Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.4 LAccepted-AOC | ₹3.4 L Quoted ₹3.5 L | L1 | Accepted-AOC Due to lowest accepted |
| 2 | L2₹3.6 L+₹7,240 (2.07%)Rejected-Finance | ₹3.6 L+₹7,240 (2.07%) | L2 | Rejected-Finance Other than lowest |
Tender Value
₹5 L
EMD Value
₹10,000
Closing Date
8 Sept 2021, 6:00 pmClosed
Garrison Engineer Ludhiana
Garrison Engineer Military Engineer Services Near Jagraon Bridge Ludhiana-141001
REPAIR/MAINT TO AC PLANT IN DEPOT AREA AT BADDOWAL UNDER GE LUDHIANA
2021_MES_466561_1
GE/LDH-25/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Baddowal under GE Ludhiana
As per NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE Ludhiana
₹10,000
Yes
5 Oct 2021
9 Aug 2021
9 Sept 2021
9 Aug 2021
8 Sept 2021
17 Aug 2021
10 Aug 2021 - 16 Aug 2021
Amount
Repair to chilled water type compressor capacity 40 TR, Make : ACCEL Model SMC 100 of AC plant including opening the complete unit, repair to crank shaft including re-metalling, grinding and polishing to bring into standard size incld replacement of unserviceable parts such as piston complet (with pin, pin lock and ring set) connecting rod, shaft seal, discharge/suction valve big end bearing set, gudgeon pin set, main bush with collar, oil pump set, suction sleeve with collar, gasket, packing compressor oil and gas etc and re-assembling all as original incld replacement of worn out nuts bolt washers etc and testing complete Note : Spare parts reqd for replacement will be paid separately under relevant items.
Supply and replacement of following spares to suit compressor SMC-100 (Make : ACCEL) :-
Main bearing /Bush
CNR Bearing/Big end Bearing
Piston pin/Small end bearing
Piston complete with ring set 2 Grelip lock
Liner for SMC-100
Suction reed set
Discharge reed set
Shaft seal/Oil seal
Gear set for oil pump
Shaft for oil pump
Loader /Unloader from
Spring set (set of six)
Bush gear pump
Gasket set
O' ring set
Discharge valve grid
suction valve grid
Safty control valve
Suction valve
Discharge valve
Connecting rod
Dismantling and removing of electric motor of capacity 12.5 HP 415 volt 3 phase, shifting to civil workshop, strip opening of motor, cutting of eisting burnt winding of stator, cleaning of stator re-winding thitable same with super enamelled copper wire.
All as per serial item No 3 here-in-before but 10 HP
All as per serial item No 3 here-in-before but 5 HP
Disconnecting, dismantling and removing central shaft of air handling units of central AC plants of any make for repair, transporting to the work shop, opening up for repairs carry out the repairs, of shaft including re-metalling, turning, brazing and polishing work of AHU shaft of any size, cleaning, greasing and overhauling incld replacement of unserviceable/worn out ball bearing and other minor spares, reassembling after repairs, bringing back to its location fixing in original position, connecting instt, and testing on full load capacity and commissioning to the entire satisfaction of Engr in charge. Note : Unit rate quoted by tenderers shall deem to incl for nuts, bolts, washers , lugs, thimbles, wires and petty items required for efficient and smooth functioning of the equipment without any extra cost to the Deptt.
Cleaning of condensor by opening of condensers from both side pouring of descaling solution in the condenser tubes, Rodding/brushing out of scaled/sedimented materials till the clean surface is achieved. Cleaning the water tubes with fresh water to remove complete acidic contents. Closing both sides of condenser using 6mm thick rubber insertion sheet and worn out nuts/bolts etc.
Supply and fixing replacement air filter of size 52cm x 47cm x 5 cm thick made out of GI sheet 16 SWG wire mesh suitable to remove dust particulars upto 5 microns incld removing old retrieved air filter all as directed.
Cleaning of cooling coil assy with descaling solution to remove deposited scale/dust incl cleaning of all tubes with wire brush to the entire satisfaction of Engr-in-charge.
S & F in replacement (MCCB) moulded case circuit breaker 415 V, 4 pole breaking capacity 36 KA thermal/magnatic release adjustable type range 400 Amp Make Havells/Indoasian/L&T.
S & F in replacement (MCCB) moulded case circuit breaker 415 V, 4 pole breaking capacity 50 KA thermal/magnatic release adjustable type range 630 Amp Make Havells/Indoasian/L&T.
S & F in replacement (MCCB) moulded case circuit breaker 415 V, 4 pole breaking capacity 25 KA thermal/magnatic release adjustable type range 160 Amp Make Havells/Indoasian/L&T.
S & F in replacement for contactors 3 pole 415 V 50 cycle coil voltage 230V current rating 32 Amps Make Indoasian or equivalent model of L&T/Havells.
S & F in replacement for contactors 3 pole 415 V 50 cycle coil voltage 230V current rating 25 Amps Make Indoasian or equivalent model of L&T/Havells
Supply and fixing in replacement copper cable PVC insulated FRLS 1100 volts grade single core, multistandrad copper conductor of size 6 sqmm dia laid in existing conduit/pipe all as specified and directed by Engr-in-charge. Make :Havells/Plaza/Kalinga
…ditto… as per item No 15 but of size 2.5 sqmm dia
Supply and fixing in replacement copper cable PVC insulated PVC sheathed armoured 1100 volts grade heavy duty three core multistandrad conductor of size 10 sqmm dia laid and including conduit/pipe. Make : Havells/Plaza/Kalinga.
Supply and charging refrigerant gas R-22 sealed cylinder of 61 kg (The empty cylinder shall be provided by department)
S & F in replacement thermostate expansion valve capacity 40 TR model TER-45 hw-100 Make : Emerson/Accel
S & F in replacement low pressure cut of switch type MP-5 for R-22 Make:-Indfoss/danfoss
S & F in replacement high pressure cut of switch type MP-5 for R-22 Make:-Indfoss/danfoss
Supply and filling of lubricating oil anti-freezing for refrigeration in factory sealed Drum of standard capacity 40 ltr . Make : Seetal-68(HP), Servo freeze-68(OC)/Freezol-68(BP)
M & L in replacement of Digital temperature & Humidity meter
M & L in replacement of control solonoids valve for central AC plant
M & L in replacement of thermometer dry & wet type
M & L in replacement of Ball bearing of size 6308 Make :-WBC/SKF
M & L in replacement of Ball bearing of size 6307 Make :-WBC/SKF
M & L in replacement of Ball bearing of size 6309 Make :-WBC/SKF
M & L in replacement of following spares of LT panel board :-
Timer 1 - 30 Sec Make : L&T /Indoasian/Havells
Over load relay 63 to 80 Amp, 415V,3/4 pole AC Make : L&T /Indoasian/Havells
Contactor 80 Amp 3 phase, 415 V,3/4 pole AC Make : L&T /Indoasian/Havells
Contactor 40 Amp 3 phase, 415 V,3/4 pole AC Make : L&T /Indoasian/Havells
Supplying Installing, commissioing and testing replacement sprinkler assembly for FRP cooling tower capacity 80 TR AC Plant.
Supply and fix Honey combing filter material complete with suitable as per existing size for 80 TR Ac Plant complete all as per specified and directed by Engr-in-charge
R K ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .