Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.5 LAdmitted-Finance 190 B VIJAY BHAWAN SUBHASH CHOWK RATANADA JODHPUR RAJ 342001 | JODHPUR | RAJASTHAN | 342001 | L1 | Admitted-Finance | |
| 2 | L2₹31.4 L+₹85,478 (2.80%)Admitted-Finance MARYADA 111 SHIKARGARH KANHAIYA NAGAR JODHPUR 342001 | JODHPUR | RAJASTHAN | 342001 | L2 | Admitted-Finance | |
| 3 | L3₹32.4 L+₹1.9 L (6.27%)Admitted-Finance | L3 | Admitted-Finance | |
| 4 | L4₹33.7 L+₹3.2 L (10.6%)Admitted-Finance HOUSE NO 01 B JANANA DODI OPP AKSHAY HOTEL RAI KA BAGH JODHPUR RAJASTHAN 342010 | 342010 | L4 | Admitted-Finance | |
| 5 | L5₹35.0 L+₹4.4 L (14.5%)Admitted-Finance | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Keystone Constructionare L3 | M/S Balkishan Panwar Construction L1 | M/S KAUTILYA GARG L2 | LOKESH ELECTRICAL WORKS CONTRACTOR L6 | ENGINEERS ASSOCIATES L5 | PARM BUILDERS L7 | Nvimal Engineers and Contractor L4 |
|---|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Servising of Diesel Engine Generating sets 15 to 50 KVA Rating to be carried out as per schedule given as under. B- check:- (Every 100 Hrs or 6 months whichever is earlier) (i) Fluid levels - Check and top off coolant, oil, and fuel levels as needed. (ii) Oil and Filter change - Change the engine oil, oil filter, fuel filter and bypass filter. (iii) Air filter replacement - replace the Air filter. (iv) Replace the water separator (v) Radiator cleaning - Clean the radiator with chemical cleaner (vi) Leakage inspection - Check for any leaks in the fuel, coolant or oil system and make necessary repairs (vii) Battery inspection - inspect the battery including terminals, for corrosion and ensure proper voltage (viii) General Inspection - Visually inspect the generator for any damage, loose parts or signs of wear, loose wire connection in terminal boxes. (ix) V- Belt Condition - Check the condition of belts (x) Exhaust system - Inspect the exhaust system for leaks and ensure proper operation (xi) Electrical system - Check the electrical system for any issues or loose connections and make necessary repairs (xii) Fire Extinguisher - Ensure the fire extinguisher is present, charged and in good working condition complete all as specified and directed.
Note:- (a) Necessary minor repair works, control wiring and materials shall be inclusive in the quoted rate.
(b) Relavant spares which are replaced in repair works shall be measured and paid as supply only. | 10 | Each Job | 1,317 ₹13,170 | 1,001 ₹10,010 | 1,500 ₹15,000 | 1,000 ₹10,000 | 799 ₹7,990 Lowest | 2,500 ₹25,000 | 1,500 ₹15,000 |
| 2.00 | All as per Item No. 01 above, but 62.5 kVA to 100 kVA. | 25 | Each Job | 1,466 ₹36,650 | 1,001 ₹25,025 | 1,200 ₹30,000 | 1,200 ₹30,000 | 799 ₹19,975 Lowest | 3,000 ₹75,000 | 1,800 ₹45,000 |
| 3.00 | All as per Item No. 01 above, but above 100 kVA and upto 160 kVA. | 18 | Each Job | 1,600 ₹28,800 | 1,001 ₹18,018 | 1,500 ₹27,000 | 1,800 ₹32,400 | 1,000 ₹18,000 Lowest | 4,000 ₹72,000 | 2,000 ₹36,000 |
| 4.00 | All as per Item No. 01 above, but above 160 kVA and upto 250 kVA. | 10 | Each Job | 1,750 ₹17,500 | 1,001 ₹10,010 | 1,800 ₹18,000 | 2,000 ₹20,000 | 1,000 ₹10,000 Lowest | 5,500 ₹55,000 | 2,100 ₹21,000 |
| 5.00 | All as per Item No. 01 above, but above 250 kVA and upto 400 kVA. | 6 | Each Job | 2,050 ₹12,300 | 1,001 ₹6,006 Lowest | 2,000 ₹12,000 | 2,200 ₹13,200 | 1,500 ₹9,000 | 6,000 ₹36,000 | 2,500 ₹15,000 |
| 6.00 | Servising of Diesel Engine Generating sets 15 to 50 KVA rating to be carried out as per schedule given as under. C- Check:- (Every 1500 Hrs or 1 year whichever is earlier) (i) Pollution level - Monitor exhaust emissions and ensure they meet envirnomental standards. (ii) Oil and Filters - Change enginer oil, oil filters, fuel filters, and bypass filters to maintain engine health and performance. (iii) Air filter - Replace the air filter to ensure proper air flow and prevent damage to the engine (iv) Water separator - Change the water separator (v) Cooling system - Clean the radiator and check the coolant level to ensure proper cooling and prevent over heating (vi) Gaskets check - Inspect and potentially replace gaskets in various chambers to prevent leaks and ensure proper sealing (vii) Load testing - cary over the load bank tests as required and submitt the test report kept on record complete all as specified and directed.
Note:- (a) Necessary minor repair works, control wiring and materials shall be inclusive in the quoted rate.
(b) Relavant spares which are replaced in repair works shall be measured and paid as supply only. | 8 | Each Job | 3,350 ₹26,800 | 2,002 ₹16,016 | 3,500 ₹28,000 | 2,500 ₹20,000 | 1,000 ₹8,000 Lowest | 2,500 ₹20,000 | 4,000 ₹32,000 |
| 7.00 | All as per Item No. 06 above but 62.5 kVA to 100 kVA. | 14 | Each Job | 4,850 ₹67,900 | 2,002 ₹28,028 | 3,500 ₹49,000 | 3,500 ₹49,000 | 1,000 ₹14,000 Lowest | 3,200 ₹44,800 | 5,000 ₹70,000 |
| 8.00 | All as per Item No. 06 above, but above 100 kVA and upto 160 kVA. | 12 | Each Job | 5,600 ₹67,200 | 2,002 ₹24,024 | 5,500 ₹66,000 | 3,800 ₹45,600 | 1,500 ₹18,000 Lowest | 4,000 ₹48,000 | 6,000 ₹72,000 |
| 9.00 | All as per Item No. 06 above, but above 160 kVA and upto 250 kVA. | 8 | Each Job | 7,150 ₹57,200 | 4,004 ₹32,032 | 6,500 ₹52,000 | 5,000 ₹40,000 | 1,500 ₹12,000 Lowest | 5,000 ₹40,000 | 7,000 ₹56,000 |
| 10.00 | All as per Item No. 06 above, but above 250 kVA and upto 400 kVA. | 2 | Each Job | 7,850 ₹15,700 | 4,004 ₹8,008 | 10,000 ₹20,000 | 7,500 ₹15,000 | 2,000 ₹4,000 Lowest | 6,500 ₹13,000 | 10,000 ₹20,000 |
Tender Value
₹42.3 L
EMD Value
₹84,600
Closing Date
14 Sept 2026, 6:35 pmClosed
GE (AF) Jodhpur
GE (AF) Jodhpur
REPAIR/ MAINT AND CALIBRATION OF DG SETS/ AMF PANELS INSTALLED IN TECHNICAL AREA AND SALAWAS AT AF STN JODHPUR
2026_MES_785334_1
8510/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Jodhpur
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (AF) Jodhpur
₹84,600
Yes
17 Sept 2026
19 Aug 2026
16 Sept 2026
19 Aug 2026
14 Sept 2026
2 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Servising of Diesel Engine Generating sets 15 to 50 KVA Rating to be carried out as per schedule given as under. B- check:- (Every 100 Hrs or 6 months whichever is earlier) (i) Fluid levels - Check and top off coolant, oil, and fuel levels as needed. (ii) Oil and Filter change - Change the engine oil, oil filter, fuel filter and bypass filter. (iii) Air filter replacement - replace the Air filter. (iv) Replace the water separator (v) Radiator cleaning - Clean the radiator with chemical cleaner (vi) Leakage inspection - Check for any leaks in the fuel, coolant or oil system and make necessary repairs (vii) Battery inspection - inspect the battery including terminals, for corrosion and ensure proper voltage (viii) General Inspection - Visually inspect the generator for any damage, loose parts or signs of wear, loose wire connection in terminal boxes. (ix) V- Belt Condition - Check the condition of belts (x) Exhaust system - Inspect the exhaust system for leaks and ensure proper operation (xi) Electrical system - Check the electrical system for any issues or loose connections and make necessary repairs (xii) Fire Extinguisher - Ensure the fire extinguisher is present, charged and in good working condition complete all as specified and directed.
Note:- (a) Necessary minor repair works, control wiring and materials shall be inclusive in the quoted rate.
(b) Relavant spares which are replaced in repair works shall be measured and paid as supply only. | 10 | Each Job | - | - |
| 2 | All as per Item No. 01 above, but 62.5 kVA to 100 kVA. | 25 | Each Job | - | - |
| 3 | All as per Item No. 01 above, but above 100 kVA and upto 160 kVA. | 18 | Each Job | - | - |
| 4 | All as per Item No. 01 above, but above 160 kVA and upto 250 kVA. | 10 | Each Job | - | - |
| 5 | All as per Item No. 01 above, but above 250 kVA and upto 400 kVA. | 6 | Each Job | - | - |
| 6 | Servising of Diesel Engine Generating sets 15 to 50 KVA rating to be carried out as per schedule given as under. C- Check:- (Every 1500 Hrs or 1 year whichever is earlier) (i) Pollution level - Monitor exhaust emissions and ensure they meet envirnomental standards. (ii) Oil and Filters - Change enginer oil, oil filters, fuel filters, and bypass filters to maintain engine health and performance. (iii) Air filter - Replace the air filter to ensure proper air flow and prevent damage to the engine (iv) Water separator - Change the water separator (v) Cooling system - Clean the radiator and check the coolant level to ensure proper cooling and prevent over heating (vi) Gaskets check - Inspect and potentially replace gaskets in various chambers to prevent leaks and ensure proper sealing (vii) Load testing - cary over the load bank tests as required and submitt the test report kept on record complete all as specified and directed.
Note:- (a) Necessary minor repair works, control wiring and materials shall be inclusive in the quoted rate.
(b) Relavant spares which are replaced in repair works shall be measured and paid as supply only. | 8 | Each Job | - | - |
| 7 | All as per Item No. 06 above but 62.5 kVA to 100 kVA. | 14 | Each Job | - | - |
| 8 | All as per Item No. 06 above, but above 100 kVA and upto 160 kVA. | 12 | Each Job | - | - |
| 9 | All as per Item No. 06 above, but above 160 kVA and upto 250 kVA. | 8 | Each Job | - | - |
| 10 | All as per Item No. 06 above, but above 250 kVA and upto 400 kVA. | 2 | Each Job | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.23 MB
8510TENDER.pdf
Tender Documents • 0.86 MB
BOQ_879999.xls
BOQ • 0.41 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .