Office of the Executive Engineer Metropolitan Drainage Mechanical Division Jalasampad Bhawan (4th floor) Salt Lake City, Kolkata-700091
PreMonsoon Maintenance repair work of switchgear transformer VCBHT RelayACBMCCB LT Starter control panel including allied works of VT pumps at Kurebhanga pumping stations at PS Canning Block Canning all in the district of South 24 PGS during the
2026_IWD_993254_9
WBIW/EE/MDMD/e-NIT-20/2025-26
Open Tender
ELECTRICAL WORKS M/R
Percentage
Uttarbhag
Please refer Tender documents.
5 documents required · 5 mandatory
₹9,277
11 Sept 2026
23 Jan 2026
12 Feb 2026
23 Jan 2026
11 Feb 2026
23 Jan 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Servicing and overhauling of 400 AMPS/ 500 AMPS/ 630 AMPS /1250 Amps ,11KV/ 6.6 KV. V.C.B./ V.C.U.Dismantling the rack from the housing, opening the components, necessary cleaning of the component, carbonised portion, changing of rubber gasket, defective parts, cleaning of all mechanism parts and lubricating the mechanism, opening of C.T. & P.T.S., busbar spout assembly cleaning the same and insulated properly by supply of C.T.C. etc. and refitting all the parts to its original position by making all relevant electrical connection, panel wiring etc. for satisfactory & operation. | 3 | no | 13,923.8 | ₹41,771.4 |
| 2 | Servicing, cleaning and testing, calibration of following. Relay ( for 6 KV Panel /11 KV Panel)
For Incomer Feeder:
Each relay set consists of following relays
MICOM P110 /122/127/ 1 NO. CGL 14N/C- 1 NO
VAX31 - 1 NO, VAA-33-1NO VAMP-31 - 1 NO, VAJH-13-
1NO | 3 | set | 8,617.91 | ₹25,853.73 |
| 3 | Taking out the P.T. (33 KV/110V) (11 KV/110V) (6 KV/110V)
(3.3 KV/110V) HT VCB Panel and thorough cleaning, washing the interior portion with carbon tetachloride after taking out the from P.T. housing and re-fifling the same after aflaining the desired IR. valve and re-fifling, re-fixing the P.T. complete and testing and commisining as per direction of E.I.C | 1 | per set | 4,816.06 | ₹4,816.06 |
| 4 | Supply and fixing of LT panel accessories of approved make in existing LT panel including connections etc. as required as per specification.
Supply of 22.5 mm dia LED indicating lamps | 5 | each | 139.44 | ₹697.2 |
| 5 | Complete overhauling of Sart-Delta Starter for 75 -100 H.P. Motor checking mechanical & electrical accessories including cleaning of all contacts by carbon tetra chloride and checking all incoming and outfoing connections. | 6 | per job | 1,576.75 | ₹9,460.5 |
| 6 | Complete servicing and overhauling and necessary repairing of DTH 250 A 400/250A MCCB (Make : L & T). | 12 | per job | 884.32 | ₹10,611.84 |
| 7 | Servicing and overhauling 2500 / 1600 /1250/1000 Amps A.C.B. after withdrawing the breaker from its track, complete servicing the breaker, cleaning, moving and fixed contacts and adjustment incl.mechanical lever, greasing, oiling etc. and disconnection of the armoured cable and cleaning the surface with carbon tetra chloride, marking cloth, emery papers and applying of petrolium jelly etc. to the socket terminals and taping with PVC tapes and re-connection of the same as per direction of E.I.C. | 5 | per job | 7,289.05 | ₹36,445.25 |
| 8 | Opening the transformer breather and refitting the same after changing the silica gel including the supply of necessary gasket and silica gel. | 2 | sets | 1,632.77 | ₹3,265.54 |
| 9 | Dehydration & filtration of power transformer oil to raise the dielectric strength to the value specified in IS including submission of test result. The cost includs man, machinary, and tools & plant hire charges to complete the at site as per direction of the EIC. | 1,100 | per Ltr | 12.55 | ₹13,805 |
| 10 | Taking out sample of oil and carrying out chemical test of oil in respect of its acidity test through reputed test house and submission of test result. | 2 | set | 1,543.38 | ₹3,086.76 |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.72 MB
BOQ_2429381.xls
BOQ • 0.32 MB
2911i.pdf
Tender Documents • 0.93 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .