| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹22.2 LAccepted-AOC SADARPARA PURULIA 723101 | PURULIA | PURULIA | WEST BENGAL | 723101 | L1 | Accepted-AOC Due to lowest. | |
| 2 | L2₹22.8 L+₹56,464.36 (2.54%)Rejected-Finance | L2 | Rejected-Finance Due to 2nd lowest. | |
| 3 | L3₹25.0 L+₹2.8 L (12.4%)Rejected-Finance 448 MUZAFFAR AHMED STREET KOLKATA 700 016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | L3 | Rejected-Finance Due to 3rd lowest. |
Tender Value
Refer Docs
EMD Value
₹46,363
Closing Date
16 Aug 2024, 2:00 pmClosed
EE_Prl Elect Division PWD
Ranchi Road_Purulia
Urgent arrangement of Air Conditioning facilities at the Labour Room 1st Floor_ Gynae Teaching Room 2nd Floor and Eclampsia Ward 1st Floor under the Dept of Gynae and Obs_ Deben Mahato Government Medical College and Hospital_ Purulia in the District
2024_WBPWD_714923_1
WBPWD/EE/PED/NIQ06 /2024-2025
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
PURULIA
Please refer Tender documents.
4 documents required · 4 mandatory
₹46,363
11 Dec 2025
16 Jul 2024
20 Aug 2024
24 Jul 2024
16 Aug 2024
24 Jul 2024
Amount
Supply of non-inverter Split type Air-Conditioners of cooling capacity of minimum 21600 BTU/hr. Air Flow capacity must be 600 CFM & above. The units should be factory charged with R32/R410 A refrigerant only.The indoor unit should be compatible with wireless LCD remote controller with alphabetic error display like HP, LP,SPPR. (Make: O-General/Mitshubishi Heavy/Daikin as approved by EIC). Temparature distribution should be equal at every space of the specified room. [NS]
Supply of non inverter Split type Airconditioners of cooling capacity of minimum 18000 BTU/hr. Air Flow capacity must be 600 CFM & above. The units should be factory charged with R32/R410 A refrigerant only.The indoor unit should be compatible with wireless LCD remote controller with alphabetic error display like HP,LP ,SPPR. (Make: O-General/Mitshubishi Heavy/Daikin as approved by EIC). Temparature distribution should be equal at every space of the specified room. [NS]
Installation and Commissioning of hard/soft copper refrigerant piping, complete with fitting, elbows, bends, supporting arrangement on walls for Suction Line 5/8" OD with .7mm thick For 1.5 Tr 1.8/2.0 Conceale Split type AC(Make:Ryoku/Nippon). [NS]
Installation and Commissioning of hard/soft copper refrigerant piping, complete with fitting, elbows, bends, supporting arrangement on walls for Liquid Line 1/4" OD with .7mm thick For 1.5 Tr 1.8/2.0 Tr split type AC(Make:Ryoku/Nippon)[NS]
Supply & Fixing Pipe Insulation in 5/8" with 9mm nitrile rubber tube(Make:Accoroflex/Suprime)[NS]
Supply & Fixing Pipe Insulation in suction line 1/4"with 9mm nitrile rubber tube Suction Line (Make:Accoroflex/Suprime).[NS]
Providing and laying electrical cabling 3 Core 2.5sq. mm. Communication Cable (Make:Finolex/KEI/Polycab).[NS]
Installation, testing & commissioning of the above-said 2.0/1.5 Ton split AC incl. Supply & fixing required Angle Iron Structure on wall & mending works as per direction of E.I.C. [NS]
Installation, testing & commissioning of the above-said 2.0/1.5 Ton split AC without Supply & fixing required Angle Iron Structure on wall & mending works as per direction of E.I.C. [NS]
Installation of ODU on the roof top by fabrication of a platform of appropriate size made with 25x25x5 mm Angle and grouting the four legs on roof by making CC foundation including necessary accessories as per direction of EIC.[NS]
Drain water piping work out of 20mm dia PVC/HDPE harded pipes with Insulation, fitting,accessories, bends, elbows, tees, flanges, tappings, wall sleeves, hangers, supports, anchors.[NS]
Erection & Commissioning including lifting shifting Charges for 1.5 and 1.8/2.0 TR Air Conditioner.[NS]
SITC of complete time switch for controlling of 2 nos AC machine individually housed in SS double door phosphatised powder coated box with IP- 43 protection with electrical accessories & front door locking arrangement with all connection, a) 32A DP power contactor- 2 nos, Make- L&T /Siemens /BCH /Schnider, b) Daily and weekly programmable basis digital time switch, min switching time 1 min, 25 ON/OFF programs, 6 yrs battery backup, settable DST & key pad lock features - 1 no, Make- L&T /Siemens /BCH /Schnider, c) 32A DP MCB (Breaking capacity 10 KA, 'C' characteristics) for power circuit-1 no. d) 6 A SP MCB (Breaking capacity 10KA ' C' series ) for control circuit- 1 no. The work should be completed with all fabrications, wiring with suitable guage wires of not less than 4 sq mm copper wire for power wiring & 1.5 sq mm for control circuit, with suitable heavy duty terminal blocks, terminations etc. complete as per direction of the EIC.[NS]
SITC of complete time switch for controlling of 1 no AC machine individually housed in SS double door phosphatised powder coated box with IP- 43 protection with electrical accessories & front door locking arrangement with all connection, a) 32A DP power contactor- 1 no, Make- L&T /Siemens /BCH /Schnider, b) Daily and weekly programmable basis digital time switch, min switching time 1 min, 25 ON/OFF programs, 6 yrs battery backup, settable DST & key pad lock features - 1 no, Make- L&T /Siemens /BCH /Schnider, c) 32A DP MCB (Breaking capacity 10 KA, 'C' characteristics) for power circuit-1 no. d) 6 A SP MCB (Breaking capacity 10KA ' C' series ) for control circuit- 1 no. The work should be completed with all fabrications, wiring with suitable guage wires of not less than 4 sq mm copper wire for power wiring & 1.5 sq mm for control circuit, with suitable heavy duty terminal blocks, terminations etc. complete as per direction of the EIC.[NS]
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment Up to 250A Legrand- 8 way Enclosure (607723) [D-11/15]
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment Up to 160A Legrand- 4 way Enclosure (607913) [D-11/15]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment
4Way (Legrand) Enclosure (607715) [D-10/14]
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection
160 A (Make- Legrand) [D-8/10]
100 A (Make- Legrand) [D-8/10]
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. 63 A(FP) (Make- Legrand) [D-5/6]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection
6-32 A SP MCB- Legrand make [D-6/7]
63A TP MCB- Legrand [D-6/7]
Supply and fixing 415V, 100A TPN SFU with sheet steel enclosure(Make- L&T) with HRC Fuses as out going on angle iron frame on wall. [D-3/4(a)]
Supply and laying of 3.5 core 95 sq mm Al arial bunched cable with stay wire on overhead with 4 nos 25x25x5 mm MS angle grouted on wall for holding the cable with necy cable hooks, fastner etc and necy connections.[NS]
Supply and drawing of 1.1 Kv grade XLPE insulated 3.5 core 50 sq mm Al PVC/XLPE insulated arial bunched cable with PVC/XLPE insulated massenger on the pole top with necy hooks and clips and over the ground with 2 nos 40 x 40 x 5 mm MS angle grouted on wall and necy accessories as required.[NS]
Finishing the end of following XLPE/PVC armoured or arial bunched cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials :
3.5 core 50 sq mm [F-5/8(b)(xvi)]
3.5 core 95 sq mm [F-5/8(b)(xviii)]
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works as per GS.
20 mm size [ E-16/7(a) ]
25 mm size [ E-16/7(b) ]
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire(Brand approved by EIC) of the following sizes in the 19mm/25mm prelaid polythene pipe/PVC rigid conduit as per GS.
2x(4 sqmm)+1x (2.5 sqmm) [ E- 9/1(v) ]
4x(16 sqmm)+2x (10 sqmm) [ E- 9/1(g1) ]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
4 sqmm [F-5/9(ii)]
2.5sqmm [F-5/9(i)]
10 sq mm [F-5/9(iv)]
16 sq mm [F-5/9(v)]
Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [E-19/17]
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections. [E-17/5(b)]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc.S & F 230 V 25 Amps 3 pin Modular type Plug socket (Brand approved by EIC) with 2 module GI Modular type switch board with top cover plate flushed in wall & making necy. Connections with pvc cu wire and earth continuity wire etc. [E-17/5(a)]
MODERN ELECTRICALS
RASH ELECTRICAL WORKS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .