Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance PLOT NO 1076 BEHERA SAHI NAYAPALLI BHUBANESWAR 751012 | KHORDHA | ODISHA | 751012 | Admitted-Finance |
Tender Value
₹5.1 L
EMD Value
₹10,106
Closing Date
18 Oct 2022, 3:00 pmClosed
DIRECTOR NISER
DIRECTORATE NISER
Provision for Power point fixing Cable laying from LCS1 LED light and Fan fixing with wiring in the proposed Furnace Room in the Gas Bank-1
2022_NISER_716623_1
NISER/IWD-ELECT/SPS/22-23/10
Open Tender
Electrical Works
Works
60 days
NISER JATNI
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹10,106
31 Oct 2022
7 Oct 2022
19 Oct 2022
7 Oct 2022
18 Oct 2022
7 Oct 2022
Supply,installation, testing & commissioning of following readymade distribution boards,double door, IP 65 degree protection Out door Panel, complete with necessary, MCB isolators, MCBs, earth leakage circuit breaker (ELCB) etc., including interconnections with appropriate capacity size of PVC insulated copper conductor wires,suitable for floor mounting /wall mounting with MS frame work of 40 x 40 x 5 mm MS angle iron, with M.S. enclosure fabricated out of min 18 SWG thick M.S.CRCA sheet with concealed hinged door, locking arrangement etc., including earthing clamps for both incoming & outgoing circuits,interconnections, per phase isolation kit as required,cable end box & wire way box if required, continuous copper earth wire in the wire way box with single/duplicate brass earthing terminals, danger board, name plate, flexible earthing for the door, metal treatment & powder coated painting, Phase Distribution drawing etc., all as per drawings (G.A. & fabrication drawing to be got approved), etc., relevant IS & instruction of Engineer-in-charge. Notes: 2. Blanking Plates shall be included in scope of work. 1. MCB shall be minium 10k breaking capacity (type-C) 3. DB shall be approved manufacturers as indicated in preferred makes of material. 1. Sample of various DB shall be got approved by E-I-C including G.A & fabrication drawing. 5. Routine tests will be conducted at factory as per relevant IS. The double door type 12 way VTPN MCCB DB IP-42 comprising of the following: a) 200 A FP, 16 kA TM release MCCB with earth protection relay-- 1 No. as incoming and mulltifunction meter and LED indicators as required. b) 40/63 A TP C curve MCB -- 08 nos
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 MCCB VTPN Suitable for Flush Mounting and Surface Mounting • With 250 A Copper Busbar for each phase • With 2 Neutral bar, 2 Earthbar and Cable ties for Cable management • Fully insulated busbar & shrouded Neutral bars • Improved Pan assembly for ease of installation • Prefitted masking sheet • Reversible Door for IP 43 & IP 54 DB's • With provision for DPX³ 160 MCCB as incomer and SP/TP MCB's as outgoing 8way MCCB incomer VTPN DB along with 1no. 125 amp 25KA MCCB, 63 amp TP MCB-1no. and 32 amp TP MCB-4nos. and 16-25 Amp SP MCB-15 Nos. Make: Legrand/Hager/Schnieder
Supplying and fixing of double door TPN sheet steel enclosure on surface/ recess along with 40/32 A 415 V "C" curve TPN MCB complete with connections, testing and commissioning etc. as required. Make: Legrand/Hager/Schnieder
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. Make: Legrand/Hager/Schnieder
Supplying and fixing following size/ modules, PVC surface box alongwith modular base & cover plate for modular switches in recess etc. as required along with fixing of 6/16A 6pin socket outlet and 15/16 A Modular switch including installation, fixing of switch and socket and connection 6 Module box and 2nos. of Switch and 2 nos. of socket each Make: Legrand (Myrius/Mylinc)
SITC of Size 18 INCH, 450MM, EXHAUST FAN (HEAVY DUTY) Power 230 V, Speed 1400 RPM, Vibration free balanced impellers with Pre-lubricated double ball bearing for maintenance free running Sound level-65-70dB. Make: Almonard/Crompton Greaves
Supplying and fixing following size/ modules, PVC surface box alongwith modular base & cover plate for modular switches in recess etc. as required along with fixing of 6/16A 6pin socket outlet and 15/16 A Modular switch including installation, fixing of switch and socket and connection 3Module modular type Switch socket box with 1 no. Switch and 1 no. socket. Make: Legrand Mylinc/Myrius
SITC of 1200MM sweep Ceiling fan with Step Regulator, Opal white color, institunal/ISI Ceiling fan, Power consumption 70 W, Speed 380 RPM, Air delivery 200 CMM
Supply, installation of 2'x2' LED recessed mounted Panel light, 3600Lm@ 31watt, LED 36S : 115lm/W. CCT-6500K,Dia-150mm to 175mm, IK-02, IP-20, Life-50000 Hours , 597×597x 70 mm Max. Housing CRCA, Fully Diffused Luminaire Serviceability-Class B. Authorised certificate to be produced by the Agency if required. Make: Philips /Wipro/Panasonic
Supply, Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. 3.5Cx50 Sq MM AL Armoured XLPE Cable Make: Polycab/Finolex/RR Kabel
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5Cx50 sqmm AL XLPE Armoured Cable
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (AC's wiring and Sub-main ckt wiring for Fan Light) Cable: 4 X 4 sq. mm + 2X 4 sq. mm earth wire Make: Make: Polycab/Finolex/RR Kabel
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (AC's wiring and Sub-main ckt wiring for Fan Light) Cable: 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire Make: Make: Polycab/Finolex/RR Kabel
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (AC's wiring and Sub-main ckt wiring for Fan Light) Cable: 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire Make: Make: Polycab/Finolex/RR Kabel
Numbering of Power points/ DB/ceiling fan/ exhaust fan/ fittings etc. with one sided adhesive sticker as required.
M/S TATHAGATA ENGINEERING
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .