundant double conversion IGBT based with active! Passive filter as installed at site with isolation transformer as installed at site
Battery Bank (AMRON Quanta) 12V SMF mono block 100AH (Min) battery bank with Battery Breaker as installed at site (Each Bank includes 34 batteries of the mentioned model).
Main LT Panel MAIN LT Panel including of followings as installed at site but not limited to: A. INCOMER: - 2 Nos 1250 Amps and 2 nos of 1250Amps EDO TYPE ACB 50 kA, 4 pole, microprocessor release, and Motor wound spring charged closing mechanism. Each Incomer shall have one set of the following items: B. BUS COUPLER :- ACB, 1250 Amps, 50 kA, microprocessor release, Motor wound spring charged closing mechanism, EDO type, -01 No Indication Lamps, LED type, for breaker 'ON’, ’OFF’,’TRIP’ indication with SP MCB control fuses- 3 sets Suitable arrangement, interconnection required for electrical and mechanical interlock among 2 Nos. Incomers and 1 No Bus coupler - 01 Set Outgoing Feeders: -:-MCB, 630 Amps, 4 Pole, 36kA, microprocessor release -3 Nos. MCCB, 400 Amps, 4Pole, 36 kA, microprocessor release -5 Nos. MCCB, 160 Amps, 4 Pole, 25 kA -3 Nos. MCCB, 100 Amps, 4Pole, 25 kA -5 Nos MCCB, 63 Amps, 4Pole, 25 kA -3 Nos. 32 Amps, 4 Pole, 25 kA -1 Nos. Indicating lamps LED type, for breaker “ON“,“OFF“,“TRIP“ indicate on with SP MCB control fuses 14 Sets.( only for ACBs )As installed at site
APFC panel 300 kVAR automatic, manual Power Factor Correction Panel including followings & as installed at site: Capacitors Type - MD -XL,500V, 3 ph, 50 Hz
PAC Panel 2 nos of PAC Panel, including the followings & as installed at site: A. INCOMER: 1 Nos 400 Amps microprocessor based MCCB 36 kA 4 pole B. Outgoing: 6 nos 100 Amps microprocessor MCCB 25 kA 4 pole Outgoing Feeders: - 3 Nos CTs, 15 VA, class 1.0 and control circuit wiring with SP MCB control fuses.
3 Phase Transformer of 750 kVA (Make: United)
Lighting DB for item no 11, 12, 13, 14, 15, 16, 17 details given below as installed at site
Double door Distribution Boards including surge arrester for each phase (For Light DBs only): - 12-way TPN
Incomer - 63 Amps TPN -1 nos
Outgoing - 36 nos SP MCB
Double door Distribution Boards including surge arrester for each phase (For Light DBs only): - 12-way TPN Outgoing - 35 nos SP MCB
Incomer - 63 Amps TPN -1 nos
Outgoing - 36 nos SP MCB
Distribution Boards including surge arrester for each phase (For Light DBs only): - 12-way TPN Incomer - 63 Amps TPN - Outgoing - 36 nos SP MCB
UPS OUTPUT PANEL/PDU (for Rack Loads) as installed at site UPS output Panel, including following: Incomer: 400 Amps 36 kA 4pole microprocessor based MCCB 1 no. Outgoing: 16 Amps SP MCB – 4 no. 32 Amps SP MCB – 32 No. 32 Amp TP MCB – 10 no, 63 Amp TP MCB – 3 no.
CABLING Upkeep and maintenance of 1100 volt grade, PVC insulated and armored, copper or aluminum conductor cables of the following sizes as installed at site: for item no 21, 22, 23, 24, 25, 26, 27,28
4 core x 4 sq. Mm. Cu armored Cable (As installed)
4 core x 6 sq.mm. Cu. Armored (As installed)
4 core x 16 sq.mm. Cu. Armored (As installed)
4 core x 25 sq.mm. Cu. Armored (As installed)
1 core x 300 sq.mm. Cu. armored cables (As installed)
3.5 core x 400 sq.mm. Al. armored cables (As installed)
3.5 core x 150 sq.mm. Al. armored cables (As installed)
3.5 core x 120 sq.mm. Al. armored cables (As installed)
EARTHING
Upkeep and maintenance of 3.0-meter-long gel type earthling with copper electrode as installed at site. (As installed)
Upkeep and Maintenance of 600 X 600 X 3 mm copper Plate Type Earthing as installed at site. (As installed)
LIGHTING & POWER WIRING Upkeep and Maintenance of standard wiring electrical points including Wires, sockets/switches (6 Amps,16 Amps & 32 Amps) etc as installed at site: (As installed)
LIGHTING FIXTURES (make: Philips) Upkeep and Maintenance of the following fixtures wired with high Frequency ballasts, lamp holders and complete with lamps / LED fixtures as installed at site:
2 x PL - C 18 watts recessed ceiling mounting light luminaries with recessed glass Raindrops
2 xPL -L 36 watts decorative panel lights white direct luminaries for modular ceiling.
1 x 18 watts recessed mounting Down light luminaries with recessed glass Raindrops.
2 x 36 watts decorative Down lights white direct luminaries.
40 wattsP/F recessed type 2'x2' sized standard quality LED lighting fixtures
Maintenance of PAC auto changeover switches per the specs
Maintenance of Automatic fuel level monitoring with flow meter tank
Air Conditioning System
PRECISION PACKAGED UNITS (Make: Emerson) as installed at site with Indoor and Outdoor units 20 TR (min) sensible capacity Precision air - conditioning unit for Datacenter as installed at site.
Air grills with volume control damper
Return Air Motorized Damper
Comfort Cooling System (Make: Blue Star) a) Air cool duct able type AC units comprising ofb1 X indoor unit, 8.46 TR nominal capacity complete as installed at site.
Air Cooled Cassette Type AC Units (Make: Blue Star) comprising of: 1 x Indoor Unit, 3 TR Nominal Capacity complete & as installed at site.
Access Control System
ACCESS CONTROL UNIT (RTU), (Honeywell)
MAGNETIC LOCK SINGLE 600 LBS, (Bell)
ACCESS READER, (HID)
EXIT PUSH SWITCH
EMERGENCY DOOR REALEASE
TEMA SERVER, (Honeywell)
BIOMETRIC READER, (BioScrypt-4G)
RS 232 TO 485 CONVERTER, (Q Com)
RTU RELAY
MAGNET POWER SUPPLY 24V
MAGNET POWER SUPPLY 12V
DPS SWITCH
MAGNETIC LOCK DOUBLE 600 LBS, (Bell)
U SHAPE BRACKET FOR GLASS DOOR, (Bell)
TEMA SERVER POWER SUPPLY, (Honeywell)
BIO-METRIC WORKSTATION, (Secure-Admin)
CCTV SYSTEM
NVR MONITOR, (Samsung)
NVR REMOTE, (Samsung)
CCTV SYSTEM
RODIANT PANEL, (Maser)
STAND WITH BRACKET, (Honesty)
RODIANT SATELITE, (Maser)
WLD SYSTEM
WLD PANEL 4 ZONE, (Jay Fire)
WLD HOOTER, (Honeywell)
FIRE ALARM SYSTEM
FIRE ALARM PANEL, (Honeywell)
LOOP POWER MODULE
LOOP CARD DRIVER
485 COMM. CARD
NETWORK MODULE, (Honeywell)
REPETER PANEL, (Honeywell)
PHOTO ELECTRIC SMOKE DETECTOR WITH BASE,(Honeywell)
MANUAL CALL POINT
HOOTER CUM STROBE
CONTROL RELAY MODULE
MONITOR RELAY MODULE
ISOLATER RELAY MODULE
BATTERY, (AMCO-BEST)
RESPONSE INDICATOR, (Honeywell)
PANIC WAR, (DAFIKAS)
VESDA
VESDA 4 ZONE PANEL, (XTRALIS)
POWER SUPPLY
DISPLAY MODULE
P.A SYSTEM
RACK For PA &NVR
CEILING MOUNT SPEAKER, BOSCH
MAIN CONTROLLER, BOSCH
AMPLIFIER 200 W, BOSCH
CALL STATION, BOSCH
FM 200 SYSTEM
FM-200 CYLINDER WITH ASS., KIDDE
GAS RELEASE PANEL, Honeywell
ABORT SWITCH WITH MOUDLE, ADWARDS
MANUAL SWITCH WITH MOUDLE, SUPER FIRE
SERVICE DIS-CONNECT SWITCH WITH MOUDLE, ADWARD
FM 200 NOZZLE, KIDDE
PRESSURE TRANSMETER
POWER SUPPLY
2 Kg NAF PIV Fire Extinguisher, (Safex)
5 Kg ABC Type PIV Fire Extinguisher, (Safex)
CO2 4.5 kg portable Fire Extinguisher, (Safex)
DDC PANEL, (RITTAL)
IPC CONTROLLER, (Honeywell)
EXPIO CONTROLLER(Honeywell)
TEMP CUM RH SENSOR(Honeywell)
485 TO LAN CONVERTOR, (SAN-TELEQUID)
232 TO 485 CONVERTOR, (Q COM)
TANK LEVEL TRANSMITER, (TECHTROL)
EBI SERVER WITH MONITOR, (DELL)
PLC CONVERTOR, (SAN-TELEQUID)
Projector PT-F200NT XGA, (Panasonic)
Description of Work / Item(s)
Amount
Civil Work
FIRED RATED DOOR with lock and heavy-duty door closer.
WOODEN DOOR Single and double Leaf for BMS and Storage Rooms, NOC and Call Centre area.
Glass Door with 12 mm toughened glass, floor spring, arrangement for access control, handle, lock etc.
13mm thk nitrile rubber insulation with Aluminium Foil use under the false flooring & true ceiling with adhesive and pvc jointing tapes wherever necessary as per standard installation (Server Room Only)
Productivity work chair
Long back executive chair, Visiting chair
Vertical blinds, aluminium perforated, of approved shade to be used for covering the glass wall and windows excluding NOC & Development Centre.
Sofa set with 3 + 2 seating arrangement along with Tea table
Wooden Door with Louvers covering Fire suppression Cylinder
Fire Safe (300 lt) Godrej for Media/ backup tapes
Ramp & steps
Fire rated Glass window with powder coated Aluminium Frame for Data Centre Area
H.T. Works:
Cables and Terminations 1(3C x 240 Sq.mm), 11kV cross linked polyethylene (XLPE) insulated aluminium conductor steel armoured cables buried underground. ( As installed)
1(3C x 240 sq.mm), 11kV cross linked polyethylene (XLPE) insulated aluminium conductor cable gland, outdoor type cable sealing kits, insulation tape,
HT METERING CUBICLE (OUTDOOR)
11kV HT Metering Cubicle including all CT's,PTs etc. Suitable for cable entry on both sides.
HT Panel with 1 Incomer and 3 Outgoing of 630A,11kV,20KA HT VCB Breaker (EDO type)
Battery Charger: Battery charger with one set of 24V DC 100AH station batteries with suitable battery charge inclusive of 6 way SPN DB
3 Phase, 50 Hz, Copper Wound, Oil Immersed, Core Type Transformer of 1000 kVA Rating, ONAN (Oil Natural Air Forced) OLTC with voltage ratio 11/.433 kV, Connection HV/LV: delta/star. The Transformer should have one side HT cable termination and secondary provision for bus bar for terminating bus duct.
Transformer Output breaker of 1600 Amp breaker panel(outdoor type)
Spreading of 40 mm metal in outdoor H.T.yard - upto 100 mm - thick layer ( As installed)
Fire buckets with stand filled with fine river sand. 2 buckets with round botton, red painted duly marked as FIRE
LT PANELS
415 Volts, 3Phase 50HZ Panel as per Specification "415V switch boards" as per the specifications and schematic drawing complete as required. DG SYNC CUM AMF panel
415 Volts, 3Phase 50HZ Panel as per Specification "415V switch boards" as per the specifications and schematic drawing complete as required. Datacentre Main panel - 1 and 2 as per RFP Schematic
Supply, loading, unloading, erection, testing & commissioning of 415 Volts, 3Phase 50HZ Panel as per Specification "415V switch boards" as per the specifications and schematic drawing complete as required. 200KVA/ KW DATSON Isolation Transformer
415 Volts, 3Phase 50HZ Panel as per Specification "415V switch boards" as per the specifications and schematic drawing complete as required. 40 KVA UPS output panel
415 Volts, 3Phase 50HZ Panel as per Specification "415V switch boards" as per the specifications and schematic drawing complete as required. PAC panel
415 Volts, 3Phase 50HZ Panel as per Specification "415V switch boards" as per the specifications and schematic drawing complete as required. CAC Panel -01
415 Volts, 3Phase 50HZ Panel as per Specification "415V switch boards" as per the specifications and schematic drawing complete as required. CAC Panel -02
415 Volts, 3Phase 50HZ Panel as per Specification "415V switch boards" as per the specifications and schematic drawing complete as required. PDU 1A/2A and 1B/2B
415 Volts, 3Phase 50HZ Panel as per Specification "415V switch boards" as per the specifications and schematic drawing complete as required. 380 KVAR APFCR bank
32A, DP, MCB Isolator wall mounted type with suitable enclosure and required accessories for Comfort AC as per RFP Schematic
800 Amp Rating Automatic Changeover panel (installed in server room) ( As installed)
Bus duct for Transformer-01 & 02 up to the Data Centre LT panel-01 & 02 Respectively. DG Sync Panel to the DC LT panel-01 and 02 1600A Aluminium IP65 Straight Feeder ( As installed)
Bus duct for DG-01, 02 & 03 up to the DC Sync Panel-01 & 02 Respectively 800A Aluminium IP65 Straight Feeder ( As installed)
Track Busways overhead power distribution in data centres and Labs with spring pressure copper conductors in continuous PVC insulation, Extruded aluminium housing, light weight to install with Hitech rods and anchor fasteners. Housing will have continuous bottom access to facilitate insertion of outlet box anywhere along the length. outlet boxes are suitable to reverse to face either cold aisle or hot aisle Busway are for indoor use, finger proof to UL. 100Amp Track Busway,100%N, Busway Section, 3 mtr 200% Note: Proposed busduct shall be capable to plun the tapp-off box at any point of busway. ( As installed)
Providing the end terminations with copper lugs for all the above cables with Double compression brass cable glands, taping, crimping, gland and armour earthing, complete electrical system of DC
power wiring circuits (Raw power and UPS Power)
INTERNAL LIGHT FIXTURES
complete DC excluding NOC, CC Area
Motion Sensors for multiple areas for automatic switching the lights on an off
STEEL ITEMS
Rubber mats, first aid box, shock treatment charts and other sundry items (sizes/capacities to be got approved).
PRECISION AIR CONDITIONING UNITS (SWEGON BLUE BOX) UEDH 100.4 HH (+)
Air cooled condenser with fan speed controller Inside design condition Server Room - 22 +/- 1 deg. C & Relative humidity: 50% RH +/- 5% a. Nominal Capacity 26 TR - e. BMS Interface for integration with necessary network integration card
Supply air floor grilles with Damper, 600mm x 600mm
CAC/VRV
Outdoor Units: MULTI-VRF units complete with 100% Inverter driven scroll compressor, 22 HP (Cooling-Only), (2x5)
Indoor Comfort AC units:4-Way Cassatte Unit (2TR)
Indoor Comfort AC units: 4-Way Cassatte Unit (2.5TR)
Indoor Comfort AC units: 4-Way Cassatte Unit (3TR)
Indoor Comfort AC units: 4-Way Cassatte Unit (4TR)
Indoor Comfort AC units: MSP Ductable (4.6TR)
Indoor Comfort AC units: Hi-Wall (1TR)
Indoor Comfort AC units: Wireless Remote
Wired Remote
Centralize Remote (Touch Type)
32A, 1 PH, IP Metered PDU (Strip level Monitoring) Rack PDU, Metered, Zero U, 32A, 230V, (20)C13 & (4)C19
32A, 3 PH, IP Metered PDU (Strip level Monitoring) Rack PDU, Metered, Zero U, 32A, 230V, Minimum of 6 No's C13 & 6 No's C19
Cold Aisle Containment System_Row -1 (SR1 to SR72+ 10NR) includes:a. Start & End Roof Element 800x1200 Stable roof elements in a composite metal with a high level of light permeability)b. Centre Roof Element 600x1200 (Stable roof elements in a composite metal with a high level of light permeability)C. Door Element 1200W x 2100H (Slimline door element with viewing window, sliding door) ( As Installed)
UPS (Delta)
UPS of 200 KW (Model UPS204DH), 3 Phase IN, 3 Phase out, 415 V, Modular hot swappable Design Consisting capable to parallel up to minimum 400KW of IT load. 80 batteries of 12V SMF (EXIDE 12V 130AH) capacity along with each UPS
UPS of 40 KW (Model GES403HH3300B0), 3 Phase IN, 3 Phase out, 415 V, Modular hot swappable. 40 batteries of 12V SMF (EXIDE 12V 42AH) capacity along with each UPS, BMS system emergency light and Non_IT Load
Battery MS Stand, Inter cell connection, Battery to UPS main Cable for 200/40 kVA UPS
DG Set (Kirloskar-KOEL Green)
500 KVA (+/- 5%) DG set and (Cable /Bus duct) with extended Alternator terminal with bus bars includingcontrol switchgear etc.
Exhaust of DG Sets including providing suitable self-supporting arrangement
Control Cabling
Copper earthing for DG set
Intelligent Addressable fire alarm control panel with 1 loop card and battery backup of 24 hrs in normal condition and 30 min in alarm condition with necessary accessories
Multisensor Detector with accessories (SMOKE DETECTOR)
Response Indicator with accessories
Fault Isolators module with accessories
Addressable Control relay modules. (for GRP, ACS, Hooters, PAS)
Addressable Manual Call Points with accessories
Addressable monitor modules with accessories (monitoring VESDA)
Sounders with strobes with accessories as per technical specification
Ceasefire 4 Kg Fire Extinguisher Clean Agent,
Public Address System.
6W Ceiling Mount Speaker (BOSCH)
Volume Control (for DC Manager Cabins)
Access Control System.
Access Control System TCP/IP enabled 2 Reader Access Door Controller with Power supply and housing
Fingerprint biometric reader with smart card reader with accessories
Smart Card reader with accessories
Smart Cards
electromagnetic lock with inbuilt magnetic contact & Power Supply with accessories
Emergency break glass unit with accessories
Access Management Software with Time & Attendance Software (DDS)
PC for Access Control Software
Card Printer with accessories
CCTV Surveillance System.
PC for Monitoring camera (ACER)
32" Colour LED monitor as per technical specification
Aspiration based Detection System
Aspiration Detection Panel for Server Room (Fire Panel)
Power Supply Unit with accessories as per technical specification
Electronic Hooter (Pantry side)
Fire Suppression System
120 Ltr. seamless cylinder with valve
Master Cylinder Kit with following items - Pr. Gauge + Low Pr. Supervisory Switch - Electromagnetic Actuator - Manual Actuator - Pneumatic Actuator - Flexible Discharge Hose - Flexible Actuation Hose
End Slave Cylinder Accessories as per technical specification Pressure Operated Control Head Actuation Hose, 30" Discharge Hose, 2" x 31"
Gas Discharge Nozzles
Gas Release Panel (BMS room)
Abort Switch
Release Switch
Hooter with Power Supply
Rodent Repellent System
Rodent Repellent System with stands
Water Leak Detection System
Water Leak Detection Panel with Modbus connectivity
Water Leak detection Cable Sensor – 10 mtrs (Mux room)
Water Leak detection Cable Sensor – 25 mtrs(Server room)
Electronic Hooter
Workstation Operator Machine: Intel i3 processor 3rd generation, 500GB HDD, 4GB RAM, 52X CD RW ,21" colour monitor, USB Mouse, 2 serial, 1 parallel port & Windows operating system
Building Management System Software
Colour Laser Printer
32 Bit DDC Controller above along with System Integration Units, Powder Coated cabinets as per IS Standards for Electrical Panels and all internal terminations and cabling to monitor temperature & humidity in server room. DDC for integration of various physical security subsystems mentioned and Temperature and humidity monitoring PAC Units Integration (30 Points / Unit) UPS Units Integration (30 Points / Unit) Fire Alarm System (BMS room) Water Leak Detection System
Temperature & Humidity Sensor
TV Screens for Manager Cabins with wall mounted 32" LED TV screen for DC manager Cabin-01 and -02
Monitor Screens for Manager Cabin-03: Wall mounted 42" LED Monitor screen for DC manager Cabin-03 with required length of VGA/HDMI Cable
Data Centre Infrastructure Management software per rack perpetual license for 80 Racks and as per RFP specification. DCIM (Data Centre Infrastructure Management) Application for Power, Cooling, Space, Environment, Safety , security Infrastructure devices Monitoring & Management to meet RFP compliance.Non IT Devices:(Device to be Monitored & Managed, Rack, PDU, Energy Meters, UPS PAC, DG set, FSS, FDA, WLD, RRD) Network Infrastructure Monitoring Application ModuleT&H Sensors- 26 No's.Temperature & Humidity Sensor (RS485, Modbus) - Minimum Capability - a. Should have digital display, b. 2 RS485 communication port, c. Temperature measurement accuracy +3- or -3-degree, d. Humidity measurement accuracy +5 % or -5 %, e. should have local alarm for identification. Controller-2 No's.Minimum Capability - 1. Should be capable to monitor up to 20 temperature & humidity sensors, up to 16 intelligent devices (SNMP & RS485 Modbus enable, 2. built in webpage of its own for monitoring 3. local storage of data upto 7 days 4. should be capable of sending email notification directly, 5. should be capable to share data with third party application over Modbus-IP or BacNet-IP or SNMP polling & trap.
Description of Work / Item(s)
Amount
Project Manager Overall in charge responsible for All Non-IT Activities RSDC P-1, P-2 & P-3
Supervisor- Overall in charge responsible for All Non-IT Activities RSDC P-1, P-2 & P-3
Electrical Engineer
Electrician, UPS and DG Operator cum Technician
PAC and CAC Operator cum Technician
Security staff
DCIM, BMS Operator
Housekeeping
Description of Work / Item(s)
Amount
Air Conditioners (Daikin Make) as installed at site (54 HP)
Ceiling mounted cassette type Acs-3.3 TR
Ceiling mounted cassette type Acs-2.5 TR
Ceiling mounted cassette type Acs-4 TR
Ceiling mounted cassette type Acs-1 TR
Ceiling mounted cassette type Acs-1.5 TR
Wall mounted cassette type Acs-2 TR
Wall mounted cassette type Acs-1.3TR
Wall mounted cassette type Acs-1.8 TR
Wall mounted cassette type Acs-0.6 TR
PRECISION PACKAGED UNITS (Emerson Make) as installed at site. 10 TR (min) sensible capacity Precision air - conditioning unit for Datacenter
UPS (Emerson Make) for item no 13 to 16 as installed at site.
20 KVA 3 Phase UPS
12V 42AH (AMARON Quanta) Each bank consists of 34 batteries.
80 KVA 3 Phase UPS
12V 200AH (AMARON Quanta) Each bank consists of 34 batteries.
Light Fittings &Luminiar (Bajaj Make) for item no 18 to 23 as installed at site.
2X36 Watt CFL/LED light panel (Recess)
2X18 Watt CFL/LED light panel (Recess & surface)
1200 mm sweep 5-star ceiling fan
400mm sweep wall fan
1X28 watt T-5 Light
Hooter
Fire Suppression System for server farm area for item no 25 to 30 as installed at site.
80 Liters seamless NOVEC cylinders
Manual release unit & abort
Sinorix1230
Discharge nozzles
Optical smoke detector
Gas release panel (Fire suppression system)
WLD (Make: Synopsys)
Rodent (Make: Maser)
DG sets (Cummins-Sudhir make) for item no 34 &35 as installed at site.
200 KVA, 415-volt, 50 Hz, 3 phase AC silent DG set
125 KVA, 415-volt, 50 Hz, 3 phase AC silent DG set
LT Panels for item no 37 as installed at site.
comprising of following: 630 Amp, FP,50 KA MCCB-1 No), (300 Amp,FP,25 KA MCCB-1 No), 300 A, FP, contactor-1 No), (400A TP 35 KA MCCB-1 No), (250 A TP 25 KA MCCB-1 No), (160 A TP 16 KA MCCB-1 No)(63 A, FP,10 KA, c curve MCB-1 No), 63A, FP,10 KA, c curve MCB-4 Nos, APFC section capacitor Bank-100 KVAr, AMF section, protection section, meeting section. 400 Amps 5 Nos MCCB, 125 Amps 2 Nos. MCB, 32 Amps 35 Nos Make Legrand, 16 Amps MCB 52 Nos., 63 Amps 2 Nos., 20 Amps 1 Nos., 6 Amps 4 Nos. Main LT 320 Amps 4 Pole for DG supply 1 Nos., 160 Amps 4 Pole 7 Nos., 100 Amps 4 Pole for VRV 5 Nos.
Description of Work / Item(s)
Amount
Electrician, UPS and DG Operator cum Technician
PAC and CAC Operator cum Technician
Description of Work / Item(s)
Amount
BOQ-1 : Overall Maintenance for 36 months for items installed in RSDC P-1 as per items details enclosed in Annexure-1 of RFP. The Maintenance is to be carried out as per maintenance schedule of Original OEM. The bidders should have back to back to maintenance contract for 24 X 7 with original OEM of items installed as per details given in RFP.
BOQ-2 : Overall Maintenance for 36 months for items installed in RSDC P-3 as per items details enclosed in Annexure-3 of RFP. The Maintenance is to be carried out as per maintenance schedule of Original OEM. The bidders should have back to back to maintenance contract for 24 X 7 with original OEM of items installed as per details given in RFP.
BOQ-3 : Overall Operation for 36 months for Systems installed in RSDC P-1 & P-3 as per items details enclosed in Annexure-1 &3 and as per number of persons / shifts details, Service Level Agreements (SLA) given in RFP. The bidder has to deploy the manpower at site at both data center premises as per details given in RFP.
BOQ- 4 : Overall Maintenance for 36 months for items installed in RSDC P-2 as per items details enclosed in Annexure-2 of RFP. The Maintenance is to be carried out as per maintenance schedule of Original OEM. The bidders should have back to back to maintenance contract for 24 X 7 with original OEM of items installed as per details given in RFP.
BOQ-5 : Overall Operation for 36 months for Systems installed in RSDC P-2 as per items details enclosed in Annexure-2 and as per number of persons / shifts details, Service Level Agreements (SLA) given in RFP. The bidder has to deploy the manpower at site at both data center premises as per details given in RFP.
VERTIV ENERGY PRIVATE LIMITED
VERTIV ENERGY PRIVATE LIMITED
VERTIV ENERGY PRIVATE LIMITED
VERTIV ENERGY PRIVATE LIMITED
VERTIV ENERGY PRIVATE LIMITED
VERTIV ENERGY PRIVATE LIMITED
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.70 MB
RFP.pdf
Tender Documents • 2.98 MB
BOQ_677149.xls
BOQ • 0.50 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .