| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.5 LAccepted-AOC 13 29 304 3RD FLOOR EAST PATEL NAGAR OPP SIDDHARTHA HOTEL NEW DELHI 08 | NEW DELHI | NEW DELHI | DELHI | 110008 | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹40.4 L+₹2.9 L (7.82%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance Not lowest | |
| 3 | L3₹47.0 L+₹9.5 L (25.3%)Rejected-Finance 154 GANDHI MARKET AMBALA CANTT HARYANA 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L3 | Rejected-Finance Not lowest | |
| 4 | Rejected-Technical 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | - | Rejected-Technical Due adverse remark in WLR |
Tender Value
Refer Docs
EMD Value
₹99,000
Closing Date
25 Mar 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF AMBALA
HQ CWE AF Ambala, Ambala Cantt
PROVN OF EXTERNAL SERVICES FOR PROJECT NFS AT AF STN AMBALA UNDER GE (AF) AMBALA
2021_MES_424788_1
CWE/AF AMB/AMB-52/2020-21
Open Tender
Miscellaneous Works
Item Rate
180 days
Ambala cantt
For enlisted in MES Class D and category b (ii) and for unenlisted refer NIT
7 documents required · 7 mandatory
₹500
Yes
GE AF AMBALA
₹99,000
Yes
20 May 2021
23 Feb 2021
27 Mar 2021
23 Feb 2021
25 Mar 2021
10 Mar 2021
23 Feb 2021 - 7 Mar 2021
60 days
Amount
Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for foundation etc or for walls, shafts, manholes not exc 10 Sqm on plan or for laying pipes/cables etc and getting out, in soft/loose soil complete all as directed
Returning filling in including spreading leveling watering and well ramming in layers not exc 25 cm thick each in soft/loose soil complete all as specified and as directed.
Removal of excavated soil to a distance not exc 50 mtrs & depositing where directed at a level not exc 1.5 mtrs above the starting point complete all as specified and as directed.
Material and labour for PCC 1:4:8, type D-2 using 40 mm graded mechanically crushed stone aggregates as in foundations, filling and mass concrete etc complete all as specified & as directed.
Material and labour for Brick work with sub class B bricks of old size, straight or curved on plan exc 6 m mean radius, built in cement mortar 1:6 complete all as specified and as directed.
Material & labour for rendering 15mm thick in cement mortar 1:3 mixed with water proofing compound @ 3% on fair faces of brick wall/concrete surfaces and finished even & smooth without using extra cement complete all as specified and directed. Note : WPC shall be measured and paid separately as supply only.
Supply only integral water proofing compound complete all as specified and as directed.
Material and labour cement concrete cast in situ, 1:3:6, type C-1 using 20 mm graded mechanically crushed stone aggregates as in lintels upto 1.5m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs and the like including weathering, slightly rounded or chamfered angles and throating complete all as specified and as directed. Note : The quoted rates include for use of formwork (straight or curved).
Material and labour Precast cement concrete, 1:2:4, type B-1 using 20 mm graded mechanically crushed stone aggregates set in cement mortar 1:6 as in landings, cover slabs (for man holes etc.) chullah hoods, chajjas, water troughs, mangers, shelves and similar articles with plain faces complete all as specified and as directed. Note : The quoted rates include for use of formwork (straight or curved).
Supply and fix mild steel TMT bars, 10 mm dia and over, cut to length, bend to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with mild steel wire (annealed) not less than 0.9 mm dia complete all as specified and directed.
Supply and fix mild steel TMT bars, 6mm to 8mm dia, cut to length, bend to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with mild steel wire (annealed) not less than 0.9 mm dia complete all as specified and directed.
Material and labour for concrete bed to drain pipe for 200mm dia incl packing under and haunching against the sides of pipes after they are laid and tested in cement concrete 1:3:6 type C-2 using 40mm graded mechanically crushed stone aggregate complete all as specified and as directed.
Material and labour for RCC hume pipe 200 mm bore, class NP-2,in any length laid and jointed with collers in cement mortar 1:1, laid in trenches complete all as specified andas directed. Note :- Excavation, earth work & bedding shall be measured and paid separetely.
Supply and fixing galvanised mild steel water tubes 15 mm bore, medium grade, with all fittings, laid in trenches complete all as specified and as directed.
Supply and fixing galvanised mild steel water tubes 20 mm bore, medium grade, with all fittings, laid in trenches complete all as specified and as directed.
Supply and fixing galvanised mild steel water tubes 25 mm bore, medium grade, with all fittings, laid in trenches complete all as specified and as directed.
Supply and fixing galvanised mild steel water tubes 40 mm bore, medium grade, with all fittings, laid in trenches complete all as specified and as directed. Note :- Excavation shall be measured and paid separetely.
Supply and fixing gun metal globe or gate valve 15 mm bore,ISI marked,class-2 with spindle and iron wheel head, screwed both ends for iron pipe fixed complete all as specified and as directed.
Supply and fixing gun metal globe or gate valve 20 mm bore,ISI marked,class-2 with spindle and iron wheel head, screwed both ends for iron pipe fixed complete all as specified and as directed.
Supply and fixing gun metal globe or gate valve 25 mm bore,ISI marked,class-2 with spindle and iron wheel head, screwed both ends for iron pipe fixed complete all as specified and as directed.
Supply and fixing gun metal globe or gate valve 40 mm bore,ISI marked,class-2 with spindle and iron wheel head, screwed both ends for iron pipe fixed complete all as specified and as directed.
Cutting to existing water mains in position upto 150mm bore cast iron pipe for taking branch connections for cast iron special as required complete all as specified and as directed.
Material and labour for construction of brick masonary valve pit in soft/loose soil, of internal size 60 cm x 60 cm x 60 cm deep (depth to be reckoned from top of the PCC in foundation to the top of MS cover), 100 mm thick PCC 1:2:4 type B-2 using 40mm graded mechanically crushed stone aggregates as in coping with & including necessary form work all as per drg No CE AF/STD-28/94 Sheet No 1/2 & 2/2 and applying two coats of black synthetic enamel paint over a coat of red oxide primer on steel and iron surfaces internally and externally and applying two coats of white wash internally to valve pit including preperation complete all as specified and directed. Note:- (i) The drawings as stated above may be referred from office of GE (AF) Ambala. (ii) Cost shall be inclusive of all items of work required for the execution (as shown on drawing) and entire completion of this item and noting extra shall be paid seprately in any other item(s).
Supplying, installation, commissioning and testing of transformer step down, 11 KV/433 volts as per IS-1180-2014 (Level- III), outdoor type, copper wound, suitable for AC, three phase, 4 wire, 50 Hz system of capacity 160 KVA, oil immersed having Vector group DYN-11, naturally cooled type with and including first filling of transformer oil, delta connection on HT side, star connection on LT side, manually, operated, off-load tap changer on HT side to vary secondary voltage to + 7.5% & -7.5% in five steps & above of 2.5% each, cable end box at HT & LT side, LT side cable box shall also be fitted with suitable size of cable glands for making connections with all the accessories and the under mentioned fittings complete all as specified and directed:- (a) Rating plate and terminal marking plate. (b) Two earthing terminal for body earthing and two additional for neutral brought out on a bushing.
(c) Lifting lugs. (d) Drain valve with plug or cover plate. (e) Dehydrating breather. (f) Oil level indicator with aluminium and maximum marking. (g) Cooling radiator. (h) Thermometer pocket. (j) Conservator. (k) Oil filling hole with cover. (l) Thermometer 100mm dial/stem type with metal guard having maximum temperature indication with resetting. (m) Silica gel breather duly filled with silica Gel. (n) Any other fittings as recommended by the manufacturer of efficient functioning of the transformer.
Notes for Srl item No. 24.00: - (i) The cost of platform/foundation as per manufacturer’s recommendation shall be included in the quoted rates and the drawing of the foundation shall be got approved by GE before construction. (ii) The transformer shall be of latest star rated and energy conservation (Energy conservation Binary Corps) for which necessary test certificate of manufacturer shall be produced by the contractor. (iii) Transformer manufacturer shall be in possession of licence from bureau of Indian standard. (iv) The fitting & accessories of the transformer shall be conforming to is 3639 : 1996. (v) The transformer shall be tested as per IS for all routine tests in the factory premises in the presence of rep of GE on the receipt of request from the contractor in addition to routine tests . The transformer shall be tested for 10% over load at factory premises for minimum 01 hour after full load cycle of 08 hours. (vi) The Transformer shall be tested by SEI/EI/AEI beore commissing. (vii)All the test results shall be produced before RAR. All necessary arrangements i.e. Co-ordination with the manufacturer & testing officer, arranging equipments and material to facilitate testing at the manufacture’s premises etc. shall be borne by the contractor.
Supplying, installation, testing and commissioning of 150 KVA voltage stablizer for automatic operation, servo controlled, three phase, naturally oil cooled, inddor type & designed for input variation between 300 volt to 480 volt with output voltage stablized at any desired voltage beeween 400 volt to 440 volt with accuracy of (+/-)2.5% and speed of correction 8 votls per second, unbalance type including supply and first filling of oil complete all as specified and directed.
Supplying, installation, testing and commissioning of 160 KVA Isolation transformer, 3 phase input/output voltage 410 (+/-)5 volt, frequency 50 Hz, oil cooled, oil immersed double copper wound outdoor type, Insulation class 'E', No load loss should be less than 0.5% with all standard fitting with oil including meeting primary & secondary connections with existing UG cable & necessary PCC platform in 1:3:6 type C-2 using 40mm graded mechanically crushed stone aggregate complete all as specified and directed. Note:- The size of platform as recommended by manufacturer & approved by Engineer-in-charge.
Supplying, installation, testing & commissioning floor mounted LT panel, outdoor type, factory made, IP -54 class protection (CPRI type test cerified firm) suitable for operation on 415 volts, AC 3 phase, 4 wire, 50 Hz electric supply system, made out of 50 x 50 x 6 mm angle iron frame and 3.15 mm thick CRCA sheet side covers with front and back hinged doors with proper locking arrangement, width of panel not less than 75cm, rubber gasket on front and back to make it dust and vermin proof, powder coated including 500 Amp rated aluminium busbar sleeved with heat shrink sleeve colour coated for 3 Phase, 4 wire electric supply system and wiring with suitable size of copper cable, mounted on PCC 1:2:4 type B-1 (with 20 mm graded stone aggregate) foundation block of suitable size upto 40 cm above ground level complete with the following accessories all as specified and directed:- (a) Incoming (i) MCCB 315 Amp, 415 Volts, 35 KA, 4 pole, 50 Hz, with adjustable thermal & adjustable magnetic setting - 01 No. (ii) Multifunction energy meter in 96x96 sqmm flush mounted case with six direct access keys & backlit LCD display, accuracy class 1.0, 5amp CT input LV networks AC auxliary suppluy measurement : V, I, In, P, Q, S, PF, F, Ea, Er & Es , THD for V& I - 01 set (iii) CTs of ratio 100/50/ 5Amp, class -1 VA vurden 15 - 01 set of three (iv) Phase indicator lamp - 01 set (Set of three) (v) On load change over switch, 4 pole, 315 Amp
(b) Outgoing (i) MCCB 250 Amp 415 Volts, 35 KA, 4 pole, 50 Hz, with adjustable thermal & adjustable magnetic setting - 01 No (ii) Outgoing MCCB, 125 Amp 415 Volts, 16 KA, 4 pole, 50 Hz, with adjustable thermal & fixed magnetic setting - 02 Nos. (iii) Outgoing, MCCB 63 Amp 415 Volts, 16 KA, 4 pole, 50 Hz, with adjustable thermal & fixed magnetic setting - 02 Nos. (iv) MCB TPN, 32 Amp 415 Volts, 10 KA, 4 pole, - 01 Nos. (v) Time switch 0.6 sec 12 Hrs single phase, 240 volt AC, 15 Amps, 50 Hz, complete with synchronous motor, contractor - 01 Nos Note: The cost of the PCC block shall be deemed to be included in the unit rate quoted for the item
Supplying, laying, jointing, testing and commissioning of HT XLPE cable, 11000 volts (earthed), insulated, screened, sound compacted aluminium conductor, screening with extruded semi conducting layers, insulation screening with copper tape covers laid up with PVC (ST-2), extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 Part II with amendment, size cross sectional area 95 Sqmm, 3 core, laid in trenches /pipes /ducts /along poles/ walls/ equipment etc complete all as specified and directed. NOTES : (i) Cable shall be of manufacturing date not earlier than Dec 2020. All the cable shall be embossed with year of manufacturing, meterage at every metre, in addition to its own standard markings as per IS i.e. Size, voltage etc. (ii) Excavation & earth work, sand cushioning, protection pipes, end termination joints & protection covers shall be measured and paid separately. (iii) No straight through joint shall be permitted in less than single drum length. (iv) The contractor shall produce original purchase vouchers duly machine numbered alongwith excise duty gate pass of factory for verification and record.
Supplying, laying, jointing, testing and commissioning under ground LT XLPE electric cable 1100 Volts grade, heavy duty, PVC insulated and sheathed armoued electric power cable with stranded aluminium conductor, of cross sectional area 185 Sqmm 3.5 core conforming to IS- 7098 (Part I) 1988 as in trenches or along the wall/pole through pipe etc served with an inner sheathing of PVC tape and overall PVC sheathed armoured with galvanized steel wire or tape, complete all as specified and directed.
Supplying, laying, jointing, testing and commissioning under ground LT XLPE electric cable 1100 Volts grade, heavy duty, PVC insulated and sheathed armoued electric power cable with stranded aluminium conductor, of cross sectional area 120 Sqmm 3.5 core conforming to IS- 7098 (Part I) 1988 as in trenches or along the wall/pole through pipe etc served with an inner sheathing of PVC tape and overall PVC sheathed armoured with galvanized steel wire or tape, complete all as specified and directed.
Supplying, laying, jointing, testing and commissioning under ground LT XLPE electric cable 1100 Volts grade, heavy duty, PVC insulated and sheathed armoued electric power cable with stranded aluminium conductor, of cross sectional area 50 Sqmm 3.5 core conforming to IS- 7098 (Part I) 1988 as in trenches or along the wall/pole through pipe etc served with an inner sheathing of PVC tape and overall PVC sheathed armoured with galvanized steel wire or tape, complete all as specified and directed.
Supplying, laying, jointing, testing and commissioning under ground LT XLPE electric cable 1100 Volts grade, heavy duty, PVC insulated and sheathed armoued electric power cable with stranded aluminium conductor, of cross sectional area 10 Sqmm 4 core conforming to IS- 7098 (Part I) 1988 as in trenches or along the wall/pole through pipe etc served with an inner sheathing of PVC tape and overall PVC sheathed armoured with galvanized steel wire or tape, complete all as specified and directed. Note for Srl item No 31.00 to 34.00:- Excavation & earth work, sand cushioning, protection pipes, end termination joints & protection covers shall be measured and paid separately.
Material and labour for Sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after laying the cable (punned down to 18 cms depth after laying and stretching of cable ) complete all as specified and as directed.
Supply and laying old size, sub class 'B' bricks, laid flat for protection of cable , adjacent to each other, perpendicular to central axis of cable complete all as specified and as directed.
Material and labour GI pipe 80 mm bore , light grade as in trenches, under road,under floor, fixed to wall with fixing arrangement with suitable size of MS clamps made from 40x3 mm size flat iron including nuts,bolts & washers or along the pole with fixing arrangement etc for cable protection complete all as specified and as directed .
Material and labour GI pipe 50 mm bore , light grade as in trenches, under road,under floor, fixed to wall with fixing arrangement with suitable size of MS clamps made from 40x3 mm size flat iron including nuts,bolts & washers or along the pole with fixing arrangement etc for cable protection complete all as specified and as directed .
Supply and fixing cable jointing kit for 11000 volt earthed grade cable for outdoor end termination cold shrinkable type joints with jointing material and accessories for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including cutting complete all as specified and as directed.
Supply and fixing cable jointing kit for 1100 volt earthed grade cable for outdoor/indoor end termination heat shrinkable type joints with jointing material and accessories for 3.5 core XLPE armoured aluminium conductor cable of size 185 Sqmm including cutting complete all as specified and as directed.
Supply and fixing cable jointing kit for 1100 volt earthed grade cable for outdoor/indoor end termination heat shrinkable type joints with jointing material and accessories for 3.5 core XLPE armoured aluminium conductor cable of size 120 Sqmm including cutting complete all as specified and as directed.
Supply and fixing cable jointing kit for 1100 volt earthed grade cable for outdoor/indoor end termination heat shrinkable type joints with jointing material and accessories for 3.5 core XLPE armoured aluminium conductor cable of size 50 Sqmm including cutting complete all as specified and as directed.
Supply and fixing cable jointing kit for 1100 volt earthed grade cable for outdoor/indoor end termination heat shrinkable type joints with jointing material and accessories for 4 core XLPE armoured aluminium conductor cable of size 10 Sqmm including cutting complete all as specified and as directed.
Supplying and errecting, true vertical strut steel tubular, swaged welded pole conforming to IS-2713 part II ,type 410 SP 55, 11 metre long complete with mild steel base plate of 6 mm thick of size 300 X 300 mm, finial taper plug, cap, bolts, nuts, washer and screws, hole of required size and Nos for fixing cross arms including painting with two coats of aluminium paint over a coat of red oxide primer for exposed surface and two coats of black bituminious paint for embeded portion in concrete complete all as specified and as directed. Note :- Excavation and earth work and PCC shall be measured and paid separately.
Supplying and errecting, true vertical strut steel tubular, swaged welded pole conforming to IS-2713 part II ,type 410 SP 31, 9 metre long complete with mild steel base plate of 6 mm thick of size 300 X 300 mm, finial taper plug, cap, bolts, nuts, washer and screws, hole of required size and Nos for fixing cross arms including painting with two coats of aluminium paint over a coat of red oxide primer for exposed surface and two coats of black bituminious paint for embeded portion in concrete complete all as specified and as directed. Note :- Excavation and earth work and PCC shall be measured and paid separately.
Supply and fixing cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed with and including applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
Supply and fixing anti climbing device ,spikes type fabricated out of MS bars ,round square and flat with and including providing required nuts ,bolts,washers etc., welding in two halves, made to shape, to suit the cross section of the pole and applying two coats of aluminium paint over a coat of red oxide complete all as specified and as directed.
Supply and laying stay assembly complete with accessories comprising of stay wire 7/2.50 mm dia, 1800 mm long ,MS galvanised stay plate 6 mm thick of size 300x300 mm stay bow including loop type insulator porcelain viterous 90x140 mm clearance hole 25 mm as shown in electrical plate No. 1 complete all as specified and as directed. Note :- Stay clamps, excavation and earth work and concrete shall be measured and paid separately.
Supply and fixing danger notice board of 1.6 mm thick mild steel sheet,vitreous enamelled white,with letters ,figure and conventional skull and bones in signal red colour, fixed with MS clamps ,bolts and nuts,for HT of 25x20cm size complete all as specified and as directed.
Supply and fixing lightening arrester (set of three), expulsion type,11000 Volts, 65 kilo amp discharge capacity with all fittings and necessary connections & testing, complete all as specified and as directed.
Supply and fixing gang operated air breaker switch ,triple pole, mechanically operated , mounted on insulators and steel frame with operating mechanism worked from ground level using heavy duty GI pipe, for current rating 400 amps, out door type (confirming to IS specifications) HT 11 KV , triple pole with fixed contacts of phosphorous and bronze and a set of drop out HT fuse Assembly , fuse carrier fitting , 12 insulator type mounted on MS channel operating rod with pad lock arrangement complete all as specified and as directed.
Supply and fixing synthetic insulating mat 2m x 1m x 19mm for HT 11000 Volt complete all as specified and as directed.
Supply and fixing security light bracket made of GI Pipe, light grade,40 mm dia bend to shape, of length 1.2 mtr long including flat iron clamp made of FI 50x6 mm , nuts, bolts, washers etc duly painted with two coats of synthetic enamel paint over a coat of red oride primer complete all as specified and as directed.
Supply and fixing outdoor type SMC junction box of size 170 x 170 x105 mm one peace moulded SMC door hinged fixed base with hinged right or left side and fixed to the foundation pole with suitable fixing arrangedment bus bar with single electolyitc aluminium for both phase and neutral supported on FRP insulatror and cut out complete fixed on the pole with suitable inlet and outlet, provision for calble connection, kit kat fuse 6 Amp for conrtrolling the pole light, including connecion with 4 sqmm two core PVC insulated aluminium cable to be drawn through pole for suitable length from SMC box to fitting complete all as specified and as directed.
M&L PVC copper conductor cable 3 x 1.5 sqmm through PVC / GI pipe on pole for security light fitting connection complete all as specified and as directed..
Supply and fixing energy efficient LED street light fitting , Beamer, 90 watt ,input voltage 230 VAC, 50 Hz, PF 0.95, CRI>70,THD> 20, minimum 50000 burning hours with ingress protection -IP 65 with CRCA housing, complete all as specified and as directed.
Supplying, installation, commissioning and testing advance maintenance free envionment friendly ring earting system to acheive earth resistance of less than 1 ohm ,each set consisting of 6 Nos , 10 feet long, 0.5 inch dia earth electrode copper circular rods, molecularly bonded copper on outer surface minimum copper bonding thickness 250 microns, with terminals to connect incoming strip 3 bags of 25 Kg each, of environment friendly backfill compound as per manufacturer's instructions with ROHs test certificate for each 150 X 25 X 6 mm copper bar with 4 hole exothermically welded on top to copper bonded rod to make terminal laid in minimum 80mm dia bore with manufacturer'e name embossed on rod, 25 X 3 mm copper shall be used to interconnected the earths and to make the ring with & including providing earth pit cover 300mm X 300mm made of polypropeline and testing on completion complete all as specified and as directed. Notes : (i) Earthing shall be tested after completion of work in presence of GE and proper record shall be maintained duly signed by all concerned. (ii) On testing if the desired earth resistance of less than 1.0 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. (iii) The cooper strip from test point to equipment or entire earthing system to Eqpt/bldg only shall be measured and paid seperetely.
Supply and fixing copper strip 20x3 mm on FRP insulator fixed on wall/MS sheet or floors including connecting to lightening arrester/ earthing/ test point complete all as specified and as directed. Note :- Strip should be brazed/welded at each joint
Supply and fixing gun metal test point terninal block,size 75x75x25 mm, drilled and screwed with sheet metal enclosure of size 100x100x100 mm made out of steel sheet of thickness not less than 1.6mm inlcuding 3 Nos 8 mm dia 25 mm long hexagonal head screw complete all as specified and as directed.
Material and labour for earthing complete with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to GI earth lead strip 32x6 mm upto 7.5 mtrs long by means of bolts, nuts, check nuts and washers of galvanized iron and connection to earthing test point & earth dolly including watering pipe GI 20 mm bore, light grade including protection pipe GI light grade 40mm bore , wire mesh, funnel,lugs, salt, charcoal dust, excavation & earthwork in soft/losse soil and refilling pit chamber with PCC 1:2:4 type B1 using 20 mm graded mechnically crushed stone aggregates , RCC 1:2:4 type B-1 using 20 mm graded mechnically crushed stone aggregates pit cover slab 50 mm thick reinforced with 8 mm dia TMT bars @ 15 cm c/c both ways including necessary form work all as shown in electrical plate No 3 of SSR part-I (2009), including testing on completion on site complete all as specified and as directed.
Material and labour for earthing complete with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to GI earth wire 4.0 mm upto 7.5 mtrs long by means of bolts, nuts, check nuts and washers of galvanized iron and connection to earthing test point & earth dolly including watering pipe GI 20 mm bore, light grade including protection pipe GI light grade 40mm bore , wire mesh, funnel,lugs, salt, charcoal dust, excavation & earthwork in soft/losse soil and refilling pit chamber with PCC 1:2:4 type B1 using 20 mm graded mechnically crushed stone aggregates , RCC 1:2:4 type B-1 using 20 mm graded mechnically crushed stone aggregates pit cover slab 50 mm thick reinforced with 8 mm dia TMT bars @ 15 cm c/c both ways including necessary form work all as shown in electrical plate No 3 of SSR part-I (2009), including testing on completion on site complete all as specified and as directed. Notes for Srl item 60.00 & 61.00 :- (i) Any variation in length of earth lead and protection pipe of earth lead shall be adjusted through DO. (ii) On testing if the earth resistance is not obtained, earthing will be generated at No extra cost ,till the desired earth resistance is obtained. (iii) The chamber shall be constructed atleast 0.5 mtr away from the earth electrode.
Material and labour for PCC 1:2:4, type B-1 using 20 mm graded mechanically crushed stone aggregate as in coping/padestal to pole/ stays/ struts etc with & including necessary form work with fair finished to exposed surfaces without using extra cement complete all as specified & as directed.
Material and labour for PCC 1:3:6, type C-2 using 40 mm graded mechanically crushed stone aggregates as in foundation to pole/stays/struts etc complete all as specified & as directed.
Excavation in post holes (or similar holes) each not exceeding 0.5 cum getting out, returning, filling in and ramming earth or broken rubble mixed with earth around in layers not exceeding 25cm thick in soft/loose soil and making good surface complete all as specified.
Material and labour for two coats of synthetic enamel paint over one coat of red oxide primer on new steel and iron surfaces of walls or of any description including preparation of surface over 10cm width or girth complete all as specified and as directed.
S&F for mild steel work Hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embeding in concrete and screwing etc. wind ties for roof including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified & directed.
M&L for mild steel XPM, Expanded metal of weight not less than 4Kg per Sqm, cut to length, bent to shape required and tying with and including annealed mild steel wire not less than 0.9mm dia or fixing with galvanised steel staples supplied and fixed complete to wood or steel members complete all as specified & directed. Note : Fencing post, Shutters & fillets shall be measured & paid for separately.
Supply and spread 40 mm graded crushed stone aggregate in layer not exceeding 150mm thick each layer around the transformer/LT Panel at sub station complete all as specified and directed.
Supply and spreading/filling 20mm graded stone aggrgate in layer not exceeding 150mm each layer complete all as specified and directed.
Surface excavation not exceeding 30 cm deep and averaging 15 centimetre deep and getting out in soft loose soil complete all as specified and directed.
Supplying installing testing and commissioning diesel engine driven generating set 415 V, 3 phase, 4 wire as per BS 5514/IS-10002 complete with standard control panel, of capacity continuous rating 160 KVA/128 KW at NTP conditions with acoustic enclosure and canopy cover considering all derating factors and comprising of the following :- (a) ALTERNATOR : Self regulated with brushless self excitation 160 KVA, 415 V, 3 phase, 4 wire, 50 HZ, 0.8 P.F.,1500 RPM, with voltage variation plus or minus 2.5% of rated voltage from no-load to full-load foot mounted, screen protected drip proof type with class 'F' insulation, closed coupled single bearing alternator, with necessary controls as recommended by the manufacturers, conforming to BS-5000/IS-4772, capable of supplying unbalanced load. (b) Engine : Multi/cylinder,compression ignition, heavy duty,compact diesel engine liquid cooled with standard accessories, all as per BS-5514/ISO-3046,1500 RPM,control gauges, RPM/Hours meters etc; shaft H.P. suitable for generating application and capable of giving an output of 160 KVA/128 KW for coupled alternator under NTP conditions, complete with following:- (i) Flywheel housing with flywheel to suit closed coupled single bearing alternator. (ii) Air-cleaner dry type with vacuum indicator. (iii) Fuel pump and fuel piping 15mm M.S. pipe with bends, flanges etc. (iv) Fuel filter with water separator and filter element. (v) Lub-oil filter with filter element (vi) D.C. starter 12 volts. (vii) Storage Batteries of suitable voltage and ampere-hours as recommended by the manufacturers. (viii) Residential silencer as per CPCB norms (ix) Supporting/fixing arrangement for muffler with celiling through antivibration pads.
(x) Engine overspeed stop/trip switch. (xi) Radiator with fan. (xii) Dynamo for battery charging. (xiii) Corrosion inhibitor coolant. (xiv) Engine control panel electronic digital display type consisting of battery voltage indicator, lub oil temp and pressure gauges coolant water temp gauge, RPM indicator cum hour meter etc. (xv) Safety controls for alarm due to high water temp (HWT) and low lub oil pressure (LLOP). (xvi) Any other devices/accessories recommended/supplied by the manufacturers as standard eqpt. (c ) SKID : The engine and alternator will be coupled,aligned and mounted on a specially designed common base frame fabricated from M.S. channels of suitable cross sectional area and length with bottom drilled holes suitable for and including supplying and fixing anti vibration pads of required size and numbers as recommended by the manufacturers for mounting of 160 KVA/128 KW DG set. (d) AMF Panel : AMF panel shall be of suitable size factory made indoor cubical type front openable fabricated from CRCA steel sheet 1.6 mm thick complete as per manufacturer specification of Diesel Engine suitable for DG Set of capacity 160 KVA grouted in floor by providing PCC 1:2:4 type B-2 foundation of suitable size as per manufacturers recommendations complete in all respects and consisting of the following :- (i) Contactor ML of suitable capacity. (ii) Aluminium bus bar of capacity 400 Amps (04 Nos) for phase and neutral. (iii) Sensitivity relay set unit with auxiliary relay CT's. (iv) Electronic latch circuit with tripping indication. (v) Instantneous tripping device suitable for complete panel over current 0.5 Amp. (vi) Reset facilities for complete protection of AMF Panel.
(h) Documents : Three sets of following documents :- Maintenance and operation manuals for engine and alternator, spare parts catalogue, warranty/test certificates, schematic diagrams of control panels. (j) other items : List of tools and two years normal maintenance spares as per manufacturers recommended lists, duly priced, item wise. Notes : (i) Contractor will satisfactorily conduct load test of DG set for 12 hours including run on 10% overload for 1 hour. (ii) Testing equipment will be arranged by the contractor. (iii) Fuel/oil required for load test shall be arranged by the contractor and cost thereof is deemed to be included in quoted rate by the contractor. (iv) AMF panel and DG set shall be procured from same OEM i.e make of both shall be same. (v) DG set shall be tested by the representative of Accepting Officer before commisioning and cost thereof deemed to be included in quoted rates.
Supplying, laying, jointing, testing and commissioning under ground LT XLPE electric cable 1100 Volts grade, heavy duty, PVC insulated and sheathed armoued electric power cable with stranded aluminium conductor, of cross sectional area 150 Sqmm 3.5 core conforming to IS- 7098 (Part I) 1988 as in trenches or along the wall/pole through pipe etc served with an inner sheathing of PVC tape and overall PVC sheathed armoured with galvanized steel wire or tape, complete all as specified and directed.
Supply and fixing cable jointing kit for 1100 volt earthed grade cable for outdoor end termination heat shrinkable type joints with jointing material and accessories for 3.5 core XLPE armoured aluminium conductor cable of size 150 Sqmm including cutting complete all as specified and as directed.
Raman Electric Trading Co
Esha Engineers
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .