Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.3 LAccepted-AOC AZAD COLONY B 90 FEET ROAD SOURA SRINAGAR J K 190011 | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190011 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹31.2 L+₹89,560 (2.95%)Rejected-AOC SCHEME NO 07 BLOCK NO 22 FLAT NO 03 NEW GURDASPUR DISTT GURDASPUR PB 143521 | GURDASPUR | PUNJAB | 143521 | L2 | Rejected-AOC OTHER THAN LOWEST | |
| 3 | L3₹33.5 L+₹3.2 L (10.4%)Rejected-AOC | L3 | Rejected-AOC OTHER THAN LOWEST | |
| 4 | L4₹33.8 L+₹3.5 L (11.4%)Rejected-AOC | L4 | Rejected-AOC OTHER THAN LOWEST | |
| 5 | L5₹34.9 L+₹4.6 L (15.1%)Rejected-AOC | L5 | Rejected-AOC OTHER THAN LOWEST |
Tender Value
₹50.0 L
EMD Value
₹99,980
Closing Date
24 Feb 2025, 6:00 pmClosed
GE 969 EWS C/O 56 APO
GE 969 EWS C/O 56 APO
REPAIR/MAINT OF 2 POLE AND 4 POLE STRUCTURE AND ALLIED INFRA AND OVERHAUL OF DG SETS, DISINFECTORS AND ALLIED ITEMS AT VARIOUS LOCS UNDER GE 969 EWS
2025_MES_696053_1
CA NO 969 WS - /2024-25
Open Tender
Civil Works
Item Rate
180 days
GE 969 EWS
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE 969 EWS
₹99,980
Yes
28 Mar 2025
1 Feb 2025
1 Mar 2025
1 Feb 2025
24 Feb 2025
17 Feb 2025
Amount
Servicing of Diesel engine Generating sets 15 KVA to 25 KVA Rating to be carried out as per schedule given as under. B - check :- (Every 100 Hrs or 6 months whichever is earlier) (i)Change lubricating oil (ii) change lubricating oil filters (iii)change fuel filters (iv) Change coolant (v)check Engine wiring for damage (vi)Drain fuel supply tank (vii) Change by pass lubricant filters (viii) Change air filters (ix) Check oil pressure (x)Change fuel water seperator. C - Check :- (Every 1500 Hrs or 1 year whichever is earlier) (i) Adjust valves (ii)Steam clean engine (iii)Replace hoses if required (iv) Check turbo charger mounting nuts (v ) c Check engine oil heater (vi) clean rediator (vii) Inspect following parts and replace if required (Alternator,starter etc ) (viii)Clean fuel from inside (ix) Change engine oil. Note :(i) B-check and C check spare parts will be measured and paid separately under supply only items (fixing charges included with the servicing of DG set)
Servising of Diesel engine Generating sets 30 KVA to 63 KVA Rating to be carried out as per schedule given as under. B - check :- (Every 100 Hrs or 6 months whichever is earlier) (i)Change lubricating oil (ii) change lubricating oil filters (iii)change fuel filters (iv) Change coolant (v)check Engine wiring for damage (vi)Drain fuel supply tank (vii) Change by pass lubricant filters (viii) Change air filters (ix) Check oil pressure (x)Change fuel water seperator. C - Check :- (Every 1500 Hrs or 1 year whichever is earlier) (i) Adjust valves (ii)Steam clean engine (iii)Replace hoses if required (iv) Check turbo charger mounting nuts (v)c Check engine oil heater (vi) clean rediator (vii) Inspect following parts and replace if required (Alternator,starter etc ) (viii)Clean fuel from inside (ix) Change engine oil. Note :(i) B-check and C check spare parts will be measured and paid separately under supply only items (fixing charges included with the servicing of DG set,.)
Servising of Diesel engine Generating sets 82.5 KVA to 160 KVA Rating to be carried out as per schedule given as under. B - check :- (Every 100 Hrs or 6 months whichever is earlier) (i)Change lubricating oil (ii) change lubricating oil filters (iii)change fuel filters (iv) Change coolant (v)check Engine wiring for damage (vi)Drain fuel supply tank (vii) Change by pass lubricant filters (viii) Change air filters (ix) Check oil pressure (x)Change fuel water seperator. C - Check :- (Every 1500 Hrs or 1 year whichever is earlier) (i) Adjust valves (ii)Steam clean engine (iii)Replace hoses if required (iv) Check turbo charger mounting nuts (v )c Check engine oil heater (vi) clean rediator (vii) Inspect following parts and replace if required (Alternator,starter etc ) (viii)Clean fuel from inside (ix) Change engine oil. Note :(i) B-check and C check spare parts will be measured and paid separately under supply only items (fixing charges included with the servicing of DG set,.)
S&F, new air filters cartridge elements with 'O' ring for 15 to 25 KVA DG set, complete all as specified and as directed.
S&F, new air filters cartridge elements with 'O' ring for 30 to 63 KVA DG set, complete all as specified and as directed.
S&F, new air filters cartridge elements with 'O' ring for 63 to 160 KVA DG set, complete all as specified and as directed.
Supply only fuel oil filter cartridge elements with 'O' ring for 15 to 25 KVA DG set, complete all as specified and as directed.
Supply only fuel oil filter cartridge elements with 'O' ring for 30 to 63 KVA DG set, complete all as specified and as directed.
Supply only fuel oil filter cartridge elements with 'O' ring for 63 to 160 KVA DG set, complete all as specified and as directed.
Supply only lubricant oil filter cartridge elements with 'O' ring for 15 to 25 KVA DG set, complete all as specified and as directed.
Supply only lubricant oil filter cartridge elements with 'O' ring for 30 to 63 KVA DG set, complete all as specified and as directed.
Supply only lubricant oil filter cartridge elements with 'O' ring for 63 to 160 KVA DG set, complete all as specified and as directed.
Supply only fuel water separator filters cartridge elements with 'O' ring for 63 to 160 KVA DG set, complete all as specified and as directed.
Material and labour for engine oil 20 W 40 grade in DG set, complete all as specified and as directed.
Material and labour for coolent of DG set, complete all as specified and as directed.
Material and labour for distilled water for battery, complete all as specified and as directed.
S&F, AVR of DG set, of capacity (10 KVA to 50 KVA) as per site requirment complete all as specified and as directed.
S&F, AVR of DG set, of capacity (62.5 KVA to 160 KVA) as per site requirment complete all as specified and as directed.
Cleaning of radiator complete from DG sets cleaning/scraping of depositing manualy from outside of the radiator, cleaning of all copper tubes of radiator with descaling solution from inside & outside with forged feed method & with water and air compressor (by using separate chemical pump water pump & compressor) plugging of all leakage in welding, brazing of copper tubes, cleaning of fins and replacement of gaskets etc for the following capcities of DG sets :-
(a) DG sets upto 50 KVA
(b) DG sets 62.5 KVA to 160 KVA
M&L for cleaning of Exhaust pipe of silencer, cleaning of silencer to remove carbon deposit inside exhaust and refixing including replacement of worn out rubber gasket packing and nut, bolts, complete all as specified and as directed.
Repair and maintenance of alternator of type, with opening the cover cleaning all the parts, removing dust with tightening all the electrical connection, checking the serviceability of automatic voltage regulator and voltage set,ting, tightening the loose connections, checking and set,ting the alighment properly cleaning air inlet, opening the terminals box top and front cover and tightening the cable leads, checking insulation resistance closing the covers and testing complete all as specified and as directed for the following capacity of DG set, :-
(a) Upto 63 KVA DG set, of any make
(b) 63 KVA to 166 KVA DG set, of any make
Disconnecting the defective/burnt Alternator from the engine and removing it from the base frame and shifting it to the workshop, removing rotor and cutting the field copper winding or armature winding and cleaning the slots complete for rewinding and using super enameled copper wire, varnishing and drying using three coats of insulating varnishing reassembling the motor after repairs/ re-set,ting complete re-installation at site including transportation from the site to and pro, complete of capacity upto following.
(a) DG sets Upto 40 KVA of any make
(b) DG sets 50 KVA to 63 KVA of any make
(c) DG sets 82.5 KVA of any make
(d) DG sets 100 KVA to 160 of any make
M&L for repair and maintenance of metal doors (i.e., front and back door) of DG set, of capacity from 18.75 KVA upto 166 KVA, incl taking down door to the work shop from site and fixed suitable hinged incl welding work if required and painting the same as existing colour and refixing the same on DG set, complete all as specified and as directed.
Replacement of old unserviceable self starter with new self starter, 12 Volts, DC of make as approved by Engr-in-Charge for any make and type of Diesel Generator set, of capacity upto 160 KVA, complete all as specified and as directed.
Taking down U/S battery 12V from the DG set, and supply and install 12 V 180AH maintenance free battery including brass clamps, copper lead 2 Mtr length, battery stand complete testing and commissioning, complete all as specified and as directed.
M&L for replacement of battery lead set, suitable for 180 AH capacity 1.5 mtr long including GM terminals one end coper lug and other and including 0.5 mtr connecting both end with gun metal terminals, complete all as specified and as directed.
Taking out Diesel Tank of any capacity carefully including disconnection from system, descaling the diesel tank with water pressure and removing the complete deposited, drying the tank and painting two coat with super enmelled paint out side the tank size, replacement of gate valve and fixing the tank in original location and connection with existing diesel line with replacement GI/MS fittiing replacement of diesel indicator glass/PVC tube with necessary fitting,repair to any leakage,cleaning and testing of fuel line upto FIP inlet including making of locking arrangements complete of DG set, Capacity upto 160 KVA, complete all as specified and as directed.
Cleaning of the disinfector tank of any make ,disconnecting the motor ,rod and other connecting parts with replace damaged parts and servicing of all parts includin reassembing and connections with existing water pipe line with necessary fitting,repair to any leakage,cleaning and testing complete, complete all as specified and as directed.
M&L for Tank calibration including provn of tank level indicator of fibre tube with indication of full tank capacity of showing , complete all as specified and as directed.minimum reading of 0.5 ltrs for DG set, upto 200 KVA capacity, complete all as specified and as directed.
Overhauling of DG set enigne upto four cylinder of capacity upto 40 KVA by dismantling/strip opening of the DG set, for overhauling by removing the cylinder head assemble including facing and grinding, piston connecting rod, cylinder liner, oil sump and injector including replacement of worn out spare i.e., cylinder liner with 'O' ring, Piston assembly, connectin rod, large end bearing pair, valve seat, valve guide, FIP element, lubricant oil pump, gasket for cylinder, set, of O rings, set, of hose pipes, fuel pipes nozzle calibration, FIP caliberation, water pump assembly etc and reassembling the complete engine complete all as specified and as directed.
Overhauling of DG set enigne upto six cylinder of capacity upto 63 KVA by dismantling/strip opening of the DG set, for overhauling by removing the cylinder head assemble including facing and grinding, piston connecting rod, cylinder liner, oil sump and injector including replacement of worn out spare i.e., cylinder liner with 'O' ring, Piston assembly, connectin rod, large end bearing pair, valve seat, valve guide, FIP element, lubricant oil pump, gasket for cylinder, set, of O rings, set, of hose pipes, fuel pipes nozzle calibration, FIP caliberation, water pump assembly etc and reassembling the complete engine complete all as specified and as directed.
All as per Item No 39 above but of capacity 82.5 KVA to 160 KVA, complete all as specified and as directed.
Supply and fixing on load changeover switch Range 400A, 415V, 4P, confirming to IEC 60947-3, IS/IEC 60947-3 Conforms to Staggered terminals, Site convertible fuse version for open execution Flip-able handle above 400A Interchangeable dual shaft position with site convertibility along with SS enclosure version require separate cable gland box, complete all as specified and as directed.
All as per item No. 41 here in before but of capacity 200 Amp
All as per item No. 41 here in before but of capacity 100 Amp
All as per item No. 41 here in before but of capacity 63 Amp
Repair and overhalling of FIP Nozzle of capacity 15 KVA to 63 KVA, complete all as specified and as directed.
Repair and overhalling of FIP Nozzle of capacity 63 KVA to 166 KVA, complete all as specified and as directed.
S&F of Dynamo with 12 Volts DC, Diesel Generator set, of any capacity, complete all as specified and as directed.
Supply and fixing control cards for output supply of voltage stabilizer of capacity upto 200 KVA, complete all as specified and as directed.
Supply and fixing of control cards for input supply of voltage stabilizer of capacity upto 200 KVA, complete all as specified and as directed.
Supply and fixing of control card for high voltage cut off protection reduction of voltage and automatic ON after 10 second time delay, complete all as specified and as directed.
Supply and fixing of servo motor complete including pinion for voltage correction having speed of correction 8 volts per second of capacity upto 10 Kg Torque suitable for 15 KVA to 200 KVA Stabilizer, complete all as specified and as directed.
Supply and fixing of indicator lamps to show RYB phase of 3 phase 415 volt 50 Hz AC supply as replacement of defective indicator lamp in existing panel, complete all as specified and as directed.
Material and labour for complete rewiring for power and control circuit of voltage stabilizer using standard copper wire, replacement of thimbles, connectors numbering of wiring to all control and measuring instrument for capacity upto 200 KVA voltage stabilizer, complete all as specified and as directed.
Supply and fixing of Dimmer for servo stabilizer of capacities upto 200 KVA, complete all as specified and as directed.
M&L for filling /toping up of oil in servo voltage stabilizer having dielectric strength upto 35KVA at 2.5mm gap high voltage as per IS/IEC specification ofl low viscosity, complete all as specified and as directed.
Supply and fixing in replacement of burnt defective LT copper coil of stabilizer with new one made out of suitable size/guage of copper super enameled wire of high quality matching with the existing impendence and insulation including testing, complete all as specified and as directed.
Supply and fixing in replacement of Feed Pump suitable for 30KVA to 160 KVA DG set, including testing, complete all as specified and as directed.
Supply and fixing in replacement of LLOP sensor suitable for 30KVA to 160 KVA DG set, including testing, complete all as specified and as directed.
Supply and fixing in replacement of stop Soenoid suitable for 30KVA to 160 KVA DG set, including testing, complete all as specified and as directed.
Supply and fixing in replacement of DC Alternator suitable for 30KVA to 160 KVA DG set, including testing, complete all as specified and as directed.
Supply and fixing in replacement of Fuel Pipe long suitable for 30KVA to 160 KVA DG set, including testing, complete all as specified and as directed.
Supply and fixing in replacement of Tappet Cover Jain suitable for 30KVA to 160 KVA DG set, including testing, complete all as specified and as directed.
Supply and fixing of radiator Fan of any type and size upto 160 KVA DG set, complete all as specified and as directed.
Taking down existing unserviceable/ damage HPSV/ MH/ LED Security light/Flood fitting of any sizes and capacity,complete all as specified and as directed.
Supply and fixing of LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver,lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection, complete all as specified and as directed.
All as per above serial No. 66 but 60 watt capacity complete all as specified and as directed.
All as per above serial No. 66 but 70 watt capacity complete all as specified and as directed.
All as per above serial No. 66 but 90 watt capacity complete all as specified and as directed.
Supply and fixing in replacement of LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and as directed.
Supply and fixing in replacement of Garden Light LED type 20 Watt 230 Watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp, complete all as specified and as directed.
Supply and lay of cable PVC insulated unsheathed of size 1.5 sqmm 3 core copper conductor for service connections from junction box to light fitting, complete all as specified and as directed.
Supply and Fixing of LED Driver for security lights of Watts upto 20/30/45W to suit the Existing Make, complete all as specified and as directed.
Supply and Fixing of LED Driver for security lights of Watts upto 60/70/90 W to suit the Existing Make, complete all as specified and as directed.
S&F, GI Bracket bend to shape 1.2mtr long of size 40/32/25mm GI Pipe suitable for LED Street Light Fitting of size 35/60/70W including necessary fittings such as screw, clamps, hold fast etc, complete all as specified and as directed.
Supply, laying and testing of cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core, complete all as specified and as directed.
Supply and fixing of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP- 31 (9.00 metres long), complete all as specified and as directed.
Supply and fixing of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP- 31 (11.00 metres long), complete all as specified and as directed.
M&L for cement concrete for foundation fillings and mass conctere type D2 1:4:8 (using 40 mm graded aggregate), complete all as specified and directed.
M&L for cement concrete for mass fillings of poles, conctere type C2 1:3:6 (using 40 mm graded aggregate) complete all as specified and directed.
M&L for PCC 1:2:4 type B1 (using 20 mm graded hard stone aggregate), casting in cube of size required size at site by using necessary form work for Cooping of poles, complete all as specified and as directed.
Supply and install cross arms ,bracing,support,clamps channals, grill work etc fabricated from structural steel section including nuts bolts and washers of any size or as directed including two coat of aluminium paint over a coat of red oxide primer completed all as direcded.
Dismantling of ACSR conductors
Dismantling cross-arms of M.S. channel or angle sections etc. complete and setting aside for re-use with in 50m, complete all as specified and as directed.
Note:- Schedule of credit Rs 1,44,459.00 will be deducted from total amount quoted while accepting the bid. Details of schedule of credit is given in tender documents.
HARPAL ENGINEERS AND BUILDERS (BID ID -3247080)
M/s FAYAZ AHAMD WANI AND SONS (BID ID -3246548)
M/s BEECO CONSTRUCTIONS (BID ID -3247302)
M/S KULBIR SINGH SODHI AND CO (BID ID -3248181)
M/s Manmeet Builders (BID ID -3248065)
ANUSHA ENTERPRISES (BID ID -3248223)
M/s ABDUL AHAD AND SONS (BID ID -3247985)
M/S SUMJI BROTHERS (BID ID -3247958)
M/s SONA ULLAH LONE AND SONS (BID ID -3248049)
M/S GHULAM RASOOL LONE (BID ID -3248083)
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .