Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹52.2 Cr
EMD Value
₹52.2 L
Closing Date
15 Dec 2026, 6:00 pm
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Add.City Engineer Building project
CONSTRUCTION OF FIRE STATION & STAFF QUARTERS AT RANIP (TP NO 66, FP NO 292) IN RANIP WARD, WEST ZONE, UNDER BUILDING PROJECT DEPARTMENT, AMC
368228
2026-27
Open
Civil Works - Buildings
Works
Ahmedabad
1 document required · 0 mandatory · 1 optional
₹18,000
Municipal Commissioner, Ahmedabad
₹52.2 L
21 Nov 2026
21 Nov 2026
21 Nov 2026
15 Dec 2026
21 Nov 2026
180 days
I/We am/are willing to carry out work at __________% above / below (should be written in figures and words) the estimated cost
mentioned above. The amount of my/our tender works out as under
Estimated cost put to tender : Rs. 52,19,51,650.45 Estimated cost put to tender : Rs.
Total : Rs___________ Deduct_____% Below : Rs ___________
Note-1 The contractor should get the sample of material in respect of quality and source of supply or manufacturer approved by
Consultant / AMC in all cases. All such approved samples should be kept at site in the custody of EIC-CMC/PMC/AMC. The tests
for the make in external laboratory in presence of CMC/PMC/AMC to be carried out by Contractor at his own cost as per relevant
latest codes. Reinforcement steel & cement original purchase bills shall be produced to CMC/PMC/AMC as and when asked for.
Note-2 Rate includes for any height, any level, any lead & lift and as per directed by EIC.
Note-3 For Fire Fighting System Autoglow Mandatory Signages and NOC Process and charges of NOC are included.
Signature of Contractor Additional City Engineer
Seal Building Project
Date Ahmedabad Municipal Corporation
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West
Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE - 01 : STRUCTURAL WORK
S. NO. ITEM DESCRIPTION AMOUNT
B CONCRETE WORK
E MISCELLANEOUS
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE - 01 : STRUCTURAL WORK
Item no. Item Description Unit Rate Total Qty. Amount
Excavation for foundation up to 1.5 m DEPTH including sorting out and stacking of useful material sand disposing off the excavated stuff upto 50 Meter lead.(A) Loose or
Excavation for foundation up to 1.5 m TO 3.0M DEPTH including sorting out and stacking of useful material sand disposing off the excavated stuff upto 50 Meter lead.(A)
Loose or soft soil
Excavation for foundation up to 3.0M TO 5.0M DEPTH including sorting out and stacking of useful material sand disposing off the excavated stuff upto 50 Meter lead.(A)
Loose or soft soil
Excavation for depth more than 5.0 m for excavation for foundation including sorting out and stacking of useful material sand disposing off the excavated stuff upto
Meter lead.(A) Loose or soft soil
Filling available excavated earth (excluding rock) in trenches. plinth, sides of foundations etc. in layers not exceeding 20cm. In depth consolidating each disposited layer by
ramming and watering.
6 Conveyance charge of lime , murrum, building rubbish, earth manure or sludge, and excavated earth and fly ash upto lead of 5.00 Kms. CUM 235.51 30,768.98
TOTAL OF EARTH WORK
B CONCRETE WORK
Providing and laying cement concrete 1:2:4 (1-Cement:2-Coarse sand:4-graded stone aggregates 20mm nominal size) and curing complete excluding cost of formwork in
(A) Foundation and Plinth
Providing and laying in position Ready Mixed M- 250 grade concrete for reinforced cement conctere work , using cement content as per approved Design Mix
manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead up to 10 kms having continuous agitated mixer, manufactured as
per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering
8 shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve CUM 4,853.56 826.11
workability without impairing strength and durability as per direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 450 kg ) (GRADE SLAB)
Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement content as per approved Design Mix
manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead up to 10 kms having continuous agitated mixer, manufactured as
per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering
9 shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve CUM 5,043.66 1,768.16
workability without impairing strength and durability as per direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 475 kg ) (Foundation/PEDESTAL)
Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement content as per approved Design Mix
manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead up to 10 kms having continuous agitated mixer, manufactured as
per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering
10 shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve CUM 5,043.66 1,964.94
workability without impairing strength and durability as per direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 475 kg ) (RCC BEAM) from basement upto any floor
Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement content as per approved Design Mix
manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead up to 10 kms having continuous agitated mixer, manufactured as
per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering
11 shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve CUM 5,043.66 1,540.84
workability without impairing strength and durability as per direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 475 kg ) (RCC COLUMN) from basement upto any floor
Item no. Item Description Unit Rate Total Qty. Amount
Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement content as per approved Design Mix
manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead up to 10 kms having continuous agitated mixer, manufactured as
per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering
12 shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve CUM 5,043.66 956.99
workability without impairing strength and durability as per direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 475 kg ) (RCC WALL) from basement upto any floor
Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement content as per approved Design Mix
manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead up to 10 kms having continuous agitated mixer, manufactured as
per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering
13 shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve CUM 5,043.66 2,562.51
workability without impairing strength and durability as per direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 475 kg ) (RCC SLAB) from basement upto any floor
Providing and laying in position Ready Mixed M-300 grade concrete for reinforced cement conctere work , using cement content as per approved Design Mix
manufactured in fully automatic batching plant and transported to site of work in transit mixer for a lead up to 10 kms having continuous agitated mixer, manufactured as
per mix design of specified grade for reinforced cement concrete work including pumping of R.M.C. from transit mixer to site of laying, excluding the cost of centering
14 shuttering finishing and reinforcement including cost of admixtures in recommended proportions as per IS: 9103 to accelerate/ retard setting of concrete, improve CUM 5,043.66 140.74
workability without impairing strength and durability as per direction of the Engineer - in - charge. Without Fly Ash (Min cement level as per latest IS 456 shall be
maintained) (Cement level 500 kg ) (STAIRCASE) from basement upto any floor
Bored cast-in-situ M30 grade R.C.C. pile excluding reinforcement complete as per drawing and technical specifications and removal of excavated earth with all lifts and
lead upto 1000 m. (Pile diameter- 300 mm)
16 Providing TMT Bar FE 500D reinforcement for R.C.C. work including bending, binding and placing in position complete upto floor two level
FOUNDATION kg 75.46 2,60,655.47
BASEMENT FLOOR LEVEL kg 75.46 2,44,569.99
GROUND FLOOR LEVEL kg 75.46 1,95,795.98
1ST FLOOR LEVEL kg 75.46 1,13,192.74
Providing TMT Bar FE 500D reinforcement for R.C.C. work including bending, binding and placing in position complete for additional lift of reinforcing steel for all R.C.C.
work above floor two level.
2ND FLOOR LEVEL kg 76.45 1,16,456.33
3RD FLOOR LEVEL kg 77.44 1,17,513.87
4TH FLOOR LEVEL kg 78.43 70,786.39
5TH FLOOR LEVEL kg 79.42 59,350.90
6TH FLOOE LEVEL kg 80.41 47,052.23
7TH FLOOR LEVEL kg 81.40 49,035.40
8TH FLOOR LEVEL kg 82.39 47,057.74
9TH FLOOR LEVEL kg 83.38 47,057.74
10TH FLOOR LEVEL (TERRACE FLOOR LEVEL) kg 84.37 47,057.74
STAIR CABIN / OHWT kg 85.36 42,491.35
TOTAL OF CONCRETE WORK
Providing formwork of ordinary timber planking so as to give a rough finish including centering shuttering strutting and propping etc. Height of propping and centering
18 below supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ reinforced concrete and plain concrete work in. (A) Foundations Footings Bases SQM 171.68 1,772.80
of Columns etc. and Mass concrete.
Providing formwork of ordinary timber planking so as to give a rough finish including centering shuttering strutting and propping etc. height of propping and centering below
19 supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ reinforced concrete and plain concrete work in. (G) Columns PillarsPosts and struts. SQM 297.68 12,956.45
(1) Square Rectangular Polygonal in plan.
Item no. Item Description Unit Rate Total Qty. Amount
Extra for additional height of propping and centering where the height of propping and centering exceeds 4 .O M between supporting floor to ceiling including temporary
brick or stone pillars for supporting as required. (ii)Height more than 5.0 M.and upto 6.0 M.
Extra for additional height of propping and centering where the height of propping and centering exceeds 4 .O M between supporting floor to ceiling including temporary
brick or stone pillars for supporting as required. (ii) Height more than 5.0M.and upto 6.0 M.
Extra for additional height of propping and centering where the height of propping and centering exceeds 4 .O M between supporting floor to ceiling including temporary
brick or stone pillars for supporting as required. (ii) Height more than 6.0M.and upto 7.0 M.
Providing formwork of ordinary timber planking so as to give a rough finish including centering shuttering strutting and propping etc. height of propping and centering below
23 supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ reinforced concrete and plain concrete work in. (C) Vertical surface such as walls (any SQM 229.95 5,191.49
thickness) partitions and the like including attached buttresses & string course & the like.
Providing formwork of ordinary timber planking so as to give a rough finish including centering shuttering strutting and propping etc. Height of propping and centering
24 below supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ reinforced concrete and plain concrete work in. (B) Flat surfaces such as soffits SQM 252.00 16,899.37
of supspened floors slabs Landings and the like. (1) Floors etc. upto 200 mm in thickness.
Providing formwork of ordinary timber planking so as to give a rough finish including centering shuttering strutting and propping etc. height of propping and centering below
25 supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ reinforced concrete and plain concrete work in. (H) (1) Sides and soffits of Beams SQM 192.15 15,605.06
Beam Haunchings cantilevers Girders Bressumers and Lintels not exceeding 1 M. in Depth.
Providing formwork of ordinary timber planking so as to give a rough finish including centering shuttering strutting and propping etc. Height of propping and centering
below supporting floor to ceiling not exceeding 4 M. and removal of the same for in situ reinforced concrete and plain concrete work in. M) Staircase with slopingor
26 stepped soffits including risers and stringers excluding landing. SQM 242.55 780.19
TOTAL OF FORM WORK
Earthwork for embankment including breaking clods, dressing with all lead and lift and including watering rolling and consolidation of subgrade in layers at O.M.C. to
required dry density including filling the depression which occur during the process using power roller 8T to 10T.(E)From Borrow area within 3.0KM. lead
Construction of granular sub-base by providing machine crushed B.T. material satisfying MORT&H specification (Fifth revision) of grading I including spreading in uniform
28 layer with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC and compacting with vibratory roller to achieve the desired density etc. CUM 1,117.00 451.72
Providing and filling PCC in foundation with ordinary cement concrete M15 grade and providing necessary pin headers including formwork, vibrating, ramming,
compaction, leveling, curing, etc. complete.
Providing and casting in situ controlled cement concrete M-30 for wearing coat laid as directed dincluding tamping, vibrating, finishing, curing and fillingin joints with
bitumen complete
TOTAL OF ROAD WORK
Item no. Item Description Unit Rate Total Qty. Amount
E MISCELLANEOUS
Rebar Fixing In Concrete Using Adhesive - Providing and fixing heavy duty injection adhesive for rebar of any size any length fixing in concrete using chemical. The
31 system should be made of two foils consisting of resin and Hardener foil pack. The installation and the setting instructions should be strictly followed as per the No. 2,160.08 315.00
manufacturers recommendations. Reinforcements will be supplied free of cost at site. (Rate considered as the weighted average of the total rebar quantities)
Providing and fixing in position high-grade PVC water stopper of size 250 mm wide × 10 mm thick at construction / expansion joints in underground water tanks, STP
structures and similar water-retaining structures, complete as per drawings and directions of Engineer-in-Charge
Trimix flooring - BROOM FINISH
Providing and laying C.C. pavement of mix M-25 with ready mixed/ batch mixed concrete (with use of PP cement) from batching plant. The ready mixed concrete shall be
casted in panel and finished with screed board vibrator, vacuum dewatering process and finally finished by floating, brooming with machine. Grooves to be made of size
33 5mm wide and one third of thickness of concrete within 48 Hours of concreting to form bay of 4 x 4 meters using heavy duty cutting machine with diamond cutting wheel SQM 312.91 5,360.25
and filling of the groove with appropriate sealant etc. complete as per specifications and as directed by the EIC. If trimix concrete shall be laid over on existing concrete
surface, bonding agent shall be applied before laying of concrete at all basements floors. Reinforcement if required shall be paid in relevant tender item.
TOTAL OF MISCELLANEOUS
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West
Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE - 02 : CIVIL WORK
S. NO. ITEM DESCRIPTION AMOUNT
2 MASONARY WORK
2 PLASTER & CLADDING WORK
3 FLOORING & PAVING WORK
3 PAINTING AND POINTING
4 CEILING & PARTITION WORK
4 WATER PROOFING WORK
5 DOOR AND WINDOW WORK
5 MISCELLENEOUS
6 FURNITURE WORK
7 MEPF CIVIL WORK
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE - 02 : CIVIL WORK
Item no. Item Description Unit Rate Total Qty. Amount
A DEMOLITION & EARTH WORK
1 Demolition including stacking of serviceable materilas and disposal of unserviceable materials with all lead and lift. (i) R.C.C. work CUM 1,047.38 165.00
Demolition of Brick work and stone masonry including stacking of serviceable materilas and disposal of unserviceable materials with all lead and
lift.(ii) In Cement Mortar.
3 Conveyance charge of Modular Brick (Statement 5, Page-6)
a Lead From 5 Km to 10 Km. CUM 668.28 5.00
b Lead From 10 Km to 15 Km. CUM 681.40 5.00
c Lead From 15 Km to 25 Km. CUM 693.32 5.00
4 Conveyance charge of Cement (Statement 5, Page-7)
a Lead From 5 Km to 10 Km. CUM 202.65 38.50
b Lead From 10 Km to 15 Km. CUM 207.24 38.50
c Lead From 15 Km to 25 Km. CUM 211.41 38.50
5 Conveyance charge of Steel (Statement 5, Page-7)
a Lead From 5 Km to 10 Km. CUM 212.65 16.50
b Lead From 10 Km to 15 Km. CUM 217.24 16.50
c Lead From 15 Km to 25 Km. CUM 221.41 16.50
Conveyance charge of (A) lime murrum building
rubbish earth manure or sludge & execavated rock and rubbish [Earth] (Statement 5, Page-6)
a Lead From 5 Km to 10 Km. CUM 417.67 11,842.00
b Lead From 10 Km to 15 Km. CUM 425.87 11,842.00
c Lead From 15 Km to 25 Km. CUM 433.32 11,842.00
Earthwork for embankment including breaking clods, dressing with all lead and lift and including watering rolling and consolidation of subgrade in layers at O.M.C. to required
dry density including filling the depression which occur during the process using power roller 8T to 10T. From Borrow area as per lead available.
8 Filling in foundation and plinth with murrum or selected soil in layers of 20cm. thickness including watering, ramming and consolidating etc. complete. CUM 286.20 2,199.00
TOTAL OF EARTH WORK
B MASONARY WORK
Brick work using common burnt clay building bricks having crushing strength not less than 35 kg./Sq.Cm. in foundation and plinth in Cement Mortar 1:5. (1- Cement : 5 -fine
sand)(B) Conventional
Brick work using common burnt clay building bricks having crushing strength not less than 35 kg./Sq.Cm. above plinth level upto floor two level in Cement Mortar 1:5. (1-
Cement : 5 -fine sand)(B) Conventional
a Basement Cu.m 4,283.91 43.00
b Ground Floor Cu.m 4,283.91 354.00
c 1st Floor Cu.m 4,283.91 583.00
Brick work using common burnt clay building bricks having crushing strength not less than 35 kg./Sq.Cm. for brick work in superstructure above floor two level in Cement
Mortar 1:5. (1- Cement : 5 -fine sand)(B) Conventional
a 2nd Floor Cu.m 4,324.00 526.00
b 3rd Floor Cu.m 4,364.09 509.00
c 4th Floor Cu.m 4,404.18 390.00
d 5th Floor Cu.m 4,444.27 395.00
e 6th Floor Cu.m 4,484.36 390.00
f 7th Floor Cu.m 4,524.45 390.00
Item no. Item Description Unit Rate Total Qty. Amount
g 8th Floor Cu.m 4,564.54 395.00
h 9th Floor Cu.m 4,604.63 390.00
i 10th Floor Cu.m 4,644.72 390.00
j Terrace / Mumty Cu.m 4,684.81 106.00
(i) Half brick masonry in common brunt clay building bricks having crushing strength not less
12 than 35 Kg/Sq.Cm. in Cement mortar 1:4 (1- Cement : 4 -coarse sand ) for half brick masonry in superstructure above plinth level upto floor two level. (B) Conventional
a Ground Floor SQM 646.70 297.00
b 1st Floor SQM 646.70 492.00
(i) Half brick masonry in common brunt clay building bricks having crushing strength not less
than 35 Kg/Sq.Cm. in Cement mortar 1:4 (1- Cement : 4 -coarse sand ) for brick work in superstructure above floor two level (B) Coventional
a 2nd Floor SQM 652.64 588.00
b 3rd Floor SQM 692.73 440.00
c 4th Floor SQM 732.82 385.00
d 5th Floor SQM 772.91 385.00
e 6th Floor SQM 813.00 385.00
f 7th Floor SQM 853.09 385.00
g 8th Floor SQM 893.18 385.00
h 9th Floor SQM 933.27 385.00
i 10th Floor SQM 973.36 385.00
j Terrace / Mumty SQM
Providing and filling sunken portion with light weight AAC block bats of size 40–60 mm, including placing, packing and filling voids with cement sand mortar 1:5 (1 cement :
14 coarse sand) admixed with integral waterproofing compound conforming to IS 2645, properly compacted and levelled, and finishing with 25 mm thick cement sand mortar cum 6,407.00 123.00
screed 1:4 laid to required levels and slopes, smooth and ready to receive floor finish, complete as required.
TOTAL OF MASONARY WORK
C PLASTER & CLADDING WORK
Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior plastering upto floor two level and finished even and smooth in (i)Cement mortar
1:3 (1-cement:3-sand)
a Basement SQM 127.58 1,812.00
b Ground Floor SQM 127.58 2,125.00
c 1st Floor SQM 127.58 2,235.00
Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior plastering above two floor level and for below listed floors and finished even and
smooth in (i)Cement mortar 1:3 (1-cement:3-sand) : interior plastering (1) Single coat plaster
a 2nd Floor SQM 150.74 3,678.00
b 3rd Floor SQM 173.90 1,732.00
c 4th Floor SQM 197.06 1,732.00
d 5th Floor SQM 220.22 1,732.00
e 6th Floor SQM 243.38 1,732.00
f 7th Floor SQM 266.54 1,732.00
g 8th Floor SQM 289.70 1,732.00
h 9th Floor SQM 312.86 1,732.00
i 10th Floor SQM 336.02 1,732.00
j Terrace / Mumty SQM
Item no. Item Description Unit Rate Total Qty. Amount
20mm thick sand faced cement plaster on walls upto height 10 metres above ground level consisting of 12mm thick backing coat of C.M. 1:3 (1-cement : 3-sand) and
8mm thick finishing coat of C.M. 1:1 (1-cement : 1-sand) etc. complete.
a Ground Floor SQM 297.68 3,184.00
b 1st Floor SQM 297.68 4,369.00
c 2nd Floor SQM 297.68 5,258.00
20mm thick sand faced cement plaster on walls upto height 10 metres above two floor level and for below listed floors consisting of 12mm thick backing coat of C.M.
1:3 (1-cement : 3-sand) and 8mm thick finishing coat of C.M. 1:1 (1-cement : 1-sand) etc. complete. (2) Two coat plaster
a 3rd Floor SQM 324.14 3,976.00
b 4th Floor SQM 350.60 3,399.00
c 5th Floor SQM 377.06 3,446.00
d 6th Floor SQM 403.52 3,399.00
e 7th Floor SQM 429.98 3,399.00
f 8th Floor SQM 456.44 3,446.00
g 9th Floor SQM 482.90 3,399.00
h 10th Floor SQM 509.36 3,399.00
i Terrace / Mumty SQM 535.82 1,092.00
Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or half brick walls for interior plastering upto floor two level and finished even and
smooth in (ii) Cement mortar 1:4 (1-cement :4-sand)
a Basement SQM 155.61 29.00
b Ground Floor SQM 155.61 220.00
c 1st Floor SQM 155.61 292.00
Providing 15mm thick cement plaster in single coat on Rough (Similar)side of single or half brick walls for interior plastering above two floor level and for below listed
floors and finished even and smooth in (ii) Cement mortar 1:4 (1-cement :4-sand) (1) Single coat plaster
a 2nd Floor SQM 178.77 475.00
b 3rd Floor SQM 201.93 215.00
c 4th Floor SQM 225.09 215.00
d 5th Floor SQM 248.25 215.00
e 6th Floor SQM 271.41 215.00
f 7th Floor SQM 294.57 215.00
g 8th Floor SQM 317.73 215.00
h 9th Floor SQM 340.89 215.00
i 10th Floor SQM 364.05 215.00
Providing 10mm thick cement plaster in single coat for interior plastering upto floor two level for plastering on ceilings and sofits of stairs upto floor two level instead
of plastering on walls. and finished even and smooth in (i)Cement mortar 1:3 (1-cement:3-sand)
a Basement SQM 152.15 2,838.00
b Ground Floor SQM 152.15 2,564.00
c 1st Floor SQM 152.15 2,882.00
Providing 10mm thick cement plaster in single coat for interior plastering above two floor level and for below listed floors for plastering on ceilings and sofits of stairs
upto floor two level instead of plastering on walls. and finished even and smooth in (i)Cement mortar 1:3 (1-cement:3-sand)
a 2nd Floor SQM 175.31 1,922.00
b 3rd Floor SQM 198.47 1,308.00
c 4th Floor SQM 221.63 1,260.00
d 5th Floor SQM 244.79 1,260.00
Item no. Item Description Unit Rate Total Qty. Amount
e 6th Floor SQM 267.95 1,260.00
f 7th Floor SQM 291.11 1,260.00
g 8th Floor SQM 314.27 1,260.00
h 9th Floor SQM 337.43 1,260.00
i 10th Floor SQM 360.59 1,260.00
j Terrace / Mumty SQM 383.75 101.00
Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior plastering upto floor two level and finished even and smooth in (i)Cement mortar
1:3 (1-cement:3-sand) and for finishing with a floating coat of neat cement slurry.
a Basement SQM 152.15 106.00
b Ground Floor SQM 152.15 318.00
c 1st Floor SQM 152.15 289.00
Providing 10mm thick cement plaster in single coat on brick/concrete walls for interior plastering above two floor level and for below listed floors and finished even and
smooth in (i)Cement mortar 1:3 (1-cement:3-sand) : interior plastering (1) Single coat plaster and for finishing with a floating coat of neat cement slurry.
a 2nd Floor SQM 175.31 487.00
b 3rd Floor SQM 198.47 275.00
c 4th Floor SQM 221.63 151.00
d 5th Floor SQM 244.79 151.00
e 6th Floor SQM 267.95 151.00
f 7th Floor SQM 291.11 151.00
g 8th Floor SQM 314.27 151.00
h 9th Floor SQM 337.43 151.00
i 10th Floor SQM 360.59 151.00
j Terrace / Mumty SQM 383.75 106.00
WET CLADDING POLISHED GRANITE : Providing and fixing machine cut, composite patterned wall wet cladding out of 18-20mm thick mirror polish granite machine cut,
machine polished to walls and columns. Stone fixed with required stainless steel pins / dowels / cramps including drilling holes, making notches etc. for securedly fixing with
25 pins / cramps to wall. Stone fixed in position with approved readymix ploymer based adhesive in line and level and in pattern as shown in the drawing. Joints cleaned, SQM 4,546.00 301.00
grouted with approved ready made ploymer modified grout or cured and cleaned, further to include required double legged independent scaffolding etc. complete to the
satisfaction of the EIC.
Washed stone grit plaster on exterior walls height upto 10 metre above ground level, in two layers, under layer 12 mm cement plaster 1:4 (1 cement : 4 coarse sand ),
furrowing the under layer with scratching tool, applying cement slurry on the under layer @ 2 Kg of cement per square metre, top layer 15 mm cement plaster 1:1/ 2:2 (1
26 cement: 1/2 coarse sand : 2 stone chipping 10 mm nominal size), in panels with groove all around as per approved pattern, including scrubbing and washing the top layer SQM 647.00 1,376.00
with brushes and water to expose the stone chippings ,complete as per specification and direction of Engineer-in-charge (payment for providing grooves shall be made
GROOVE IN STONE CRETE : 'Forming groove of uniform size in the top layer of washed stone grit plaster as per approved pattern using wooden battens, nailed to the
27 under layer, including removal of wooden battens, repair to the edges of panels and finishing the groove complete as per specifications and direction of the Engineer-in- RMT 40.00 1,000.00
charge . 15mm wide and 15mm deep groove.
STONE CRETE for above 10m level :
Washed stone grit plaster on exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof, in two layers, under layer 12 mm
cement plaster 1:4 (1 cement : 4 coarse sand ), furrowing the under layer with scratching tool, applying cement slurry on the under layer @ 2 Kg of cement per square metre,
28 top layer 15 mm cement plaster 1:1/ 2:2 (1 cement: 1/2 coarse sand : 2 stone chipping 10 mm nominal size) using white cement and selected pigment, in panels with groove SQM
all around as per approved pattern, including scrubbing and washing the top layer with brushes and water to expose the stone chippings, complete as per specification and
direction of Engineer-in-charge (payment for providing grooves shall be made separately).
Item no. Item Description Unit Rate Total Qty. Amount
TOTAL OF PLASTER & CLADDING WORK
D FLOORING & PAVING WORK
Granite Flooring - Leather Finish : Providing and laying lether finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the
building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement: 4 coarse sand) laid and
29 jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as SQM 1,921.00 1,789.00
specified and as directed by the Engineer-in-Charge.
lether finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent
Granite Skirting / Riser / vertical - Leather finish : Providing and laying Granite stone slab 25mm thick in risers of steps,skirting Dedo and pillars laid on 10mm thick
30 cement mortar 1:3 (1-Cement : 3 coarse sand) and jointed with gray cement slury mixed with pigment to match the shade of slab including rubbing and polishing etc. SQM 2,323.00 327.64
Granite Flooring - Polished : Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all
complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement: 4 coarse sand) laid and jointed
31 with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and SQM 2,250.00 635.00
as directed by the Engineer-in-Charge. Polished granite stone slab of colour black, cherry/ruby red or equivalent.
Polishe Kota Stone Flooring : Providing and laying polished Kota stone slab flooring over 20mm (Average) thick base of cement mortar 1:6 (1-cement : 6-coarse sand) or
L.M. 1.1.5 laid over and jointed with grey cement slurry including rubbing and polishing etc. complete. (B) 30 mm thick
Polishe Kota Stone Skirting / Riser / vertical : Providing and laying polished kota stone slab 25mm thick in risers of steps,skirting Dedo and pillars laid on 10mm thick
33 cement mortar 1:3 (1-Cement : 3 coarse sand) and jointed with gray cement slury mixed with SQM 1,176.03 327.00
pigment to match the shade of slab including rubbing and polishing etc. complete.
Vitrified Tile Flooring - polished : P & L 24" x 24" vitrified 8 mm thick tile flooring over 20 mm (average) base of cement mortar 1:6 ( 1 cement: 6 coarse sand) on new
34 surface or fixing on existing flooring by adhesive material including dismentaling of existing flooring and jointed with color cement slurry including finised with flush pointing & SQM 1,261.58 6,242.00
cleaning the surface etc. complete for shade as per architect/client
Vitrified Tile Flooring - antiskit : P & L 24" x 24" vitrified 8 mm thick tile flooring over 20 mm (average) base of cement mortar 1:6 ( 1 cement: 6 coarse sand) on new
35 surface or fixing on existing flooring by adhesive material including dismentaling of existing flooring and jointed with color cement slurry including finised with flush pointing & SQM 1,383.99 944.00
cleaning the surface etc. complete for antiskit
Vitrified Tile Skirting / Dado / Vertical (Rooms) : Providing and laying Vitrified tiles 8 to 10 mm thick , 24'' x 24'' in skrting risers of steps and dedo on 10mm thick cement
plaster 1:3 (1-cement : 3- coarse sand) and jointed with white cement slurry
Ceramic Tile Flooring : Providing and laying Ceramic tiles 6mm thick in flooring treads of steps and landing laid on a bed of 12mm thick cement mortar 1:3 (1-cement : 3-
coarse sand ) finishing with flush pointing in white cement.
Ceramic Tile Skirting / Dado / Vertical : Providing and layingCeramic tiles 6mm thick in skrting risers of steps and dedo on 10mm thick cement plaster 1:3 (1-cement : 3-
coarse sand) and jointed with white cement slurry
Granite Skirting / Riser / vertical - Polished : Providing and laying GRANITE STONE SLAB 25mm thick in risers of steps,skirting Dedo and pillars laid on 10mm thick
39 cement mortar 1:3 (1-Cement : 3 coarse sand) and jointed with gray cement slury mixed with pigment to match the shade of slab including rubbing and polishing etc. SQM 2,511.00 17.00
Item no. Item Description Unit Rate Total Qty. Amount
Granite Treads - Leather Finish : 'Providing and fixing 20mm thick approved up to 600mm wide leather finish Granite stone treads of length of step and machine cut,
machine polished. Treads to be rounded at front and all exposed edges machine polished. Further treads to have edge polished chamfering with 3 nos. (6mm x 3mm deep)
40 grooves on top at front or as detailed in drawing for antiskid effect as shown in the drawing. Treads fix to be using approved adhesive over cement concrete screed joints SQM 3,641.00 676.00
grouted with approved matching coulour grout,, curing, cleaning, polishing etc. all complete at all heights and leads to the approval of the Engineer in charge.
Polished Granite Coping : Providing and fixing premoulded and prefinished, machine cut polished 18-20 mm thick granite stone for coping, parapet top and similar
locations of required size, approved shade, colour and texture laid using approved adhesive over cement concrete screed (paid separately), joints grouted with approved
41 matching colour grout, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels, as per sample SQM 6,980.00 2,620.00
approved by Engineer in-charge.
Sandwich Kitchen Platform : 'Providing & Fixing Sandwich type Kitchen Platform of Min. 750mm wide using Top 18mm thick granite of approved shade and sample and
bottom 25mm thick single side Polished kota stone with 25 mm thick screed of cement mortar 1:3 With granite Facia Patti. and vertical End granite supports. The stone shall
42 be fixed by chassing in to the wall surface and supported vertically with 25mm thick sandwich kota stone support to complete job as directed by Architect/Engineer -in- SQM 3,159.00 388.00
charge. It is inclusive of all necessary chasses & civil work, holes and cuts etc. comp. No extra payment shall be made in any case.
Toilet Wash Basin Counters - Providing & Fixing Granite wash basin counter of granite of Min. 600mm wide using Top 18mm thick granite having drop facia with epoxy
adhesive to 25mm tk. marine play wood along the platform as per typical details given in. ref. drawing of approved shade and sample. It allows for all necessary mirror polish
43 moulding, edge polishing, chamfering, etc. completed. Necessary arrangement of MS 50mmx50mmx2mm customized bracket fixed to given wall to support granite top shall SQM 4,418.00 25.00
be part of this item. It is inclusive of all necessary chasses & civil work, holes and cuts etc. comp. No extra payment shall be made in any case.
Granite Urinal Partitions : Providing and fixing stone slab with table rubbed, edges rounded and both side polished, of size 450x900 mm deep and 40 mm thick, fixed in
44 urinal partitions by cutting a chase of appropriate width with chase cutter and embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 SQM 1,793.00 5.00
coarse sand : 4 graded stone aggregate 6 mm nominal size) as per direction of Engineer-in-charge and finished smooth.Granite Stone of approved shade
Providing and fixing pre-cast Rubber Dye / steel Dye inter locking concrete block 60mm thick with grade of concrete M300 pnumatic compressed / vibrated mechanically and
as per approved design Confirming to IS 15658 : 2006 including 35 mm Sand layer for levelling and filling the joint with sand in proper line and level as per guidlines of IRC :
45 SP 63-2018 etc. Complete. SQM 680.10 1,203.00
Providing and fixing pre-cast concrete kerbstone of gray cement based concrete block 30cm length,30cmheightand15cmthickofM200grade concret as per approved design
and including excavationfor fixing inproper lineandlevel,filling the jointwithC:M1:3 (1cement:3fine sand) etc complete.
Providing and laying cushioning layer on R.C.C. Slab consisting of 75mm thick lime, concrete using brick aggregate of 20mm nominal size mortar compresing of 1-Lime : 2-
TOTAL OF FLOORING & PAVING WORK
E PAINTING AND POINTING
Wall painting (two coats) with plastic emulsion paint of approved brand and manufacture on undecorated wall surface to give an even shade including throughly brushing the
surface free from mortar droppings and other foreign matter and sand papered smooth.
Item no. Item Description Unit Rate Total Qty. Amount
Finishing wall with water proofing cement paint of on wall surfaces (Two coats) to give an approved brand and manufacture and of required shape even shade after
thoroughly brushing the surface to remove all dirt and remains of loose powered materials. + for finishing with cement paint on ceiling and sloping roofs.
Applying two coats of putty & two coats of primer of approved brand and manufacture on new wall surface to give an even shade including thoroughly brushing the surface
free from mortar dropping and other foreign matter and sand papered smooth.
Exterior Texture Paint : Providing and applying exterior textured paint system on prepared surfaces, comprising 1 coat primer, 2 coats textured finish, and 2 coats clear
protective top coat, including all materials, labour, surface preparation, scaffolding, and complete as per specifications.
White washing with lime on wall surface (onecoats) to give an even shade including thoroughly booming the surface to remove all dirt, dust; mortar drops and loose scales of
lime washand other foreign matter.
Metal surface primer+paint : Applying priming coat over new steel and other metel surface after and including preparing the surface by throughly cleaning, oil,grease, dirt
and other foreign matter and scoured with brushes fine steel wood, scrapers and sand paper with ready mixed priming paint brushing red lead. Painting two coats (excluding
53 priming coat) on new steel and other metal surface with enamel paint, brushing, interior to give an even shade including cleaning the surface an even shade including SQM 121.28 1,060.00
cleanicn the surface of all dirt, dust and other foreign matter. Painting two coats (excluding priming coat) on new steel and other metal surface with enamel paint, brushing,
interior to give an even shade including cleaning the surface an even shade including cleanicn the surface of all dirt, dust andother foreign matter
TOTAL OF PAINTING AND POINTING WORK
F CEILING & PARTITION WORK
GYPSUM BOARD CEILING : Providing and fixing suspended false ceiling at all heights using a galvanized steel framework with ceiling drop up to 1000 mm, designed to
satisfy L/400 deflection criteria under 200 Pa load. The ceiling shall comprise single layer 12.5 mm thick tapered edge gypsum board conforming to IS 2095 (Part 1):2023
Type A / EN 520 Type A or equivalent approved standards, consisting of aerated gypsum core encased in and firmly bonded to paper liners, having required thermal and
mechanical properties.
The framework shall be made of galvanized steel sections conforming to relevant standards, manufactured from CR1 grade steel with minimum yield strength of 300 MPa 769.00
and appropriate corrosion protection (minimum 120 GSM or equivalent coating), including perimeter channels fixed along walls/partitions at specified intervals using
approved fasteners suitable for the substrate, ceiling angles suspended from the soffit using cleats and anchors, intermediate channels, and ceiling sections fixed at required
54 spacing to form a rigid grid. SQM
The gypsum boards shall be fixed to the framework using suitable drywall screws at specified spacing. All joints shall be treated with approved jointing compound and jointing
tape, finished in multiple layers to achieve a smooth, seamless surface ready to receive paint.
The work shall include making necessary cut-outs and providing framing for light fixtures, diffusers, grills and other services, complete in all respects as per approved
drawings and directions of the Engineer-in-Charge.
The item shall include all materials, labour, scaffolding, tools and tackles, all leads and lifts, complete, but excluding final painting.
MOISTURE RESISTANT GRID CEILING :Providing and fixing tiled false ceiling in true horizontal level using 600x600 mm grid system with hot-dip galvanized steel sections,
comprising main runners (~24x38x0.3 mm) at 1200 mm c/c, cross tees (~24x25x0.3 mm) at 600 mm c/c and secondary tees forming 600x600 mm grid, supported on GI wall
angles (~24x24x0.4 mm) fixed along periphery. The framework shall be suspended from soffit using cleats, hangers and approved fasteners at specified spacing, ensuring
55 proper alignment and level. All sections shall be of galvanized steel conforming to relevant standards with minimum 90–120 GSM coating. SQM 1,179.00 449.00
The grid shall accommodate 12–12.5 mm thick square edge gypsum/plasterboard tiles of size 595x595 mm conforming to IS 2095 or equivalent, factory laminated with
decorative/facing finish and sealed edges, laid in the grid to form a uniform ceiling. The system shall include all necessary supports, hangers, fasteners and accessories,
complete in all respects as per drawings and directions of the Engineer-in-Charge.
Item no. Item Description Unit Rate Total Qty. Amount
GYPSUM GRID CEILING : Providing & Fixing of Soft Fibre Acoustical Suspended Ceiling System with Optra Beveled Tegular Edge Tiles With Armstrong Silhouette 15mm
Exposed Grid. The tiles should have Humidity Resistance (RH) of 95%, NRC 0.9, Light Reflectance ≥85%, Colour White, Fire Performance UK Class 0 / Class 1 (BS 476 pt -
6 &7) in module size of 600x600x15mm, suitable for Green Building application, with Recycled content of 66% GW & 74% RW. The tile shall be laid on Armstrong Silhouette
profile grid system with 15mm white flanges incorporating a 6mm central reveal in white/black colour and with a web height of 38mm and a load carrying capacity of minimum
7.90 Kgs/M2 (as per standard installation layout mentioned below) & pull out strength of 100Kgs. Silhouette, Main Runners & Cross Tees to have mitred ends & “birdsmouth” 264.00
notches to provide mitred cruciform junctions. The T Sections have a Galvanizing of 90 grams per M2 and need to be installed with Suspension system of Armstrong make.
The Tile & Grid system used together should carry a 10 year warranty.ARMSTRONG SUSPENSION SYSTEM accessories manufactured and supplied by Armstrong World
Industries consisting of M6 Anchor Fasteners with hanger hole, pre Straightened Hanger wire of dia – 2.5 mm of 1.80 m length having a tensile strength of 344-413 MPa and
a minimum pull strength of 110 kgs. (Adjustable hook clips of 0.7mm thick, galvanized spring steel can also be used for installation purpose as an additional accessory. The
adjustable clip also consists of a 4 mm aquiline wire to be used with the main runner).Hanging system up to 1.5 M (for above mentioned item)
Cement Board False Ceiling - Designing, Fabricating, testing, installing and fixing of Heavy-duty GI Sections, 8mm thk. Cement fibre sheet fixed with self-tapping screw,
keeping 3-4 mm gaps at every joint. Acrylic Sealant will be applied to all cement board joints. All the joints are treated with 150 mm-wide 160 GSM Fibre Mesh and Styrobond
57 DP. Terabond A (Mixing Ration with water 1:5) will be applied to the cement board. Finish TOP Coat - Exposed Concrfete Finish Decorend will be applied in two layers. SQM 2,440.00 48.00
TOTAL OF CEILING AND PARTITION WORK
G WATER PROOFING WORK
RAFT: Supplying and installing waterproofing treatment for Raft/Grade slab by using fully bonded HDPE sheet, membrane 1.2mm thick before casting of the RCC Raft.
The preapplied, fully bonded HDPE sheet membrane to get bonded to the underneath of the poured concrete used as base/ raft slab to resist lateral water migration. The
fully bonded HDPE sheet membrane shall consist of a thick HDPE film, a highly aggressive pressure sensitive adhesive and Granuels which bonds integrally to poured
concrete of base slab. 2,966.00
The membrane shall conforms to basement waterproofing protection to grade 3 as defined in BS 8102:2009. The fully bonded HDPE sheet waterproofing membrane shall
have following minimum properties :
1) Resist hydrostatic pressure of - 60 +/- 6 m head of water (as per ASTM D5385)
2) Peel Adhesion to concrete- Minimum 1.5 N/mm
3) Puncture Resistance – 800 +/- 100 N
58 4) Tensile strength -21 +/- 3 N/mm2 SQM
5) Engloation :400%
6) Bare HDPE Thickness > 0.8 mm
7) Joint Strength at overlap - 15 +/- 2 N/mm
The fully bonded HDPE sheet membrane shall be installed with heat welded method by accurately positioning sheets by overlapping them for 100 mm. The membrane shall
be laid over the concrete blinding having smooth dried surface including necessary removal of release liner while applying, necessary overlaps between the membranes and
fixing overlaps by Double sided adhesive tape firm rolling onto the surface to get a tight seal, etc. Hot applied materials or protective screed shall NOT be
permitted. All systems to be installed as per manufacturer's recommendations, etc. complete with all lead and lift for all materials and labour and as directed by Engineer in-
This membrane shall be terminated Horizontally and fixed using EVA at the junctions/ pheriphary of the basement wall & Raft as per Manufacturers recommendation,
including all materials & labour, etc, all complete.
Retaining Wall Waterproofing :
Surface preparation: The substrate must be free of loose aggregate, slush, mud, sharp protrusions and stagnated water. Ground water level needs to be kept under the PCC
59 level, continues dewatering to be done till completion of concreting. The surface of retaining wall should be dry (moisture content <5%) before application of
primer.Construction Joint treatment: All the construction joints in retaining wall should be opened in a V groove manner of size 10mm X 10mm using a grinder or suitable
tool & should be sealed with Polymer Modified Mortar prepared with ReArm Bond SBR 45 or equivalent @5 liter per 50 kg bag of cement.
Filling of tie rod holes: The tie rod holes shoukd be filled with Polymer modified mortar prepared using ReArm Bond SBR 45 or equivalent @5 liter per 50 kg bag of
Item no. Item Description Unit Rate Total Qty. Amount
Preparation of chamfer or vatta at wall & raft junction: The junction between RCC raft & retaining wall should be treated by preparation of vatta of size min. 50mm X 50mm
with Polymer Modified Mortar prepared ReArm Bond SBR 45 or equivalent @5 liter per 50 kg bag of cement.
Application of primer: Bituen based Primer should be applied on treated, dry concrete surface at coverage of 4 to 6 SQM per liter using a brush or roller. Primer should be
allowed to dry for minimum 2 hrs. The SBS membrane should be fixed within 24 hours after application of primer.
SBS Membrane: Supplying and applying waterproofing of RCC Retaining wall using High performance, self adhesive membrane with cross laminated HDPE film
AquaArm SBS 3000 X or equivalent,conforming to BS 8102 & IS 16471 as per the specifications listed below - Puncture Resistance: 300 N (as per ASTM E 154) and
Hydrostatic Head Resistance: not less than 70 m head (ASTM D 5385), Tensile Strength - 4.0/3.5 N/mm² (ASTM D 412) ,Elongation of > 230 % (ASTM D 412), Low
Temperature Flexibility up to: -15°C. The SBS membrane should be fixed on the primed concrete surface by removing the release film with maintaining overlap of 75 mm at
the sides & 100 mm at the end sections.'
Protection of membrane: The SBS Membrane should be protected by means of 6-8 mm thick dimple boards against any physical damage before commencement of
Termination of Membrane on retaining wall: The SBS membrane should be secured with a Metal strip on retaining wall (300 mm above the ground level) used in
60 conjunction with polyurethane sealant between the membrane and Metal Strip. The termination bar / Metal strip must be installed directly into the wall width and RMT 291.00 268.00
mechanically fixed at c/c using appropriate fasteners. A bead of Sealant is applied along the top edge of the termination bar.
TERRACE WATERPROOFING : Surface Preparation: Providing and laying water proofing treatment to horizontal and vertical surfaces of concrete, including cleaning the
61 surface with wire brush, treating all surface cracks, construction joints and honeycombs by grouting with specialised non shrink grout,coving preparation at wall -
slab joint and preparation of surface in all aspects to receive the waterproofing.
Injection Grouting (If required): Providing Chemical injection treatment in the form of pressure grouting to the cold joint by injecting cement slurry mixed with grout
admixture ArmGrout Additives @ 250 gms.per bag of cement, in the required consistency through the pre fixed PVC nozzles in the 10mm dia holes, fixing of PVC nozzles
with quick setting compound ReArm Fix 10S of MYK Arment or equivalent and final cutting the projected nozzles and sealing off the PVC nozzles after the injection operation
is over with quick setting compound , no shrink rapid setting mortar compound, finishing, curing etc. as per manufacturers specification and as directed.If any lekages found
ponding then this need to be done.
Coving: Providing and Applying at the junction of slab and vertical offsets with Cement Mortar 1:4 and admixed with SBR polymer at dosage of 5Ltr per 50kg cement. SQM 2,091.00 4,738.00
Application of Primer: Apply Epoxy based primer over well prepared surface at 200-400 gm per SQMr.
Application of Polyurethane waterproof coating: Providing and applying Two coats of liquid applied single component polyurethane based waterproofing system . It
has to be applied @1.95 kg/SQMr to achieve a thickness of 1.2 mm in two coats.The membrane will have the following technical parameters: Tensile Strength : 2 N/mm²
Elongation at break : 400% , Adhesion To concrete: >1.5 N/mm²
Providing and laying 150 Gsm Geo fabric membrane as separation layer
Protection Screed:Horizontal Areas: Providing and Laying M25 grade screed concrete in 1:100 to a average thickness of 100 mm mixed with Integral Waterproofing
admixture at the dosage of 125 ml/bag of cement over waterproofing layer to a minimum thickness of 75 mm as per site requirement including control joints of 4M X 4M
size and filling the panels with polyurethane sealant.
WET AREA (Kitcen, Toilets, Wash Area) : Surface Preparation: Providing and laying water proofing treatment to horizontal and vertical surfaces of concrete, including
62 cleaning the surface with wire brush, treating all surface cracks, construction joints and honeycombs by grouting with specialised non shrink grout,coving
preparation at wall - slab joint and preparation of surface in all aspects to receive the waterproofing.
Injection Grouting (If required): Providing Chemical injection treatment in the form of pressure grouting to the cold joint by injecting cement slurry mixed with grout
admixture @ 250 gms.per bag of cement, in the required consistency through the pre fixed PVC nozzles in the 10mm dia holes, fixing of PVC nozzles with quick setting
compound and final cutting the projected nozzles and sealing off the PVC nozzles after the injection operation is over with quick setting compound , no shrink rapid setting
mortar compound, finishing, curing etc. as per manufacturers specification and as directed. If any lekages found in preponding then this need to be done.
Coving: Providing and Applying at the junction of slab and vertical offsets with Cement Mortar 1:4 and admixed with SBR polymer at dosage of 5Ltr per 50kg cement.
Waterproofing Coating-Providing and application of a two component, cementitious acrylic polymer based high performance water proofing coating. It offers
seamless coating applied@ 2 Kg /SQM for 2 coats @ 1.00 mm DFT .Technical Data: Inter coat application time, Hrs 2-3, Tensile strength (ASTM D 412) >2 N/mm²
Elongation at break (ASTM D 412)
>175%, Adhesion strength (ASTM D 4541) >1.2 N/mm², Crack bridging (ASTM C 836) pass up to 2 mm.
Item no. Item Description Unit Rate Total Qty. Amount
Toilet Sunk Filling : (not applicable for toilets with underslung plumbing) :
Providing and filling sunken area with Light Weight Block bat (40-60 mm) with cement mortar mixed in ratio 1:3:6 (1 cement : 3 sand : 6 brick bats) including mixing of water
proofing compound 4 % by weight of cement to sunk portions of toilets to the entire satisfaction of the PM. Toilet / Sunk portion shall be tested by ponding water for 72 hrs.
WATER RETAINING STRUCTURES (UGT & OHT) : Surface Preparation: Providing and laying water proofing treatment to horizontal and vertical surfaces of concrete,
63 including cleaning the surface with wire brush, treating all surface cracks, construction joints and honeycombs by grouting with specialised non shrink grout,coving
preparation at wall - slab joint and preparation of surface in all aspects to receive the waterproofing.
Injection Grouting (If required): Providing Chemical injection treatment in the form of pressure grouting to the cold joint by injecting cement slurry mixed with grout
admixture @ 250 gms.per bag of cement, in the required consistency through the pre fixed PVC nozzles in the 10mm dia holes, fixing of PVC nozzles with quick setting
compound and final cutting the projected nozzles and sealing off the PVC nozzles after the injection operation is over with quick setting compound , no shrink rapid setting
mortar compound, finishing, curing etc. as per manufacturers specification and as directed.If any lekages found in pre ponding then this need to be done. SQM 2,556.00 1,599.00
Coving: Providing and Applying at the junction of slab and vertical offsets with Cement Mortar 1:4 and admixed with SBR polymer at dosage of 5Ltr per 50kg cement.
Protective Plaster: providing and laying avg. 15 mm thick, CM 1:4 plaster admixed with Integral Waterproofing Compound @ 150 ml / bag of cement at Vertical Walls. Food
Grade epoxy coating- Application of food grade epoxy coating in Inner side of tank: providing and applying CFTRI Certified epoxy coating applied @ 0.600 kg/m2 in two
coats. It will give 400 microns thickness. Pot life: 30 Minutes at 25°C ,20 Minutes at 30°C,Mixing Ratio, by Weight: 100(Base):38(Hardener), Touch dry: 4 Hours at 30ºC, Re
coatable: 12 -18 Hours at 30ºC, Open to foot traffic: 24 Hours at 30ºC, Final cure: 7 Days at 30ºC, Adhesive bond strength to concrete, (ASTM D 4541): >1.5 MPa (concrete
WATERPROOFING FOR PODIUM WITH HARDSCAPE : Surface Treatment: Providing and laying water proofing treatment of terrace including cleaning the surface with
wire brush, treating all surface cracks, construction joints and honeycombs by grouting with specialised non shrink grout and preparation of surface in all aspects to receive
the waterproofing.
Coving: Providing and Applying at the junction of slab and vertical offsets with Cement Mortar 1:4 and admixed with SBR polymer ReArm Bond SBR 45 of MYK Arment or
equivalent at dosage of 5Ltr per 50kg cement.
64 Application of primer: Providing and applying Epoxy based primer FloArm Primer PUDC of MYK Arment or equivalent over well prepared surface at 200-400 gm per Sq.Mtr.
Application of Polyurethane waterproof coating: Providing and applying Two coats of liquid applied single component polyurethane based waterproofing system AquaArm
SPU-SPL of MYK Arment or equivalent . It has to be applied @1.95 kg/sqmtr to achieve a thickness of 1.2 mm in two coats.The membrane will have the following SQM 2,440.00 2,596.00
technical parameters: Tensile Strength : 2 N/mm2 ,. Elongation at break : 400% , Adhesion To concrete: >1.5 N/mm2,
Providing and laying 150 Gsm Geo fabric membrane as separation layer
Protection Screed:Horizontal Areas: Providing and Laying M25 grade screed concrete in 1:100 to a average thickness of 100 mm mixed with Integral Waterproofing
admixture AquaArm Prufe IWP 10 of MYK Arment or equivalent at the dosage of 125 ml/bag of cement over waterproofing layer to a minimum thickness of 75 mm as per
site requirement(Civil Contractor Scope) including control joints of 4M X 4M size and filling the panels with polyurethane sealant.
WATERPROOFING FOR PODIUM WITH SOFTSCAPE : Surface Treatment: Providing and laying water proofing treatment of podium including cleaning the surface with
wire brush, treating all surface cracks, construction joints and honeycombs by grouting with specialised non shrink grout and preparation of surface in all aspects to receive
the waterproofing.
Coving: Providing and Applying at the junction of slab and vertical offsets with Cement Mortar 1:4 and admixed with SBR polymer ReArm Bond SBR 45 of MYK Arment or
equivalent at dosage of 5Ltr per 50kg cement.
65 Application of primer: Providing and applying Epoxy based primer FloArm Primer PUDC of MYK Arment or equivalent over well prepared surface at 200-400 gm per Sq.Mtr.
Application of Polyurethane waterproof coating: Providing and applying Two coats of liquid applied single component polyurethane based waterproofing system AquaArm
SPU-SPL of MYK Arment or equivalent . It has to be applied @1.95 kg/sqmtr to achieve a thickness of 1.2 mm in two coats.The membrane will have the following
technical parameters: Tensile Strength : 2 N/mm2 ,. Elongation at break : 400% , Adhesion To concrete: >1.5 N/mm2,
Providing and laying 150 Gsm Geo fabric membrane as separation layer
Protection Screed:Horizontal Areas: Providing and Laying M25 grade screed concrete in 1:100 to a average thickness of 100 mm mixed with Integral Waterproofing
admixture AquaArm Prufe IWP 10 of MYK Arment or equivalent at the dosage of 125 ml/bag of cement over waterproofing layer to a minimum thickness of 75 mm as per
site requirement including control joints of 4M X 4M size and filling the panels with polyurethane sealant.
Dimple Board for Protection of membrane before Backfilling:
Providing and applying Extruded Polystyrene Protection Board of approved make and around 8 mm thick and shall be laid down to the membrane and then soil filling can be
done as per manufacturer's recommendation.
Item no. Item Description Unit Rate Total Qty. Amount
TOTAL OF WATERPROOFING WORK
H DOOR AND WINDOW WORK
FLUSH DOOR (SINGLE / DOUBLE LEAF) WITHOUT HARDWARE WITHOUT LOUVERS : Providing and fixing 35 mm thick pre-laminated (1mm) hinged door made out of
150mm x 70mm cp-sag indian teak wood outer frame with holdfast and shutters made of 35 mm thick facory fabricated flush door including concealed lipping (35mmx6mm-
matt malamine polished to exposed surface) to receive hinges. colour and shade for laminates shall be as architect. All necessaty carpentery and civil work to fix in true line
66 & level, plumb at all level shall be part of contractor and commissioned as directed by EIC. Hardware shall be paid extra under relavent item. It is inclusive of matt melamine SQM 5,233.00 1,274.00
polish (1 coat sealer + minimum 2 coat matt mellamine polish) with sanding, rubbing, etc. complete
For single / double leaf shutter without hardwares without louvers
FLUSH DOOR (SINGLE LEAF) WITHOUT HARDWARE WITH LOUVERS : Providing and fixing 35 mm thick pre-laminated (1mm) hinged door made out of 150mm x
70mm cp-sag inidan teak wood outer frame with holdfast and shutters made of 35 mm thick facory fabricated flush door including concealed lipping (35mmx6mm-matt
malamine polished to exposed surface) to receive hinges. colour and shade for laminates shall be as architect. All necessaty carpentery and civil work to fix in true line &
67 level, plumb at all level shall be part of contractor and commissioned as directed by EIC. Hardware shall be paid extra under relavent item. It is inclusive of matt melamine SQM 5,644.00 25.00
polish (1 coat sealer + minimum 2 coat matt mellamine polish) with sanding, rubbing, etc. complete
Do as above for single leaf with louvers without hardwares
HARDWARE FOR DOORS :
HINGE FOR ALL FLUSH DOORS : dormakaba 3043F, 5 Knuckle, 2 Ball bearing butt hinges size 4" x 3" x 3mm, Material: SS 304, Finish: Satin Stainless Steel (SSS).
68 Suitable for Wooden door weight up to 120kgs, Grade 13, Template Drilled. Approved to EN 1935, Fire-rated, Square Corners, Durability - 200,000 Cycles, Corrosion Nos. 273.00 1,992.00
Resistance - Very High
MORTICE SASH LOCK FOR REGULAR DOORS : dormakaba Mortice sash lock 271a with 55mm backset, 20mm square forend with 72 mm centers and prepared for euro
69 profile cylinder including strike plate in satin stainless steel as per EN 12209, Durability - 200,000 Cycles, Load on Latch Bolt - 50N , Door mass - 200 kg, Corrosive Nos. 1,599.00 196.00
resistance - Very High ( - 20 C to +80 C)
MORTICE SASH LOCK FOR TOI. DOORS : dormakaba Mortice WC lock 275a with 55mm backset, 20mm square forend with 78 mm centers and prepared for 8mm
70 bathroom follower including strike plate in satin stainless steel as per EN 12209, Durability - 200,000 Cycles, Load on Latch Bolt - 50N , Door mass - 200 kg, Corrosive Nos. 1,598.00 265.00
resistance - Very High ( - 20 C to +80 C)
MORTICE DEAD LOCK : dormakaba Mortice dead lock 278a with 55mm backset, 20mm square forend, prepared for euro profile cylinder including strike plate in satin
stainless steel as per EN 12209, Durability - 200,000 Cycles, Load on Latch Bolt - 50N , Door mass - 200 kg, Corrosive resistance - Very High ( - 20 C to +80 C)
LOCK PROFILE FOR DEAD LOCK : dormakaba Mortice dead lock 278a with 55mm backset, 20mm square forend, prepared for euro profile cylinder including strike plate in
72 satin stainless steel as per EN 12209, Durability - 200,000 Cycles, Load on Latch Bolt - 50N , Door mass - 200 kg, Corrosive resistance - Very High ( - 20 C to +80 C) Nos. 459.00 17.00
EURO PROFILE CYLINDER - BSK (Both Side Key) : dormakaba DEC 6 Plus 60, 6 pin Euro profile cylinder with inline brass keys. Master keyed system included as per
73 client requirement. Nos. 1,997.00 185.00
External & Internal key operation. Length: 60mm
EURO PROFILE CYLINDER - KT (Key + Thumbturn) : dormakaba DEC 6 Plus 60T, 6 pin Euro profile cylinder with inline brass keys. Master keyed system included as per
74 client requirement. Nos. 2,168.00 112.00
External key & Internal thumb turn operation. Length: 60mm
EURO PROFILE CYLINDER - CT (Coin + Thumbturn) for Toilets : dormakaba 3016, 6 pin Euro profile knob cylinder with internal thumb turn and external coin operation
standard length 60mm in satin nickle plated finish. NMK.Durability: 100,000 Cycles
LEVER HANDLE (PAIR): dormakaba Pure Lever handle 8906 lever with round roses, escutcheons prepared for Euro profile cylinder and spindle 114 in satin stainless steel.
76 Complete set including the fixing accessories for 50mm thick door. Material:SS 304. Approved to EN 1906 , Durability - 200,000 Cycles, Corrosion Resistance - Very High Nos. 2,639.00 452.00
LEVER HANDLE WITH INDICATOR (PAIR): dormakaba Pure 8906 Lever Handle with 6501 Roses,7122 WC Indicator, 8mm Spindle with Fixing Screws for door thickness
35-55mm, SS 304, Finish : Satin
78 TOWER BOLT : dormakaba 3200-2 Surface Mounted Tower bolt of Length 6" in Satin chrome finish Nos. 474.00 88.00
79 PEEP HOLE : 180° brass/SS, dormakaba equivalent Nos. 748.00 84.00
DOOR CLOSER : dormakaba rack and pinion door closer TS 68 with selectable closing force, size EN 2, 3 and 4 , std. arm adjustable closing speed in two independent
ranges. Non-handed. Approved to EN 1154. Durability - 500,000 Cycles ,Corrosive resistance - Moderate, Finish:Silver
Item no. Item Description Unit Rate Total Qty. Amount
PULL HANDLE (PAIR) : dormakaba pull Handle TGDI-D 300 back to back with adjustable fixing for glass, wood and metal doors in satin stainless steel. The pull handles
should have supporting washer with raised bevelling on the outer surface.CTC - 300mm, 22mm dia, Material - SS304
82 DEAD BOLT FOR SHAFT FLUSH DOORS : dormakaba Mortice shaft dead bolt with key with BS 57mm and 25mm Sq forend with escutheions in SSS. Nos. 1,031.00 38.00
83 OVAL PULL HANDLE FOR SHAFT FLUSH DOORS : dormakaba Recessed Oval Flush Pull Handle 1207, SSS Nos. 434.00 38.00
HARDWARE FOR ADA TOILET DOOR :
ADA TOILET DOOR - HINGES : dormakaba 3043F NRP, 5 Knuckle, 2 Ball bearing butt hinges size 4" x 3" x 3mm with Non-Removable Pin, Material: SS 304, Finish: Satin
Stainless Steel (SSS). Suitable for Wooden door weight up to 120kgs, Grade 13, Template Drilled. Approved to EN 1935, Fire-rated, Square Corners, Durability -
Cycles, Corrosion Resistance - Very High
ADA TOILET DOOR - DOOR CLOSER : dormakaba TS 92 B barrier free access designed cam action door closer complying to BS 8300 & ADM opening force of below 30N
between 0º and 30º degrees and below 22.5N between 30º and 60º degrees. Complies to CEN 15894 Guidelines of 40% reduced opening force & minimum 65% door closer
efficiency. Door closer with G-N slide channel arm for pull side fixing, adjustable closing speed in two independent ranges. closing force infinitely variable between size EN
and EN 4. Non-handed.
Approved to EN 1154 and CERTIFIRE, CE Marked. Durability - 500,000 Cycles, Corrosive Resistance - High. Finish: Silver
ADA TOILET DOOR - LOCK : dormakaba Mortice WC lock 375a with 55mm backset, 20mm square forend with 78 mm centers and prepared for 8mm bathroom follower
86 including strike plate in satin stainless steel as per EN 12209, Durability - 200,000 Cycles, Load on Latch Bolt - 120N , Door mass - 200 kg, Corrosive resistance - Very High Nos. 1,873.00 2.00
ADA TOILET - LEVER WITH INDICATOR : dormakaba Pure Lever handle 8100 lever with round roses, 7122 WC Indicator and spindle 114 in satin stainless steel. Complete
87 set with fixing accessories for 50mm thick door. Approved to EN 1906, Durability - 200,000 Cycles, Corrosion Resistance - Very High Nos. 3,084.00 2.00
88 ADA TOILET DOOR - GRAB BAR : dormakaba GBDI D-600 Grab Bar of Length 610mm, 25mm Diameter in Satin stainless Steel Finish. Nos. 5,234.00 2.00
METAL DOORS - FIRE RATED (120 Mins)
METAL FIRE DOORS (120 Minutes) with 30 min insulation As per IS3614:
Supply and fixing of Hollow metal fire rated doors as per IS 3614:2021 for stability and integrity with 30minutes insulation. Pressed Galvanized steel confirming to IS 277 with
the following specification. Recommended fire door shall have doors tested at CBRI /NABL Approved Labs for maximum rating of 2hrs tested . Individual Test certificates
should also be available for glass used in vision lites confirming the required fire ratings /panels being a part of the fire door assembly. Doors should be finished in
89 Thermosetting Powder Coating desired RAL Shades. Manufacturer test certificate shall cover doors both single & double leaf doors and Hardware's should pass European
certificate "CE" of conformity / UL with required fire ratings. Any deviation in specification and sheet thickness other than what is mentioned in the test certificates are not
allowed. Proper label confirming the type of door and the hourly rating is mandatory. Approved manufacturer Navair International or equivalent subject to architect’s
approval. And should be ISO Certified company.
Door frame shall be Single rebate profile of section 100 x 57 mm made out of 1.60mm thick galvanised steel sheet with a factory pre-punched groove so as to accomodate
Fire & smoke seal size 10x4mm . Frames should be butt jointed and field assembled with bolting system for proper strength .Frames should be provided with back plate for
anchor fasteners (payable extra ) for installation on a finished plastered wall opening.
Door leaf shall be minimum 46mm thick fully flush double skin door with or without vision lite. Door leaf shall be manufactured from 1.2mm minimum thick galvanised steel
sheet. The internal construction of the door should be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be Rockwool treated with Viper
FRS 881 LH. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The
edges should be interlocked with a bending radius of 1.4mm. For pair of doors astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite
wherever applicable should be provided as per manufacturers recommendation with a beading and screws from inside.
All doors and frames shall be finished with Powder coating in desired Shades. Once frame installed should be filled with PUF as recomended by the manufacturer or
HARDWARE FOR METAL DOORS
90 SS Ball Bearing Hinges of size 100 x 75x 3mm complete with SS Screws of Becker fs make ( 4 Nos per panel ) Nos. 253.00 376.00
91 Door closer overhead STD arm Becker fs make Nos. 2,553.00 55.00
92 Fire glass 6MM Thick 200x300mm Vision Glass from Saint Gobain Nos. 2,128.00 66.00
93 Mortise dead lock with both side key cylinder Becker fs make Nos. 2,502.00 115.00
94 SS Pull handle 300 mm long back to back D type Becker fs make Nos. 1,909.00 115.00
Item no. Item Description Unit Rate Total Qty. Amount
95 Fire seal 10x4mm & smoke seal RMT 299.00 553.00
96 Hilti fasteners 10X 80mm Nos. 64.00 765.00
97 Concealed flush bolt 600mm long for double door Becker fs make Nos. 1,403.00 85.00
98 Frameless "U" Channel glazing (INTERNAL FIXED GLAZING)
Design, Fabrication, Supply, Installation, Protection, Cleaning & Handover of Frameless glazing system with Aluminium "U" Channel custom designed to with stand the
design wind pressure confirming to IS -875 part III. (The system must pass the proof test at 2 times design wind pressure without any failure).
The system shall be support the glass at bottom and wind resistance at top by means of continuous U-channel at the finished floor level and vertically butt glazed with non
staining sealant joint between glass to glass. The weather sealant of approved make, baker rod, SS 304 grade fasteners & hard setting blocks of EPDM, all in complete
required to perform as per specification and drawing in conjunction with BOQ. Complete system shall be warranted for minimum 10 yrs against design & workmanship
The extruded aluminium sections of Alloy 6063 T5 / T6 & tolerances confirming to DIN / EN standard from approved extruder. All the visible surfaces shall have high
Durability (Akzonobel) / Super durable (Jotun) Powder coating of 60 - 80 micron.
All Material Make / Vendor list / Supplier list shall be as per tender specification.
All shade approval shall be as per Architect's Approval.
The quote rate shall include all design, engineering & Approval from architect & consultant.
Quote rate for complete system as mentioned above under (B) U-Channel Design in line with Tender drawings for Ground Floor and First Floor Retail Area, Providing &
Fixing Façade 12mm Clear FT Glass.
Frameless Swing Doors_ (Patch Fitting Doors)
Design, Fabrication, Supply, Installation, Protection, Cleaning & Handover Single & Double leaf double swing patch fitting door made out 12mm thick fully tempered (FT)
glass with Dorma make stainless steel patch fittings for external facade application (PT Series ). Complete with 38mm dia SS handle 1000mm long , PT series patch fittings,
US 10 Door lock at bottom of each shutter and BTS 80, 90 deg with EN 1-4 spring capacity floor spring. Floor spring covers shall be SS satin finish. as per Architect's
approved shop drawings.
Door glass of 12 mm thk clear float fully tempered with holes and notches as per patch fitting requirement. Edges Machine ground mirror polished. The door glass shall have
silicon gasket at bottom to act as weather seal.
All Material Make / Vendor list / Supplier list shall be as per tender specification.
The quote rate shall include all design & shop drawing approval from architect & consultant.
Quote rate for complete system for Frame Less Patch Fitted Door as mentioned above under (C)
99 1 - Double Leaf Swing Door:- (Size:- 1500mm x 2100mm) with 12mm Thk. Clear FT Glass. Location:- First floor Internal Portion. Nos. 80,500.00 1.00
100 2 - Single Leaf Swing Door:- (Size:- 1000mm x 2100mm) with 12mm Thk. Clear FT Glass. Location:- First floor Internal Portion. Nos. 40,250.00 4.00
Aluminium Louvers ( "Y" Type Louvers) System_
Vantilation Lover system - BUILDING FAÇADE AT SHAFTS LOCATION
Design, Fabrication, Supply, Installation, Protection, Cleaning & Handover of Aluminium " Y " shape Louvers System custom designed to with stand the design wind
pressure confirming to IS -875 part III.
Aluminium Louvers shall be made out of 60mm x 36mm x 1.5mm thk. of " Y " shape louvers system spaced at equivalent distance support to Aluminium frame. Louvers
profile shall be fixed on the 3mm thick Al flat to form a frame. The louver frame is supported on the aluminium box frame with necessary fasteners in SS 316 in line with
The extruded aluminium sections of Alloy 6063 T5 / T6 & tolerances confirming to DIN / EN standard from approved extruder. The structural profiles shall have minimum 2 SQM 8,349.00 511.00
mm wall thickness. All the internal & External visible surfaces shall have Super Durable Powder coating finish of 60-80 micron thickness as per Approved shade by
Architect. The non visible aluminium surfaces shall have mill Finish.
All Material Make / Vendor list / Supplier list shall be as per tender specification.
All shade approval shall be as per Architect's Approval.
The quote rate shall include all design & shop drawing approval from architect & consultant.
Quote rate for complete Aluminium "Y" Type Louvers system as mentioned above under (F)
Aluminium "Y" Type Louvers system_Vantilation Louver System, Location:- Staff Qtrs exterior face shafts
Item no. Item Description Unit Rate Total Qty. Amount
Sliding Window - 4 track : Providing and fixing extruded aluminum window having extruded aluminum Colour Powder Coated section frame main outer size 127mm x
38.10mm x 1.35mm ,@ Wt.1.384 Kg/mt,horizontal Four track member size 122.20mm x 31.75mm x 1.10mm @ Wt. 1.205 Kg/mt,vertical member of size 122.20mm x
102 31.75mm x 1.50mm ,@ Wt. 1.398 Kg/mt with sliding shutters of horizontal member size 40mm x 18mm x 1.29mm @ wt.of 0.456Kg/mt,vertical member of size 40mm x 18mm SQM 2,119.14 186.00
x 1.29mm @ wt.of 0.456Kg/mt,@ with 5 mm thick transparent bronze colour tinted float glass with powder coated aluminum fittings and fixtures and transparent silicon
sealant glass fixing to frame as per details etc complete for window.
Sliding Window - 3 track : Providing and fixing window having extruded aluminum Colour Powder Coated section frame main outer size 95mm x 24mm x 1.17mm @ wt.of
0.738 Kg/mt, horizontal Three track member size 92mm x 31.75mm x 1.30mm @ Wt.1.07 Kg/mt, vertical member of size 92mm x 31.75mm x 1.50mm ,@ Wt. 1.06 Kg/mt
103 with sliding shutters of horizontal member size 40 mmx18mm x1.29mm @ wt.of 0.456 Kg/mt, vertical member of size 40mm x 18mm x 1.29 mm @ wt.of 0.456Kg/mt with 5 SQM 1,576.11 643.00
mm thick transparent bronze colour tinted float glass with powder coated aluminum fittings and fixtures and transparent silicon sealant glass fixing to frame as per details etc
Sliding Window - 2 track : Providing and fixing window having extruded aluminum Colour Powder Coated section frame main outer size 63.50 x 38.10 x 1.95 mm,@ Wt
1.094 Kg / Rmt, horizontal two track member size 1.85 mm x 31.75 mm x 1.20mm @ wt.of 0.695 Kg/mt, vertical member of size 61.85 mm x 31.75mm x 1.30 mm @ wt.of
104 0.0.659 Kg/mt with sliding shutters of horizontal member size 40mm x 18mm x 1.29mm @ wt.of 0.456Kg/mt, vertical member of size 40mm x 18mm x 1.29mm @ wt.of SQM 1,688.78 330.00
0.456Kg/mt with 5 mm thick transparent bronze colour tinted float glass with powder coated aluminum fittings and fixtures and transparent silicon sealant glass fixing to frame
as per details etc complete for window
VENTILATION : Design, Fabrication, Installation, Protection, Cleaning and Handover of Alum. Glass Louver windows with exhaust Fan fixing Provision in Toilet areas with
hardware's and accessories.
The extruded aluminium sections of Alloy 6063 T5 / T6 & tolerances confirming to DIN / EN standard from approved extruder. All the internal visible surfaces shall have high
Durability (AkzoNobel) / Super durable (Jotun) Powder coating of 60 - 80 micron confirming to AAMA 26043. The non visible aluminium surfaces shall have minimum
chromatizing treatment.
All Material Make / Vendor list / Supplier list shall be as per tender specification.
All shade approval shall be as per Architect's Approval.
The quote rate shall include all design & shop drawing approval from architect & consultant.
Quote rate for complete Glass Louvers system as mentioned above under :
Ventilation Windows (V1) Bottom Glass Louvers With Top Fix :- SQM 3,422.00 47.00
Top Fix:- 6mm Thk. Frit Glass SQM 3,422.00 47.00
Glass Louvers:- 5mm Thk. Frit Glass @30mm C/C SQM 3,422.00 47.00
ALUMINIUM FIXED WINDOW / Top/side HUNG OPENABLE (OUT) :
Design, Fabrication,Supply,All Material & Site Testing, Protection, Handover of Alum. Fix / Top/Side Hung openable windows system custom designed to with stand the
106 design wind pressure confirming to IS -875 part III. The system shall have two barrier gasket system for weather sealing. Provision for drainage of uncontrolled water entering
to 1st barrier gasket.
Top/Side hung openable window system shall be including malti-point locking (Min.two) with Handle, projected type hinges with restrictor arm of approved make, Microwave
cured EPDM gaskets. window shutter profile to accommodate the 6mm SGU HS glass, weather sealants, SS 316 grade screws and fasteners of approved make, all in
complete required to perform as per specification and drawing in conjunction with BOQ.
The extruded aluminium sections of Alloy 6063 T5 / T6 & tolerances confirming to DIN / EN standard from approved extruder. All the internal visible surfaces shall have high
Durability (AkzoNobel) / Super durable (Jotun) Powder coating of 60 - 80 micron confirming to AAMA 26043. The non visible aluminium surfaces shall have minimum
chromatizing treatment.
All Material Make / Vendor list / Supplier list shall be as per tender specification.
All shade approval shall be as per Architect's Approval.
The quote rate shall include all design & shop drawing approval from architect & consultant.
Quote rate for complete Aluminium Windows system as mentioned above under (F) With 6mm Thk. HS Glass in line with tender drawing.
Providing and fixing a Top/Side Hung Openable vent With 6mm Thk. HS Glass . SQM 6,182.00 60.00
Providing and fixing a Fix Windows With 6mm Thk. HS Glass. SQM 5,089.00 178.00
Providing and fixing rolling shutters of approved make made of 80 mm wide M.S. laths inter-locked together through their entire length and jointed together at the ends by
107 end locks mounted on specially designed pipe shaft with bracket plates, guide channels and arragements for inside and outside locking with push-pull operation including the SQM 3,468.72 30.00
cost of hood cover and spring etc. complete. (B) Shutters having width 3.5 M. and above
108 Providing and fixing 27.5 cm. long wire spring grade No.2 of approved make for rolling shutters. EACH 630.91 4.00
109 Providing and fixing Hood cover for rolling shutters (B) Shutters having width 3.5 meters and above RMT 120.03 12.00
Item no. Item Description Unit Rate Total Qty. Amount
TOTAL OF DOORS AND WINDOWS
I MISCELLENEOUS
Pre construction Anti termite Treatment : Providing and injecting pre-constructional anti-termite treatment as per IS:6313 (Part-II) to the RCC members in immediate
contact with soil upto a min depth of 500 mm measured from made up ground level by treating all four sides at the rate of 7 Lit/Sqm of an emulsion in water of 0.5 %
Chloripyrofos 20 EC or equivalent, treating the top surface of plinth filling and the external peripheri of the building by drilling the holes up to 75 mm deep at 150 mm c/c
110 distance bothways using 12 mm dia ms rod on the surface to facilitate saturation of the soil with the chemical emulsion at the rate of 5 Lit/Sqm of surface area of an emulsion SQM 384.00 3,855.00
in water of 0.5 % Chloripyrofos 20 EC or equivalent. The contractor shall furnish 10 years guarantee for termite free structure. (Plan area at ground floor level shall be
measured for payment.)Notes:1) Allow for Min. of 10 years gaurantee as described under detailed specifications. 2) Only single time Plinth area shall be measured for
payment, deducting open to sky shafts,verandah etc. for all kinds of buildings i.e. building having basements or no basements.
Toilet Cubicals : Providing and fixing toilet cubical systems of approved make and manufactured in standard dimensions of 600mm ± 10mm width door size with 12mm
thick solid Compact Laminate panels made of KRAFT paper impregnated with Phenolic resins under high pressure and temperature, including doors, pilasters & intermediate
panels, which should be resistant to heat, bacteria, water, chemical, scratch and impact. Finished product should be as per approved texture, shade & drawing, detailing and
developed according to IS-2046 and BS-476/97 standards. The toilet cubicle setup shall include necessary hardware fittings, made out of stainless steel (Grade-304), as per 3.00
manufacturer’s specifications and approved by Engineer-in-charge.
Hardware fittings should consist of (1) Stainless steel Adjustable foot/ pedestal of SS 316 grade to give 150mm clearance from bottom and of weight not less than 600grams
(2) Stainless steel U-channels of 20 gauge and 12 x 20mm size (3) Stainless steel Top rail pipe (OD:24mm of 18 gauge) with corner connectors (4) Stainless Steel Head Rail
Tubular Holder (5) Stainless steel Gravity hinges (3 nos.) not less than 75mm length and weight not less than 210 grams of weight not less than 200 grams. (6) Stainless
steel Coat hook with nylon door stopper (7) Stainless steel Door knob (8) Stainless steel Baby latch (9) Wall bracket SS 304 (10) Corner Connector (11) Rubber noise
deafening tape (12) Stainless steel 304 Screws and PVC wall plugs
Providing and fixing 6mm thick frameless mirror of approve make in any shape and sizes as per drawing. Mirror shall be fixed on 12mm thick marine plywood backing.
Marine plywood shall be fixed to wall with approved SS 304 fastener. All edges of glass shall be sharp grinded, cut corner and polished. Glass shall be fixed with approved
112 adhesive/ 3M tape etc. complete at all floors/ all levels/ all heights as directed by Engineer In Charge. Installed area of mirror shall be considered for payment without SQM 5,897.00 121.00
Structural steel work ( Confirming to IS 4923-1997) riveted, bolted or welded in builtup for all type sections, in framed work, including cutting, hoisting, fixing in position and
applying a priming coat of approved steel primer all complete as per the structural designs and directions of Engineer in charge.
Providing, fabricating, assembling, hoisting/ erecting and fixing for structural steel work in position at all heights/ all levels/ all floors/ all shapes & sizes with all leads & lifts
using MS Rolled Steel Sections, Hollow sections, Tubular Sections, MS Plates, Chequered Plates, MS Pipes, Perforated Sheet, Flats, Bright Bars, Angles, MS Sheet, Girder,
Beam, cattle trap. deep threaded MS bolts, threaded J bolts, insert plate, support plate etc as per drawing. all confirming to latest relevant IS codes for the work of steel
structures like gratings over drain channel, I beams, staircases, railings, handrail, jali, gates, grills, bracings, platforms, brackets, monkey ladder, cattle trap, windows, pipe
rack, rungs, false ceiling frame work, Roof canopy, fencing posts, M.S. Screen & fencing jali frame work etc. including straightening, cutting, bending, bolting and welding the
members all as per structural drawings and as per detailed specifications (for materials & workmanship) including necessary scaffolding/ staging etc. complete in the
situations described hereinafter and comprising of : i) Profile Cutting of components to required length/ width and shape/ profile;
ii) Smooth grinding/ machining of edges/ faces/ all welding joints; iii) Necessary welding (electric arc welding) for required weld lengths and sizes. (non structural elements)
iv) Machine drilling of holes for joining/ anchoring (Standard measurements will be paid for as actual cut length used at site).
Note: The contractor shall be submit fabrication drawings based on construction drawings (that may be issued during construction period with at least one mock up approved
by architecture ) for approval by the Architect/ Engineer. The fabrication work shall start only after approval of the fabrication drawings submited by contractor. Any change
required in the fabrication drawings shall be carried out at No extra cost. Fabrication shall be in a perfect architectural workmanship manner and as provided in section V & VI
of IS 800 & IS 7215. Welding shall be carried out by qualified welders/ fabricators.It should also include the cost of necessary scaffolding/ staging, zinc coated nut-bolt as
required for safety, structural stability of all works at site.
Extra on STRUCTURAL STEEL item - for all kinds of sleeves in hydraulic structure Hot dip Galvanised with minimum 65microne thick (only difference shall be paid instead of
2 coat zinc chromate yellow oxide and 2 coat of enamel paint)
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing G.I. chain link fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required
115 complete as per the direction of Engineer-in-charge. SQM 3,393.00 116.00
Made of G.I. wire of dia 4 mm
Providing and wet drilling accurate and clean holes of 25‐400 mm range without vibration through Hilti diamond drilling machine DD200 having 1:1 & 1:3 gearing ratio for
116 wide range of reinforcements in concrete, control panel indicator to display proper pressure application, capable of drilling at angle from 0o‐ 45o and do overhead application.
Before coring rebar loaction to be identifed with Hilti PS 250 (ferroscanner) tool or equvivalent.
a 25 mm dia RMT 11,615.00 2.00
b 37 mm dia RMT 13,938.00 2.00
c 52 mm dia RMT 14,867.20 2.00
d 77 mm dia RMT 17,190.20 2.00
TOTAL OF MISCELLENEOUS
J FURNITURE WORK
Providing And Supply High Back Rev. Chair Upholstered with Leatherette Seat Made Up Of 12mm +/- 1mm Thick Hot Pressed Mr. Grad Plywood and Back in Two Pieces -
12mm Rear Back And 6mm Inner Back. Moulden Polyurethane Foam Used in Making Seat with Molded Density 45+/- 2 Kg/M ³. Back Is Made Out Of 32 Density Block
Foam Covered With 14mm Thick 32 Density Foam Sheet (Block Foam). Spine Bracket Made Of M.S Plate 8mm Thickness Connecting Back with Mechanism. Armrest Top
Is Soft Touch Polyurethane Molded Of 250 To 300 Density Insert Stainless Steel Pipe Having Unique " Y "Shape. The Mechanism of the Chair Have Following Features:
360⁰ Revolving Type 3.5Mm Thk Crca Seat Plate With 4Mm Thk Crca Channel Plate Synchro Mechanism, Tilt Tension Adjustable, Single Position Locking, Plastic
Component Inside the Mechanism of Grade - Mi 3530 And Epoxy Powder Coated 70 Microns with Tested 1.2 Lacs Cycles as Per Bifma Standard. The Chair Provided with
Pneumatic Height Adjustment Which Have Have Stroke Of 100mm +/- 5mm.The Five Leg Base Is Made Up Of 38Mm Dia X 1.2Mm Thick Tubular With 3.15mm Thick Centre
Hub Crc Fabricated Chrome Finish. It Have Be Fitted With 50mm Dia Twin Wheel Castor . The Size of The Base Have Be - 660 +/- 1mm Pitch-Centre-Diameter. Load Test
As Per Bifma Compliance. The Twin Wheel Castors Made Of Nylon Injection Molded In Black Color. Overall Dimensions Of Chair Have Be, Width Of Chair - 640mm, Depth
Of Chair 640mm As Measured From Base Below. Height Of Back From Ground - Min 1175 To Max 1275mm. Seat Height -Min 480mm To Max 580mm. Dimensions
Tolerance / Variations Have Be Within +/- 10mm.
Providing And Supply Med. Back Rev. Chair Upholstered With Leatherette Seat Made Up Of 12mm +/- 1mm Thick Hot Pressed Mr Grad Plywood And Back In Two Pieces -
12mm Rear Back And 6mm Inner Back. Moulded Polyurethane Foam Used In Making Seat With Moulded Density 45+/- 2 Kg/M ³. Back Is Made Out Of 32 Density Block
Foam Covered With 14mm Thick 32 Density Foam Sheet (Block Foam).Spine Bracket Made Of M.S Plate 8mm Thickness Connecting Back With Mechanism. Armrest Top
Is Soft Touch Polyurethane Moulded Of 250 To 300 Density Insert In Stainless Steel Pipe Having Unique " Y "Shape. The Mechanism Of The Chair Have Following
Features: 360⁰ Revolving Type 3.5Mm Thk Crca Seat Plate With 4Mm Thk Crca Channel Plate Synchro Mechanism, Tilt Tension Adjustable, Single Position Locking
Plastic Component Inside The Mechanism Of Grade - Mi 3530 And Epoxy Powder Coated 70 Microns With Tested 1.2 Lacs Cycles As Per Bifma Standard The Chair
Provided With Pneumatic Height Adjustment Which Have Have Stroke Of 100mm +/- 5mm.The Five Leg Base Is Made Up Of 38Mm Dia X 1.2Mm Thick Tubular With
3.15mm Thick Centre Hub Crc Fabricated Chrome Finish. It Have Be Fitted With 50mm Dia Twin Wheel Castor . The Size Of The Base Have Be - 660 +/- 1mm Pitch-
Centre-Diameter. Load Test As Per Bifma Compliance.The Twin Wheel Castors Have Be Made Of Nylon Injection Moulded In Black Colour.Overall Dimensions Of Chair
Have Be, Width Of Chair - 630mm, Depth Of Chair 630mm As Measured From Base Below. Height Of Back From Ground - Min 950 To Max 1050mm. Seat Height -Min
470mm To Max 570mm. Dimensions Tolerance / Variations Have Be Within +/- 10mm.
Providing and supply Seat and back in single piece with integrated arms like bucket shape, nylon moulded of 450 to 500 density fix inner and outer snap fit arrangement in
back with mesh fabric inside on equal interval of rectangular slots design. The mechanism of the chair have have following features : 360⁰ revolving type, 2.5mm thk CRCA
powder coated center tilt Mechanism, Tilt tension adjustment, locking in single position, Plastic component inside the mechanism of Grade - MI 3530 and Epoxy Powder
119 coated 70 Microns with tested 1.2 lacs cycles as per BIFMA Standard The chair have be provided with pneumatic height adjustment which have have stroke of 100 +/- 5 mm. Nos 11,184.00 24.00
The Base have be made of injection moulded nylon. It have be fitted with 5 nos. twin wheel castor - 50 mm diameter. The size of the base be 660 +/- 1 mm pitch-centre-
diameter. The twin wheel castors have be made of Nylon injection moulded in black colour.
Item no. Item Description Unit Rate Total Qty. Amount
Providing And Supply Med. Back Rev. Chair Upholstered With Leatherette Seat Made Up Of 12mm +/- 1mm Thick Hot Pressed Mr Grad Plywood And Back In Two Pieces -
12mm Rear Back And 6mm Inner Back. Moulded Polyurethane Foam Used In Making Seat With Moulded Density 45+/- 2 Kg/M ³. Back Is Made Out Of 32 Density Block
Foam Covered With 14mm Thick 32 Density Foam Sheet (Block Foam). Armrest Top Is Soft Touch Polyurethane Moulded Of 250 To 300 Density Insert In Chrome Finish
120 Pipe Having Unique "Bird Beak"Shape.. Pipe structure of MS CRCA finish 16 gauge round pipe having a diameter of 25 mm with epoxy powder coated. Overall Dimensions Nos 14,829.00 52.00
Of Chair Have Be, Width Of Chair - 630mm, Depth Of Chair 630mm As Measured From Base Below. Height Of Back From Ground - Min 950 To Max 1050mm. Seat Height -
Min 470mm To Max 570mm. Dimensions Tolerance / Variations Have Be Within +/- 10mm.
Type: 2 Seater Sofa
Size (approx. Over all dimension): 1500mm(W) x 800mm(D) x 780mm (H) Top: Upholstery with Latherite Finish all visible surfaces
Specifications:Providing and supply Sofa sturcture made from 18mm MR Grade Mr grad plywood supported with Maranti Solid wood, back side and curved part Covered with
3mm flexi ply, sofa arm made from 12mm thick MR Grade Mr grad plywood supported with maranti solid wood. Elastic Belt, 75mm board & 2.25 mm thick elastic webbing
121 stapling in seat frame at 100 mm centre to centre distance, belt fastern in X and Y axies of seat, elastic belt elongation 45% tensile strength 350 kg. Foam 100 mm X 40 Nos 70,414.00 6.00
density Premium Quality foam covered with 25mm X 32 density super soft Premium Quality Foam for soft touch filling in seat. 50 mm X 40 density Premium Quality foam
covered with 25mm X 32 density super soft Premium Quality foam for soft touch filling in back. Stiching Stiching work done with well known german brand (Aman /
Gutermann) Thread. Nylone & Polyster thread used as per application. Leg made from Stainless steel 316 Grade. all material selection will be as per architect's selection, etc
all complete with respect to necessary hardware and finishes
CENTER TABLE SIZE:-1100 x 600 & 450mm height
Providing fixing and arranging Center Table Providing and supply Top 20 mm thick made of PLY with 1 mm thick laminate finish with 2 mm thick PVC edge bidding matching
122 with same laminate finish. Nos 22,367.00 3.00
STRUCTURAL SUPPORT SYSTEM:- shall be constructed using 40 x 40 mm matt finish S.S. Metal frame legs as per image. Entire table to be finished with all necessary
hardware and selection of material as per architect.
SIDE TABLE SIZE:-500 x 500 & 450mm height
Providing fixing and arranging Center Table Providing and supply Top 20 mm thick made of PLY with 1 mm thick laminate finish with 2 mm thick PVC edge bidding matching
123 with same laminate finish. Nos 11,598.00 3.00
STRUCTURAL SUPPORT SYSTEM:- shall be constructed using 40 x 40 mm matt finish S.S. Metal frame legs as per image. Entire table to be finished with all necessary
hardware and selection of material as per architect.
"C" shaped table overall dimension 2250x1800x2700mm & 750mm height with 36 MM thick nail curvica post forming edges made of 17mm OSR MDF with curvica laminate
finish both long edges with ends having matching 2mm pvc edge band / beading, bottom surface to be finished with balancer white. Provision to be given for snake /
vertebrae from floor to wire manager for pop up box with switches and sockets as per detail design and drawings. Fixed Drawer Unit Outer body 17mm thick MDF with
curvica Laminate Finish. three drawers with bullnose front with lock and necessary hardware. Side Table : Size as per drawings, Top and leg 36 MM thick nail curvica post
forming edges made of 17mm OSR MDF with curvica laminate finish both long edges with ends having matching 2mm pvc edge band / beading. shutter 17mm thick OSR
124 MDF with curvica Laminate Finish bullnose curvica laminate finish with lock and necessary hardware. Back Unit size as per drawing Top and leg 36 MM thick nail curvica Nos 1,36,685.00 3.00
post forming edges made of 17mm OSR MDF with curvica laminate finish both long edges with ends having matching 2mm pvc edge band / beading. shutter 17mm thick
OSR MDF with curvica Laminate Finish bullnose curvica laminate finish with lock and necessary hardware. Entire table to be finished with all necessary hardware. There will
be provision of footrest of size 750 x 400 x 150mm & storage top side and back unit top having a ledge of 150mm x 100mm boxing as shown in image included in it. All
hardware should be concealed & not visible. All handles should be concealed with SS finish.
Item no. Item Description Unit Rate Total Qty. Amount
Product : Collaborate Loop Leg Design
Dimensions : 1200mmL x 600mmD x 750mmHT Table top + 350mmHT Screen
Table Top: 25mm thick Pre laminate particle board with 2mm PVC edge lipping on all exposed edges
Support: End Legs: MS powder coated Collaborate Loop legs
Intermediate Legs: MS podwer coated 60X40mm legs and supporting MS cross beams (40X20mm)
Main Screen : 900mmL x 350mmHT - 18mm Thick Al. Framed Fabric Magnetic Screen with in-built Accessories Rail mounted on table top with Powder coated Studs
125 Return Screen : 8mm Sandwich Glass Screen of 350mmHt x 525mmL mounted on table top with metal powder coated studs Nos 10,638.00 18.00
Modesty : 12/18mm thick PLT modesty leg to leg for privacy of 450mmHt with 225mm Floor Clearance Gap
Wire Management
250mm Ht Racway with 65mm Dia Wire Manager Grommet
Vertical Raceway with built in separator for power and data of size 250H X 70mm thick with provision to mount swicthes and sockets on laminate facia with Vertical Wire
Entry cover for wire uptake from floor to raceway with 65mm Dia Wire Manager Grommet.
TABLE SIZE Linear shaped :-1200 x 600 & 750mm height
Providing and supply Top 36 mm thick made of PLY with 1 mm thick laminate finish with 2 mm thick PVC edge bidding matching with same laminate finish. Apron 18mm
126 thick PLY board with 1mm thick laminate finish with 2 mm thick PVC edge matching with laminate bidding, under structure made of 50x50mmx1.6mm thick MS square pipe Nos 24,852.00 7.00
with powder coated (50-60 micron) finish. WIRE MANAGEMENT MS-Powder coated wire tray with pop up box switch plate and vertical cable raisers / PVC wire guard are
considered for wire management.
TABLE SIZE Linear shaped :-1350 x 600 & 750mm height
Providing and supply Top 36 mm thick made of PLY with 1 mm thick laminate finish with 2 mm thick PVC edge bidding matching with same laminate finish. Apron 18mm
127 thick PLY board with 1mm thick laminate finish with 2 mm thick PVC edge matching with laminate bidding, under structure made of 50x50mmx1.6mm thick MS square pipe Nos 24,852.00 1.00
with powder coated (50-60 micron) finish. WIRE MANAGEMENT MS-Powder coated wire tray with pop up box switch plate and vertical cable raisers / PVC wire guard are
considered for wire management.
Providing and Fixing coustmised conferece table of 3000x1200x750 STRUCTURE:- Set of table top, modesty and gable end designed in handshake pattern to build the
closed module, open module of Video conferencing pattern V-shaped configuration of the conference table with infinite seating arrangement depending upon space available
to set the conference table. TABLE TOP:- 30mm thick table top made up of 18mm thick ply wood with 1 mm thick laminate board with 12mm thick thin PVC foil wrapped
decorative profile made up of ply fixed along all the edges from the bottom side which provide decorative waterfall edge profile to top with twin colour look the decorative trim
to be connected at the angle of 45 degrees with each other. Single seater small top of size 675mm width and 600mm depth. Two-seater big top of size 1350mm width and
600mm depth can shape open type and O shape close type configuration. Two-seater end top of perfect semicircle shape of the radius of 600mm usable for the close
module with the lowest space of 1200mm in front to front seating. LEG:- 25mm thick Leg or Gable End made up of 25mm thick pre-laminated particle board with MS leveller
bracket to give floating look. MODESTY:- Modesty Panel made up of 18mm thick ply wood with 1 mm thick laminate providing stability to structure and allow sufficient leg
privacy to the user. "D" headed decorative aluminium profile fixed on it. WIRE MANAGEMENT:- Provision for wire passing throughout the structure without mixing data and
128 power connections. The wires can be pulled inside the table from floor and placed in the boxes build below openable shutter. The access point for data and power can be Nos.
mount on the main top as well as the openable top. Access flap is box structure made up of aluminium extrusion with necessay switches and sockets and connectivity to
different equipments. etc all complete with necessary hardware and complete as directed by engineer incharge. all visible and non visible surfaces to be claded with 1 mm
thick laminate as per detail design drawings.
WIRE MANAGEMENT:- Provision for wire passing throughout the structure without mixing data and power connections. The wires can be pulled inside the table from floor
and placed in the boxes build below openable shutter. The access point for data and power can be mount on the main top as well as the openable top. Access flap is box
structure made up of aluminium extrusion with necessay switches and sockets and connectivity to different equipments. etc all complete with necessary hardware and
complete as directed by engineer incharge. all visible and non visible surfaces to be claded with 1 mm thick laminate as per detail design drawings.
Providing and fixing lockable cupboard of size 1200x450x2100 mm with 4 shelves two parts. Material – 0.7mm thick (+/-0.07mm) CRCA for shelf; 0.8mm thick (+/-0.08mm)
high yield strength CRCA for doors & back; 0.9mm thick (+/-0.08mm) CRCA for all other components. It should have 2 way locking mechanism with shooting bolt & rase s
129 per req.handle or without handle.. It should have height wise adjustable shelf With uniformly distributed load capacity per each full shelf 40kg maximum. Finish – Epoxy Nos. 32,308.00 1.00
Powder Coated to the thickness of 50 microns (+/-10).etc complete with all necessary hardware. all handles to be consealed. no hinges to be visibal. shade of powercoating
will be as per architect's choice.
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing File Storage.1500x450x750mm Top made of 25 mm thick PLY bothside covered 1 mm thick laminate finish ,sides 18 mm thick PLY bothside covered
mm thick laminate finish.9mm thk PLY bothside coberd with laminate finish.Skirting and Front Shutters/drawer fascia made of 18 mm thick ply bothside covered 1 mm thick
130 laminate finish with necessary hinges and lock. Shutter hanging on Hinges, Lock and handle are consealted or profile or groove handle less etc.All edge 2mm thick Pvc Nos. 39,349.00 3.00
beading matching with laminate will be provided.etc all necessary hardware included and complete as per image and detail design and drawings. all laminate shaed are to be
as per architects's selection.
Supply, fabrication, and installation of modular kitchen cabinets using economical materials, with carcass made of commercial plywood or pre-laminated particle board
finished with 0.8 mm laminate or pre-laminated surfaces on both sides and basic edge banding to exposed edges, shutters made of commercial plywood or MDF finished
with 0.8 mm laminate on the outer face and white or balancing laminate on the inner face, and provision of drawers using basic telescopic channels (non-soft close) along
131 with stainless steel (SS) wire trolleys in place of tandem systems, including basic cutlery tray and essential storage accessories; all visible surfaces to be finished in matching RMT 20,710.00 520.15
laminate shades selected and approved by the Architect/Engineer-in-Charge, and the work to include complete installation of the kitchen unit with all necessary basic
hardware such as hinges, handles, channels, fittings, and accessories as per drawings and site requirements
Providing and fixing in position PVC Frosting Glass film of approved make (of any pattern, shade and type) on glass partitions and doors for internal use. Film shall be pasted
132 on glass without any appearing any air bubble. The rates shall be for all shapes and all heights with necessary scaffolding complete as per the Architectural drawings and SQM 1,243.00 47.00
manufacturer's specification & instructions as directed by the Architect and Engineer-in-charge. Film shall be with 10 years warranty.
Providing and fixing roller blinds with composition 100% Polyester . Fabric woven and semi opaque / coated translucent fabric & Complete Blackout. The fabric shall be
enclosed in the suitably created pocket along with tube i.e Palmate. Fabric Warranty 3Year. Weight 190 GSM, Width 280 cm, Thickness 0.48mm, Light fastness is 4 to
grade. Mechanism made in UK with ball chain mechanism & with 5 years mechanism warranty. The Roller tube extruded by non-rusting Aluminium alloy with 1.25 mm
thickness. Available in 32, 38, &45 mm diameters for small and big blinds respectively. Mechanism is designed with support beam to keep it straight and have a pocket for
133 holding the fabrics in position. The mounting brackets shall be universal and capable of mounting inside/ outside/ ceiling / wall with the clutch on either the right or left end of SQM 3,811.00 29.00
the tube. Mechanism to be operated with control unit made of high strength ABS plastic. Mechanism shall be operating with the use of a ball chain, made up of unbreakable
polyethylene plastic, 1.50mm polyester cord with 4.50 mm balls. The blind shall be able to stop at any desired position with the help of stop lock. The bottom channel of
Roller Blind shall be matching shade with fabric and made of non-rusting aluminium powder coated with 1.50 mm thickness. The fabric shall be enclosed in the suitably
created pocket along with tube.
TOTAL OF FURNITURE
Item no. Item Description Unit Rate Total Qty. Amount
Parking Suspended Sign : Providing a signs made as using Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa
made from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under
134 normal working conditions.Sign is double sided 50 mm depth profile with media accomodation depth of 6 mm media of ACP acrylic upto 5 mm thickness can be pasted Nos. 33,350.00 4.00
directly on frames or attched on frame with help of dual lock tape.Sign can be edge lite with help of edge lite led modules ,led of LUCOLED make EL31 , fitted and installed
at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge. - S1
Door Nameplate Sign - Providing a signs made as using Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa
made from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under
135 normal working conditions.Sign is single sided with 1 aluminium profile click fitted on 2 plastic moulded endcaps.Sign is including all plastic injection moulded end caps black Nos. 1,988.00 110.00
in shade which are directly press fitted ,media can be flat bed UV printed on panels/ profiles.Cosign make MPI panels fitted and installed at site in plumb and level at
specified location as per drawing to the satisfaction of the engineer-in-charge.
Floor directory sign - Providing a signs made as using Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa made
from virgin aluminium homogeneous billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under normal
136 working conditions.Sign is single sided with aluminium side tracks and common click clips for panel fitting. a.Sign is including all plastic injection moulded clips black in SQM 2,070.00 7.00
shade which are slided in side tracks ,media can be flat bed UV printed on panels/ profiles.Cosign make MPI panels fitted and installed at site in plumb and level at specified
location as per drawing to the satisfaction of the engineer-in-charge.
Toilet Door Sign - Providing a signs made as using Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa made
from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under normal
137 working conditions.Sign is single sided with 1 aluminium profile click fitted on 2 plastic moulded endcaps.Sign is including all plastic injection moulded end caps black in Nos. 746.00 10.00
shade which are directly press fitted ,media can be flat bed UV printed on panels/ profiles.Cosign make MPI panels fitted and installed at site in plumb and level at specified
location as per drawing to the satisfaction of the engineer-in-charge.
Closet Door sign - Providing a signs made as using Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa made
from virgin homogeneous aluminium billet) with Premium grade Anodizing (Thickness 15-20 microns) as per International standards, with 10 years warranty under normal
138 working conditions.Sign is single sided with 1 aluminium profile click fitted on 2 plastic moulded endcaps.Sign is including all plastic injection moulded end caps black in Nos. 746.00 38.00
shade which are directly press fitted ,media can be flat bed UV printed on panels/ profiles.Cosign make MPI panels fitted and installed at site in plumb and level at specified
location as per drawing to the satisfaction of the engineer-in-charge.
Lift Number sign - Providing sign of Cosign make Modular Aluminium extrusions (Alloy 6060 as per European standards EN755-2-2008 tensile strength 190 MPa Made from
virgin homogeneous aluminium billet) with premium grade anodizing (Thickness 15-20 microns) as peinternational standards, with 10 years warranty under normal working
139 conditions. Profile to form frame with overall depth of 10 mm with media of thickness upto 3mm. 2 mm thick acrylic/ACP . I-sign Fix profile of Cosign make with M.S zinc Nos. 1,380.00 54.00
coated corners with grub screws. Installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge.
Emergency Exit sign - Providing ready sign & fixing at location a Cosign make emergency exit sign- illuminated, surface mount (wall or ceiling) Dual sided made up of plastic
material , battery backup of 3 hours (180 mins) .Battery life of 300 cycles of charge & discharge Li- ion battery 3.7 Volt, 100 mA, Charge time of 24 hours. Input voltage 220-
240 Volt A.C, 50/60 Hz. Viewing distance 30 meter, degree of protection IP20 (rating for protection against solid object upto 12 mm) white light colour full back (white colour)
LED illumination with green white coloured graphic inserted on both sides on 0.4 mm PC (sizes, texts, symbols or graphics as per standard safety norms & regulations)
140 graphic options of -left ,right, up staircase down staircase. Test facilty button self test plus auto self test, opreration in maintained and non maintained mode (power saver Nos. 4,600.00 30.00
mode).Sign with 12 months warranty for electric circuit & 6 months warranty for battery. Sign provided with dual mounting arrangement of mounting on wall & celing both (
with flat rigid support/base).Sign is including all connection wires (upto 1 mtr) & high tensile strength zinc coated self tapering screws (4 nos with screw wall plastic packing),
installed at site in plumb and level at specified location as per drawing to the satisfaction of the engineer-in-charge.
BUILDING SIGNAGE - Aluminium Channel Letters -
Specifications:
Supply and installation of 1mm thick and 4" depth Aluminium Channel letters with proper backside fabrication with 3mm acp female and 3mm acrylic having led of GOQ
Genius 2835 having 5 years warranty and power supply of Union/E-power with 5 years warranty. Wiring to be done by using 1.5mm wire of Finolex brand.
141 5 Years warranty Power dissipation ‐ Nos. 11,500.00 16.00
View angle ‐ 175 Luminous flux ‐ 90lm
Colour cct ‐ Pure White, 10000k Cool
white Dimensions (mm) 66*15*10.5._
Item no. Item Description Unit Rate Total Qty. Amount
TOTAL OF SIGNAGES
Design, supply, delivery and installation of FRP Surface Heavy Duty Recessed Manhole Cover with Frame (450mm x 450mm clear opening) for sewer manholes and
142 storm water catchpits, including proper seating in RCC top slab, alignment, grouting, finishing and all complete as per drawings and specifications, including all materials, Nos. 8,867.00 10.00
labour, tools, transportation, and fixing at site.
Design, supply, delivery and installation of FRP Surface Heavy Duty Recessed Manhole Cover with Frame (600mm x 600mm clear opening) for sewer manholes and
143 storm water catchpits, including proper seating in RCC top slab, alignment, grouting, finishing and all complete as per drawings and specifications, including all materials, Nos. 17,118.00 20.00
labour, tools, transportation, and fixing at site.
Design, supply, delivery and installation of FRP Water Gully cover with Frame Heavy Duty (600mm x 600mm clear opening) for valve chambers, including proper seating
144 in RCC top slab, alignment, grouting, finishing and all complete as per drawings and specifications, including all materials, labour, tools, transportation, and fixing at site. Nos. 13,082.00 2.00
Providing, supplying and fixing FRP moulded grating of 38mm thickness, panel size 310mm x 1220mm, including cutting to required sizes, proper placement over
supporting frame, fixing with suitable clamps/fasteners, alignment, and all necessary accessories, complete as per drawings and specifications.
TOTAL OF MEPF WORK
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-
Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under Building
Project Department.
SUBESTIMATE - 03 : HVAC WORK
S. NO. ITEM DESCRIPTION AMOUNT
B AIR DISTRIBUTION NETWORK
D CIVIL STRUCTURE SUPPORT
E VENTILATION FAN
Total of HVAC Works
F Sub Total - Comprehensive Maintenance
TOTAL OF MAINTENANCE & OPERATION FOR HVAC
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE - 03 : HVAC WORK
Item no. Item Description Unit Rate Total Qty. Amount
Providing and erecting Inverter based approved make split air-conditioning unit consisting of condensing unit with variable speed fan motor, inverter type hermetically
sealed rotary compressor with accessories etc. duly connected separately erected evaporating unit and blower motor with its accessories by means of extra supplied
proper insulated copper tubing,drain PVC pipes suitable for ( cost includes Eco Friendly green gas charging and 15A plug top & Remote Control & MS Stand) with
necessary core cutting.
(2)For ISEER Range (KWH/KWH)(4.0 to 4.49)
1.0 a) for 0.8 to 1.0 ton capacity- Premium cat. Nos. 48,639.00 1.00
Providing and erecting Inverter based approved make Cassette type split air-conditioning unit consisting of condensing unit with fan motor, hermetically sealed
2.0 scroll/rotary compressor with accessories etc. duly connected separately erected evaporating unit and blower motor with its accessories by Eco friendly Green gas
charging & Internal copper wiring & Remote control ( 3 star and above of current year) with necessary core cutting.
2.1 (A) for 1.5 ton capacity Nos. 75,550.00 3.00
2.2 (B) for 2 ton capacity Nos. 87,925.00 5.00
2.3 (C) for 3 ton capacity Nos. 1,43,613.00 5.00
2.1 (D) for 4 ton capacity Nos. 1,75,581.00 1.00
3.0 Supplying & installing MS standard type stand mounting for outdoor unit of Split A.C. upto 4 TR capacity erected with necessary hardware materials as directed. Each 739.00 6.00
Supplying and erecting insulated pair of soft copper tubing open or concealed including power and control cable,necessary PVC drain pipes for Split AC machine up to
Supplying and installing MS angle , powder coated / Painted standard type of wall/floor stand mount for outdoor unit of split AC of following capacity, erected with
5.0 necessary hardware materials as directed. Each 1,348.00 8.00
(A) 25mm*25mm*3mm thick M.S angle suitable for upto 2 TR. Capacity of ac machine
6.0 DRAIN PIPING :
Rigid UPVC drain pipe of 10 Kg/cm2. rating with 9 mm thick.nitrile rubber insulation.
A SUB TOTAL - DX SYSTEM
B AIR DISTRIBUTION NETWORK
Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular/round ducting complete with neoprene rubber
6.0 gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness
complete as required.
6.1 Thickness 0.63 mm sheet (22 Gauge) (24 Gauge) SQM 1,296.00 305.00
6.2 Thickness 0.80 mm sheet (20 Gauge) (22 Gauge) SQM 1,504.00 10.00
6.3 Thickness 1.00 mm sheet (22 Gauge) (20 Gauge) SQM 1,663.00 5.00
Item no. Item Description Unit Rate Total Qty. Amount
6.4 Thickness 1.25 mm sheet (16 Gauge) (18 Gauge) SQM 2,162.00 5.00
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular/round ducting complete with neoprene rubber gaskets, elbows,
7.0 splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required.
7.1 Thickness 0.63 mm sheet (22 Gauge) (24 Gauge) SQM 1,245.00 30.00
7.2 Thickness 0.80 mm sheet (20 Gauge) (22 Gauge) SQM 1,453.00 5.00
7.3 Thickness 1.00 mm sheet (22 Gauge) (20 Gauge) SQM 1,867.00 2.00
7.4 Thickness 1.25 mm sheet (16 Gauge) (18 Gauge) SQM 2,091.00 2.00
Supply and installation of MS Welded rectangular ducts, complete with required flanges , necessary supports of pregalvanised steel of 275gsm and 4.8 strength class
8.0 threaded rods (as directed) and ETA Approved anchor bolts, supply air collars, vanes, splitters dampers and as per specification for Air Conditioned Areas - For Kitchen
( Support Shall be provided as free supply to the contractors )
8.1 18 G MS Ducting Sqm. 2,450.00 5.00
Supply, installation, testing & commissioning of thermal insulated flexible duct of following sizes duly supported at regular interval as
9.0 per site requirement etc. complete as required as per Mtr 696.00 10.00
specifications.(A) 200 mm dia.
10.0 SUPPLY INSTALLATION TESTING AND COMMSSIONING OF DIFFUSERS/ GRILLES AS PER FOLLOWING SCHEDULE
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers complete as per specifications and size & shape as per
site requirement and approved design.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as per specifications and size &
shape as per site requirement and approved design.
Supplying, fixing testing commissioning of supply air diffuser of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable
core and size & shape as per site requirement and approved design.
Supplying, fixing testing commissioning of Return air diffuser of powder coated aluminium without volume control dampers with anti smudge ring & removable core
and size & shape as per site requirement and approved design..
Supply fixing and testing , commisioning of Aluminium Powder Coated Slot Diffuser complete with plenum box and volume control damper. Color , size & shape as per site
11.0 requirement and approved design.. Neccessory ancilery item for fixing cost should be included.
Contractor need to revalidate the diffuser selection before preparing shop drawing.
12.0 Rain Protection Fresh Air Grill for Façade installation. Sqm 7,500.00 25.00
13.0 SUPPLY, INSTALLATION, TESTING, COMMISSIONING OF DUCT DAMPERS
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc,
as per specifications.
Item no. Item Description Unit Rate Total Qty. Amount
Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control
wiring,the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being
13.2 restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal SQM 11,905.00 0.50
complete as required and as per specifications.
(A) Fire damper
13.3 (B) Actuator Each. 11,153.00 0.50
14.0 Double Layer Weather Proof Machine Canvass Connection ( FAN ) Set 3,500.00 3.00
B SUB TOTAL - AIR DISTRIBUTION NETWORK
C CIVIL SUPPORT STRUCTURE
15.0 Vibration Absorbant spring supports for Fans ( 4 to 8 Support for each FAN ) Set 1,500.00 3.00
16.0 Engineered Rubber Support Pad for Split AC Out Foor Unit Set 1,800.00 15.00
17.0 MS Welded Structure (Supply and erection of M.S. angle stand with synthetic epoxy paint for all outdoor units) Kgs 135.00 270.00
18.0 Core Cut up to 150mm Dia Lot 1,350.00 7.00
C SUB TOTAL - CIVIL SUPPORT STRUCTURE
D DUCT INSULATION
19.0 DUCT THERMAL INSULATION
Supplying, laying, fixing, testing and commissioning of following thickness closed cell elastomeric nitrile rubber of class 'O' applied by suitable adhesive, as per
specifications and as required complete in all respect.
19.2 13 mm thick SQM 610.00 10.00
20.0 DUCT ACCOUTIC INSULATION
Providing and fixing acoustic Insulation of open cell nitrile rubber sheet having density of 180-220 kg/m3 and recommanded thickness of 15 mm. Absorption coefficient
value of Insulation material shall be 0.90 for the 2000 Hz frequency band in accordance to IS:8225/ISO:354/ASTM 423C. Material shall have fire class 1 as per BS 476
part 7. Material Shall be EPA approved and Anti-Fungal & Anti- Bacterial in accordance with ASTM G21 & ASTM E 2180 respectively. It shall be fixed inside of the duct
with the help of adhesive as per the specifications given.FSK tape shall be applied at joints.
21.0 UNDER DECK INSULATION :
21.1 Supply & Fixing Under deck Insulation with 50 mm thick Fire Retardant Extruded Polystyrene having density of 32 Kg / M3 and thermal resistance of 1.78 M2 K / W SQM 850.00 375.00
D SUB TOTAL -DUCT INSULATION
E VENTILATION FAN
22.0 CABINET TYPE INLINE CENTRIFUGAL EXHAUST AIR FAN
Item no. Item Description Unit Rate Total Qty. Amount
Supply, Installation, testing & Commissioning of Cabinet type Centrifugal Fans / Inline Fan for Exhaust Air System complete with SISW Forward Curved blower, fan
assembly shall be AMCA certified (AMCA certification requird for Air Performance & Sound) & totally enclosed, fan-cooled, provided with class F insulation, and of
approved make.,
Fan shall be provided with TEFC Sq.cage, direct driven F' Class induction motor with minimum IP-55 protection
Motor shall be suitable for 220 ± 5% volts, Single phase, 50 cycles electric supply- I OR 415+/-10% V, 50 hz, 3 phase AC. The motor (Eff1 Class-Motor must be VFD
Max. noise level shall be 56 dBA at 1.5 meter in hemispherical reverberant room condition.
The complete fan assembly shall be CE Certified in accordance with EN-12101-3:2015 (Vendor shall submit the certifications for below listed fans)
The Fan units shall be designed as per the criteria mentioned in the specifications and selected so as to operate in the best efficiency zone; the units shall be statically and
dynamically balanced.
Necessary starter shall be in scope of HVAC Contract. Power cable will be available up to starter panel. The controller will be BMS compatible with all required open
protocol and requried licence softares.
23.0 FAN FILTER UNIT
SITC of Cabinet (Square) Type Inline Centrifugal Fresh Air Fan AMCA Certified (For Air and Sound Performance) suitable for installing in any position in vertical or
horizontal ducts. The casing shall be single skin, internally acoustically lined and constructed of galvanised steel. The inline fan shall be with Farword curve up to
CFM & above shall be backward curve centrifugal impeller fitted with maintenance free external rotor motor, flexible connections at the discharge & inlet. The motor shall
be suitable for 220 / 415±10% volt single/three phase 50 Hz AC supply. 3 phase fans quoted price shall be inclusive of DOL starter panel with cabling between starter
panel and fan. The fan shall have low sound level exceeding not more than 65 DBA at 3 meter distance.
The fan shall have easily washable 20 micron fresh air filter. The Fan units shall be designed as per the criteria mentioned in the specifications and selected so as to
operate in the best efficiency zone; the units shall be statically and dynamically balanced. Necessary starter / Panel / Power Cable shall be in the scope of HVAC
Contractor. Power cable will be provided up to starter panel.
24.0 WALL MOUNTED PROPELLER EXHAUST FAN WITH GRAVITY LOUVERS
Supply, Installation, testing & Commissioning of Propeller fan for wall or panel mounting suitable for supply or exhaust use having casing, protection guard and impeller.
Impeller shall be made with galvanized steel. Entire assembly shall be black enamel painted to avoid the rust. The fan should have sickle blade impellers with external
rotor motor, fan assembly shall be AMCA certified (AMCA certification requird for Air Performance & Sound) & totally enclosed, fan-cooled, provided with class F
insulation, and of approved make.,
Fan shall be provided with TEFC Sq.cage, direct driven B' Class induction motor with minimum IP-54 protection
Motor shall be suitable for 230 ± 5% volts, Single phase, 50 cycles electric supply- I. The motor (Eff1 Class-Motor must be VFD Compatible )
Max. noise level shall be 60 dBA at 3 meter in hemispherical reverberant room condition.
The complete fan assembly shall be CE Certified in accordance with EN-12101-3 (Vendor shall submit the certifications for below listed fans)
The Fan units shall be designed as per the criteria mentioned in the specifications and selected so as to operate in the best efficiency zone; the units shall be statically and
dynamically balanced.
24.1 Necessary starter shall be in scope of HVAC Contract. Power cable will be available up to starter panel.
Item no. Item Description Unit Rate Total Qty. Amount
25.0 Lift pressurization System
Supplying, installation, testing and commissioning of AMCA Certified (For Air and Sound Performance) ceiling hung / floor mounted AXIAL flow fans of following capacity
with GSS casing/ standard M.S. construction and aluminium alloy impellers with high efficiency aero-foil sections, blades. The impeller shall be directly driven by TEFC
induction motor with high efficiency class IE2 . Motors shall be suitable for 3 Phase, 50 Hz, 415V ± 10 %. Motors to be of class 'H' insulation for Supply/Fresh Air Fans and
class 'H' insulation/ 300° C for 2 hrs for smoke or normal Exhaust Fans. The Exhaust air fans-motor assembly should be CE Listed as per EN-12101-3: 2015.. Motor make
shall be same as mentioned on the fire certificate. Fan total efficiency should not be less than 70%. Entire fan model & AMCA Seal shall appear in technical submittal of
fan. The Axial fans shall have sound level not more than 75 dB(A) at three meter distance at both ends when measured in closed room conditions. Static pressure
calculation of Fans shall be checked by Vendor/Contractor prior to supply of Fans as per site condition. If there is any discrepancy against the BOQ, the Vendor/Contractor
has to take approval from Client & Consultant, and nothing extra shall be paid.
Necessary starter shall be in scope of HVAC Contract. Power cable will be available up to starter panel. The starter should be capable to run automatically in case of fire.
25.1 9000 CFM 18 mm WC ESP ( Liftwell Pres. System ) Set 85,000.00 4.00
E SUB TOTAL - VENTILATION FANS
TOTAL HVAC WORKS
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE - 03 : HVAC AMC CHARGES WORK
Item no. Item Description Unit Rate Total Qty. Amount
ANNUAL MAINTENANCE CONTRACT
(Note : From Each RA Bill, 5% retaination money to be deduct during O&M Period)
Comprehensive AMC for SITC of High Side units and Ventilation System
It includes all preventive maintanance , break down maintanance with all spares - repair or replacement of the
defactive part or parts , this includes all cosumable if any applicable.
1.1 1st year ( From the date of Completion of DLP ) Months 9,555.00 12.00
1.2 2nd year ( From the date of Completion of DLP ) Months 9,555.00 12.00
1.3 3rd year ( From the date of Completion of DLP ) Months 9,555.00 12.00
1.4 4th year ( From the date of Completion of DLP ) Months 9,555.00 12.00
Sub Total - Comprehensive Maintenance
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under
Building Project Department.
SUBESTIMATE - 04 : ELECTRICAL & ELV WORK
S. NO. ITEM DESCRIPTION AMOUNT
A Electrical Works
3 SERVO STABILIZER
4 JUNCTION BOXES
5 DISTRIBUTION BOARD
6 LT CABLES & CABLE TERMINATION
8 INTERNAL WIRING
9 INDOOR LIGHT FIXURE
12 SAFETY ITEMS
13 EXTERNAL LIGHT FIXTURE AND POLE
14 DWC PIPE AND CHAMBER
16 SERVICE WORK
17 RACEWAY/TRUNKING & JUNCTION BOX
Total of Electrical Works
18 FIRE DETECTION & ALARM SYSTEM
19 PUBLIC ADDRESS SYSTEM
S. NO. ITEM DESCRIPTION AMOUNT
20 VOICE COMMUNICATION SYSTEM
Total of ELV Works
C Maintenance & Operation for Electrical & ELV Works
21 MAINTENANCE & OPERATION FOR ELECTRICAL & ELV WORK
E Comprehensive Maintenance for Lift Works
23 COMPREHENSIVE MAINTENANCE FOR LIFT WORK
F CCTV & Networking System Works
25 NETWORKING SYSTEM
Total of CCTV & Networking System Works
G Comprehensive Maintenance for CCTV & Networking System
25 COMPREHENSIVE MAINTENANCE FOR CCTV & NETWORKING SYSTEM
Tender Assumption List.
1 Quntity in this estimate are based on conceptual layouts and information received from various stackholders. It may very as per detial design stage.
For Fire station and residential block LT services considered , Substation , meters space marked on drawing basis of preliminary load. Liason person has
to approve same from supply comapany.
3 All cabling & related assesories upto LT meters are in the scope of supply company, Clients scope start from LT meters onwards.
4 Any specific equipent or requirement for Fire control center excluded from estimate.
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE - 04 : ELECTRICAL & ELV WORK
Item no. Item Description Unit Rate Total Qty. Amount
Supplying and erecting, commissioning and testing of Diesel Generating set confirming to IS: 4722:1968 & BS:5514 having continuous rating, 3 phase, 415 volts,
cycles A.C. supply comprising of a totally enclosed air/water cooled diesel engine with multi-cylinders developing suitable BHP not less than following capacity at
1500 RPM with 10% overload for one hour in 24 hours with standard accessories like fly wheel, lubricating oil cooler, "A" class governor, heavy duty fuel wheel and
lubricating oil filter, oil bath air filler, lubricating oil pressure gauge, end exhaust manifold, standard set of tools with adjustable spanners, screw drivers, cylinder head
to cover, joint cylinder head to exhaust, element lube oil filter, 12 / 24 volts electric starting equipment complete with standard heavy duty battery, dynamo, cut-outs,
ammeter, necessary wiring, pressure gauge, starter etc and heavy duty Residential type exhaust silencer and vertical hot air duct both
logged with asbestos rope, save oil trays, exhaust piping of required length, standard wall/floor mounted fuel with level indicator and piping and drip proof alternator,
self excited, self regulated, screen protected, with excitation system, capable of delivering the rated system output at 415 volts, 3 phase, 0.8 PF, 50 Hz, 4 wire,
1.1 running at 1500 RPM, conforming to IS-4722- 1968 with voltage regulation +/- 5% of rated voltage from no load to full load. Both the engine and alternator fitted Each 24,37,870.00 1.00
on a common fabricated steel base plate with antivibration mounting engine and alternator both connected to each other by flexible flange coupling and with
floor/wall mounted control panel box comprising of voltmeter ammeter, selector switches, ACB / MCCB / MCB of adequate capacity,
indicator lamps duly wired with HRC fuses. The alternator & control panel shall be connected with provided suitable capacity armoured cable and complete with
Acoustic enclosure (canopy) made out of 16 SWG CRCA Sheet, sound absorbing material Rockwool of 64 density & 100 mm thick conforming to IS:8183 / PU Foam
of 40 Density - at least 40 mm. The resin bonded rockwool covered from inside the canopy by perforated sheet with 3/4 mm holes, sound level not more than 75 dB
at a distance of 1 mtr, as per PVCT norms. Erection, commissioning and satisfactory testing as per requirement with first filling of fuel, oil, etc. with guarantee /
Warrantee of complete system for Two years. & with obtaining all necessary certificate from Electrical Inspector. The Capacity and Ratings of DG sets are as below.
(R) Continuous rating of 250 KVA ,BHP not less than 309 BHP
Providing & erecting approved make AMF control panel suitable for following size of 3 phase, 415 V., 50 cycles, A.C. diesel generating set complete of scope as
detailed below:
1) Power module: A pair of electromechanically interlocked contactors (for mains & generator) Overload relay for generator contactor Neutral contactor for mains
and generator Power socket for connections.
2) Control and metering module: Line voltage monitor. Generator voltage monitor Ammeter 3 items attempt start facility. Air circuit breakers/MCB/MCCB of suitable
1.2 rating for auto/manual operation. Auto/manual switch. Emergency stop push buttons. Manual start push button. frequency meter. Engine hour meter. Two earthing Each 2,20,509.00 1.00
3) Protection module: The engine shutdown in the unlikely event of Low lube oil pressure High cylinder head temperature. V belt failure.
4) Indicators with alarm Load on generator.
5) Indicators Load on mains Engine fails to start . Emergency stop battery charger.
The AMF Panel of following capacity
(D) AMF Control Panel for200 KVA/250 KVA 3 phase DG Set
Sub Total 1.....
Item no. Item Description Unit Rate Total Qty. Amount
Supply, installation, testing and commissioning of 3 phase 415V 4 wire Free Standing Floor mounted MV panel made out of minimum 14 SWG CRCA sheet after
seventank process and painting with Epoxy powder coating including all switchgear as detailed below. The panel having PU/Neoprene rubber gasket of not less than
3mm thickness,separate detachable, gland plate M.S. base channel, hinged door with locking arrangement for equipment/switchgear. The panel shall consist of
suitable rating FP/TPN Aluminium- busbar-as per SLD (at the rating of 0.8ASq.mm) supported with DMC/ SMC barriers and colour coded with Heat shrinkable
sleeves. The Metering shall be provided as specified.
The panel shall have Short circuit with standing capacity as given in SLD and consist of the switchgear as mentioned below. The panel shall be mounted on plinth,
stand, etc. including all materials. The panel shall be got fabricated from manufacturers with CPRI Test certificate only. All the Panels shall have minimum 25%
outgoing as per SLD. The earth bus shall be continuoulsy run without any jointing/welding and its Size should be per SLD. The size of all Panel Mounting Meters shall
be 96X96mm.The Panels shall be mounted on U channels including supply and fixing of the same. MCBs shall be provided for Control purposes. (All Panels shall be
extendable type only). Price shall be inclusive following:
Shifting of panels from site store to the suitable location. Installation of panel as located in electrical drawings or as per site conditions, including removing packing
etc. Earthing all components, frame etc. to a common internal earth bar. Connection, testing & commissioning. Electrical contractor shall carry out the insulation test
at site & all the readings shall be submitted in copy to the consultant or engineer-in-charge. Supply, installation, testing and commissioning all accessories, supporting
structure, hard ware etc to complete the job. Supply, installation, testing and commissioning of necessary tools, hard ware, testing hard ware, testing equipment etc.
The rates for the distribution boards apart from the Breakers and instruments shall also include the following :
This schedule of Quantities shall be read in conjuction with the technical specification, General & Special conditions as well as all tender drawings. Supporting rigid
steel framework. Cubicle type, 14 gauge CRCA sheet steel enclosed.
Proper bonding to earth. Painting/lettering on Breakers and distribution boards, the location they serve, providing on each panel its circuit diagram.
Providing cable clamps / supports within distribution boards cable alley.
All MCB’s shall be of minimum 10 KA breaking capacity.
The breaking capacity of MCCB’s are mentioned panel wise. All MCCB’s shall be with thermal magnetic releases upto 250 amps and miroprocesR&B R&B SOR
based for 250 amps and above capacity, unless specified otherwise.
All motor feeders MCCBs shall be of motor duty.
Distribution panels shall be Powder Coated with Siemens gray paint shade no. RAL-7032 of IS-5.
Degree of protection for following type of distribution panel enclosure shall be as per IS:13947-1993.
IP 4x for all Indoor panel.
IP 65 and double door for all outdoor panel.
All MCCB’s shall be provided with operating mechanism for door interlock.
All measuring instruments (Meters) shall be of digital electronic with LED of approved make.
All hinged door shall be earthed through 2.5 sq mm tinned braided copper wire.
All panels shall have provision of the following:
Pad locking of Switch board doors.All MCB’s used for protection of resistive and lightly inductive load shall be type “B” characteristic and inductive (motor) load shall
be of type “C” characteristic and discharge lamps and UPS etc. shall be of type D characteristic. All incoming and outgoing air circuit breakers shall be placed on
middle portion of the vertical in single tier formation. SPD as shown in SLD
SITC OF MAIN PANEL FOR FIRE STATION_RANIP
ALSO REFER SLD ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
SITC OF COMMON AREA FOR SITE_RANIP
ALSO REFER SLD ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
SITC OF PHE PANEL_RANIP
ALSO REFER SLD ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
SITC OF 2BHK COMMON AREA PANEL_RANIP
ALSO REFER SLD ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
SITC OF 1BHK COMMON AREA PANEL_RANIP
ALSO REFER SLD ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
SITC OF DG PANEL_RANIP
ALSO REFER SLD ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
Item no. Item Description Unit Rate Total Qty. Amount
SITC OF EXTERNAL LIGHTING PANEL_RANIP
ALSO REFER SLD ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
Providing & erecting capacitor duty contactor 3 phase, 415 V with proper connection for following rating:
2.8 Each 3,217.00 RO
SITC OF APFC PANEL - 75 KVAR
Design, Supplying, installing, testing of factory fabricated ready made Three phase APFC Panel Cubical Panel fabrication should be type tested as per IEC
61439:1&2 Capacitor Duty Contactor for switching as per following Steps Incomer Switch of MCCB type Icu=Ics=50KA at 400/440 Volts, with OC, SC, internal earth
fault protection Incomer Switch of MCCB type Icu=Ics=50KA at 400/440 Volts, with OC, SC, internal earth fault protection,Copper tinned insulated Busbar,Cubical
2.9 panel should be indoor type with IP 43 and IK 10,Metalized polypropylene film tye3-phase 550Volt Capacitor,De tuning Reactor for each capacitor,Panel having Each 2,16,103.00 RO
Short Circuit and Overload protection,Each step Capacitor having suitable MCB with Sc, OL, internal earth fault relay,Each stage having Stage Contactor (Capacitor
load rating),PF regulator master controller having suitable steps with LCD display, Rs 485 Communication port, Indication LED Lamps for main incomer and ON-OFF
for each capacitor bank,MS Chanel for Floor mounting, Cable entry as per site situation,Cooling fans for panel
ALSO REFER SLD ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
SITC OF APFC PANEL - 100 KVAR
Design, Supplying, installing, testing of factory fabricated ready made Three phase APFC Panel Cubical Panel fabrication should be type tested as per IEC
61439:1&2 Capacitor Duty Contactor for switching as per following Steps Incomer Switch of MCCB type Icu=Ics=50KA at 400/440 Volts, with OC, SC, internal earth
fault protection Incomer Switch of MCCB type Icu=Ics=50KA at 400/440 Volts, with OC, SC, internal earth fault protection,Copper tinned insulated Busbar,Cubical
panel should be indoor type with IP 43 and IK 10,Metalized polypropylene film tye3-phase 550Volt Capacitor,De tuning Reactor for each capacitor,Panel having
2.10 Short Circuit and Overload protection,Each step Capacitor having suitable MCB with Sc, OL, internal earth fault relay,Each stage having Stage Contactor (Capacitor Each 2,86,018.00 2.00
load rating),PF regulator master controller having suitable steps with LCD display, Rs 485 Communication port, Indication LED Lamps for main incomer and ON-OFF
for each capacitor bank,MS Chanel for Floor mounting, Cable entry as per site situation,Cooling fans for panel
ALSO REFER SLD ALONG WITH THIS. ALL SHOULD BE AS PER SLD & REQUIREMENT.
[FOR RANIP FIRE STATION & COMMON AREA SITE FOR RANIP]
Sub Total 2.....
3 JUNCTION BOXES
Supply, Transportation, Installation, testing and commissioning of IP-67 Rated weather proof Outdoor type junction boxes having dimensdios Height x Width x Depth:-
104 x 104 x 70 mm with terminal having black colour RAL 7035. with 5 pole terminal set upto 4 sqmm cables
Supply, Transportation, Installation, testing and commissioning of IP 66/69 weather proof Outdoor type junction boxeshaving dimensdios Height x Width x Depth:-
155 x 210 x 92 mm with terminal having black colour RAL 9011. with 5 pole terminal set upto 16 sqmm cables
Sub Total 3.....
4 DISTRIBUTION BOARD
SPN Distribution Board :
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms
to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for
4.1 (A) Single phase incoming and horizontal single phase outgoing Each 1,141.00 15.00
(b) Sheet Steel double door (IP-43)
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms
to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for
4.2 (A) Single phase incoming and horizontal single phase outgoing Each 1,478.00 70.00
(b) Sheet Steel double door (IP-43)
Item no. Item Description Unit Rate Total Qty. Amount
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms
to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for
4.3 (A) Single phase incoming and horizontal single phase outgoing Each 1,664.00 1.00
(b) Sheet Steel double door (IP-43)
TPN Distribution Board :
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms
to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for
suitable for (PPI DB)
(B) three phase incoming and single phase horizontal type outgoing Per phase isolation type (PPI)
(b) Sheet Steel double door
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms
to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for
suitable for (PPI DB)
(B) three phase incoming and single phase horizontal type outgoing Per phase isolation type (PPI)
(b) Sheet Steel double door
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms
to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for
suitable for (PPI DB)
(B) three phase incoming and single phase horizontal type outgoing Per phase isolation type (PPI)
(b) Sheet Steel double door
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms
to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs.(The DBs should be used of same company of MCB to be used) suitable for
suitable for (PPI DB)
(B) three phase incoming and single phase horizontal type outgoing Per phase isolation type (PPI)
(b) Sheet Steel double door
VTPN Distribution Board :
Providing and erecting Sheet Steel powder coated Vertical MCB distribution board (VTPN) - flush / surface mounted double door (IP54) fitted with copper insulated
busbar, isolated neutral bar, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3, suitable for 63/100 AMP TPN MCCB + RCCB as incomer and
4.8 three phase outgoing as per following .(The DBs should be used of same company of MCB to be used) Each 5,760.00 1.00
(A)4 way outgoing
Providing and erecting Sheet Steel powder coated Vertical MCB distribution board (VTPN) - flush / surface mounted double door (IP54) fitted with copper insulated
busbar, isolated neutral bar, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3, suitable for 63/100 AMP TPN MCCB + RCCB as incomer and
4.9 three phase outgoing as per following .(The DBs should be used of same company of MCB to be used) Each 6,433.00 2.00
(B)6 way outgoing
Item no. Item Description Unit Rate Total Qty. Amount
Providing and erecting Sheet Steel powder coated Vertical MCB distribution board (VTPN) - flush / surface mounted double door (IP54) fitted with copper insulated
busbar, isolated neutral bar, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3, suitable for 63/100 AMP TPN MCCB + RCCB as incomer and
4.10 three phase outgoing as per following .(The DBs should be used of same company of MCB to be used) Each 8,319.00 4.00
(C)8 way outgoing
Providing and erecting Sheet Steel powder coated Vertical MCB distribution board (VTPN) - flush / surface mounted double door (IP54) fitted with copper insulated
busbar, isolated neutral bar, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3, suitable for 63/100 AMP TPN MCCB + RCCB as incomer and
4.11 three phase outgoing as per following .(The DBs should be used of same company of MCB to be used) Each 10,857.00 RO
(D)12 way outgoing
MCB 's and its Accessories
4.12 Providing & erecting insulated socket 3P+N+E with Plug16A rating which is comprised of Four pole MCB slot and insulated socket IP40 Cat-III. Each 1,690.00 1.00
providing and erecting Miniature circuit breaker single pole 6A to 25A suitable to operate on 240 V A.C. system and having breaking capacity 10 KA to be erected
in existing box. confirming to IS 8828/1996 with ISI Mark Cat.III.
Providing & erecting 240 V MCB double pole switch for motor & inductive load having 10 KA breaking capacity & confirms to IS : 8828 in existing box having
4.14 following capacity Each 326.00 1.00
(A) 6 to 32 Amp.
Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load having 10KA breaking capacity & confirms to IS :8828 in existing box having following
4.15 capacity Each 649.00 33.00
(a) 6 to 32 Amp. ( Cat.III)
Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load having 10KA breaking capacity & confirms to IS :8828 in existing box having following
4.16 capacity Each 729.00 4.00
(b) 40 Amp. ( Cat.III)
Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load having 10KA breaking capacity & confirms to IS :8828 in existing box having following
4.17 capacity Each 803.00 4.00
(c) 63 Amp. (cat III)
Providing & erecting 415 V MCB three Pole for Motor & Inductive Load having 10KA breaking capacity & confirms to IS :8828 in existing box having following
4.18 capacity Each 641.00 14.00
(a) 6 to 32 Amp. (Cat.III)
Providing & erecting 415 V MCB three Pole for Motor & Inductive Load having 10KA breaking capacity & confirms to IS :8828 in existing box having following
4.19 capacity Each 706.00 1.00
(b)40 Amp.(Cat.III)
Providing & erecting 415 V MCB three Pole for Motor & Inductive Load having 10KA breaking capacity & confirms to IS :8828 in existing box having following
4.20 capacity Each 780.00 1.00
(C)63 Amp. (Cat.III)
Providing and erecting Approved make RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and suitable
for operation on single phase 240 V,50Hz. having characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component. for
4.21 following Max. rating erected as directed Each 2,145.00 93.00
(i) 25 Amps.DP ( Cat. III)
Providing and erecting Approved make RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and suitable
for operation on single phase 240 V,50Hz. having characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component. for
4.22 following Max. rating erected as directed Each 2,434.00 12.00
(ii) 40Amps. DP ( Cat. III)
Item no. Item Description Unit Rate Total Qty. Amount
Providing and erecting Approved make RCCBs conforming to IS: 12640 and having sensitivity of 30 mA and Short Circuit withstand capacity of 10 KA and suitable
for operation on single phase 240 V,50Hz. having characteristic of quick action & tripping with all advance feature & do not incorporate any electronic component. for
4.23 following Max. rating erected as directed Each 2,891.00 6.00
(iii) 63Amps. DP ( Cat. III)
Supplying & erecting approved make RCCB + MCB (Electro magnetic type only) working on residual current device having 10 KA short circuit breaking capacity
and 30 mAmp. Sensitivity & 30 mili sec. tripping time conforming to IS 12640 test knob facility trip free mechanism operating for rated leakage at nominal ten volt,
complete erected including all materials lugs screws etc. completed.
[a] 6A / 10A / 16A / 20A / 25A 2 pole single phase
Supplying & erecting approved make RCCB + MCB (Electro magnetic type only) working on residual current device having 10 KA short circuit breaking capacity
and 30 mAmp. Sensitivity & 30 mili sec. tripping time conforming to IS 12640 test knob facility trip free mechanism operating for rated leakage at nominal ten volt,
complete erected including all materials lugs screws etc. completed.
[b] 32A / 40A, 2 pole Single Phase
Supplying & erecting approved make RCCB + MCB (Electro magnetic type only) working on residual current device having 10 KA short circuit breaking capacity
and 30 mAmp. Sensitivity & 30 mili sec. tripping time conforming to IS 12640 test knob facility trip free mechanism operating for rated leakage at nominal ten volt,
complete erected including all materials lugs screws etc. completed.
[e] 32A to 40 A, 4 Pole Three Phase
Supplying & erecting approved make RCCB + MCB (Electro magnetic type only) working on residual current device having 10 KA short circuit breaking capacity
and 30 mAmp. Sensitivity & 30 mili sec. tripping time conforming to IS 12640 test knob facility trip free mechanism operating for rated leakage at nominal ten volt,
complete erected including all materials lugs screws etc. completed.
[f] 63A, 4 pole Three Phase
4.28 SITC of Sheet steel metal enclouser for DP MCB Each 175.00 1.00
4.29 SITC of Sheet steel metal enclouser for FP MCB Each 623.00 1.00
SITC of 80-100 A FP MCCB with thermal magnetic release.
4.3 Note:-1 Add Rs. 10% extra for housing/Encloser of MCCB for Item No 3-4-1 to 3-4-12 (The Enclosures should be used of same company of MCCBs to be Each 7,395.30 4.00
SITC of 125A FP MCCB with thermal magnetic release with sheet steel metal enclosure.
4.31 Note:-1 Add Rs. 10% extra for housing/Encloser of MCCB for Item No 3-4-1 to 3-4-12 (The Enclosures should be used of same company of MCCBs to be Each 9,651.40 1.00
SITC of 200A FP MCCB with thermal magnetic release with sheet steel metal enclosure.
4.32 Note:-1 Add Rs. 10% extra for housing/Encloser of MCCB for Item No 3-4-1 to 3-4-12 (The Enclosures should be used of same company of MCCBs to be Each 26,235.50 3.00
used) *Add 35% additional for microprocessor type of mccb in place of conventional for item no.3-4-1 to 3-4-12
SITC of 250A FP MCCB with thermal magnetic release with sheet steel metal enclosure.
4.33 Note:-1 Add Rs. 10% extra for housing/Encloser of MCCB for Item No 3-4-1 to 3-4-12 (The Enclosures should be used of same company of MCCBs to be Each 33,877.31 RO
used) *Add 35% additional for microprocessor type of mccb in place of conventional for item no.3-4-1 to 3-4-12
SITC of 315-400A FP MCCB with thermal magnetic release with sheet steel metal enclosure.
4.34 Note:-1 Add Rs. 10% extra for housing/Encloser of MCCB for Item No 3-4-1 to 3-4-12 (The Enclosures should be used of same company of MCCBs to be Each 30,224.70 2.00
used) *Add 35% additional for microprocessor type of mccb in place of conventional for item no.3-4-1 to 3-4-12
4.35 SITC of IP 65 - outdoor type - 4Way SPN DB Each 1,833.45 1.00
Item no. Item Description Unit Rate Total Qty. Amount
4.36 SITC of IP 65 - outdoor type - 8Way SPN DB Each 2,891.68 1.00
4.37 SITC of Blank Plates Each 9.00 84.00
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal encloused plug top alongwith 20 A "C" curve, SP, MCB, in sheet
4.38 steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. Each 2,024.17 10.00
Sub Total 4.....
5 LT CABLES & CABLE TERMINATION
5.1 UNARMOURED COPPER CABLES.
Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size.
(E) 3 core 2.5 Sq. mm
Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size.
(F) 3 core 4 Sq. mm
Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size.
(G) 3 core 6 Sq. mm
Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size.
(J) 4 core 2.5 Sq. mm
Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size.
(K) 4 core 4 Sq. mm
Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size.
(L) 4 core 6 Sq. mm
Supplying & erecting XLPE(IS:7098)(I)-88 ISI unarmoured copper cable 1.1 KV grade to be erected as directed of following size.
(M) 4 core 10 Sq. mm
5.2 ARMOURED ALUMINIUM CABLES
Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps or in
existing trench / pipe of following size of cables
(A) 4 core 16 Sq. mm
Providing and erecting XLPE (IS:7098)(I)-88 ISI armoured cable multistrand / Solid Aluminium conductor for 1.1 KV. to be laid on wall with necessary clamps
or in existing trench / pipe of following size of cables
(C) 4 core 10 Sq. mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(I) 3 1/2 core 25 Sq. mm( 16 Sq. mm 1/2 core)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(I) 3 1/2 core 35 Sq. mm( 25 Sq. mm 1/2 core)
Item no. Item Description Unit Rate Total Qty. Amount
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(C) 3 1/2 core 50 Sq. mm ( 25 Sq.1/2 mm core)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(D) 3 1/2 core 70 Sq. mm ( 35 Sq. mm 1/2 core)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(E) 3 1/2 core 95 Sq. mm ( 50 Sq. mm 1/2 core)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(F) 3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 core)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(G) 3 1/2 core 150 Sq. mm ( 70 Sq. mm 1/2 core)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(H) 3 1/2 core 185 Sq. mm ( 95 Sq. mm 1/2 core)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(I) 3 1/2 core 240 Sq. mm( 120 Sq. mm 1/2 core)
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Aluminium conductor with water swellable coating which should protect against
saline water & for 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe of following size of cables
(I) 3 1/2 core 300 Sq. mm( 150 Sq. mm 1/2 core)
5.3 ARMOURED COPPER CABLES
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor with water swellable coating which should protect against saline
water & 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cable.
(A) 3 core 2.5Sq. Mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor with water swellable coating which should protect against saline
water & 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cable.
(B) 3 core 4 Sq. mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor with water swellable coating which should protect against saline
water & 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cable.
(C) 3 core 6 Sq. mm
Item no. Item Description Unit Rate Total Qty. Amount
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor with water swellable coating which should protect against saline
water & 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cable.
(C) 3 core 10 Sq. mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor with water swellable coating which should protect against saline
water & 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cable..
(A) 4 core 2.5 Sq. mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor with water swellable coating which should protect against saline
water & 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cable.
(B) 4 core 4 Sq. mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor with water swellable coating which should protect against saline
water & 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cable.
(C) 4 core 6 Sq. mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor with water swellable coating which should protect against saline
water & 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cable.
(A) 4 core 10 Sq. mm
Providing and erecting XLPE(IS:7098)(I)-88 ISI armoured cable multistrand Copper conductor with water swellable coating which should protect against saline
water & 1.1 KV. to be laid on wall with necessary clamps or in existing trench / pipe at road crossing or floor of following size of cable.
(B) 4 core 16 Sq. mm
5.4 CABLE GLANDS.
Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable complete with out going tails, insulating tape etc for
following size of cables.
(A) 2 to 4 core 2.5/4 Sq. mm
Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable complete with out going tails, insulating tape etc for
following size of cables.
(B) 2 to 4 core 6 Sq. mm
Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable complete with out going tails, insulating tape etc for
following size of cables.
(C) 2 to 4 core 10 Sq. mm
Providing and, fixing heavy duty flange type brass cable gland with rubber ring for PVC insulated armoured cable complete with out going tails, insulating tape etc for
following size of cables.
(D) 2 to 4 core 16 Sq. mm
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete with out going
tails, insulating tape etc for following size of cables.
(B) 3 & 1/2 core 25Sq. mm
Item no. Item Description Unit Rate Total Qty. Amount
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete with out going
tails, insulating tape etc for following size of cables.
(B) 3 & 1/2 core 35/50 Sq. mm
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete with out going
tails, insulating tape etc for following size of cables.
(C) 3 & 1/2 core 70 Sq. mm
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete with out going
tails, insulating tape etc for following size of cables.
(D) 3 & 1/2 core 95 Sq. mm
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete with out going
tails, insulating tape etc for following size of cables.
(E) 3 & 1/2 core 120 Sq. mm
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete with out going
tails, insulating tape etc for following size of cables.
(F) 3 & 1/2 core 150 Sq. mm
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete with out going
tails, insulating tape etc for following size of cables.
(G) 3 & 1/2 core 185 Sq. mm
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete with out going
tails, insulating tape etc for following size of cables.
(H) 3 & 1/2 core 240 Sq. mm
Providing and, fixing heavy duty flange type brass double compression type cable gland with rubber ring for PVC insulated armoured cable complete with out going
tails, insulating tape etc for following size of cables.
(I) 3 & 1/2 core 300 Sq. mm
5.5 Aluminium lugs
Supply, installation, testing and commissioning of Solder less crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solder less crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Item no. Item Description Unit Rate Total Qty. Amount
Supply, installation, testing and commissioning of Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solderless crimping type Aluminium lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
5.6 Copper lugs
Supply, installation, testing and commissioning of Solder less crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solder less crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Supply, installation, testing and commissioning of Solder less crimping type Copper lugs conforming to IS suitable for cable of following size evenly crimped with
high pressure tool & connected to switchgear terminals with brass/cadmium plated nut bolts in an approved manner.
Sub Total 5.....
Perforated type cable tray
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing approved make Perforated C type cable tray. Made from sheet steel. The cable tray should be single or double bended as per required and
as per IS 2062/1079 and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware
6.1 like nut - bolt and washers etc. erection with necessary support( included) as per Specification and as per instruction of engineer in charge.. Rmt 357.00 12.00
(2) 100 X 50 X 1.6 mm Thick
Providing and fixing approved make Perforated C type cable tray. Made from sheet steel. The cable tray should be single or double bended as per required and
as per IS 2062/1079 and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware
6.2 like nut - bolt and washers etc. erection with necessary support( included) as per Specification and as per instruction of engineer in charge.. Rmt 420.00 170.00
(3) 150 X 50 X 1.6 mm Thick
Providing and fixing approved make Perforated C type cable tray. Made from sheet steel. The cable tray should be single or double bended as per required and
as per IS 2062/1079 and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware
6.3 like nut - bolt and washers etc. erection with necessary support( included) as per Specification and as per instruction of engineer in charge. Rmt 616.00 10.00
(5) 300 X 50 X 2.0 mm Thick
Providing and fixing approved make 'T' Junction for Perforated C type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079
and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware like nut - bolt and
6.4 washers etc. erected on existing support as per Specification and as per instruction of engineer in charge of following size Ea. 158.00 3.00
(2) 100 X 50 X 1.6 mm Thick
Providing and fixing approved make 'T' Junction for Perforated C type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079
and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware like nut - bolt and
6.5 washers etc. erected on existing support as per Specification and as per instruction of engineer in charge of following size Ea. 183.00 11.00
(3) 150 X 50 X 1.6 mm Thick ' T' Junction
Providing and fixing approved make 'T' Junction for Perforated C type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079
and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware like nut - bolt and
6.6 washers etc. erected on existing support as per Specification and as per instruction of engineer in charge of following size Ea. 289.00 2.00
(5) 300 X 50 X 2.0 mm Thick ' T' Junction
Providing and fixing approved make '90° Elbow' for Perforated C type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079 and
shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing
6.7 support as per Specification and as per instruction of engineer in charge.. Ea. 115.00 5.00
(2)100 X 50 X 1.6 mm Thick 90° Elbow
Providing and fixing approved make '90° Elbow' for Perforated C type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079 and
shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing
6.8 support as per Specification and as per instruction of engineer in charge.. Ea. 162.00 18.00
(3)150 X 50 X 1.6 mm Thick 90° Elbow
Providing and fixing approved make '90° Elbow' for Perforated C type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079 and
shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing
6.9 support as per Specification and as per instruction of engineer in charge.. Ea. 243.00 5.00
(5) 300 X 50 X 2.0 mm Thick 90° Elbow
Providing and fixing approved make 'Cross over Junction' for Perforated C type cable tray. Made from sheet steel. The Junction should be bended as per IS
2062/1079 and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware like nut -
6.10 bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in charge.. Ea. 213.00 2.00
(2) 100 X 50 X 1.6 mm Thick Cross Junction
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing approved make 'Cross over Junction' for Perforated C type cable tray. Made from sheet steel. The Junction should be bended as per IS
2062/1079 and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware like nut -
6.11 bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in charge.. Ea. 242.00 2.00
(3) 150 X 50 X 1.6 mm Thick Cross Junction
Providing and fixing approved make 'Cross over Junction' for Perforated C type cable tray. Made from sheet steel. The Junction should be bended as per IS
2062/1079 and shall be coated with hot dip galvanizing as per IS 2629/4759. with max 17.5% perforation with coupler plate / Fish plate and GI hardware like nut -
6.12 bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in charge.. Ea. 370.00 1.00
(5) 300 X 50 X 2.0mm Thick Cross Junction
Ladder type cable tray
Providing and fixing approved make Ladder type cable tray. Made from M.S sheet. The cable tray should be bended as per IS 2062/1079 shall be fabricated of
double bended channel section longitudinal members with single bended Channel section. Rungs of members welded to the base of the longitudinal members at
250 mm c/c spacing . as per IS and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and
6.13 washers etc. erected on existing support as per Specification and as per instruction of engineer in charge.. Mtr. 518.00 125.00
(8) 150 X 100 X 1.6 mm Thick
Providing and fixing approved make Ladder type cable tray. Made from M.S sheet. The cable tray should be bended as per IS 2062/1079 shall be fabricated of
double bended channel section longitudinal members with single bended Channel section. Rungs of members welded to the base of the longitudinal members at
250 mm c/c spacing . as per IS and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and
6.14 washers etc. erected on existing support as per Specification and as per instruction of engineer in charge.. Mtr. 530.00 30.00
(9) 200 X 100 X 1.6 mm Thick
Providing and fixing approved make Ladder type cable tray. Made from M.S sheet. The cable tray should be bended as per IS 2062/1079 shall be fabricated of
double bended channel section longitudinal members with single bended Channel section. Rungs of members welded to the base of the longitudinal members at
250 mm c/c spacing . as per IS and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and
6.15 washers etc. erected on existing support as per Specification and as per instruction of engineer in charge.. Mtr. 551.00 22.00
(10) 300 X 100 X 2.0 mm Thick
Providing and fixing approved make Ladder type cable tray. Made from M.S sheet. The cable tray should be bended as per IS 2062/1079 shall be fabricated of
double bended channel section longitudinal members with single bended Channel section. Rungs of members welded to the base of the longitudinal members at
6.16 250 mm c/c spacing . as per IS and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and Mtr. 658.00 250.00
washers etc. erected on existing support as per Specification and as per instruction of engineer in charge..
(12) 500 X 100 X 2.0 mm Thick
Providing and fixing approved make Ladder type cable tray. Made from M.S sheet. The cable tray should be bended as per IS 2062/1079 shall be fabricated of
double bended channel section longitudinal members with single bended Channel section. Rungs of members welded to the base of the longitudinal members at
6.17 250 mm c/c spacing . as per IS and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and Mtr. 688.00 55.00
washers etc. erected on existing support as per Specification and as per instruction of engineer in charge..
(13) 600 X 100 X 2.0 mm Thick
Providing and fixing approved make 'T' Junction for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(8) 150 X 100 X 1.5 mm Thick 'T' Junction
Providing and fixing approved make 'T' Junction for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(9) 200 X 100 X 1.5 mm Thick 'T' Junction
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing approved make 'T' Junction for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(10) 300 X 100 X 2.0 mm Thick 'T' Junction
Providing and fixing approved make 'T' Junction for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(12) 500 X 100 X 2.0 mm Thick 'T' Junction
Providing and fixing approved make 'T' Junction for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(13) 600 X 100 X 2.0 mm Thick 'T' Junction
Providing and fixing approved make '90° Elbow' for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(8) 150 X 100 X 1.6 mm Thick
Providing and fixing approved make '90° Elbow' for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(9) 200 X 100 X 2.0 mm Thick
Providing and fixing approved make '90° Elbow' for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(10) 300 X 100 X 2.0 mm Thick
Providing and fixing approved make '90° Elbow' for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(12) 500 X 100 X 2.0 mm Thick
Providing and fixing approved make '90° Elbow' for ladder type cable tray. Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing support as per Specification and as per instruction of engineer in
(13) 600 X 100 X 2.0 mm Thick
Providing and fixing approved make 'Cross over Junction' for ladder type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079
and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing
6.28 support as per Specification and as per instruction of engineer in charge.. Ea. 729.00 1.00
(8) 150 X 100 X 1.6 mm Thick
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing approved make 'Cross over Junction' for ladder type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079
and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing
6.29 support as per Specification and as per instruction of engineer in charge.. Ea. 759.00 2.00
(9) 200 X 100 X 2.0 mm Thick
Providing and fixing approved make 'Cross over Junction' for ladder type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079
and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing
6.30 support as per Specification and as per instruction of engineer in charge.. Ea. 823.00 1.00
(10) 300 X 100 X 2.0 mm Thick
Providing and fixing approved make 'Cross over Junction' for ladder type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079
and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing
6.31 support as per Specification and as per instruction of engineer in charge.. Ea. 1,069.00 1.00
(12) 500 X 100 X 2.0 mm Thick
Providing and fixing approved make 'Cross over Junction' for ladder type cable tray. Made from sheet steel. The Junction should be bended as per IS 2062/1079
and shall be coated with hot dip galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc. erected on existing
6.32 support as per Specification and as per instruction of engineer in charge.. Ea. 1,174.00 1.00
(13) 600 X 100 X 2.0 mm Thick
Supplying , fabricating and installation of various sizes clamps for cable tray supports using available M.S. sections & rod as per drawings or instructions of engineer
in charge or consultant including applying zinc chromate yellow oxide and two to three coats of required enamel paints with anchor fasteners etc.
Sub Total 6.....
7 INTERNAL WIRING
Point wiring for Tissino / Modular secondary light point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade ZHFR/
HRFR PVC insulated multi strand copper wires, in below type of pipe to be erected complete with earth continuity and necessary connection with primary light with
accessories erected on Metal / PVC / wooden box covered with 3 mm thick PC(Polycarbonate) / Acrylic sheet for open / concealed wiring. with necessary Lamp
7.1 holder / ceiling rose / H.D.Connector as directed. Pt. 208.95 1,450.00
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete
NOTE:1. For use of ZHFR/HRFR Copper wires in place of FRLS PVC wires add 5% in Item of Point wiring Item No 1-1-1 to 1-2-6 & 1-5-1 & 1-5-2.
Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade ZHFR/ HRFR PVC insulated multi
strand copper wires up to 10 mtr length , in below type of pipe erected with 6A Modular type switch / bell push & accessories and earth continuity of following type,
erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front plate modules erected on / in wall / ceiling as per pipe
7.2 erected, with necessary Lamp holder/ceiling rose / H.D.Connector as directed. Pt. 605.85 900.00
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete(cat lll)
NOTE:1. For use of ZHFR/HRFR Copper wires in place of FRLS PVC wires add 5% in Item of Point wiring Item No 1-1-1 to 1-2-6 & 1-5-1 & 1-5-2.
Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of .ISI marked 1.1 KV Grade ZHFR/ HRFR PVC insulated multi strand
copper wires up to 10 mtr length, in below type of pipe erected with 6A Modular type switch and hum free EME step type electronic fan regulator mounted and
accessories with earth continuity of following type erected on PVC / Metallic/Wooden box, single mounting base frame covered with textured/metallic/white front
7.3 plate modules erected on / in wall / ceiling as per pipe erected. with necessary ceiling rose / H.D.Connector as directed. Pt. 841.05 380.00
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete(cat III)
NOTE:1. For use of ZHFR/HRFR Copper wires in place of FRLS PVC wires add 5% in Item of Point wiring Item No 1-1-1 to 1-2-6 & 1-5-1 & 1-5-2.
Item no. Item Description Unit Rate Total Qty. Amount
Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade ZHFR/ HRFR PVC insulated multi strand copper
wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with
appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories.
[I] For 6A Plug and 6 a switch with 2-1.5 sq.mm Cu. Wire from nearby switchboard/mcb db board
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete (cat III)
NOTE:1. For use of ZHFR/HRFR Copper wires in place of FRLS PVC wires add 5% in Item of Point wiring Item No 1-1-1 to 1-2-6 & 1-5-1 & 1-5-2.
Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade ZHFR/ HRFR PVC insulated multi strand copper
wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with
appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories.
[II] For 16A Plug and 16 amp switch with 2-2.5 sq.mm Cu. Wire from mcb db board.
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete (cat III)
NOTE:1. For use of ZHFR/HRFR Copper wires in place of FRLS PVC wires add 5% in Item of Point wiring Item No 1-1-1 to 1-2-6 & 1-5-1 & 1-5-2.
Point wiring for Individual Plug with & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade ZHFR/ HRFR PVC insulated multi strand copper
wires up to 10 mtr length, in below type of pipe erected complete with Modular type switch & 5 pin Plug erected on PVC / Metallic/Wooden box covered with
appropriate front plate modules erected on / in wall / ceiling as per pipe erected with following type of accessories.
[III] For 16A Plug and 16 amp switch with 2-4 sq.mm Cu. Wire with 2.5 sq.mm ( green) earthing wire from mcb d b board.
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete (cat III)
NOTE:1. For use of ZHFR/HRFR Copper wires in place of FRLS PVC wires add 5% in Item of Point wiring Item No 1-1-1 to 1-2-6 & 1-5-1 & 1-5-2.
Point wiring for on board Looped Plug with 6A Modular type switch & 5 pin socket erected on PVC / Metallic/Wooden box, single mounting base frame covered with
textured / metallic/white front plate modules erected on / in wall / ceiling with following type accessories
NOTE:1. For use of ZHFR/HRFR Copper wires in place of FRLS PVC wires add 5% in Item of Point wiring Item No 1-1-1 to 1-2-6 & 1-5-1 & 1-5-2.
Point wiring for Two Way Controlled Light Point with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (green) both are of .ISI marked 1.1 KV grade ZHFR/ HRFR
PVC insulated multi strand copper wires erected in below type of pipe with 6A Modular type switches and following type of accessories erected on PVC /
Metallic/Wooden box, single mounting base frame covered with textured / metallic/white front plate modules erected on / in wall / ceiling as per pipe erected. with
7.8 necessary batten/angle holder or ceiling rose or H.D.Connector as directed. Pt. 753.90 120.00
(f) with medium class Rigid PVC pipe and accessories erected concealed in wall/ceiling complete(cat III)
NOTE:1. For use of ZHFR/HRFR Copper wires in place of FRLS PVC wires add 5% in Item of Point wiring Item No 1-1-1 to 1-2-6 & 1-5-1 & 1-5-2.
Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in
/flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size
7.9 (A) With medium class Rigid PVC pipe and accessories Rmt. 78.00 1,050.00
(a) 2 wire 1.5 sq. mm
Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected concealed in
/flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size
7.10 (A) With medium class Rigid PVC pipe and accessories Rmt. 103.00 50.00
(b) 2 wire 2.5 sq. mm
providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall /
ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size
7.11 (A) with medium class Rigid PVC pipe and accessories Rmt. 139.00 50.00
(a) 2 wire 4 sq. mm
Item no. Item Description Unit Rate Total Qty. Amount
providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall /
ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size
7.12 (A) with medium class Rigid PVC pipe and accessories Rmt. 183.00 1,240.00
(b) 2 wire 6 sq. mm
providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall /
ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size
7.13 (A) with medium class Rigid PVC pipe and accessories Rmt. 293.00 1,380.00
(c) 2 wire 10 sq. mm
(use earth wire of 4 sq.mm )
providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall /
ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size
7.14 (A) with medium class Rigid PVC pipe and accessories Rmt. 323.00 850.00
(h) 4 wire 6 sq. mm
providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI marked stranded Copper conductor wire in following type of pipe to be erected in / on wall /
ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following size
7.15 (A) with medium class Rigid PVC pipe and accessories Rmt. 527.00 150.00
(i) 4 wire 10 sq. mm
(use earth wire of 4 sq.mm )
Providing & erecting Switch board for Computer or electric apparatus consisting of following modular type accessories mounted with PVC / Metallic
concealed/open box with single mounting base frame covered with textured/metallic /white front plate,modules erected with necessary connections as directed
1 no. 6A/16A universal plug-switch combined.
7.16 3 nos. 6A Switch Pt. 1,122.00 40.00
3 nos. 6A 5 pin Plug
For Modular Type accessories Cat. III
SITC of following type of Modular Type accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white
7.17 front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. Ea. 395.00 380.00
(5) Electronic hum Free four or more steps EME Fan regulator (cat III)
providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi stranded, annealed copper conductor with heat resistant PVC insulated conforms to IS
694, IEC - 227 erected in existing pipe of following size (Specifically for control panel, relays, power switchgears, motor starters & control wiring) with required size of
7.18 copper lugs, nuts and bolts if required. Mtr. 373.00 100.00
(i) One wire 35.00 sq. mm
Providing following type of Modular Type Accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white
7.19 front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. Ea. 159.00 200.00
(4) TV Co-axial Socket outlet
SITC of following type of Modular Type accessories mounted with PVC / metallic/Wooden box, single mounting base frame covered with textured / metallic/white
7.20 front plate , modules erected with necessary connections as per site situation directed by Engineer In charge. Ea. 25.00 25.00
(7) Blank Plate Single (cat III)
Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to be erected on/in wall or ceiling erected with necessary PVC fittings &
Junction boxes fixed with adhesive solution & Clamps with following dia of pipes, in approved manner as directed
Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to be erected on/in wall or ceiling erected with necessary PVC fittings &
Junction boxes fixed with adhesive solution & Clamps with following dia of pipes, in approved manner as directed
Item no. Item Description Unit Rate Total Qty. Amount
Providing and erecting ISI mark Medium class RIGID PVC PIPES of following size complete to be erected on/in wall or ceiling erected with necessary PVC fittings &
Junction boxes fixed with adhesive solution & Clamps with following dia of pipes, in approved manner as directed
Batten Holder/Angle Holder with modular frame with metal ring.
Sub Total 7.....
8 INDOOR LIGHT FIXURE
Supply, Installation Testing and Commissioning of 20W CEILING/WALL MOUNTED TUBE LIGHT POINT
8.1 (A) Tube Light with integral driver Each 293.00 15.00
(iii) 18-20 Watts, Surge - 2KV,IP-20, conventional 4 feet
Supply, Installation Testing and Commissioning of 36W CEILING/WALL MOUNTED TUBE LIGHT POINT
8.2 (A) Tube Light with integral driver Each 530.00 100.00
(v) 36-40 Watts, Surge-2 KV, IP-20, conventional 4 feet
Supply, Installation Testing and Commissioning of 10W WALL MOUNTED MIRROR LIGHT POINT
(H) Mirror Light 9 Watts, wall mounted minimum 1 feet long
Supply, Installation Testing and Commissioning of 24W CEILING SURFACE MOUNTED LIGHT POINT
8.4 (A) Square/ Circular shaped Surface/Recessed Mount Downlight with provision for spring loaded mounting clips complete.IP20 Each 751.00 970.00
(iv) 22-24 watts, Surge-2 KV
Supply, Installation Testing and Commissioning of 24W CEILING RECESSED MOUNTED LIGHT POINT
8.5 (A) Square/ Circular shaped Surface/Recessed Mount Downlight with provision for spring loaded mounting clips complete.IP20 Each 751.00 185.00
(iv) 22-24 watts, Surge-2 KV
Supply, Installation Testing and Commissioning of 18W CEILING SURFACE MOUNTED LIGHT POINT
8.6 (A) Square/ Circular shaped Surface/Recessed Mount Downlight with provision for spring loaded mounting clips complete.IP20 Each 584.00 250.00
(iii) 16-20 watts, Surge-2 KV
Supply, Installation Testing and Commissioning of 18W CEILING RECESSED MOUNTED LIGHT POINT
8.7 (A) Square/ Circular shaped Surface/Recessed Mount Downlight with provision for spring loaded mounting clips complete.IP20 Each 584.00 25.00
(iii) 16-20 watts, Surge-2 KV
Supply, Installation Testing and Commissioning of 10W CEILING SURFACE MOUNTED LIGHT POINT
8.8 (A) Square/ Circular shaped Surface/Recessed Mount Downlight with provision for spring loaded mounting clips complete.IP20 Each 423.00 25.00
(ii) 11-15 watts, Surge-2 KV
Supply, Installation Testing and Commissioning of 10W CEILING RECESSED MOUNTED LIGHT POINT
8.9 (A) Square/ Circular shaped Surface/Recessed Mount Downlight with provision for spring loaded mounting clips complete.IP20 Each 423.00 30.00
(ii) 11-15 watts, Surge-2 KV
Supply, Installation Testing and Commissioning of Flood Light:
8.10 (B) Flood Light (IP-65), Surge protection -4KV integral and ,Light must have 440VAC line supply with over-voltage protection. Each 8,120.00 16.00
(vi) above 160 to 200 watts
Providing & erecting Approved make Power Saving 50 Watt Ceiling Fan with double ball bearing ISI mark with Condenser 230 volt A.C. 50 Hz 1200 mm sweep
8.11 complete having 3blades with aluminium blades with , canopy & 30 cm. down rod erected with earthing.(Make shall be approved by Engineer in charge)) Each 1,929.00 380.00
Supplying & erecting of approved make low noise decorative exhaust fan having size 250mm with 1350 RPM with square frame.ABS body with inbuilt lowers &
8.13 Supplying & erecting of suitable M.S. louver shutter of the Exhaust fan. Each 365.00 305.00
Item no. Item Description Unit Rate Total Qty. Amount
Wall bracket fan:
Supplying and erecting approved make oscillating type bracket fan A.C. 23OV. 50cy/s 400/450 mm sweep wall mounted with height adjustment and rotary tilting
8.14 device complete with guard, flexible Core plug top complete erected with lead wires as directed. Each 2,509.00 2.00
Sub Total 8.....
9.1 SITC of required size HOT deep Galvanised iron strip for earthing of H.T. , OCB/ ACB/ Transformer LT panel board, Motors etc. using proper clamp. Kg. 77.00 1,162.00
9.2 SITC of required size Copper strip for earthing of H.T. OCB / ACB/ Transformer, LT panel board, Motors etc. using copper clamp. Kg. 787.00 150.00
9.3 SITC of Annealed bare Copper wire 8 to 16 SWG. Kg. 787.00 90.00
9.4 SITC of HOT deep Galvanised iron strip wire 8 to 16 SWG. Kg. 77.00 15.00
Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of
corrosion free hot dipped G.I.Pipes having Outer pipe dia of 50mm having 80-200 Micron galvanising, Inner pipe dia of 25 mm having 200-250 Micron galvanising,
connection terminal dia of 12mm with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for following type of
applications with chamber and heavy duty cover. (A)(approved make OEM has to submit test certificate including value of earth resistance of installation duly
stamped and signed by agency and officer Incharge has to ensure the value of earthing resistane mentioned in test Certificate) & having back filling compound of (B)
Inner chemical (CCM Compound)- Resistivity:- 0.2 ohm / meter testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no load & dry form, Sulphar content:-
9.5 <2%(C) Back fill Compound :- Earthing compound should be capable to retain moisture for long time Necessary test report must be submitted by Agency. Each 8,551.00 60.00
(c) For Electrical Installation covering Transformer Neutrals, Lightning arrester Earthing, A.C.Plant & Sensitive Computer System(like Automation, SCADA) i.e
independent Earthing in normal soil.
Length of Pipe : 3.00 mtrs
Back filling Compound :2 nos Bags of 25 Kg.
Sub Total 9......
Supplying and erecting approved make online Un-interruptible Power Supply system comprising flat cum-boost charger with IGBT base rectifier & Inverter &
sealed maintenance free SMF batteries. The charger having operating capacity for input 160-270V AC & inverter having output 230V,50 Hz Ac with 0.8 load power
10.1 factor with battery, over/under voltage output with over load & short circuit protection equipment. The system housed in CRC sheet duly powder coated paint with Each 47,425.00 2.00
following power backup.with MS painted batteries stand, 10% Overload capacity for momentary load.
(B) 2KVA with 1Hr Backup
Supplying and erecting approved make online Un-interruptible Power Supply system comprising flat cum-boost charger with IGBT base rectifier & Inverter &
sealed maintenance free SMF batteries. The charger having operating capacity for input 160-270V AC & inverter having output 230V,50 Hz Ac with 0.8 load power
10.2 factor with battery, over/under voltage output with over load & short circuit protection equipment. The system housed in CRC sheet duly powder coated paint with Each 1,28,815.00 1.00
following power backup.with MS painted batteries stand, 10% Overload capacity for momentary load.
(D) 5KVA with 1Hr Backup
Supplying and erecting approved make online Un-interruptible Power Supply system comprising flat cum-boost charger with IGBT base rectifier & Inverter &
sealed maintenance free SMF batteries. The charger having operating capacity for input 160-270V AC & inverter having output 230V,50 Hz Ac with 0.8 load power
10.3 factor with battery, over/under voltage output with over load & short circuit protection equipment. The system housed in CRC sheet duly powder coated paint with Each 5,75,425.00 1.00
following power backup.with MS painted batteries stand, 10% Overload capacity for momentary load.
(K) 30 KVA 3 - phase with 1Hr Backup
Sub Total 10......
11 SAFETY ITEMS
SITC of metallic vitrified danger notice board as per language suggested by engineer incharge for MEDIUM VOLTAGE installation to be erected as per IS-2551.
11.2 SITC of metallic vitrified danger notice board as per language suggested by engineer incharge for HIGH VOLTAGE installation to be erected as per IS.2551. Ea. 81.00 1.00
SITC of printed instruction chart both in English and Gujarati and duly framed with front glasses, for treatment of person suffering from Electric shock with minimum
50" diagonally size.
11.4 SITC of pair of rubber hand gloves suitable for working on 11 KV supply. Ea. 212.00 1.00
Item no. Item Description Unit Rate Total Qty. Amount
SITC of rubber matting of 3 mm thickness as per IS 15652 and IEC
SITC of stand first AID box with antiseptic cream, medicine for use on wounds due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-
aid) adhesive tape for medicinal user, ScisR&BR&BSORs, anti-septic solution (Savlon or similar) etc. (All above contents shall be of standard makes)
SITC of FIREbucket round bottom of9 litres capacity made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside andRed out side with
FIRE mark,filled with dry-sand and kept on existing stand provided or hung on wall hook.
SITC of floor mounting stand for keeping four nos. of FIRE buckets comprising 1500 mm in length, 900 mmheight frame made out of 30mm X30 mm X 4 mm angle
iron with cross supports for legs, welded with 4 hooks and duly painted with one coat of red lead and two coats of approved enamelled silver paint.
11.9 Wall hook 22 to 25 cms. projection for keeping fire buckets made out of 15 mm dia. M.S rod grouted in wall to a depth of minimum 15 cms. Ea. 60.00 1.00
Supplying & erecting D.C.P. type fire extinguisher for following capacity cartridge type with gun metal cap 150 gram CO2 gas cartridge, powder and brackets
11.10 confirming to IS 2171 1985 and complete erected with necessary clamps made from 50 x 6 mm M S Flat with nuts and bolts grouted in wall complete. Ea. 1,696.00 5.00
[A] For 5 Kg Capacity
Supply and installtion of expanding firestop foam equivalent to Hilti CP 620 on both sides of wall, with minimum 2 hours fire rating when tested in accordance with UL
1479/ASTM-E 814, for horizontal openings in floors or slabs made of concrete/ masonry or Gypsum after passing service lines like cable trays or cables/cable
bundles. The expanding foam expands seven times its volume to fill the cavity at the time of dispensing the material and shall fully cure within two minutes after
dispensing. The product shall be age tested as per Dafstb and DIBT standards. The product shall provide water tightness when tested for W rating as per UL
11.11 standards and shall carry test certificate for sound insualtion of 50 db when tested in accordance with ASTM E 90. The product shall carry test certificate for mold Ea. 10,643.83 5.00
resistance rating of 0 as determined by ASTM G21-96 and shall have a VOC content of approx. 1.3 g/l as per LEED 2009. The product shall be tested in accordance
with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. The system shall
be UL listed & classified. The system shall be UL & FM approved.
Supply and installation of Fire stop mortar system equivalent to Hilti CP 636 , with minimum 2 hours fire rating when tested in accordance with UL 1479/ASTM-E
standards, for horizontal openings in floors or slabs after passing service lines like cables/cable bundles, cable trays etc. The mortar shall be a light weight
cementitious product and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-
11.12 history method and VERTEQII for seismic zone 4. The product shall be age tested as per Dafstb and DIBT standards. The product shall carry test certificate for mold Sq. mtr 13,043.30 10.00
resistance rating of 0 as determined by ASTM G21-96. The product shall be age tested as per Dafstb and DIBT standards.The system shall be UL listed. The gaps
around inaccessible or complicated openings shall be sealed with exapnding firestop foam.
Sub Total 11.....
12 EXTERNAL LIGHT FIXTURE AND POLE
PLANT UPLIGHTER
SITC of Plant Uplighter:
System Wattage : 12W LED,Driver Integral : Constant Current,Operating Voltage : 100-300Vac,Operating Temperature : -15°C~+50°C,Body : Die-cast Aluminium
12.1 Alloy,Diffuser : Clear Toughened Glass,Mounting : Spike / Die-castAluminium BracketFinish : Powder coated.Light Source : CITIZEN.CRI (Ra) : ≥80.LED Colour Each 3,445.40 10.00
Temperature : 3000K.Driver Power Supply : Integral.Input Voltage : 230-240Vac.Frequency : 50-60 Hz.Power Factor : >0.95.
THD : <10%.Surge Protection : 4KV.Efficiency : >80%.Beam Angle : 25°.IP66
Item no. Item Description Unit Rate Total Qty. Amount
Supply of approved make frp/grp pole having followiing specifications :
FRP/GRP pole made by centrifugal moulding process using thermoset resin polyester/epoxy resin system having minimum glass content 45.0%.The pole should be
in one pieceand tapered round in shape,having smooth outside surface finish and should be totally fre from corrosion as well as non conductive and shock proof.
Pole should be provided with FRP/GRP base bracket dully fabricated from metal(M.S) and dully claded with FRP/GRP material to avoid any metal exposer and
painted with PU paint.Pole should mechanical properties i.e 1. Specfic gravity (ASTM D 792) 1.3‐1.8 Kg/m3, 2. Glass Content % by weight (ASTM D 2584)
‐55.0%, 3. Water absorption (ASTM D 570)
<0.5%, 4. Tensile Strength(ASTM D 638) 200+/‐50Mpa, 5. Flexural strength (ASTM D 790) 250+/‐50Mpa, 6. Compressive Strength (ASTM D 695) 200+/‐50MPa,
Yeild Strength(ASTM D638) 250 +/‐50MPa.Pole should be flame retardant as per IS 6746.Resin used shall be UV resistance and pigmented. Pole should be painted
with first coat of epoxy primer and then two coat of highly weather resistance polyurethen paint to ensure proper addhesion of the paint.Minimum thickness shall be
12.2 80 to 100 micron.Defelection of the pole shall not exceed more than 10.0 % of the length of the pole for the given load.Pole should be generally made as per the Each 9,932.00 20.00
dimensional data,performance criteria and some interchagebility features of poles as per the standard ANSI C123.20 latest version of ASTM D 923/01 including cable
termination box with necessory accessories.The size of pole and type of installation with foundation , Anchor Base & Internal junction box as per the manufacturer
details and site requirement .
(1) 'A' class frp/grp pole suitable for base plate mounting
[B] Overall Length of 4.0 meter, Average thickness : 4mm, Top/Bottom Outside Dia. 76/143mm +/ ‐ 2.Weight of Pole 10.0 Kg approx. (Without base) Metal Anchor
Base dully frp claded (Size : 290 Ø * 12mmthk , Mounting hole PCD 240mm * 4 nos. of 16 Ø hole)
(Color of pole shall be as per architeture intent)
Supply of approved make frp/grp pole having followiing specifications :
FRP/GRP pole made by centrifugal moulding process using thermoset resin polyester/epoxy resin system having minimum glass content 45.0%.The pole should be
in one pieceand tapered round in shape,having smooth outside surface finish and should be totally fre from corrosion as well as non conductive and shock proof.
Pole should be provided with FRP/GRP base bracket dully fabricated from metal(M.S) and dully claded with FRP/GRP material to avoid any metal exposer and
painted with PU paint.Pole should mechanical properties i.e 1. Specfic gravity (ASTM D 792) 1.3‐1.8 Kg/m3, 2. Glass Content % by weight (ASTM D 2584)
‐55.0%, 3. Water absorption (ASTM D 570)
<0.5%, 4. Tensile Strength(ASTM D 638) 200+/‐50Mpa, 5. Flexural strength (ASTM D 790) 250+/‐50Mpa, 6. Compressive Strength (ASTM D 695) 200+/‐50MPa,
Yeild Strength(ASTM D638) 250 +/‐50MPa.Pole should be flame retardant as per IS 6746.Resin used shall be UV resistance and pigmented. Pole should be painted
with first coat of epoxy primer and then two coat of highly weather resistance polyurethen paint to ensure proper addhesion of the paint.Minimum thickness shall be
12.3 80 to 100 micron.Defelection of the pole shall not exceed more than 10.0 % of the length of the pole for the given load.Pole should be generally made as per the Each 15,488.00 5.00
dimensional data,performance criteria and some interchagebility features of poles as per the standard ANSI C123.20 latest version of ASTM D 923/01 including cable
termination box with necessory accessories.The size of pole and type of installation with foundation , Anchor Base & Internal junction box as per the manufacturer
details and site requirement .
(1) 'A' class frp/grp pole suitable for base plate mounting
[D]Overall Length of 6.0 meter, Average thickness : 5mm, Top/Bottom Outside Dia. 76/176mm +/ ‐ 2.Weight of Pole 19.0 Kg approx. (Without base) Metal Anchor
Base dully frp claded (Size : 340 Ø * 12mmthk , Mounting hole PCD 285mm * 6 nos. of 20 Ø hole)
(Color of pole shall be as per architeture intent)
Providing 1:2:4 cement concrete foundation & 70 % PCC from bottom including excavation for the pole of size 45 x 45 x 100 cm. Deep in below ground level with
12.4 plinth of 45 cm x 45 cm (or 45 cm dia x 45 cm) high upper ground level with necessary curing and finishing in approved manner. Each 801.00 25.00
( for 4 & 6 mtr pole)
Supply, Installation Testing and Commissioning of Street Light:
Supplying and erecting LED street light / Flood light fittings with High power White LEDs wattage of 3 Watt and above assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses, with toughened glass with company mark/name engraved or embossed 160 to 270 V,Power Factor more than 0.95, THD < 10 %, CCT
3000 K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency > 85 %.( fittings required LM-79 & LM-80 certificates)(NOTE:
12.5 Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) Each 2,815.00 20.00
(A) Street Light (IP-65), Surge protection -4KV integral and ,Light must have 440VAC line supply with over-voltage.
(i) above 36 to 48 watts
Note: All lighting fixture colour to be matched with architecture finishes.
Item no. Item Description Unit Rate Total Qty. Amount
Supply, Installation Testing and Commissioning of Street Light:
Supplying and erecting LED street light / Flood light fittings with High power White LEDs wattage of 3 Watt and above assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth finish powder coated and heat sink extruded aluminium with diffuser and
Polycarbonate optics/ lenses, with toughened glass with company mark/name engraved or embossed 160 to 270 V,Power Factor more than 0.95, THD < 10 %, CCT
3000 K to 5700K,Uniformity ratio >0.45, Luminaire efficacy> 100 lumens/watt . LED driver efficiency > 85 %.( fittings required LM-79 & LM-80 certificates)(NOTE:
12.6 Below description have shown ranges of Wattage capacity of LED fittings.The Engineer incharge may select any wattage capacity between the ranges shown.) Each 4,206.00 5.00
(A) Street Light (IP-65), Surge protection -4KV integral and ,Light must have 440VAC line supply with over-voltage.
(ii) above 48 to 60 Watts
Note: All lighting fixture colour to be matched with architecture finishes.
Providing and fixing Terminal board of size 5.0 x 127 x 152.4 mm.bakelite sheet with suitable brass studs with nuts, washers and clamps of size 25mm x 3mm
suitable for pole painted with one coat of red lead paint.
Supplying and erecting Water tight M.S.Box of size 20 x 15 x 15 cm. to erect suitable kitkat fuse / MCB to be . erected on polished wooden board inside the box
12.8 with hinged/sliding door with rubber rings and erected on pole with suitable pole clamp, all duly painted with one coat of red oxide and two coats of paints. (Cost of Nos. 232.00 1.00
Fuse / MCB shall be taken extra)
Providing & erecting approved make street light / wall mounting junction box compression moulded from SMC (thermoset plastic) vertical sliding cover
having locking with square head stud loop in / loop out in built terminal suitable for four core cable, waterproof of I.P. 54 protected with clamp or bolt nut & earth bolt
12.9 of following size Each 610.00 25.00
Providing FRP/GRP arm bracket of having 15˚ arm with 50 mm OD pipe *5 mm thk,1000mm long from pole centre
(A) Single arm bracket
Providing FRP/GRP arm bracket of having 15˚ arm with 50 mm OD pipe *5 mm thk,1000mm long from pole centre
(B) Double arm bracket
Supplying and erecting B class Galvanized iron pipe having smooth finished bore of the pipe on both ends erected nuts and bolts along the pole / wall shaping the
12.12 pipe as per site requirement. Pipe dia as following. Rmt 247.00 50.00
12.13 Painting of street light pole having post top lantern complete with primer with two coats of Aluminium paint. Nos. 213.00 RO
Painting of street light pole with bracket complete with two coats of Aluminium paint for following size of pole.
(A) up to 4 mtr
Painting of street light pole with bracket complete with two coats of Aluminium paint for following size of pole.
(B) up to 6 mtr.
SITC of Step Light:
System Wattage : 12W LED,Driver Integral : Constant Current,Operating Voltage : 100-277Vac,Operating Temperature : -15°C~+50°C,Body : Die-Cast
12.16 Aluminium,Diffuser : Clear Acrylic,Gasket : Silicone,Mounting Sleeve : ABS Plastic,Mounting : Wall - Recess,Finish : Powder coated,Light Source : NICHIA,CRI (Ra) Nos. 1,611.96 20.00
: ≥80,LED Colour Temperature : 3000K,Driver Power Supply : Integral,Input Voltage : 230-240Vac,Frequency : 50-60 Hz,Power Factor : ≥0.90,THD : <10%,Surge
Protection : 2KV / 2.5KV,Efficiency : >85%,IP65
Sub Total 12.....
13 DWC PIPE AND CHAMBER
SITC of R.C.C. Hume pipe for cable to be laid 90 cm. below ground across the road crossing or on floor with necessary material in an approved manner and making
the ground as per original.
SITC of R.C.C. Hume pipe for cable to be laid 90 cms. below ground across the road crossing or on floor with necessary material in an approved manner and making
the ground as per original.
Item no. Item Description Unit Rate Total Qty. Amount
SITC of approved make Double walled corrugated pipes (DWC) of polyethylene(conforming to IS 14930 II )with necessary connecting accessories of same material
at required depth in existing trench for laying of cable. below ground / road surface for enclosing cable.
(A)50 mm outer dia
SITC of approved make Double walled corrugated pipes (DWC) of polyethylene(conforming to IS 14930 II )with necessary connecting accessories of same material
at required depth in existing trench for laying of cable. below ground / road surface for enclosing cable.
(B)63mm outer dia
SITC of approved make Double walled corrugated pipes (DWC) of polyethylene(conforming to IS 14930 II )with necessary connecting accessories of same material
at required depth in existing trench for laying of cable. below ground / road surface for enclosing cable.
(D)120 mm outer dia
Excavating hard Murrum or Metal road by chiselling for preparing pit for poles or earth plates or for laying pipes & clearing the site by removing debris & making site
Sub Total 13.....
SITC of Vertical Air Termination Solid aluminium with Base- 10 mm dia and 1000 mm long. Air Termination Base tested for conditioning, Ageing Test & Lightning
14.1 impulse current withstand test: 100 kA of 10/350µs waveform in an accredited Third party laboratory as per 6.3 & 6.4 of IEC 62561-1 2017 protocol with MAST 34mm Nos. 9,323.00 7.00
dia 3000 mm long- Cold Galvanized
SITC of 16mm Dia Aluminium Air termination 3000mm Long with 2 nos SS Clamp Suitable for side mounting on wall;Universal cross and T Connector -SS -for 8mm
and 16mm dia conductor
SITC of 8 mm dia solid Aluminium Conductor for roof top mesh grid and tested as per IEC 62561- 2 conducted in the Govt. accredited thirty party laboratory to
meet the requirement of IS/IEC 62305 with Required Accessories - Aluminium Holding clamp at every 1 mtr distance, Aluminium/SS cross splicer at every crossing of
Alu. conductor, Expansion piece with connectors at every 20 mtr distance, Aluminium straight Splicer to connect conductors. All Accessories should be tested as per
14.3 IEC 62561-1 2018 Cl. 6.3 for conditioning & Ageing Test & 6.4 for Lightning impulse current withstand test: 100 kA of 10/350µs waveform(Ageing & Electrical test ) Meter 297.00 515.00
conducted in a sequence manner & tested in the Govt. accredited Third party laboratory to meet the requirements of IS/IEC
SITC of 10 mm MS Round Solid Conductor having smooth surface Should be tested and use exclusively for lightning protection (Vertical Riser/Down Conductor
which shall be concealed in Column) to meet the requirement of IS IEC 62305 With Accessories - Earthing stud of dimension SS-75mm OD plate with 10mm dia tail
connector used in structural steel ring earthing system to meet the requirements of IS/IEC 62305. (For Interconnecting the Column and the Terrace AL Conductor /
Strip/Flat), SS Cross Connector to connect Earth fixing point to vertical raiser/Down conductor, SS Straight Splicer at every 4 Mtr to connect MS conductor in column,
14.4 Bonding /Rebar Clamp at every 3 mtr suitable for interconnecting round conductor with reinforcement inside the concrete for structural earthing system, SS connector Meter 721.00 595.00
-To connect external conductor 8- 10 mm with earth fixing point. All Accessories should be tested as per IEC 62561-1 2018 Cl. 6.3 for conditioning & Ageing Test &
6.4 for Lightning impulse current withstand test: 100 kA of 10/350µs waveform(Ageing & Electrical test )
conducted in a sequence manner & tested in the Govt. accredited Third party laboratory to meet the requirements of IS/IEC
SITC of Galvanized Steel Flat 25x6 mm thickness from earth electrode directly in ground as required. Zinc coating: 500 g/m square (Approx:70 micron coating)
tested and used exclusively for lightning protection earthing system and ring equipotential bonding.
SITC of 14.2 mm dia 3 mtr long Earth electrode of High tensile steel electrode with 250 micron copper bonding & 1 bag of Carbon fill Based environment friendly
14.6 backfill tested as per IEC 62561-7 in NABL accredited Laboratory and suitable stainless Steel double sided clamp. Eco Friendly rust proof heavy duty weather proof set 5,933.00 14.00
Polyethylene Earth Pit Chamber with following dimensions :254 mm dia (top), 330 mm dia (bottom) & 260 mm (height).
Sub Total 14.....
15 SERVICE WORK
Liasoning work for power supply procurement (New Service/Load Ext./reduction/Shifting) with Site Visit, Test Report Submission, Meter Connection in
T.P.L/U.G.V.C.L. and Also all necessary work as per site as and when require.
15.1 Single site more than 10 No. of Service Connection. Per Service 1,500.00 88.00
15.2 Liasoning Work of HIgh Rise NOC Job 25,000.00 1.00
Sub Total 15.....
Item no. Item Description Unit Rate Total Qty. Amount
16 RACEWAY/TRUNKING & JUNCTION BOX
Supplying under floor pregalvanised corrosion proof rectangular sheet steel cable trunking of 1.6 mm thick having with stand point load up to 1.33 Ton & free from
seepage of concrete of screed water with all accessories,Junction Box,Joints as required and demanded by engineer-incharge and laying/erecting as per OEM
guidelines and as per instruction of engineer incharge having following size of dimensions and No of compartments (W x D x T) Cat-III
[1] 50mm x 25mm x 1.6 mm with One Compartment
Supplying under floor pregalvanised corrosion proof rectangular sheet steel cable trunking of 1.6 mm thick having with stand point load up to 1.33 Ton & free from
seepage of concrete of screed water with all accessories,Junction Box,Joints as required and demanded by engineer-incharge and laying/erecting as per OEM
guidelines and as per instruction of engineer incharge having following size of dimensions and No of compartments (W x D x T) Cat-III
[3] 100mm x 25mm x 1.6 mm with one compartment
Supplying under floor pregalvanised corrosion proof rectangular sheet steel cable trunking of 1.6 mm thick having with stand point load up to 1.33 Ton & free from
seepage of concrete of screed water with all accessories,Junction Box,Joints as required and demanded by engineer-incharge and laying/erecting as per OEM
guidelines and as per instruction of engineer incharge having following size of dimensions and No of compartments (W x D x T) Cat-III
[4] 225mm x 25mm x 1.6 mm with Three Compartment
Supply, installation, testing and commissioning of following sizes of Floor junction boxes having Back Box made from hot-dip pre-galvanized 275 GSM zinc coated
steel sheet having specification as per IS277:2003 with base box thickness not less than 1mm. Back Box formation should be done by assembling sheared and bent
modular parts. Lid of the junction box should be made from 2.5mm thick, epoxy coated steel sheet. Lid formation should be done by shearing, bending, and welding
steel sheet to form 8mm recess to accommodate floor tile, stone, or carpet. Trap cover screws should be made from stainless steel for extra protection. Height
16.4 adjustable support pillars should be made from high pressure die cast aluminum and provided with adjustable height from 55mm to 70mm. Modular side wall of the Ea. 1,923.27 5.00
box should be provided with knockout suitable to accommodate raceway of 25mm and 38 mm height. The junction box should be having IP rating of 20 with
temperature handling capacity of -5˚ c to 60˚ c. The junction box should be able to bear load up-to 2.5 Ton/m2 as per IEC 61084-1:2017 & 61084-2-2:2017
standards. Earth wire connector should be provided in all the boxes. Throwaway lid should be provided free of cost to protect from water seepage during
cementing/screeding process at site. Size - 150x150x55-70mm
Supply, installation, testing and commissioning of following sizes of Cross over junction boxes having Back Box made from hot-dip pre-galvanized 275 GSM zinc
coated steel sheet having specification as per IS277:2003 with base box thickness not less than 1mm. Back Box formation should be done by assembling sheared
and bent modular parts. Lid of the junction box should be made from 2.5mm thick, epoxy coated steel sheet. Lid formation should be done by shearing, bending, and
welding steel sheet to form 8mm recess to accommodate floor tile, stone, or carpet. Trap cover screws should be made from stainless steel for extra protection.
Height adjustable support pillars should be made from high pressure die cast aluminum and provided with adjustable height from 55mm to 70mm. Modular side wall
of the box should be provided with knockout suitable to accommodate raceway of 25mm and 38 mm height. The junction box should be having IP rating of 20 with
temperature handling capacity of -5˚ c to 60˚ c. The junction box should be able to bear load up-to 2.5 Ton/m2 as per IEC 61084-1:2017 & 61084-2-2:2017
standards. Crossover junction box with epoxy powder coated flyover should be available to make crossover of all sizes required in BOQ and facilitate segregation
and 90° crossing between data and power wherever desired. Earth wire connector should be provided in all the boxes. Throwaway lid should be provided free of cost
to protect from water seepage during cementing/ screeding process at site. Size - 250x250x55-70mm
Supplying , fabricating and installation of various sizes junction boxes made out to 14 gauge sheet with all necessary accessories & hardware etc All the necessary
16.6 fabrication required will be included in the scope of contractor. Scope also includes two coat of primer and two coat of paining of each items on all the sides complete Kg 179.00 2.00
in all respect.
Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride rigid material with ignition free and flame proof confirming BS with
necessary end caps Internal and external bend, flat bends, coupler, tee etc..All necessary accessories and measuring of following sizes
(4)100 mm x 50 mm trunking with TWIN compartment With clip in divider
Item no. Item Description Unit Rate Total Qty. Amount
Supplying and laying UPVC cable trunking system comprising unplasticised polyvinyl, chloride rigid material with ignition free and flame proof confirming BS with
necessary end caps Internal and external bend, flat bends, coupler, tee etc..All necessary accessories and measuring of following sizes
(3) 50 mm x 50 mm trunking
Providing & Erecting eight module pop up floor box/flushed with table surface Conform to IEC 60670-1, IEC 60670-23 & IEC 60884-1 with required items as
demanded by engineer in charge with complete finishing .cat-III
Supply & installation of modular type accessories for U PVC snap-on adaptable trunking/Pop up Box with required items erected with necessary connection. As
16.10 desired by Engineer In charge Ea. 204.00 1.00
i) 6 A SP 1 Way Switch cat-III
16.11 ii) 16A SP 1 Way Switch cat-III Ea. 351.00 2.00
16.12 iii) Bell Push 6 A SP 1 Way cat-III Ea. 288.00 2.00
16.13 iv) 6A universal socket shuttered cat-III Ea. 347.00 2.00
16.14 iv) 6/16 A universal socket shuttered cat-III Ea. 458.00 1.00
16.15 v) RJ-11 Telephone socket cat-III Ea. 244.00 2.00
16.16 vi) Cat-6 LAN Socket cat-III Ea. 561.00 2.00
Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted black surface/concealed of following size complete to be erected on/in wall or ceiling with
erected with necessary saddles, screws, bends, junction boxes etc. with following (Nominal Bore) dia of pipes, in approved manner as directed
Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted black surface/concealed of following size complete to be erected on/in wall or ceiling with
erected with necessary saddles, screws, bends, junction boxes etc. with following (Nominal Bore) dia of pipes, in approved manner as directed
Providing & erecting 16 gauge HGS conduit pipe (as per IS) painted black surface/concealed of following size complete to be erected on/in wall or ceiling with
erected with necessary saddles, screws, bends, junction boxes etc. with following (Nominal Bore) dia of pipes, in approved manner as directed
Sub Total 16.....
Total Of Electrical Items Amount in Rs.
17 FIRE DETECTION & ALARM SYSTEM
Supply, Installation, Testing and Commissioning of Intelligent Addressable Fire Alarm Control Panel. The Fire Alarm Control panel shall have Built in 6 Loops and
expandable upto 16 loops with each supporting 127 devices of any combination, and 127 analog sounder bases. It shall have UL listed, 4 programmable class B
(style Y) NAC circuits rated 2.5 Amps each, Class B or 2 Class A with internal synchronization. The user shall have a choice of using the panel with 5.25 A (charges
up to 60 Ah) or 10.25 A (charges up to 100 Ah) power supply. The Panel shall have 3 voltage-free programmable inputs and 5 programmable relay outputs 30 V DC
1 Amp, 7 inch full-color resistive touch screen with intuitive user interface, Up to 24 programmable soft “function keys”, Up to 64 user login accounts, Hard-wired fire
17.1 and trouble routing inputs and outputs, Modular and expandable electronics, 400 sub address points per loop (800 per loop module), Option to “invert” inputs and Each 6,38,517.52 1.00
outputs. The panel shall support up to 5000 programmable Cause and Effects entries; over 40,000 inputs and outputs, minimum 10,000 events log @ 1 second
resolultion, 2000 software zones, 5000 software groups, 2 AUX 24V output each rated at 900 mA, Can be networked with programmable functionality, Programming
via USB port to PC or memory stick. The Panel shall have dedicated RS232 serial port for optional printer, UL approved.
Supply, Installation, Testing & Commissioning of Network Vision Annunciator. The Annunciator shall have Full color 7” (800 x 480 pixel) interface, Replicates
17.2 information displayed at the FACP, Automatic display brightness adjustment, Internal buzzer, Connects via control panel network terminals, Low current, 24V DC Each 1,32,524.85 3.00
powered, Configurable functionality, Enable key-switch, Sheet steel enclosure, UL approved
Item no. Item Description Unit Rate Total Qty. Amount
Supply, Installation, Testing and Commissioning of Analog Multi-Criteria Sensor Features, Low profile - only 2" high including base, variable sensitivity from 0.7 to
17.3 4% obs/Ft Simple and reliable device addressing, Automatic compensation for sensor contamination , Built in Fire test feature, Two built-in power/alarm LEDs, Each 5,490.49 176.00
programmable non-polling LEDs, Non-directional Smoke chamber, Vandal resistant security locking feature, Approved by UL and FM
Supply, Installation, Testing and Commissioning of Fixed Temperature/Rate of Rise sensor, Low profile-only 2.00" high, including base, simple and reliable device
addressing method, Rate of rise temperature threshold = 15° F/Min, Adjustable threshold temperature = 135° - 190°, Approved by UL and FM
Supply, Installation, Testing and Commissioning of Multi-Criteria Sensor (Smoke+Heat+CO) Features, Low profile - only 2" high, Simple and reliable device
addressing, Supports 16 operational modes, Automatic compensation for sensor contamination , Built in Fire test feature, Two built-in power/alram LEDs,
17.5 programmable non-polling LEDs, Non-directional Smoke chamber, Vandal resistant security locking feature, 10 years CO sensor life span, Approved by UL and FM Each 14,624.49 110.00
Supply, Installation, Testing and commissioning of sensor common mounting base, includes stainless steel contacts, slim profile - only 8mm, quick
connection via square cable clamps, facility for remote indicator, Approved by UL
17.7 Supply, Installation, Testing and commissioning of sensor common mounting base, Features integral Short-Circuit isolator, slim profile, Approved by UL Each 2,816.61 34.00
Supply, Installation, Testing and Commissioning of Addressable Single Action Manual Pull Station features including Addressable intergrated design, All metal
17.8 construction, Extremely easy to operate, Bi-colored status LED indicates standby and Alarm conditions, Address is programmable in EEPROM, Enclosed switch with Each 8,420.31 50.00
glass rod, Terminals accept up to 14AWG wire, ADA compliant. Approved by UL and FM
Supply, Installation, Testing and Commissioning of low profile Horn/Strobe. The device shall have Nominal voltage 24VDC. The device shall produce 100 dBA @
10ft and has a minimum flash rate of 1Hz regardless of input voltage. The device approved by UL and CSFM
Supply, Installation, Testing and Commissioning of Fast Response Contact Monitoring Module. The Module shall have UL 864 9th Edition Listed, Single Input
17.10 contact monitor, can be programmed to monitor Normally Open (NO) or Normally Closed (NC) contacts, operates on Class A or Class B SLC loop, Accepts up to 12 Each 4,795.26 60.00
AWG wire. Approved by UL and FM
Supply, Installation, Testing and Commissioning of Class A Supervised Output Module. The Module shall have Flexible application, Quick response to emergency
17.11 conditions, Contacts are rated 2.0 Amps@ 24VDC, Programming is highly flexible providing 16 prioriy states plus zoning capability, Approved by UL and FM Each 8,463.38 60.00
17.12 Supply, Laying and Fixing of Red back box for mounting of detector, MCP and module Each 189.50 475.00
17.13 Supply, Laying and Fixing of 2 Core X 1.5 Sq.mm FRLS Multistrand PVC insulated Copper armoured RED cable with all required accessories. Mtr 189.50 5,500.00
Sub Total 17.....
18 PUBLIC ADDRESS SYSTEM
SITC of Controller Public address and emergency sound system control unit
Control and routing of 4 simultaneous audio channels
One controller supports 12 zones, expandable up-to 492 zones with 24-zone routers
18.1 Four controllers can be networked using OMNEO interface module Nos. 2,20,124.00 1.00
EN 54-16 and ISO 7240-16 system certification
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Router Expansion of PAVIRO system by 24 zones
Total 4000 W speaker load, max 500W per zone
20 GPI, 24 GPO and 2 control relays
18.2 Up to 20 routers per controller Nos. 1,88,860.00 1.00
EN 54-16 and ISO 7240-16 system certification
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Power amplifier, 2x500W 2 ✕ 500 W class-D power amplifier (70/100 V output)
Low power consumption in standby mode
18.3 Excellent sound quality, high signal-to-noise ratio Nos. 2,17,686.00 2.00
EN 54-16 and ISO 7240-16 system certification
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
Item no. Item Description Unit Rate Total Qty. Amount
SITC of Call station Call station with soft touch button for PAVIRO system
15 freely programmable buttons
Customization via built-in display and keys
18.4 Provision for installing emergency button and key switch Nos. 78,156.00 1.00
EN 54-16 and ISO 7240-16 system certification
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer
SITC of Call station extension Call station extension keypad with 20 freely programmable buttons
Soft-touch selection buttons
18.5 Up to 5 extension keypads can be connected to one call station Nos. 46,891.00 1.00
EN 54-16 and ISO 7240-16 system certification
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Ceiling loudspeaker 6W, ABS with clamps
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of ABS back box
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Cabinet loudspeaker, 15W, black High-fidelity music and speech reproduction
Selectable 8 ohm, 70 V and 100 V inputs
Compact yet robust ABS enclosure
18.8 Supplied with adjustable mounting bracket Nos. 9,288.00 12.00
Complies with international installation and safety regulations
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
18.9 Supply, Laying and Fixing of 2 Core X 1.5 Sq.mm FRLS Multistrand PVC insulated Copper armoured BLUE/BLACK cable with all required accessories. Mtr. 190.73 2,000.00
Supply, Installation, Testing & Commissioning of 17U (600W X 600D)MM floor rack with PDU, Horizontal Cable manager, self, mounting hardware and cooling fan
18.10 with standard accessories. UL Certified. Racks should be manufactured by ISO9001:2015, ISO14001:2004 & OHSAS 18001 : 2007, DIN41494 and Equivalent Nos. 31,849.03 1.00
EIA/ISO/EN /CEA Certified company and should have proper EHS Policy.
Sub Total 18.....
19 VOICE COMMUNICATION SYSTEM
Supply, Installation, Testing & Commissioning of IP-PBX System having the following minimum specifications: Built-in Facilities: 4 Analog trunk (CO) port and 2 TDM
19.1 Ports, 50 SIP Extensions,50 SIP IP Subscribers, 8 SIP Trunks, minimum 4 Voice mai Channel, Optional Interfaces: GSM Module, Power Supply: External power Nos 39,894.04 1.00
Adaptor - 24V DC, 2.5A.
Supply, Installation, Testing and Commissioning of SIP-based IP Telephone with PoE support, supporting standard SIP protocol, dual Ethernet ports, display
19.2 (minimum 124 × 64 pixels), minimum 3 programmable feature keys, minimum 4 context-sensitive keys, dedicated volume control keys, and power support via PoE Nos 8,329.25 29.00
and 5V DC, 0.6A external power adapter.
Sub Total 19.....
Total Of ELV Items Amount in Rs.
20 COMPREHENSIVE MAINTENANCE FOR ELECTRICAL & ELV WORK
Provide Comprehensive Maintenance (including supply of material) for 4 years after handing over of work for electrical and ELV works as per schedule including
necessary materials to be given under warantee free of cost, etc.
20.2 1st Year ( From the date of Completion of DLP ) Year 7,12,197.30 1.00
20.3 2nd Year ( From the date of Completion of DLP ) Year 7,12,197.30 1.00
20.4 3rd Year ( From the date of Completion of DLP ) Year 7,12,197.30 1.00
20.5 4th Year ( From the date of Completion of DLP ) Year 7,12,197.30 1.00
Sub Total 20.....
(a) General Features & Special Features of the all lift items shall be taken as below.
(b) for Handicap Lifts, Minimum 10 Passengers Lift Capacity shall be considered.same is to be informed to architect /civil authority to keep necessary size of lift well.
Item no. Item Description Unit Rate Total Qty. Amount
(c) The lifts of 15/ 16 and above passenger capacity shall be taken for Hospital Lifts; Where in Description “ Stretcher Lifts” shall be mentioned.
(d) The Rates of the following items are for the lift of Machine room less. For Machine room Lifts, rate for Rs. 1,50,000/- shall be deducted in Total Cost for the Lifts
from 4 to 13 Passenger Lift. Rs. 2,00,000/- shall be deducted in Total Cost for the Lifts 15 and above passenger capacity as extra cost.
(e) Add Rs. 80,000/- for the DUPLEX control for the lifts up to 10 floors and add Rs. 10,000/- for additional each floor above 10 floors.
(A) GENERAL DESCRIPTION OF LIFTS.
[1] GEAR LESS LIFT DRIVE (MRL) comprising of High Starting torque Lift 3 phase 440 V A. C. Permanent Magnet Synchronous motor of proper rating with high
efficiency shall be used.[2] Micro processor based / PLC, ACVVVF, vector control drive with encoder feedback closed loop system shall be used for lift car and door
operation which shall be full collective selective operation hall call demand response, UP/DOWN hall stops, Main, Up/ Down Contactor with overload and phase
reversal relay and safety controls.
[3] Car with M S platform with bracings of adequate size and to sustain the impact load cabin + passenger with safety factor of fire for steel and side panels of
Stainless steel of sheet of grade 304 duty. Car ceiling will be S.S. finishes with aesthetic appearance with LED ceiling lights. Car flooring shall be of s/s 304 chaker
plate design sugeested of engineer in charge. of engineer in charge. Car doors shall be of stainless steel grade 304, hairline finish with centre opening / telescopic
automatic doors. Car panel will also be S.S. 304 finished with emergency stop device, mechanical door safety device, facility of auto/ attended mode. All car panel
buttons and all floor switches must be with brail language as per lift act.
[4] All landing doors must be fire rated for 2 hour shall be fully automatic centre opening/ telescopic opening made of hairline finish steel grade of 304 with key holes
and infrared curtains with Unlocking facility from outside
[5] Appropriate battery operated emergency light in the car along with alarm switch shall be provided. Also, Emergency Light & Fan should start immediately without
any Time Delay as soon as power fails.
[6] Digital scrolling indicator system for up-down arrow along with floor position indicator shall be provided inside the car and at all floors.
[7] Full height infra red curtain with multiple cross / crossing light beams shall be provided.
[8] Automatic Rescue Device (ARD) shall be provided accordingly of passenger capacity with Manual Rescue Operation ( Manual Cranking Facility).
[9] Audio visual indication in the lift car showing over loading shall be provided such that doors kept open till excess load is removed.
[10] Spring buffers/PU Buffers shall be provided.
[11] Car fan as per passenger capacity with automatic sleep timer shall be provided.
[12] Voice annunciator with suitable music shall be provided in lift car.
[13] Self diagnostics system for operational and safety parameters shall be provided in control panel.
[14] Mechanical over speed governor with governor calibration as per actual site parameters and submission of calibration certificate submission, door key holes in
the floor doors, fireman switch shall be provided.
[15] Lift machine hoisting arrangement in the lift machine room and monkey ladder for lift pit should be provided by the lift agency, along with the other steel structure
works, foundations for the machine etc…
[16] In the hoist way fascia plate shall be provided without any extra cost, where ever required as / if directed by engineer in charge.
[17] Permanent wiring with necessary safety devices like RCCB in all circuit, Over Voltage Under Voltage protection and THD eliminator in circuit for lift machine
room and lift well with proper numbers of light points, with fixtures, exhaust fan and plug points shall be provided by the agency. Only 3 phase Power Supply shall be
made available by department in lift machine room. Necessary Earthing as per Lift Act/Rules shall be arranged by Lift Agency.
[18] Any civil/ electrical works for additional and alteration in lift shaft and machine room related to erection of lift shall be made by lift agency without any extra cost.
(granite/marble fixing around all landing door openings are not in lift agency’s scope.)
[19] Agency has to provide all working drawings and documents and liaison services for obtaining all necessary permission from lift inspector and other authorities.
[20] acrylic transparent licence/display A4 size holder in lift car
[20A] As per statutory requirement of Govt. Of Gujarat lift & escalator act 2000, lift agency has to provide
1. Car top safety barricade
2. Push & talk communication system.
3. Fireman's switch operation at Ground Floor.
4.carrying out third party lift inspection during/after lift erection and provide report by third party authorized by concern licensing authority 5.agency has to provide
third party insurance upto completion of free maintenance period and submit the document for the same.
Item no. Item Description Unit Rate Total Qty. Amount
[21] Car Panel Operating Buttons with floor position indicator/buttons must be of Auto Glow type clearly visible when view from inside cabin.
[22] For Physically Handicapped person Full Length Handrails of hairline finish steel grade of 304 should be provided at appropriate height on the Rear & Side Wall
Panels in Lift Car.
[23] With Necessary KVA rating voltage controlled Stabilizer suitable for your controller, drive and all equipments of lift.
[24] Necessary rating of DP Elcb and FP Elcb required for lift is in scope of work which rating is sugested by CEICED Department (electrical Inspector)
(B) SPECIAL FEATURES DESCRIPTION OF LIFTS for PREMIUM category
1. Advanced control system dual 64 bit embedded microprocessor with CANBUS Serial Communication mode including Regenerative power efficient operation,on
site programming facility, Anti nuisance, Pte-opening, BMS/RMS with necessary online real time monitoring system having necessary connectivity for remote
monitoring & other suitable supporting hardware & software devices to fulfil the purpose.
2. Floor Indication LCD Display with call registration & brail mark with arrival gong and hall lantern & TFT Screen in the car with MP3 Voice Announcer.
3. CAR Panel should be Scratch resistive SS Moonrock finish / Hair Line / Honeycomb for car and all Doors, All landing doors must have fire rating up to 2 hours
and car door must have multi-level crisscross beam door protection.
4. To & fro communication system & wiring (i.e. car , control room & guard room ) and Each elevator are equipped with remote monitoring system.agency has to
provide mobile app and user id and password for monitoring
21.1 DESCRIPTION OF LIFT :
Supplying, Erecting, Testing & Commissioning the passenger / stretcher lift having following main features:
4/5/6 Passengers, Ground plus 11 upper floors with Rated Speed of 2.0 /2.5 m/sec.,
(B) With General PLUS ADDITIONAL SPECIAL FEATURES attached herewith. Prem. Cat.
8 / 10 Passengers, Ground plus 3 upper floor with Rated Speed of 1.0 m/sec.,
(C) With General PLUS ADDITIONAL SPECIAL FEATURES attached herewith. Prem. Cat.
8 / 10 Passengers, Ground plus 11 upper floors with Rated Speed of 2.0 / 2.5 m/sec.,
(B) With General PLUS ADDITIONAL SPECIAL FEATURES attached herewith. Prem. Cat.
21.2 Additional facilities for lift -
Supplying & erecting approved make Lift Announcing solid state system in the Passenger/ Stretcher lifts having AC2/ACVV/ACVF drives & automatic doors only.
The system comprising following features & facilities.
(i) Announcing floor message, message to close period.(ii) Announcing ‘Emergency Message’ when lift is stuck between floors due to power failure or any other
(iii) Instrumental Music between floor announcing.(iv) Announcement in English / Hindi & Gujarati Languages..
(v) Flexible to accommodate special per-programmed message such as name of the building /office.(vi)Volume adjustment control
Providing & erecting approved make overload non-start feature & overload warning Indicator system in the lift with making use of sound isolated floating platform &
micro switches on SI frame to get sensation of live load inside lift cage at any given moment, with provides new fixtures of overload warning inside lift cage with new
21.2.2 relay in the existing control panel to activate ‘Overload Non-Start Function with carrying out additional wiring including laying of new travelling cable, include minor Each 32,205.00 6.00
civil work & without changing the existing capacity speed stops, travel & operation of the desired lift
Sub Total 21.....
22 COMPREHENSIVE MAINTENANCE FOR LIFT WORK
Provide Comprehensive Maintenance (After Defect Liability Period) Of All LIFTS including all Electromechnical Items / Spare parts, Material and Labour with all
respect During DLP-Free of Cost.
22.2 1st Year ( From the date of Completion of DLP ) Year 4,51,058.58 1.00
22.3 2nd Year ( From the date of Completion of DLP ) Year 4,51,058.58 1.00
22.4 3rd Year ( From the date of Completion of DLP ) Year 5,15,495.52 1.00
22.5 4th Year ( From the date of Completion of DLP ) Year 5,79,932.46 1.00
Sub Total 22.....
Supply, Installation, Testing and Commissioning of 2MP IR Bullet Camera 3.6mm fix Lens with Aperture of F1.6, 1/2.8” image sensor, 0Lux with IR LED ON,
Horizontal Field of View: 87 degrees and IR Range of up to 30 meters, H.265/H.264/MJPEGVideo Compression, Certification: BIS, CE, FCC, IP67, Support ONVIF S
23.1 & G, PoE Support, NAS Storage, Triple or higher Stream Support, True WDR, 3D Noise Reduction, Adaptive Streaming, Smart Streaming and ROI, Cyber Security Nos. 6,842.81 30.00
Features: STQC Certified, NDAA Compliant, with require back box.
Item no. Item Description Unit Rate Total Qty. Amount
Supply, Installation, Testing and Commissioning of 2MP IR Dome Camera 2.8mm fix Lens with Aperture of F1.6, 1/2.8” image sensor, 0Lux with IR LED ON,
Horizontal Field of View: 107 degrees and IR Range of up to 30 meters, H.265/H.264/MJPEGVideo Compression, Certification: BIS, CE, FCC, RoHS, IK10, IP67,
23.2 Support ONVIF S & G, PoE Support, NAS Storage, triple or higher Stream Support, True WDR, 3D Noise Reduction, Adaptive Streaming, Smart Streaming and Nos. 6,842.81 95.00
ROI, Cyber Security Features: STQC Certified, NDAA Compliant, with require back box.
Supply, Installation, Testing and Commissioning of 64 Channel NVR with 4K Support and 8 HDD Slots (support up to 18TB capacity per slot), having 4K HDMI, 1/1
Audio I/O and 2/1 Alarm I/O, 12MP, 8MP, 5MP, 4MP, 3MP, 2MP, 720p, D1 and CIF Recording Resolution, 4x 4K/ 10x 3MP/16x 1080p Local Decoding, Save
23.3 Storage Space with Adaptive Recording and Camera-wise Recording Retention, SMS & Email Notification, Video Pop-up, Alarms and Calling from Mobile Nos. 1,03,872.66 2.00
Application, Throughput - 512Mbps Uplink, 512Mbps Downlink, ONVIF and Major Camera Brands Support, Cascading: Create Mutiple NVR Clusters to Monitor and
Control Multiple NVRs Centrally, NDAA Compliant.
23.4 Supply, Installation, Testing and Commissioning of 10 TB Surveillance Hard Disk for 30 days recording at 25 fps on 2 MP resolution Nos. 66,258.73 12.00
Supply, Installation, Testing and Commissioning of CCTV management work station Processor: i7-12700-12th Gen OS: Windows 11 Pro DEFAULT STORAGE:
23.5 512 GB SSD, RAM: 32 GB DDR5, (16 GB DDR5 - 2 nos), NVIDIA T400 4 GB Quadro graphic card, Additional Storage: 512GB HDD, KEYBOARD - 1 nos, MOUSE - Nos. 2,58,406.23 1.00
Supply, Installation, Testing & Commissioning of 65-inch Professional Grade Display suitable for 24/7 usage, with minimum 400 nits brightness, 50,000 hours
23.6 panel life, HD resolution (1920x1080), 20W built-in speakers, Connectivity: 2 x HDMI 2.0 port, 2 x USB port, 1 x 1G Ethernet ports, 10 mtr HDMI cable. Nos. 1,22,766.99 2.00
Sub Total 23.....
24 NETWORKING SYSTEM
Supply, Installation, Testing & Commissioning of 15U (550W X 600D)MM Wall mount closed rack with PDU, Horizontal Cable manager, self, mounting hardware and
24.1 cooling fan with standard accessories. UL Certified. Racks should be manufactured by ISO9001:2015, ISO14001:2004 & OHSAS 18001 : 2007, DIN41494 and Nos. 18,336.91 10.00
Equivalent EIA/ISO/EN /CEA Certified company and should have proper EHS Policy.
Supply, Installation, Testing & Commissioning of 42U (800W X 1000D)MM floor rack with PDU, Horizontal Cable manager, self, mounting hardware and cooling fan
24.2 with standard accessories. UL Certified. Racks should be manufactured by ISO9001:2015, ISO14001:2004 & OHSAS 18001 : 2007, DIN41494 and Equivalent Nos. 99,066.32 1.00
EIA/ISO/EN /CEA Certified company and should have proper EHS Policy.
24.3 SITC of O. F.Cable 06F Outdoor - Armoured Unitube SM - HDPE Sheath [Approved by Competent Authority i.e. not Below the rank of Executive Engineer ] Mtr. 50.00 600.00
SITC of LIU 12 PORT Rack Mount - Loaded (LC) SM
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of PATCH CORD LC-LC SM DUPLEX LENGTH- 3m
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of CAT6 UTP 23AWG Solid: Per Meter
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Patch Panel Cat 6 UTP Keystone Type- 24 Port-Fully Loaded
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Jack Cat 6 Keystone UTP
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Face Plate - Single (Keystone Jack,square)
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of Face Plate - Dual (Keystone Jack,square)
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of CAT6 UTP 24AWG PATCH CORD:1M,Plug 30U' Snag less
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of CAT6 UTP 24AWG PATCH CORD:2M,Plug 30U' Snag less
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
24.13 SITC of RJ45 Connector Nos. 39.38 140.00
Item no. Item Description Unit Rate Total Qty. Amount
SITC of 24 x 10/100/1000BASE-T PoE ports
4 x Gigabit RJ45/SFP Combo ports
Advanced L2 switching and security features
24.14 L2+ Static Routing Nos. 31,680.00 14.00
Optional “standard mode” or “surveillance mode” management user interface
193 W PoE budget
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
SITC of 24 x 10/100/1000BASE-T ports
4 x Gigabit RJ45/SFP Combo ports
Advanced L2 switching and security features
24.15 L2+ Static Routing Mtr. 15,247.00 2.00
Optional “standard mode” or “surveillance mode” management user interface
[Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
Supply, Installation, Testing and Commissioning of 4X4 Dual Band PoE Multi-Gig Wi-Fi 6 Access Point, Management: stand alone or cloud controller, security
:WPA3, wall\ceiling mount (Kit included ), Total users supported: 250, Concurrent Users:75, Including 3 year Cloud controller based license
SITC of Maximum distance of up to 10 km
Single-mode fiber
24.17 1000BASE-LX (IEEE 802.3z standard) Nos. 4,754.00 26.00
Duplex LC connector
MSA, RoHS-compliant [Approved by Competent Authority i.e. not Below the rank of Executive Engineer ]
24.18 Supply, Laying and Fixing of 25 mm diameter MMS PVC conduit with all required acccessories. Mtr. 86.14 5,800.00
24.19 Supply, laying and fixing of HDPE pipe 25mm Mtr. 114.44 300.00
24.20 Supply, Laying and Fixing of Flexible Pipe White 32 MM Mtr. 78.75 350.00
24.21 Supply, Laying and Fixing of Flexible Pipe White 50 MM Mtr. 142.74 115.00
24.22 Supply, Installation, testing and commissioning of 100 x 50 mm trunking Mtr. 616.48 25.00
Supply, installation, testing and commissioning of 4KE
(WUXGA) Resolution, 5200 lumens Laser projector,16:10
Aspect ratio, Over 5,000,000:1 Contrast ratio, 127 -
24.23 cm (50 - 500") diagonal image size,Interfaces : HDMI in Nos. 2,71,657.49 2.00
x2, HDMI out, HDBaseT, RS-232C, USB Type A (2A), USB
Type B, with ceiling mount kit (2feet + 2feet) or as per
site requirement technical specification etc. as required.
Supply, installation, testing and commissioning of
inch Fiber Glass MW Tubular Motorized Screen with RF
24.24 remote, Aspect Ratio-16:10 as per the technical Nos. 34,832.99 2.00
specifications etc. as required.
Sub Total 24.....
Total Of CCTV & Networking System Items Amount in Rs.
25 COMPREHENSIVE MAINTENANCE FOR CCTV & NETWORKING SYSTEM
Provide Comprehensive Maintenance (including supply of material) and operation for 4 years after handing over of work for CCTV & Networking System works as
per schedule including necessary materials to be given under warantee free of cost, etc.
25.2 1st Year ( From the date of Completion of DLP ) Year 1,96,585.35 1.00
25.3 2nd Year ( From the date of Completion of DLP ) Year 1,96,585.35 1.00
25.4 3rd Year ( From the date of Completion of DLP ) Year 1,96,585.35 1.00
25.5 4th Year ( From the date of Completion of DLP ) Year 1,96,585.35 1.00
Sub Total 25.....
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in
Ranip Ward, West Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE - 05 : PHE WORK
ITEM DESCRIPTION AMOUNT
1 SANITARY FIXTURES AND FITTINGS
INTERNAL DRAINAGE AND RAIN WATER WORKS (SOIL, WASTE, VENT AND RAIN WATER PIPING &
3 INTERNAL WATER SUPPLY NETWORK
4 EXTERNAL WATER SUPPLY NETWORK
5 EXTERNAL SEWAGE NETWORK
6 EXTERNAL STORM NETWORK
7 PUMP AND EQUIPMENT WORKS
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE -05 : PHE WORK
Item no. Item Description Unit Rate Total Qty. Amount
SANITARY FIXTURES AND FITTINGS
SPECIAL NEED FOR DISABLED TOILET
Providing and Fixing EWC wall hung, Wash basin, Grab bar, Hinged rail & special faucet with spachula including seat cover, and concealed cistern body
with control plate, fittings, nuts, bolts and gasket etc complete for disabled toilet of approved make and conforming to IS Standards. Wash basin with one
pair mounting brackets, Waste coupling 32 mm size full thread with 80 mm heightJaquar make with 7 years warranty: Chrome plated, Bottle trap Jaquar
make with 7 years warranty: Chrome plated etc., EWC S Trap & Cistern complete with fittings & seat cover, one no. hinged rail 750 mm & Two nos of grab
rails 600 mm ,etc. complete as per directed by the Engineer's Representative.
W.C Wall Hung : Jaquar, Model No. : DIS-WHT- 93955P180UF
1.01 Concealed Cistern : Jaquar, Model No. : JCS-WHT-2400P Set. 55,675.00 2
Flush Plate : Jaquar, Model No. : JCP-CHR-152415
Wash Basin : Wall Hung Basin With Fixing Accessories, Size : 650X565X155 Mm
Cat. No. ALD-CHR-573 Hand Shower (Health Faucet) With 8Mm Dia 1 Meter Long Flexiăle Tuăe And Wall Hook
Cat. No. WAC-SAP- BR0600CSN Wall mounted Grab Bar 680 mm Long
Cat. No.WAC-SAP- BG0800CSN Grab Bar Vertical Swing
Providing and fixing wash down wall mounting EWC-P of approved shade, conforming to Pattern 2 of IS: 2556 (Part -II), with SWR Self it Soil PVC pipe and
plug bend as per specifications; glazed vitreous / Coloured European Water Closet with Metropole flush valve, connecting PVC 110mm dia soil pipe with
PVC coupling, nuts, mounting cistern on WC., Ragbolt, Gasket Fitiiing and solid verity heavy duty plastic seat cover as per IS-2548, of approved make; hole
in walls/slab/beam and making good etc. complete as per directed by the Engineer's Representative.
1.02 EWC-P with PP Soft close Seat cover, Cistern with cistern fittings: Set. 31,375.00 123
W.C Wall Hung : Jaquar, Model No. : ARS-WHT- 39953BIUFSM
Concealed Cistern : Jaquar, Model No. : JCS-WHT-2400FS
Flush Plate : Jaquar, Model No. : JCP-CHR-292415
Providing and fixing in position 15 mm C.P. brass bib cock of best quality including cutting and making good the wall where required etc. complete as per
directed by the Engineer's Representative.
Bib Cock : Jaquar, Model no.
Providing and fixing 15mm C.P. brass angle valve with wall flange complete, including cutting and making good the wall where required etc. complete as
per directed by the Engineer's Representative.
Angle Valve :Jaquar, Model No. OPP-CHR-15053PM
Providing and fixing of Hand Shower (Health Faucet), with 8mm Dia,1Rmt Long pvc Tube and Wall Hook accessories to .complete the item etc. complete
as per directed by the Engineer's Representative.
Health Faucet :Jaquar, Model no.ALD-CHR-565
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing White glazed vitreous Oval Wash Basin Under-Counter, size 560x430x195 mm., with supporting M.S. or C.I. Brackets, necessary pipe
connection up to the outside face of the wall, having Telephonic Black / Colour Granite of 180 mm thick fixed on Black Kadappa Framework, Waste
coupling 32 mm size full thread with 80 mm height Chrome plated, Bottle trap Chrome plated , Pressmatic Pillar Cock including necessary fittings with wall
Flange etc. complete in all respects including cutting and making good the walls etc. complete as per directed by the Engineer's Representative.
1.06 Wash basin : Jaquar, Model No. : FLS-WHT-5701 Set. 6,975.00 124
Waste coupling : Jaquar, Model No. : ALD-CHR-705
Bottle trap : Jaquar, Model No. : ALD-CHR- 769L300X190
Providing and fixing Pressmatic Pillar Cock of best quality necessary fittings with Flange etc. complete in all respects including cutting and making good the
walls etc. complete as per directed by the Engineer's Representative.
Pressmatic Pillar Cock :FLP-CHR-5031PM
Providing and fixing Stainless Steel A ISI 304 (18/8) Pantry Sink as per ls:13983 with C.I. brackets and stainless steel plug 40 mm, including painting Of
fittings and brackets, cutting and making gcod the walls wherever required :
Pantry sink with drain board : Nirali ORRA BG
Providing and fixing Sink cock of best quality necessary fittings with wall Flange etc. complete in all respects including cutting and making good the walls
etc. complete as per directed by the Engineer's Representative.
Sink Cock Jaquar - FLP-CHR-5357PMD
Providing and fixing of C.P. copper connecting pipe 450 mm long and nuts, washer and brass flange complete, including cutting and making good the wall
where required etc. complete as per directed by the Engineer's Representative.
Braided Hose Copper Pipe : :Jaquar, Model No. :ALD-CHR-805B
Providing and fixing white vitreous china flat back Urinal of size 385x325x635mm as per IS-2556 (Part-2) with C.I. hangers and pipe to wall with C.P. flange
with Sensotronic Sensor Type Urinal flush valve with installation box with control valve Battery / Electric operated automatic flushes of approved make.
System provided with a solenoid valve and valve connected to a 6 volts lithium battery. Unit automatically serves (the range in about 40 cms) and flushes in
two steps. The pre flush is for 2 seconds duration and the final flushing is for 7 seconds duration. The outlet from the flusher shall be connected to urinal
1.11 with required braided pipes from sensor to urinal flush connection in fixture. Set. 24,400.00 9
complete including cutting and making good the walls wherever required etc. complete as per directed by the Engineer's Representative.
Urinal :Jaquar : URS-WHT-13255
Urinal Flush Valve,Jaquar, SNR-CHR-51097
Providing and fixing in position best Indian make toilet recessed type paper holder complete in all respects including cutting and making good the walls etc.
complete as per directed by the Engineer's Representative.
Toilet Paper Holder : Jaquar, Model no. ACN-CHR-1153S
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing in position best Indian make C.P. brass twin way QUOTE and hat hooks fixed into wall with C.P. Brass screws and rawlplugs etc.
complete including cutting and making good the walls etc. complete as per directed by the Engineer's Representative.
Twin Way coat Hook: Jaquar, Model No. :ACN-CHR-1161N
Providing and fixing electrical hand dryer, fully automatic type etc. complete as per directed by the Engineer's Representative.
1.14 Hand Dryer : Jaquar : HDR-SSF-AK2807 Nos. 11,200.00 4
Providing and fixing of Automatic Fragrance Dispenser fixed to wooden cleats with C.P. brass screws etc. complete as per directed by the Engineer's
Representative.
Fragrance Dispenser: EURONICS, Model No.: EURONICS, Model No.: EA44
Providing and fixing C.P. brass liquid soap container of best quality etc. complete as per directed by the Engineer's Representative.
1.16 Liquid Soap Container : Jaquar, Model no. Model no. ACN-1137N Nos. 1,750.00 122
Providing and fixing Long Body Bib Cock with Wall Flange best quality including cutting and making good the wall where required etc. complete as per
directed by the Engineer's Representative.
1.17 Long Body Bib cock : Jaquar Continental, Model No: CON-CHR-107KN Nos. 2,050.00 88
1.18 Providing and fixing of 2 way Single Lever Diverter Mixer including of Concealed Fitting with Built in Non return Valve , concealed stop cock for hot and cold
water supply controlling with Diverter Handle with Spout and overhead shower etc. complete as per directed by the Engineer's Representative.
Diverter, Make : Jaquar, Model : KUP-CHR- 35065MKPM
Concealed body for Diverter : Jaquar, Model : ALD-CHR-065M 16,990.00 114
Shower head, Make : Jaquar, Model : OHS-CHR-1757
Shower arm, Make : Jaquar, Model : SHA-CHR-455L400
Spout, Make : Jaquar, Model : SPJ-CHR-35429PMGB
1.19 Providing & fixing stainless steel recessed type soap dish of approved make. Including providing & fixing screws, washers, cutting & making good the walls
etc. complete as per directed by the Engineer's Representative.
Soap Dish : Jaquar, Model No. :ACN-CHR-1131N
1.20 Providing and fixing towel rail of approved make including, providing and fixing C.P. brass screws, making holes in walls and making good etc. complete as
per directed by the Engineer's Representative.
Towel Rail : Jaquar, Model No. : ACN-CHR-1111BNM
1.21 Providing and fixing of 25 Litre electrical Storage type water Geyser including all required accessories cutting, chassing and making good the same, etc.
complete as per directed by the Engineer’s Representative.
Electrical Storage Type Water Geyser 25 Litre Storage: Jaquar, Model No.: ELM-WHT-V025 (Elena Vertical)
SUB TOTAL FOR SANITARY FIXTURES AND FITTINGS
Item no. Item Description Unit Rate Total Qty. Amount
INTERNAL DRAINAGE AND RAIN WATER WORKS (SOIL, WASTE, VENT AND RAIN WATER PIPING & FITTINGS)
Providing laying and jointing in true line and level 40mm dia. U.P.V.C. Pipe ( SCH- 40) for cold water including fittings as approved by Engineer In Charge.
Pipe shall be fixed on the wall with the help of clamp at every two metre C/C or shall be concealed as directed including necessary fittings etc. including
2.01 testing of pipe and joints and fixing the same with adhesive solvent, including cost of all materials. Rmt. 146.65 469
Providing laying and jointing in true line and level 50mm dia. U.P.V.C. Pipe ( SCH- 40) for cold water including fittings as approved by Engineer In Charge.
Pipe shall be fixed on the wall with the help of clamp at every two metre C/C or shall be concealed as directed including necessary fittings etc. including
2.02 testing of pipe and joints and fixing the same with adhesive solvent, including cost of all materials. Rmt. 193.73 8
Providing, fixing, testing and commissioning of 75 mm SWR UPVC PIPE TYPE-B (6Kg/cm2.) with all the engineered support as per detail technical
specification self fit pipe conforming to IS:13592 including all fittings such as bends, junctions, inspection doors, offsets, cowl, access pieces/plugs,
2.03 cleanout, etc. jointing with PVC Adhesive joints including holes in walls and making good the same. Rmt. 585.00 693
Providing, laying and jointing in true line and level 110 mm diametre U.P.V.C (Type B) conforming to IS 13592-1992 with one end plain and other end
socketed with rubber ring, & fittings conforming to ISI 14735-1999 of approved make for drainage system pipe line, pipe shall be jointed with eachother with
rubber lubricant, pipe shall be fixed on wall using of PVC clamp of the size 110 mm diametre x 149 mm length x 145 mm heigh at every 2000 mm center to
2.04 center or shall be concealed in walls as directed including necessary fittings such as bends, shoes etc. including testing of pipes and joints and jointed with Rmt. 826.88 2356
adhesive solvent cement including cost of all materials.
Providing, laying and jointing in true line and level 160 mm diametre U.P.V.C (Type B) conforming to IS 13592-1992 with one end plain and other end
socketed with rubber ring, & fittings conforming to ISI 14735-1999 of approved make for drainage system pipe line, pipe shall be jointed with each other with
rubber lubricant, pipe shall be fixed on wall using of PVC clamp of the size 160 mm diametre x 210 mm length x 196 mm heigh at every 2000 mm center to
2.05 center or shall be concealed in walls as directed including necessary fittings such as bends, shoes etc. including testing of pipes and joints and jointed with Rmt. 822.99 148
adhesive solvent cement including cost of all materials.
Providing, installation, testing and commissioning of 110 mm dia. Acoustic Multilayer Polyproplene pipe conforming to BS EN 1451-Part 1-6 with 3 layer
pipe made of PP + PP-MD + PP and one layer fittings in PP MD, Push fit/ Ring fit type, Halogen and Cadmium free, having high impact resistance as per
DIN EN ISO 291:2008-08, Fire resistancy DIN 4102 B2, Ring stiffness SN6 6KN/m2 as per ISO 9969, offering sound levels of 21 dBA as per EN 14366 at a
flow rate of 4 l/s, water tightness as per EN 1451-1 minimum of 0.5 bar for 15 minutes, density of pipe = 1.15to1.25 gms/cm3, elongation = 0.09mm/mn/K
and E modulus 2300-3000 as per ISO 178, along with factory fitted EPDM lip ring, Fire Behavior Classification according to EN 13501-1:2009 & classified D-
s2-d2 (EN 13501-1), meets the requirements of EN 4102-2 with Fire Classification B2, Smoke Development Category Q1 & Drip Formation category TR1.
The scope shall be Including all fittings such as bends, junctions, inspection doors, offsets, cowl, access pieces/plugs etc. including cutting holes in walls,
slab and beam, chasing the wall by grinder cutter, including all the engineered support (support, hanger, nuts/bolts, anchor fasteners, fixing clamp/ channels
2.06 with U-bolts, etc) as per detail technical specification etc. complete the job and making good the same etc. complete the job as directed by Engineer in Rmt. 2,059.44 444
The scope shall be also include Providing and laying 100mm thickness cement concrete 1:5:10 (1 cement : 5 coarse sand :10 graded stone aggregate
mm nominal size) around the pipe etc. complete the job as directed by Engineer in charge.
(Soil, Waste & Vent Pipe))
160 mm dia.(Basement )
Item no. Item Description Unit Rate Total Qty. Amount
Providing, installation, testing and commissioning of 110 mm dia. Acoustic Multilayer Polyproplene pipe conforming to BS EN 1451-Part 1-6 with 3 layer
pipe made of PP + PP-MD + PP and one layer fittings in PP MD, Push fit/ Ring fit type, Halogen and Cadmium free, having high impact resistance as per
DIN EN ISO 291:2008-08, Fire resistancy DIN 4102 B2, Ring stiffness SN6 6KN/m2 as per ISO 9969, offering sound levels of 21 dBA as per EN 14366 at a
flow rate of 4 l/s, water tightness as per EN 1451-1 minimum of 0.5 bar for 15 minutes, density of pipe = 1.15to1.25 gms/cm3, elongation = 0.09mm/mn/K
and E modulus 2300-3000 as per ISO 178, along with factory fitted EPDM lip ring, Fire Behavior Classification according to EN 13501-1:2009 & classified D-
s2-d2 (EN 13501-1), meets the requirements of EN 4102-2 with Fire Classification B2, Smoke Development Category Q1 & Drip Formation category TR1.
The scope shall be Including all fittings such as bends, junctions, inspection doors, offsets, cowl, access pieces/plugs etc. including cutting holes in walls,
slab and beam, chasing the wall by grinder cutter, including all the engineered support (support, hanger, nuts/bolts, anchor fasteners, fixing clamp/ channels
2.07 with U-bolts, etc) as per detail technical specification etc. complete the job and making good the same etc. complete the job as directed by Engineer in Rmt. 1,321.45 17
The scope shall be also include Providing and laying 100mm thickness cement concrete 1:5:10 (1 cement : 5 coarse sand :10 graded stone aggregate
mm nominal size) around the pipe etc. complete the job as directed by Engineer in charge.
(Soil, Waste & Vent Pipe))
110 mm dia.(Basement)
Providing and fixing in position cowel went topipes.
Providing & fixing PVC SWR TYPE B P Trap of 110 X 110 mm diameter with Height riser/ necessary 110MM Diameter of distance piece for wash basin/
sink drain connection with cockroach trap - square flat cut, Satin-matt finish - 150mm x 150mm of approved Make, making necessary slab/ wall/ beam holes
2.09 and cutting walls, etc. complete. Nos. 1,700.00 399
Providing & fixing PVC SWR TYPE B of 110 X 110 mm diameter with Height riser/ necessary 110MM Diameter of distance piece for urinal drain connection
with floor clean out square cut 150mm- Satin of approved Make, making necessary slab/ wall/ beam holes and cutting walls, etc. complete.
Providing & fixing floor clean out square cut 150mm- Satin of approved Make with making necessary slab/ wall/ beam holes and cutting walls, etc.
2.11 complete. Nos. 1,200.00 62
Providing, Installing, testing and commisssioning advantix balcony drain with system dimension 70, UV resistance,without sealing flange,odour trap, round
70mm dia plastic grat plug with load class K=300 kg, including cost of cutting and making good the walls and floors where ever required complete in all
2.12 respects with necessary arrangements with proper care at all levels, protecting fittings and floor trap till the final handing over etc as per technical Nos. 1,200.00 84
specifications, drawings and directed by the Project Manager.
(Viega- Article no: 779719)
Making Khurras 45x45cm with average minimum thickness of 50 mm. cement concrete 1:2:4 (1 cement:2 coarse sand :4 graded stone aggregate of 20mm
nominal size) over P.V.C. sheet 1mx1mx400micron, finished with 12mm cement plaster 1:3 (1 cement: 3 coarse sand) and a QUOTE of neat cement
2.13 rounding the edge sand making and finishing the outlet complete depth as per site requirement. Nos. 785.00 14
Providing and fixing to the inlet mouth of rain water pipe cast iron grating 15cm diameter not less than 440grams.
SUB TOTAL FOR INTERNAL DRAINAGE AND RAIN WATER WORKS
(SOIL, WASTE, VENT AND RAIN WATER PIPING & FITTINGS)
INTERNAL WATER SUPPLY NETWORK
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable
3.01 water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete. Rmt. 202.97 494
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable
3.02 water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete. Rmt. 247.25 453
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable
3.03 water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete. Rmt. 330.36 13
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable
3.04 water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete. Rmt. 437.66 4
Providing laying and jointing in true line and level 25mm dia. U.P.V.C. Pipe ( SCH- 40) for cold water including fittings as approved by Engineer In Charge.
3.05 Pipe shall be fixed on the wall with the help of clamp at every two metre C/C or shall be concealed as directed including necessary fittings etc. including Rmt. 90.93 248
testing of pipe and joints and fixing the same with adhesive solvent, including cost of all materials.
Providing laying and jointing in true line and level 32mm dia. U.P.V.C. Pipe ( SCH- 40) for cold water including fittings as approved by Engineer In Charge.
3.06 Pipe shall be fixed on the wall with the help of clamp at every two metre C/C or shall be concealed as directed including necessary fittings etc. including Rmt. 117.97 329
testing of pipe and joints and fixing the same with adhesive solvent, including cost of all materials.
Providing laying and jointing in true line and level 40mm dia. U.P.V.C. Pipe ( SCH- 40) for cold water including fittings as approved by Engineer In Charge.
3.07 Pipe shall be fixed on the wall with the help of clamp at every two metre C/C or shall be concealed as directed including necessary fittings etc. including Rmt. 146.65 292
testing of pipe and joints and fixing the same with adhesive solvent, including cost of all materials.
Providing laying and jointing in true line and level 50mm dia. U.P.V.C. Pipe ( SCH- 40) for cold water including fittings as approved by Engineer In Charge.
3.08 Pipe shall be fixed on the wall with the help of clamp at every two metre C/C or shall be concealed as directed including necessary fittings etc. including Rmt. 193.73 366
testing of pipe and joints and fixing the same with adhesive solvent, including cost of all materials.
Providing and fixing unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as per detail technical specification, having thermal
stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes and fittings with one step UPVC solvent cement
and testing of joints complete as per direction of engineer in charge. Scope shall also including cutting, chasing the wall/beam by grinder cutter and making
Pipe Dia upto 50MM: UPVC (SCH 40)
Pipe Diameter above 50MM: UPVC (SCH 80)
The rate shall be including all the engineered support (support, hanger, nuts/bolts, anchor fasteners, fixing clamp/channels with U-bolts, etc) as per detail
technical specification etc. complete the job.
Product to compliance with occupational safety standards.
Providing and fixing unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as per detail technical specification, having thermal
stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes and fittings with one step UPVC solvent cement
and testing of joints complete as per direction of engineer in charge. Scope shall also including cutting, chasing the wall/beam by grinder cutter and making
Pipe Dia upto 50MM: UPVC (SCH 40)
Pipe Diameter above 50MM: UPVC (SCH 80)
The rate shall be including all the engineered support (support, hanger, nuts/bolts, anchor fasteners, fixing clamp/channels with U-bolts, etc) as per detail
technical specification etc. complete the job.
Product to compliance with occupational safety standards.
Item no. Item Description Unit Rate Total Qty. Amount
Providing and fixing unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as per detail technical specification, having thermal
stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes and fittings with one step UPVC solvent cement
and testing of joints complete as per direction of engineer in charge. Scope shall also including cutting, chasing the wall/beam by grinder cutter and making
Pipe Dia upto 50MM: UPVC (SCH 40)
Pipe Diameter above 50MM: UPVC (SCH 80)
The rate shall be including all the engineered support (support, hanger, nuts/bolts, anchor fasteners, fixing clamp/channels with U-bolts, etc) as per detail
technical specification etc. complete the job.
Product to compliance with occupational safety standards.
Providing and fixing male/ female screw ended full way lever operated forged ISI marked brass ball valves with brass body with forged brass hard chrome
plated ball / stem, union.Rated to temperature of 85 Deg C, The valves to be PN 10kgm class on CPVC or GI pipe lines. ( For cold water supply lines)
Providing and fixing male/ female screw ended full way lever operated forged ISI marked brass ball valves with brass body with forged brass hard chrome
plated ball / stem, union.Rated to temperature of 85 Deg C, The valves to be PN 10kgm class on CPVC or GI pipe lines. ( For cold water supply lines)
Providing and fixing male/ female screw ended full way lever operated forged ISI marked brass ball valves with brass body with forged brass hard chrome
plated ball / stem, union.Rated to temperature of 85 Deg C, The valves to be PN 10kgm class on CPVC or GI pipe lines. ( For cold water supply lines)
Providing and fixing male/ female screw ended full way lever operated forged ISI marked brass ball valves with brass body with forged brass hard chrome
plated ball / stem, union.Rated to temperature of 85 Deg C, The valves to be PN 10kgm class on CPVC or GI pipe lines. ( For cold water supply lines)
Providing and supplying ISI mark CI D/F Butterfly Valves as per IS:13095 (Latest Edition) of class PN 10, including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading, unloading, conveyance to departmental stores, stacking etc. complete.
Lowering, laying and jointing in position C. I. D/F Butterfly valves including cost of all labour, jointing material, including nut bolts and giving satisfactory
3.16 hydraulic testing, etc. complete. Nos. 1,958.00 14
Providing and supplying ISI mark CI D/F Butterfly Valves as per IS:13095 (Latest Edition) of class PN 10, including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading, unloading, conveyance to departmental stores, stacking etc. complete.
Lowering, laying and jointing in position C. I. D/F Butterfly valves including cost of all labour, jointing material, including nut bolts and giving satisfactory
3.17 hydraulic testing, etc. complete. Nos. 2,098.00 3
Item no. Item Description Unit Rate Total Qty. Amount
Providing and supplying ISI mark CI D/F Butterfly Valves as per IS:13095 (Latest Edition) of class PN 10, including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading, unloading, conveyance to departmental stores, stacking etc. complete.
Lowering, laying and jointing in position C. I. D/F Butterfly valves including cost of all labour, jointing material, including nut bolts and giving satisfactory
3.18 hydraulic testing, etc. complete. Nos. 2,784.00 3
Providing and supplying ISI mark CI D/F Butterfly Valves as per IS:13095 (Latest Edition) of class PN 10, including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading, unloading, conveyance to departmental stores, stacking etc. complete.
Lowering, laying and jointing in position C. I. D/F Butterfly valves including cost of all labour, jointing material, including nut bolts and giving satisfactory
3.19 hydraulic testing, etc. complete. Nos. 3,002.00 2
Providing and fixing Gun metal check or non-return
3.20 fullway wheel valve.(E) 40mm dia. Nos. 656.86 1
Providing and supplying ISI mark CI D/F Reflux Valves as per IS:5312 (Latest Edition) of PN 10 class, including all taxes, insurance, transportation, freight
charges, octroi, inspection charges, loading, unloading, conveyance to departmental stores, stacking etc. complete.
3.21 Lowering, laying and jointing in position C. I. D/F Reflux valves including cost of all labour, jointing material, including nut bolts and giving satisfactory Nos. 3,307.00 2
hydraulic testing, etc. complete.
Providing and supplying ISI mark CI D/F Reflux Valves as per IS:5312 (Latest Edition) of PN 10 class, including all taxes, insurance, transportation, freight
charges, octroi, inspection charges, loading, unloading, conveyance to departmental stores, stacking etc. complete.
3.22 Lowering, laying and jointing in position C. I. D/F Reflux valves including cost of all labour, jointing material, including nut bolts and giving satisfactory Nos. 3,831.00 2
hydraulic testing, etc. complete.
Providing and supplying ISI mark CI D/F Reflux Valves as per IS:5312 (Latest Edition) of PN 10 class, including all taxes, insurance, transportation, freight
charges, octroi, inspection charges, loading, unloading, conveyance to departmental stores, stacking etc. complete.
Lowering, laying and jointing in position C. I. D/F Reflux valves including cost of all labour, jointing material, including nut bolts and giving satisfactory
3.23 hydraulic testing, etc. complete. Nos. 4,346.00 3
Supply, Installation, Testing and Commissioning of Gun metal 25 mm dia. air release valve.
Supplying, installation, testing and commisioning of 32 mm dia. Heavy Quality Gun metal Pressure Reducing Valve with Strainer set and best quality having
by-pass arrangement consisting of the following :
3.25 1 No. pressure reducing valve with Strainer screwed ends, Nos. 20,246.30 18
3 Nos. gunmetal gate valve screwed ends.
Item no. Item Description Unit Rate Total Qty. Amount
Supplying, installation, testing and commissioning of 50mm dia. Heavy Quality Gun metal Pressure Reducing Valve with set of best quality having by-pass
arrangement consisting of the following :
3.26 1 No. pressure reducing valve screwed ends, Nos. 35,110.00 1
3 Nos. brass ball valve screwed ends.
Supplying, fitting and fixing of SS 316, Solenoid Valve, confirming to latest IS 8935, PN 16.0, with IP 67 logic controller, float switch, IP 67 Battery, with all
accessories viz. power and control cables, cabinets, hardwares specials, union, flange, cable upto tank, lower & upper level floats with, 3 Nos. gunmetal
3.27 gate valve screwed ends, etc., to complete the job. Nos. 28,262.50 1
Supplying, fitting and fixing of SS 316, Solenoid Valve, confirming to latest IS 8935, PN 16.0, with IP 67 logic controller, float switch, IP 67 Battery, with all
accessories viz. power and control cables, cabinets, hardwares specials, union, flange, cable upto tank, lower & upper level floats with, 3 Nos. gunmetal
3.28 gate valve screwed ends, etc., to complete the job. Nos. 29,750.00 1
Supplying, fitting and fixing of SS 316, Solenoid Valve, confirming to latest IS 8935, PN 16.0, with IP 67 logic controller, float switch, IP 67 Battery, with all
accessories viz. power and control cables, cabinets, hardwares specials, union, flange, cable upto tank, lower & upper level floats with, 3 Nos. gunmetal
3.29 gate valve screwed ends, etc., to complete the job. Nos. 31,237.50 1
SUB TOTAL FOR INTERNAL WATER SUPPLY NETWORK
EXTERNAL WATER SUPPLY NETWORK
Supply, laying, testing & commissioning external piping (UNDERGROUND) unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as
per detail technical specification, having thermal stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes
and fittings with one step UPVC solvent cement and testing of joints complete as per direction of engineer in charge.
Pipe Dia upto 50MM: UPVC SCH
4.01 Pipe Diameter above 50MM: UPVC SCH 40 Rmt. 790.00 28
(External water pipe )
Supply, laying, testing & commissioning external piping (UNDERGROUND) unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as
per detail technical specification, having thermal stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes
and fittings with one step UPVC solvent cement and testing of joints complete as per direction of engineer in charge.
Pipe Dia upto 50MM: UPVC SCH
4.02 Pipe Diameter above 50MM: UPVC SCH 40 Rmt. 987.00 8
(External water pipe )
Supply, laying, testing & commissioning external piping (UNDERGROUND) unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as
per detail technical specification, having thermal stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes
and fittings with one step UPVC solvent cement and testing of joints complete as per direction of engineer in charge.
Pipe Dia upto 50MM: UPVC SCH
4.03 Pipe Diameter above 50MM: UPVC SCH 40 Rmt. 1,234.00 17
(External water pipe )
Item no. Item Description Unit Rate Total Qty. Amount
Supply, laying, testing & commissioning external piping (UNDERGROUND) unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as
per detail technical specification, having thermal stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes
and fittings with one step UPVC solvent cement and testing of joints complete as per direction of engineer in charge.
Pipe Dia upto 50MM: UPVC SCH
4.04 Pipe Diameter above 50MM: UPVC SCH 40 Rmt. 1,371.00 88
(External water pipe )
Supply, laying, testing & commissioning external piping (UNDERGROUND) unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as
per detail technical specification, having thermal stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes
and fittings with one step UPVC solvent cement and testing of joints complete as per direction of engineer in charge.
Pipe Dia upto 50MM: UPVC SCH
4.05 Pipe Diameter above 50MM: UPVC SCH 40 Rmt. 1,523.00 11
(External water pipe )
Supply, laying, testing & commissioning external piping (UNDERGROUND) unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as
per detail technical specification, having thermal stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes
and fittings with one step UPVC solvent cement and testing of joints complete as per direction of engineer in charge.
Pipe Dia upto 50MM: UPVC SCH
4.06 Pipe Diameter above 50MM: UPVC SCH 40 Rmt. 1,603.00 66
(External water pipe )
Supply, laying, testing & commissioning external piping (UNDERGROUND) unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as
per detail technical specification, having thermal stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes
and fittings with one step UPVC solvent cement and testing of joints complete as per direction of engineer in charge.
Pipe Dia upto 50MM: UPVC SCH
4.07 Pipe Diameter above 50MM: UPVC SCH 40 Rmt. 1,781.00 22
(External water pipe )
Supply, laying, testing & commissioning external piping (UNDERGROUND) unplasticized polyvinyl chloride (UPVC) pipes with all the engineered support as
per detail technical specification, having thermal stability for water supply including all UPVC plain and brass threated fitting. This includes jointing of pipes
and fittings with one step UPVC solvent cement and testing of joints complete as per direction of engineer in charge.
Pipe Dia upto 50MM: UPVC SCH
4.08 Pipe Diameter above 50MM: UPVC SCH 40 Rmt. 1,875.00 26
(External water pipe )
Item no. Item Description Unit Rate Total Qty. Amount
Providing and supplying ISI mark CI D/F Butterfly Valves as per IS:13095 (Latest Edition) of class PN 10, including all taxes, insurance, transportation,
freight charges, octroi, inspection charges, loading, unloading, conveyance to departmental stores, stacking etc. complete.
Lowering, laying and jointing in position C. I. D/F Butterfly valves including cost of all labour, jointing material, including nut bolts and giving satisfactory
4.09 hydraulic testing, etc. complete. Nos. 3,002.00 2
Supply, installation, testing and commissioning of CI Y strainer approved make and best quality confirming to latest IS , PN 10.0, with necessary specials,
etc. for pump suction header and wherever required, to complete the job.
Woltman Type Bulk Water Meter- AMR Based:
Water Meter: 100 mm
Design, Supply, Installation, Testing, Commissioning of Woltman type Bulk Water Meter, CI/ Brass/ Bronze body material, totalizer made of copper can/
suitable anti corrosive metallic material, totaliser metalic shall have 5 mm thick glass cover suitable against antifraud attempts, Flange End process
connection, IP 68 protection class, AMR Woltman Type Water Meter with removable mechanism, magnetic drive, dry dial, and be fitted with a low mass
rotor which is parallel to the direction of water flow and exhibits dynamic thrust relief, water meters complete with T Type strainer, ISO 4064 : 2005 with valid
CE mark mentioning notified body number along with MlD / OIML / ISO certification from a recognized International laboratory.
AMR System shall be Walk By / Drive By mode, Wireless AMR trans-receivers shall be directly fitted on meter or inbuilt, IP 68 protection class, water meter
& AMR Module shall be of same brand, Single Command based AMR Reading and Minimum 90 days historical data retrive facility, alaram indication/
recording (for Reverse Flow, back flow, Peak Flow,Minimum Flow, Low Battery Alram, Volume below threshold, Volume above threshold, Reverse Meter,
Meter Stopped), Minimum 10 years of AMR module bateery life considering one no. communication per day.
Providing and supplying ISI standard R.C.C pipes (of sulphate Resisting Cement) in standard lengths of NP3 class and 150 diameter suitable for either
collar joints or rubber ring joints including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to
department stores, stacking etc.
Note : One coller should be supplied with each full length plain ended RCC pipe, cost included in rates. One rubber ring should be supplied with each full
4.12 length socketed pipe, cost included in rates. Rmt. 394.00 22
Lowering, laying and jointing R.C.C pipes in C.M. 1:1 1/2 of 150 diameter in proper position, grade and alignment at all level as directed by Engineer-in-
charge including conveyance from stores to site of work, labour, giving hydraulic testing as per ISI code.
Making point of new connection from Existing/ Municipal water supply line with all support, clamps, civil work, etc. required, providing suitable fittings, to
4.13 connect to Existing line and good the same as per engineer in charge. Work to be done including Liasoning cost. Job. 50,000.00 1
Supply, installation, testing and commissioning of 20mm diameter Garden Hydrant with gun metal Ball Valve, Flexible hose Connection Provision and all
4.14 required accessories etc. Nos. 3,250.00 2
Supply, laying, testing & commissioning of 20 mtr. Length 20 mm garden hose pipe.
Item no. Item Description Unit Rate Total Qty. Amount
Drilling and reaming bore hole at site using appropriate drilling methodology such rotary, semi rotary, DTH as suitable to site geology up to designed depth
by bentonite or mud flushing of the borehole including suppling, loading, unloading and filling of sticky clay balls and gravel packing in surrounding gaps
while developing of each water bearing zones by using required capacity of air compressor including required machineries, equipment's, safety measures
as per approved design/ drawing and direction of site engineer.
Including of pumping machinary related, piping & valve work and cablling work etc complete the job.
Rate inclusive of creating pit for drilling process, if required and removal of mud by mud tankers or any other way suitable to site condition, obtain bore-log
report from govt. authorized agencies
Drilling of bore hole an Alluvial strata by direct Rotary rig size 250/300mm diameter.
Reaming of 250/300 pilot bore hole including Assembling, lowering housing casing, strainer pipes, gravel packing, clay packing etc. conplete size 550mm
4.17 diameter. Rmt. 308.00 150
Manufacture, supply and delivery of ISI marked ERW M.S. pipes conforming to IS: 4270/2001 with latest amendment in rendom length of 4 to 7 meter size
4.18 250mm diameter (min. 7.10 mm thickness) (including 18% of GST) Rmt. 2,490.00 150
Job work of slotting of M S ERW blind pipe of following size having slot size as 6.75 cm x 6.35 cm x 3.12 mm (including unloading of blind pipes from truck
4.19 & reloading slotted pipes into truck). Per Slot 0.24 59400
Clamp made from M.S. plate with 3 holes on either side with nuts & bolts of Std. Make and suitable size.
4.2 900 mm X 100 mm X 16 mm flat suitable for 250 mm dia.Pipe. Per Pair 1,922.00 1
Bore plug having 100 mm height made from M.S. plate with 3 holes at equal distance on circumference for nut-bolts type, locking arrangement with nuts-
4.21 bolts & lock nuts of std. Make complete. From 5mm thick M.S. plate (for top also) suitable 250mm diameter pipe. Nos. 1,095.00 1
M.S. Bail plug having length 0.45 mtr from medium class pipe as per I.S.S. suitable for 250mm diameter pipe.
Steel bent plates suitable to 250 mm dia ERW pipe size 200 mm x 150mm x 6 mm.
Supply of Best quality of well sorted Sevaliya gravel of size 4mm to 6mm.
Cement sealing including the cost of cement by means of mud pump.
Charges of electrologging test of bore hole.
Lowering and removing of 100mm dia. Drop line and 32mm dia air line for development of each water bearing zones comes across upto the full depth of
deep tube well size 200mm/ 250mm/ 300mm dia. For the tube well having depth of 186 meter and above through suitable air compressor. the job is for
4.27 complete period of development of tueb well without air compressor charges. Job 24,122.00 1
Charges of air compreesor capacity 900 CFM/200 including all the require accessories and machinaries. (Min 6hr & upto sand free discharge)
Geohydrological Ground Water investigation (with vehicle charges) deep tube well (with water sample testing) for 200mm/250mm diameter deep tube well
4.29 (with water sample chemical analysis) Job 12,000.00 1
Supply of Clay ball of size 25mm to 50mm from Stickly Clay at site of work.)As certified by Hydrologist).
Item no. Item Description Unit Rate Total Qty. Amount
Supply, installation, testing and commissioning of 80mm UPVC column pipe of Heavy grade in the borewell of required depth, with "O" rings on the threads
makes the joints watertight and absorb pump vibrations. These rings are made from EPDM (Ethylene Propylene Diene Monome) rubber which is most
4.31 suitable for drinking water option with negative thermal expansivity. Rmt. 2,400.00 175
Supply, installation, testing and commissioning of Providing and erecting ISI marked PVC insulated PVC Sheathed Flat flexible Submersible copper cable
in the borewell of required depth approved make of following Size.
4.32 Size: 3Cx25 sqmm-Cu Rmt. 950.00 350
SUB TOTAL FOR EXTERNAL WATER SUPPLY NETWORK
EXTERNAL SEWAGE NETWORK
Providing and supplying 150 mm Inner Dia. Pipe of Class SN8 Structured Wall polyethelene Piping systems (Pipe with online/offline coupler and
elastomeric sealing ring) with non-smooth External Annular Corrugated and Smooth Internal Surfaces (Double Wall) for non-pressure underground
Sewerage & Drainage application as per EN:13476-3 including all local and central taxes, transportation, freight charges, octroi, inspection charges,
loading, unloading, conveyance to the departmental stores etc. complete.(ID Dia)
Lowering, laying and jointing of class SN 8 structured wall ( External Annular Corrugated & Smooth Internal surface) Polyethylene Piping and fittings with
5.01 the help of coupler ( on line / off line ) attached with one end of pipes, sliding over the elastomeric sealing rubber ring placed on the specified valley of the Rmt. 396.00 56
corrugation at the spigot end, lowering the same into the trench at all level, laying on the lower bedding (constructed at bottom of trenches) at prescribed
gradient,depth & alignment ,testing the water tightness of the joints, ensuring the continuity tests of specified pipe segments etc. complete as per drawing,
specifications & detailed engineering, including carriage of pipes & fittings from site stacks to the place of laying etc. as per direction of Engineer-in-charge.
Providing and supplying 200 mm Inner Dia. Pipe of Class SN8 Structured Wall polyethelene Piping systems (Pipe with online/offline coupler and
elastomeric sealing ring) with non-smooth External Annular Corrugated and Smooth Internal Surfaces (Double Wall) for non-pressure underground
Sewerage & Drainage application as per EN:13476-3 including all local and central taxes, transportation, freight charges, octroi, inspection charges,
loading, unloading, conveyance to the departmental stores etc. complete.(ID Dia)
Lowering, laying and jointing of class SN 8 structured wall ( External Annular Corrugated & Smooth Internal surface) Polyethylene Piping and fittings with
5.02 the help of coupler ( on line / off line ) attached with one end of pipes, sliding over the elastomeric sealing rubber ring placed on the specified valley of the Rmt. 771.00 113
corrugation at the spigot end, lowering the same into the trench at all level, laying on the lower bedding (constructed at bottom of trenches) at prescribed
gradient,depth & alignment ,testing the water tightness of the joints, ensuring the continuity tests of specified pipe segments etc. complete as per drawing,
specifications & detailed engineering, including carriage of pipes & fittings from site stacks to the place of laying etc. as per direction of Engineer-in-charge.
Providing and supplying 100 mm Inner Dia. Pipe of Class SN8 Structured Wall polyethelene Piping systems (Pipe with online/offline coupler and
elastomeric sealing ring) with non-smooth External Annular Corrugated and Smooth Internal Surfaces (Double Wall) for non-pressure underground
Sewerage & Drainage application as per EN:13476-3 including all local and central taxes, transportation, freight charges, octroi, inspection charges,
loading, unloading, conveyance to the departmental stores etc. complete.(ID Dia)
Lowering, laying and jointing of class SN 8 structured wall ( External Annular Corrugated & Smooth Internal surface) Polyethylene Piping and fittings with
the help of coupler ( on line / off line ) attached with one end of pipes, sliding over the elastomeric sealing rubber ring placed on the specified valley of the
corrugation at the spigot end, lowering the same into the trench at all level, laying on the lower bedding (constructed at bottom of trenches) at prescribed
gradient,depth & alignment ,testing the water tightness of the joints, ensuring the continuity tests of specified pipe segments etc. complete as per drawing,
specifications & detailed engineering, including carriage of pipes & fittings from site stacks to the place of laying etc. as per direction of Engineer-in-charge.
(From GT to First Chamber)
Item no. Item Description Unit Rate Total Qty. Amount
Constructing water tight brick masonry grease trap with second class bricks in cement mortar 1:4 (1 cement :4 coarse sand), R.C.C. top slab with
1:2:4 mix (1 cement :2 coarse sand :4 graded stone aggregate 20 mm nominal size, foundation concrete 150 mm thick 1:4:8 (1 cement :4 coarse
sand :8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement :3 coarse sand) finished with a
floating coat of neat cement & FRP. foot rests including fixing in 20 x 20 x 10 cm cement concrete blocks 1:3:6 (1 cement :3 coarse sand :6 graded
5.04 stone aggregate 20 mm nominal size), two brick masonry baffle walls each of 500 mm depth & third one 600 mm deep each of 115 mm thickness, 1 Nos. 58,237.00 2
No. cast iron double seal manhole cover with frame (internal size 455 x 610 mm & total weight of cover & frame to be not less than 38 kgs) & 2 Nos
C.I. double seal medium duty covers each of 450 x 450 mm size including excavation, backfilling & disposal of surplus earth complete as per standard
Grease Trap (Size 2500 x 1500 x 1500 mm lequid depth).
Making connection to Municipal existing sewer line including breaking them in a systematic way with suitable excavation, dewatering, dismantling of the
RCC or masonry wall or pipe line, passing the plumbing sewer line in the existing structure either through masonry or RCC and providing suitable "Y" tee to
the connect to existing pipe line, Reconstructions of dismantled existing structure according to the original one to bring to the working conditions testing etc.
5.05 work to be done in the presence of municipal eng. including Liasoning cost. complete as per standard as directed by Engineer-in-charge to complete the Nos. 50,000.00 1
SUB TOTAL FOR EXTERNAL SEWAGE NETWORK
EXTERNAL STORM NETWORK
Providing and supplying 150 mm Inner Dia. Pipe of Class SN8 Structured Wall polyethelene Piping systems (Pipe with online/offline coupler and
elastomeric sealing ring) with non-smooth External Annular Corrugated and Smooth Internal Surfaces (Double Wall) for non-pressure underground
Sewerage & Drainage application as per EN:13476-3 including all local and central taxes, transportation, freight charges, octroi, inspection charges,
loading, unloading, conveyance to the departmental stores etc. complete.(ID Dia)
Lowering, laying and jointing of class SN 8 structured wall ( External Annular Corrugated & Smooth Internal surface) Polyethylene Piping and fittings with
6.01 the help of coupler ( on line / off line ) attached with one end of pipes, sliding over the elastomeric sealing rubber ring placed on the specified valley of the Rmt. 396.00 11
corrugation at the spigot end, lowering the same into the trench at all level, laying on the lower bedding (constructed at bottom of trenches) at prescribed
gradient,depth & alignment ,testing the water tightness of the joints, ensuring the continuity tests of specified pipe segments etc. complete as per drawing,
specifications & detailed engineering, including carriage of pipes & fittings from site stacks to the place of laying etc. as per direction of Engineer-in-charge.
Providing and supplying 200 mm Inner Dia. Pipe of Class SN8 Structured Wall polyethelene Piping systems (Pipe with online/offline coupler and
elastomeric sealing ring) with non-smooth External Annular Corrugated and Smooth Internal Surfaces (Double Wall) for non-pressure underground
Sewerage & Drainage application as per EN:13476-3 including all local and central taxes, transportation, freight charges, octroi, inspection charges,
loading, unloading, conveyance to the departmental stores etc. complete.(ID Dia)
Lowering, laying and jointing of class SN 8 structured wall ( External Annular Corrugated & Smooth Internal surface) Polyethylene Piping and fittings with
6.02 the help of coupler ( on line / off line ) attached with one end of pipes, sliding over the elastomeric sealing rubber ring placed on the specified valley of the Rmt. 771.00 6
corrugation at the spigot end, lowering the same into the trench at all level, laying on the lower bedding (constructed at bottom of trenches) at prescribed
gradient,depth & alignment ,testing the water tightness of the joints, ensuring the continuity tests of specified pipe segments etc. complete as per drawing,
specifications & detailed engineering, including carriage of pipes & fittings from site stacks to the place of laying etc. as per direction of Engineer-in-charge.
Item no. Item Description Unit Rate Total Qty. Amount
Providing and supplying 250 mm Inner Dia. Pipe of Class SN8 Structured Wall polyethelene Piping systems (Pipe with online/offline coupler and
elastomeric sealing ring) with non-smooth External Annular Corrugated and Smooth Internal Surfaces (Double Wall) for non-pressure underground
Sewerage & Drainage application as per EN:13476-3 including all local and central taxes, transportation, freight charges, octroi, inspection charges,
loading, unloading, conveyance to the departmental stores etc. complete.(ID Dia)
Lowering, laying and jointing of class SN 8 structured wall ( External Annular Corrugated & Smooth Internal surface) Polyethylene Piping and fittings with
6.03 the help of coupler ( on line / off line ) attached with one end of pipes, sliding over the elastomeric sealing rubber ring placed on the specified valley of the Rmt. 1,046.00 6
corrugation at the spigot end, lowering the same into the trench at all level, laying on the lower bedding (constructed at bottom of trenches) at prescribed
gradient,depth & alignment ,testing the water tightness of the joints, ensuring the continuity tests of specified pipe segments etc. complete as per drawing,
specifications & detailed engineering, including carriage of pipes & fittings from site stacks to the place of laying etc. as per direction of Engineer-in-charge.
Geophysical Survey Involving Earth Resistivity Principals Vertical electrical sounding using Schlumberger 4 Electrode Array.
Geomagnetic Survey by using TESLA 6 ground water detector or similar equipment working on magnetotellurics 6 channel detection method.
Carrying out borehole logging to make geophysical measurements in better resolution in the required depth dimension to know Lithology, Identification of
6.06 water-bearing zones, Delineation of groundwater quality and Borehole fluid conductivity estimates. Nos. 20,000.00 1
Required Excavation for pits and trenches for Filtration chamber 2.5MX2.5mX3M in soil of required width, length and depth for the rainwater harvesting
system in all types of soil, sand, gravel, clay, soft and hard Murom including removing all excavated material within the premises up to 100 meter lead,
6.07 cleaning of site, removing shrubs, tree roots, vegetation and dewatering if required as per site condition, back filling, ramming, watering for depth up to 3.0 Job. 13,000.00 1
m as per the approved design/ drawing and specifications.
Providing and laying 150mm thick plain cement concrete 1:4:8 for base of the system using graded stone aggregate of 40 mm and below size including
necessary formwork at various locations, including mixing, laying, consolidation, finishing, curing & dewatering the pits etc. all as per drawings,
6.08 specifications and as directed. Lot. 4,500.00 1
Providing, fixing, testing and commissioning of readymade and light weight Polyethylene (PE) material rainwater harvesting system with HDPE ladder
specially designed for underground application to absorb surrounding dynamic load having adequate water conveying capacity to function as primary
surface filtration unit / secondary surface filtration unit having filter media up to 300 to 500 mm height in required shape/ size to achieve an effective
6.09 sedimentation process connecting storm water drainage having as per manufacturer guidelines and approved design/ drawings with following specifications. Nos. 85,000.00 1
1000 mm dia x 1800 mm deep x 8 mm thick for Regarge well & Storm water reuse filtration
Providing, fixing and commissioning of readymade 600MM X 600MM Clear opening FRP recess manhole cover with frame adjustable to filtration chamber
for the system specially designed with locking arrangement for various load bearing capacities for vehicular or nonvehicular movement suitable to
6.10 application to be fixed to primary/ secondary filtration systems as per manufacturer guidelines and approved design/ drawings. Nos. 7,000.00 1
5 T load carrying capacity.
Providing, laying and fixing in position unplasticised rigid PVC pipes conforming to IS: 4985 ( working pressure 6 kg/Sqcm) including all fittings such as
bends, clamps to the specified invert levels and slope with provision of water meter fixing arrangement supported by sand filled bags, including all fittings
such as NRV, bends, junctions, Tee, air vent, end-cap, flange adapters, in-situ adapter, access pieces/plugs jointing with uPVC adhesive including cutting
6.11 holes and making it good water tight by using specially designed leak proof flange adapters joining, testing & commissioning of overall 10 meter pipe length Set. 6,000.00 1
for sub-surface filtration system as per design/ drawing as approved.
110 mm dia. For Recharge well
Item no. Item Description Unit Rate Total Qty. Amount
Supply, installation, testing and commissioning of smart water management system to collect real time water quantity parameters for conductive liquids like
rainwater for underground application to be fixed in-line horizontal uPVC pipe having weather proof connection, with data logging device having IP68
housing with required isolated flow signal with paddle wheel flow sensor, microprocessor based transmission option for flow pattern recording with GSM /
6.12 GPRS modern interface feature including 10 meter long cable for 12-24V DC power supply and 12V 3500mAh battery capacity, communicate all data to Nos. 48,000.00 1
BMS, BMS Compatible including all necessary fixing arrangement as per design/ drawing as approved.
Supply, installation, testing and commissioning of smart water management system to collect real time water quantity parameters for conductive liquids like
rainwater for underground application to be fixed in-line horizontal uPVC pipe having weather proof connection, with data logging device having IP68
housing with required isolated flow signal with paddle wheel flow sensor, microprocessor based transmission option for flow pattern recording with GSM /
6.13 GPRS modern interface feature including 10 meter long cable for 12-24V DC power supply and 12V 3500mAh battery capacity, communicate all data to Year 30,000.00 1
BMS, BMS Compatible including all necessary fixing arrangement as per design/ drawing as approved.
Centralized Monitoring along with third party API (Application Program Interface) integration
Supplying and fixing two sets of four stage filtration arrangement on inlet and outlet pipes using suitable material to be fixed on uPVC pipe with SS clamp as
6.14 per approved drawing/ design. For Sotrm water Recharge & Reuse Filtration system Set. 10,500.00 1
Drilling and reaming bore hole at site using appropriate drilling methodology such rotary, semi rotary, DTH as suitable to site geology up to designed depth
by bentonite or mud flushing of the borehole including suppling, loading, unloading and filling of sticky clay balls of size 25mm to 50mm and gravel packing
in surrounding gaps while developing of each water bearing zones by using required capacity of air compressor including required machineries,
equipment's, safety measures as per approved design/ drawing and direction of site engineer.
6.15 Rate inclusive of creating pit for drilling process, if required and removal of mud by mud tankers or any other way suitable to site condition, obtain bore-log Rmt. 2,150.00 150
report from govt. authorized agencies
450 mm dia bore hole
Providing, laying and fixing in position solid uPVC Casing pipe having minimum 6 kg/ sqcm pressure rating including all leakproof fittings jointing with uPVC
adhesive including joining, testing & commissioning as per aprpoved design/ drawing.
6.16 160 mm dia with solid CM grade casing pipes. Rmt. 900.00 75
Providing, laying and fixing in position perforated uPVC Casing pipe having minimum 6 kg/ sqcm pressure rating including all leakproof fittings jointing with
uPVC adhesive including joining, testing & commissioning as per aprpoved design/ drawing.
6.17 160 mm dia with perforated CM grade casing pipes. Rmt. 950.00 75
Making connection to existing Municipal storm water line including breaking them in a systematic way with suitable excavation, dewatering, dismantling of
the RCC or masonry wall or pipe line, passing the plumbing storm water line in the existing structure either through masonry or RCC and providing suitable
"Y" tee to the connect to existing pipe line, Reconstructions of dismantled existing structure according to the original one to bring to the working conditions
6.18 testing etc. work to be done in the presence of municipal eng. including Liasoning cost. complete as per standard as directed by Engineer-in-charge to Nos. 50,000.00 1
complete the job.
Providing and supplying ISI standard R.C.C pipes (of sulphate Resisting Cement) in standard lengths of NP3 class and 200 diameter suitable for either
collar joints or rubber ring joints including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to
department stores, stacking etc.
Note : One coller should be supplied with each full length plain ended RCC pipe, cost included in rates. One rubber ring should be supplied with each full
6.19 length socketed pipe, cost included in rates. Rmt. 505.00 22
Lowering, laying and jointing R.C.C pipes in C.M. 1:1 1/2 of 200 diameter in proper position, grade and alignment at all level as directed by Engineer-in-
charge including conveyance from stores to site of work, labour, giving hydraulic testing as per ISI code.
Item no. Item Description Unit Rate Total Qty. Amount
SUB TOTAL FOR EXTERNAL STORM NETWORK
PUMP AND EQUIPMENT WORKS
Providing and fixing S.S. water cooler of 80ltr storage capacity with 60ltr per hr. cooling capacity. Including inbuilt R.O.Plant consisting of considering
the inbuilt booster pump,dry run protection, water purification filters, piping, isolation valves, instruments supports, etc. complete & Medium Penetration UV.
Including all Inter connection piping and valve all comp. System as per drinking water IS stadard requirment. it is recommendate to provide blending system
7.01 of water at attain TDS level between 250-300 ppm. The suppliear has to also supply and installation of SS-316 storage tank - 80 ltr. capacity. Nos. 96,495.00 2
Supplying, installation, testing and commissioning of Submersible multi stage pump Set. conforming to IS 8034 and motor conforms to IS-9283 working
at 3 phase 400/440 volt 50 C/S A.C. supply & 2900 R.P.M. Complete in Stainless steel 316 including with body, casing, impeller, shaft to suitable to handle
clear water. Pump should be completely made of stainless Steel 316 construction to avoid the corrosion formation. All bearings are water lubricated and
octagonally shaped bearings for sand flush, inlet strainer for prevents entering of particles , in-built non return valve for preventing back flow and reduce the
water hammer, stop ring for prevents damage of the pump due to up-thrust load. Pump should coupled with high efficiency oil cooled submersible motor
with ball bearing for smooth operation. Motor should be re-windable type made in stainless steel 316 parts in contact with water. Removable cable
connector for allow fast and easy maintenance. In build overload motor protection feature need to be provided. Pumps should be tested as per ISO
Pump: SS 316, Impeller: SS 316, Motor: SS
Enclosure class (IEC 34-5): IP
Insulation class (IEC 85): F
Supply, installation, testing and commisioning of made from Panel mounted Star Delta starter, Supplying & erecting approved make motor control cubical
panel [Star delta] made from 16G CRCA sheet duly epoxy powder painted inside and outside with hinged doors and locking with suitable size of ON - OFF
isolator (AC 3 / 23 duty) main fuses. Digital volt and current meter (in a single unit) with micro controller based control unit and current sensing single
phasing preventer electronic overload protection, over voltage (Programmable) protection and under voltage (Programmable) protection, prod less dry run
protection programming facility for Set.ting of all parameter like overload current, high voltage limit, low voltage limit, dry run limit with digital indication on
seven segment LED display for any fault like over load, high voltage, low voltage, dry running single crimped, electronic star delta timer, feather touch start/
7.02 stop push buttons to be erected on angle iron frame. Grouted on wall the contactors will be of approved make only). Scope shall also include local & remote Set. 3,92,000.00 1
pump control application consisting of MPCB, ON-OFF and Trip Indicating lamps in each incomer and outgoing feeders, overload relay and contactors as
per Type II coordination including digital voltmeter, analogue ammeter with selector switch, run hour meter, required protective relays & control accessories
with suitable out door IP 55 enclouser. Scope shall also include remote on/off operation complete as require. The on/off operation for all pumps shall be
available on central BMS system. Each incomer and Outgoing feeder should be capable for protection against Overload, Short Circuit and Phase reversal
condition and shall be capable to communicate with BMS. Scope shall also include supply, laying, termination of power cables of adequate size, and
arrangement of cable tray from Borewell to to Control panel etc. to complete the job.Scope Shall also include 6A seperate feeder in the panel for FLow
Supplying & erecting approved make Automatic liquid level controller 6A. as per instruction of Engineer in charge on site complete with wiring connection,
with copper conductor from pump to upper and lower tank. Scope shall also include of required control cable from Borewell to UG tank for automatic.
Capacity per pump - 8.0 m3/hour
1 Set. = 1 Nos. Pump
Item no. Item Description Unit Rate Total Qty. Amount
DOMESTIC WATER TREATMENT PLANT
Supply installation, testing and commissioning of dometic water treatment plant comprising of Pressure sand filter, and softner Plant accrording to input
water quality/analysis. Water treatment plant consisting of FRP tank, filter media, resins, brine tank, CPVC SCH 80 piping, isolation valves, instruments
supports. The scope shall include CPVC SCH 80 interconnection piping, Butterfly Cast Iron valves, NRV, instruments, autoback wash arrangement, Brine -
preparation tank & agitator platform, 1 nos Agitator require capacity and Ventury etc.complete the job .Scope shall also includes one month operation
including consumable and training for operation of staff.
Inlet Flow Range : 8.0 CMT/ Hr. -
Input Water Parameters: - AS PER SITE -
Output Water Hardness : < 50 PPM -
Centtrifugal Monoblock Transfer pump
Supplying, installing, testing and commissioning of centrifugal pumps Complete with SS-316 casing, S.S 316 impeller and SS-316 shaft, C.I. Base CED
(Cathode Electrode Deposition) coating & head TEFC motor (with mechanical seal) driven by 415 V AC, 3 phase, 50HZ., motor running at 2900 rpm speed
dry run protection, antivibration paid, 2 pole Motor & IE3 Efficiency, shall be supplied with all accessories viz., base plate, coupling, motor etc. complete.
Contractor to submit performance curves and technical catalogue of the proposed model for review and information.
Panel mounted microprocessor based multi pump controller with large graphical display with VGA 240 x 320 pixels and IP 55 enclosure, diodes to indicate
pump ready, earthing, pump running and fault condition, Cascade Operation. Each incomer and Outgoing feeder should be capable for protection against
Overload, Short Circuit and Phase reversal condition and shall be capable to communicate with other controllers following. The PLC shall support MODBUS-
IP communication for its compatability to intergrate with 3rd party BAS system. Controller shall authorise Read/Write command via BMS.All alarms should
be displayed in the controller. System should be equipped with dry running protection. Indication of all type of faults / on-off status / electrical parameters
shall be available on panel and central IBMS monitors. On-off operation for all pumps shall be available on BMS system. SITC of elctronic type low water
level controler with LED panel to operate pump (necessary contacts along with minium one PLC operated spare contacts required), shall prevent the pump
from dry running
Mounting Height : 500mm from the bottom of Raw Water tank.
7.03 Electronic type low, Medium & High water level controller with LED panel to operate pump (necessary contacts along with minimum one PLC operated Nos. 2,50,754.00 1
spare contacts required),level controller with operational mode as one pump working at Medium level and cut off at High level complete the job.
Mounting Height (Medium Level) : (Domestic Treated water Tank)
Mounting Height (Hight Level ): (Domestic Treated water Tank) with probe & all control wiring from Pump room Panel to operate the system
automatic/manual & shall prevent the pump from dry running.
Scope shall also include power and control cable of required size, termination, cable tray from Pump to Control panel, control cable as whereever required
etc. complete the job.
Set of accessories such as GI C Class headers of suction and discharge for (working and Standby pump assembly) with CED Coating, Gun Metal Isolation
valves, Gun Metal non return valves, pressure gauge with Isolation Valve of PN 10 etc. complete the job.
Capacity per pump - 8.0 m3/hour, Head - 35 mt, 1 Set = 2 Nos. Pump (1 Working + 1 Standby - cascade operation), location - Plant room
Item no. Item Description Unit Rate Total Qty. Amount
Supply installation, testing and commissioning of Multigrade sand filter. Water treatment plant consisting of FRP tank, filter media, CPVC SCH
interconnection piping, isolation valves, instruments supports. The scope shall include Multiport valves, NRV, instruments, autoback wash arrangement
etc.complete the job.
Quantity : 1 nos.
M.O.C. : As per vendor
Flow Rate : 8 .0cum/hr
7.04 Filter Media : Silica, Pables, Gravels And Quartz Sand Nos. 1,74,022.00 1
Type of Unit : Vertical Cylindrical
Working Pressure Kg/cm2 :
interconnection Piping: CPVC SCH
Accessories & Instruments : 1. Pressure gage : at inlet & outlet
Supply installation, testing and commissioning of activated carbon filter. Water treatment plant consisting of FRP tank, filter media, CPVC SCH
interconnection piping, isolation valves, instruments supports. The scope shall include Multiport valves, NRV, instruments, autoback wash arrangement
etc.complete the job.
Quantity : 1 nos.
M.O.C. : As per Vendor
Flow Rate : 8.0 cum/hr
7.05 Filter Media : Activate Carbon Nos. 1,89,084.00 1
Type of Unit : Vertical Cylindrical
Working Pressure Kg/cm2 :
interconnection Piping: CPVC SCH
Accessories & Instruments : 1. Pressure gage : at inlet & outlet
Supply installation, testing and commissioning of Water Softening Unit. Water treatment plant consisting of FRP tank, resin, CPVC SCH
interconnection piping, isolation valves, instruments supports. The scope shall include Multiport valves, NRV, instruments, regeneration
arrangement, Brine preparation tank, Agitator, Venturi & Agitator platform etc. complete the job.
Quantity: 1 nos.
Feed hardness considered: 400 ppm
Flow Rate: 8 cum/hr
Regeneration rate: each day
Regeneration: Manual
Regeneration Media (NaCl): Saturated Salt Brine
OBR: 50 M3 (1 Day)
Type of Unit: Vertical Cylindrical
7.06 Resin Quantity: 300 Liter Set. 4,18,120.00 1
Salt Preparation Tank Capacity: 200 Liter
Working Pressure Kg/cm²:
Interconnection Piping: CPVC SCH
Accessories & Instruments: 1. Pressure gauge; 2. inlet & outlet
Agitator: 1 Nos to be mounted on MS FRP platform of Brine Tank
Agitator Platform: MSFRP
Agitator Motor: As per Vendor
Agitator MOC: MSFRP
Regeneration: Venturi (As per vendor Design)
Item no. Item Description Unit Rate Total Qty. Amount
HYDRO PNEUMATIC SYSTEM FOR Domestic and Flushing Water Distribution Hydropneumatic System
Variable Speed Hydro-booster System
Compact self contained Hydro-booster system comprising of following
SITC of In-line, vertical multistage, centrifugal clear water pumps with SS-304 casing, S.S 304 impeller and SS-304 shaft, C.I. Base CED (Cathode
Electrode Deposition) coating & head TEFC motor (with mechanical seal), dry run protection, antivibration paid, 2 pole Motor & IE3 Efficiency. Vendor to
submit performance curves and technical catalogue of the proposed model for review and information.Panel mounted microprocessor based multi pump
controller with large graphical display with VGA 240 x 320 pixels and variable frequency drive (VFD) integrated in a single body, pressure sensor
transmitter, IP 55 enclosure, diodes to indicate pump ready, earthing, pump running and fault condition, Cascade Operation. Each incomer and Outgoing
feeder should be capable for protection against Overload, Short Circuit and Phase reversal condition and shall be capable to communicate with other
controllers following. The PLC shall support MODBUS-IP communication for its compatability to intergrate with 3rd party BAS system. Controller shall
authorise Read/Write command via BMS.System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in the
controller. System should be equipped with dry running protection. Indication of all type of faults / on-off status / electrical parameters shall be available on
panel and central IBMS monitors. On-off operation for all pumps shall be available on BMS system.
7.07 Electronic type low water level controller with LED panel to operate pump (necessary contacts along with minimum one PLC operated spare contacts set. 6,36,401.85 1
required), with probe & all control wiring from Panel to tank to operate the system automatic/manual & shall prevent the pump from dry running.
Scope shall also include power and control cable of required size, termination, cable tray from Pump to Control panel, control cable as whereever required
etc. complete the job.
Pre-charged diaphragm pressure vessel with interchangeable membrane, charging connection, connected to outlet header with necessary flanges, gaskets,
isolating valves, nuts/bolts etc. complete (size of pressure vessel shall be as per manufacturer recommendation).
Set of accessories such as GI C Class headers of suction and discharge for (working and standby pump assembly) with CED Coating, Cast iron Isolation
valves, Cast Iron non return valves, pressure transducers, pressure gauge with Isolation Valve of PN 10 etc. complete the job.Require complete company
fitted ready-to-connect packaged system.
Capacity per pump - 10.0 m3/hour, Head -70 mt, 1 Set = 2 Nos. Pump (1 Working + 1 standby - cascade operation), Location - Centralized UGT
Plant Room, Suction head - flooded positive suction.
Item no. Item Description Unit Rate Total Qty. Amount
Plant Pump Room Sump Drain Pump
Supply, installation, testing & commissioning of Submersible Non Clog, single stage, single entry pumps connected to TEFC submersible motor for 415 +
10% volts, 3 phase, 50 cycles A.C. power supply with mechanical seal, pump connector unit with rubber diaphragm and bend, vertical discharge pipe. The
pump shall be provided with a lifting devise of pull chain/guide rail.
(Pumps suitable to handle solids upto 20 mm size with C.I. body, SS304 shaft, SS impeller).
Panel mounted pump controller with DOL starter, IP 55 enclosure, ON-OFF and Trip indicating lamps in each incomer and outgoing feeders. The controller
shall support MODBUS-IP communication for its compatability to integrate with 3rd party BAS system. Necessasary contactors & relays shall be provided
for BMS connectivity. It shall authorised Read/write command via BMS, interlocking arrangement, dry run protection, cascade operation, working/Asist
selection, with provision of remote on/off operation complete as require. The on/off operations for all pumps shall be available on central BMS system. Each
incomer and outgoing feeder should be capacble for protection against overload, earthing, short circuit and phase reversal condition and shall be capable to
communicate with BMS. Scope shall also include supply, laying, termination of control and power cables of adequate size and arrangemnt of cable trayfrom
pump to control panel etc. to complete the job. SITC of elctronic type High & Low water level controler with LED panel to operate pump, level controller with
operational mode as one pump working at low level, both pumps at high level with a hooter alarm and cut off at dry level with probe & all control wiring to
operate the system automatic/manual & shall prevent the pump from dry running.
Mounting Height (Low Level) : 100mm bottom of Sump
Mounting Height (High Level) : 1000 mm from the bottom of Sump
Set of accessories such as CPVC SCH 80 headers of suction and discharge for (working and Standby pump assembly), Gun Metal Ball Valve, Gun metal
non return valves, pressure gauge of PN 10 etc. etc. complete the job.
Capacity per pump - 10.0 m3/hour, Head -15 mt, 1 Set = 2 Nos. Pump (1 Working + 1 Standby - cascade operation)
Item no. Item Description Unit Rate Total Qty. Amount
Rain Water Sump Drain Pump
Supply, installation, testing & commissioning of Submersible Non Clog, single stage, single entry pumps connected to TEFC submersible motor for 415 +
10% volts, 3 phase, 50 cycles A.C. power supply with mechanical seal, pump connector unit with rubber diaphragm and bend, vertical discharge pipe. The
pump shall be provided with a lifting devise of pull chain/guide rail.
(Pumps suitable to handle solids upto 20 mm size with C.I. body, SS304 shaft, SS impeller).
Panel mounted microprocessor based multi pump controller with large graphical display with VGA 240 x 320 pixels and IP 55 enclosure, diodes to indicate
pump ready, earthing, pump running and fault condition, Cascade Operation. Each incomer and Outgoing feeder should be capable for protection against
Overload, Short Circuit and Phase reversal condition and shall be capable to communicate with other controllers following. The PLC shall support MODBUS-
IP communication for its compatability to intergrate with 3rd party BAS system. Controller shall authorise Read/Write command via BMS.All alarms should
be displayed in the controller. System should be equipped with dry running protection. Indication of all type of faults / on-off status / electrical parameters
shall be available on panel and central IBMS monitors. On-off operation for all pumps shall be available on BMS system.Scope shall also include supply,
laying, termination of control and power cables of adequate size and arrangemnt of cable trayfrom pump to control panel etc. to complete the job.
Electronic type low, Medium & High water level controller with LED panel to operate pump (necessary contacts along with minimum one PLC operated
7.09 spare contacts required),level controller with operational mode as one pump working at Medium level, both pumps at High level with a hooter alarm and cut set. 2,00,001.00 2
off at Low level complete the job.
Mounting Height (Low Level ): (Sump)
Mounting Height (Medium Level) : (Sump)
Mounting Height (Hight Level ): (Sump) with probe & all control wiring from Pump room Panel to Sump to operate the system automatic/manual & shall
prevent the pump from dry running.
Scope shall also include power and control cable of required size, termination, cable tray from Pump to Control panel, control cable as whereever required
etc. complete the job.
Set of accessories such as CPVC SCH 80 headers of discharge for (working and Standby pump assembly) , Gun Metal Isolation valves, Gun Metal non
return valves, pressure gauge with Isolation Valve of PN 10 etc. complete the job.
Capacity per pump - 10.0 m3/hour, Head -15 mt, 1 Set = 2 Nos. Pump (1 Working + 1 Standby - cascade operation)
Item no. Item Description Unit Rate Total Qty. Amount
Ground Floor pit Rain Water Drain Pump
Supply, installation, testing & commissioning of Submersible Non Clog, single stage, single entry pumps connected to TEFC submersible motor for 415 +
10% volts, 3 phase, 50 cycles A.C. power supply with mechanical seal, pump connector unit with rubber diaphragm and bend, vertical discharge pipe. The
pump shall be provided with a lifting devise of pull chain/guide rail.
(Pumps suitable to handle solids upto 20 mm size with C.I. body, SS304 shaft, SS impeller).
Panel mounted microprocessor based multi pump controller with large graphical display with VGA 240 x 320 pixels and IP 55 enclosure, diodes to indicate
pump ready, earthing, pump running and fault condition, Cascade Operation. Each incomer and Outgoing feeder should be capable for protection against
Overload, Short Circuit and Phase reversal condition and shall be capable to communicate with other controllers following. The PLC shall support MODBUS-
IP communication for its compatability to intergrate with 3rd party BAS system. Controller shall authorise Read/Write command via BMS.All alarms should
be displayed in the controller. System should be equipped with dry running protection. Indication of all type of faults / on-off status / electrical parameters
shall be available on panel and central IBMS monitors. On-off operation for all pumps shall be available on BMS system.Scope shall also include supply,
laying, termination of control and power cables of adequate size and arrangemnt of cable trayfrom pump to control panel etc. to complete the job.
Electronic type low, Medium & High water level controller with LED panel to operate pump (necessary contacts along with minimum one PLC operated
7.10 spare contacts required),level controller with operational mode as one pump working at Medium level, both pumps at High level with a hooter alarm and cut set. 1,79,928.00 2
off at Low level complete the job.
Mounting Height (Low Level ): (Sump)
Mounting Height (Medium Level) : (Sump)
Mounting Height (Hight Level ): (Sump) with probe & all control wiring from Pump room Panel to Sump to operate the system automatic/manual & shall
prevent the pump from dry running.
Scope shall also include power and control cable of required size, termination, cable tray from Pump to Control panel, control cable as whereever required
etc. complete the job.
Set of accessories such as CPVC SCH 80 headers of discharge for (working and Standby pump assembly) , Gun Metal Isolation valves, Gun Metal non
return valves, pressure gauge with Isolation Valve of PN 10 etc. complete the job.
Capacity per pump - 1.0 m3/hour, Head -15 mt, 1 Set = 2 Nos. Pump (1 Working + 1 Standby - cascade operation)
SUB TOTAL FOR PUMP AND EQUIPMENT WORKS
GRAND TOTAL PLUMBING
GRAND TOTAL PLUMBING
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-
Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under
Building Project Department.
SUBESTIMATE - 06 : FIRE PROTECTION WORK
S. NO. ITEM DESCRIPTION AMOUNT
1 FIRE EXTINGUISHERS AND SIGNAGES
2 FIRE PIPING AND ACCESSORIES
3 PUMP & ACCESSORIES
4 SPRINKLER & RELATED ACCESSORIES
CHARGES FOR LIASONING WITH CFO AND
GETTING ALL APPROVALS
Notes for scope of work:-
1) Quantities in above estimate are based on conceptual layouts it may vary as per actual detail
2) Fire detection & fire alarm system has been considered in low voltage tender.
AHMEDABAD MUNICIPAL CORPORATION
Construction of Fire Station and Staff Quarters at T.P 66 (Ranip-Chenpur-Chandlodiya) F.P. 292 in Ranip Ward, West Zone, Ahmedabad city under Building Project Department.
SUBESTIMATE -06 : FIRE PROTECTION WORK
Item no. Item Description Unit Rate Total Qty. Amount
FIRE PROTECTION WORK
A FIRE EXTINGUISHERS AND SIGNAGES
Supplying, installation testing and commissioning of capacity 6 kg ABC (Powder Type - MAP 90%) Fire Extinguisher. In HP Mild Steel Cylinders ISI marked fitted with
pressure indicating gauge, internal tube, squeeze lever type valve fully charged with ABC powder (Mono Ammonium Phosphate) pressured by Nitrogen complete in all
1 respects including wall suspension bracket and conforming to IS:15683 Providing and Fixing of fire extinguishers with necessary accessories, stand, trolley, etc. Nos. 3,770.00 43.00
Extinguisher Suitable For Class-A, B and C Type Fire As per IS
All accessories need to be confirming to relevant Indian standards.
Supplying & erecting carbon dioxide (CO2) fire extinguisher user of following capacity with necessary clamps made from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall
2 complete. Nos. 6526.00 43.00
(A)For 4.5 Kg Capacity
Supplying, installation testing and commissioning of celling mounted capacity 15 kg CLEAN AGENT FK 5-1-12 Automatic Modular(Self Activated) fire extinguisher
Automatic type Fire Extinguishers, Applicable fire classes A,B & C, UGTS Pressure Gauge, Empty Weight 2.64 kg, Full weight 7.64 kg, Can Height 370mm, DiaMtrs. 230 ±
10mm, Made up from 2 mm thick sheet,, Body Construction Deep Drawn with MIG Welding technology, Brass forged sprinkler valves with Nozzle is specially designed to
3 give more than 99% discharge. Together with orifice characteristic to cover adequately fire risks with scattering cone of 40 to 45° Angle. Internal & External Pure polyester Nos. 49000.00 22.00
(UV Resistant) powder coated, Heat Sensitive Glass bulb of 68 °C. including pressure indicating gauge , celling mounted bracket.All accessories need to be confirming to
relevant Indian standards.
Design, supply and installation of safety signages made of zinc base glow in the dark rigid sheet with high luminous with pasted on 3mm thick on rigid PVC foam sheet.
Providing AUTOGLOW Signages in Block / Small Letters of Specified Sizes:
4 Fire Hydrant: 4" X 12" Nos. 410.00 35.00
Design, supply and installation of safety signages made of zinc base glow in the dark rigid sheet with high luminous with pasted on 3mm thick on rigid PVC foam sheet.
Providing AUTOGLOW Signages in Block / Small Letters of Specified Sizes:
5 "ABC" Extinguisher: 8" X 4" Nos. 295.00 43.00
Design, supply and installation of safety signages made of zinc base glow in the dark rigid sheet with high luminous with pasted on 3mm thick on rigid PVC foam sheet.
Providing AUTOGLOW Signages in Block / Small Letters of Specified Sizes:
6 "CO2" Extinguisher: 8" x 4"" Nos. 295.00 43.00
Total of FIRE EXTINGUISHERS AND SIGNAGES
Item no. Item Description Unit Rate Total Qty. Amount
B FIRE PIPING AND ACCESSORIES
Supplying, installation testing and commissioning of the following ‘C' class MS pipe as per IS1239 with welded / flanged / screwed joints and with all the engineered
support as per detail technical specification, heavy clamps, hangers, brackets or pipe supports (all with screwed/welded joints) as required including MS C class pipe of
shorter lengths, tapering connecting pieces, short or long bends, MS C class specials like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the
system operative as required by LFA authorities. The pipes will have to be laid and fixed on walls, ceilings, into brick walls or RCC with lead anchor fastners. The work
7 includes making holes in brick or RCC walls, slabs/ roofs and making good the damages by bringing to the original condition to the satisfaction of the Mtr. 12,570.00 15.00
Architect/Consultant/Client and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved primer for over ground / overheads pipes.
Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest codes & standars before applying the paint
300 mm dia. Pipe
8 250mm dia pipe Mtr. 8,420.00 9.00
9 200 mm dia. Pipe Mtr. 6488 117.00
10 150 mm dia. Pipe Mtr. 4190 728.00
11 100 mm dia. Pipe Mtr. 2816 82.00
12 80 mm dia. Pipe Mtr. 2005 175.00
13 65 mm dia. Pipe Mtr. 1643 94.00
14 50 mm dia. Pipe Mtr. 1493 81.00
15 40 mm dia. Pipe Mtr. 1148 95.00
16 32 mm dia. Pipe Mtr. 935 129.00
17 25 mm dia. Pipe Mtr. 733 816.00
Supplying, installation testing and commissioning of the following ‘C’ class MS Pipe as per IS : 1239-1973 tested to 200 PSI complete with fitting & welding of pipes &
fittings wherever required complete with flanges & painting , with all the engineered support as per detail technical specification. underground pipes with welded / flanged
connection with saddles, supports (all with screwed/welded joints) as required including pipe of shorter lengths, tapering connecting pieces, short or long bends, specials
like sockets, union nuts, elbows, reducers, plugs, Tees etc. complete to make the system operative as required by LFA authorities the pipes will have to be laid and fixed in
trenches. The work includes excavation in all types of soils and back filling, dewatering, etc., making holes in brick or RCC walls, slabs/ roofs and making good the damages
by bringing to the original condition to the satisfaction of the Architect and painting two coats of approved shade(Post office red)of enamel paint over a coat of approved
18 primer for over heads pipes and providing and fixing pypkote (corrosion protection tape) including supply and application of pipe coating and spiral Wrapping for Mtr. 6,832.00 72.00
underground piping (wrapping should have overlap of 15 to 20 mm) etc.
complete as per ASTM standards/IS:10221 for corrosion protection of pipes for the under ground installation.
Note : The piping installation has to be put to hydraulic test to1.5 times the working pressure & as per latest applicable codes & standard before applying paint or pipe
coating or wrapping etc. complete.
200mm dia. Pipe
19 150mm dia Pipe Mtr. 4,880.00 28.00
20 100mm dia Pipe Mtr. 3,742.00 28.00
21 80mm dia Pipe Mtr. 3,048.00 132.00
22 50mm dia Pipe Mtr. 2,348.00 5.00
Providing and erecting BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
Providing and erecting BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
200 mm dia. Pipe
Providing and erecting BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
150 mm dia. Pipe
Providing and erecting BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
100 mm dia. Pipe
Providing and erecting BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
80 mm dia. Pipe
Item no. Item Description Unit Rate Total Qty. Amount
Providing and erecting BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
65 mm dia. Pipe
Providing and erecting BUTTERFLY VALVE (MANUAL) with C I body SS disc nitrile sheet & O - ring & PN 16 pressure rating as specified.
50 mm dia. Pipe
Supplying, fixing, testing & commissioning of CI double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with
30 nuts, bolts, washers, gaskets and conforming to lS 780 of following sizes as required : set 66,350.00 4.00
Supplying, fixing, testing & commissioning of CI double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with
31 nuts, bolts, washers, gaskets and conforming to lS 780 of following sizes as required : set 51,046.00 6.00
Supplying, fixing, testing & commissioning of CI double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with
32 nuts, bolts, washers, gaskets and conforming to lS 780 of following sizes as required : set 32,292.00 7.00
Supplying, fixing, testing & commissioning of CI double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with
33 nuts, bolts, washers, gaskets and conforming to lS 780 of following sizes as required : set 24,765.00 2.00
Supplying, fixing, testing & commissioning of CI double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with
34 nuts, bolts, washers, gaskets and conforming to lS 780 of following sizes as required : set 16,285.00 1.00
Supplying, fixing, testing & commissioning of CI double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with
35 nuts, bolts, washers, gaskets and conforming to lS 780 of following sizes as required : set 14,377.00 2.00
Supplying, fixing, testing & commissioning of CI double flanged sluice valve of rating PN 1.6 with non rising spindle, bronze/gun metal seat, ISI marked complete with
36 nuts, bolts, washers, gaskets and conforming to lS 780 of following sizes as required : set 10,558.00 2.00
Supplying, installation testing and commissioning of single headed Gunmetal internal hydrant valve with 80 mm flanged inlet , 63 mm dia female instantaneous SS
outlet with cast iron wheel ISI marked ,blank cap and chain twist release type lug & all accessories conforming to IS 5290 Body duly painted with 2 coats of superior quality
paint and ISI certified heavy type hydraulically tested to 1.5 times working pressure with necessary nuts, bolts etc.
37 All accessories need to be confirming to relevant Indian standards. set 11,109 39.00
Single Headed Gunmetal
Supplying, installation testing and commissioning of single headed Gunmetal external hydrant valve with 80 mm flanged inlet , 63 mm dia female instantaneous SS
304 outlet with cast iron wheel ISI marked ,blank cap and chain twist release type lug & all accessories conforming to IS 5290 Body duly painted with 2 coats of superior
38 quality paint and ISI certified heavy type hydraulically tested to 1.5 times working pressure with necessary nuts, bolts etc. set 15,111 9.00
All accessories need to be confirming to relevant Indian standards.
Single Headed Gunmetal
Supplying, installation testing and commissioning of RRL hose pipe ISI marked as per IS 636 TYPE B, approved of 63mm dia x 15 mtr. standard length of approved
pattern and size including GUN METAL (LTB-2) 63mm x 63mm inst. male & female coupling as per IS: 903 ISI marked banded with COPPER binding wire.
39 All accessories need to be confirming to relevant Indian standards. set 7,350 84.00
Item no. Item Description Unit Rate Total Qty. Amount
Supplying, installation testing and commissioning of M.S. fire hose cabinet size 600x 750x 250mm for installation with internal hydrant, suitable to accomodate 2 nos
15 meter long hose pipe, 1 no branch pipe , mounted on wall or with steel support , including all other related accessories fabricated from M.S. sheet of 16 Gauge
thickness having central opening and partially 4 mm thick glazed glass doors (Two No.) (4mm thick glass with high quality silicon rubber beeding) suitably marked on the
outside with the letters "FIRE HOSE" including necessary locking arrangement and Cabinet shall be powder coated and painted with one coat of primer and two coats of
40 stove enamel paint of approved shade and White Inside .(or as approved by Architect)All accessories need to be confirming to relevant Indian standards. Nos. 6,720 35.00
(Cost shall be inclusive of providing break glass box containing key for the cabinet).
Supplying, installation testing and commissioning of stand mount M.S. fire hose cabinet size 600x 750x 250mm for installation with external yard , suitable to
accomodate 2 nos 15 meter long hose pipe, 1 no branch pipe , mounted on wall or with steel support , including all other related accessories fabricated from M.S. sheet of
thickness having central opening and partially 4 mm thick glazed glass doors (Two No.) (4mm thick glass with high quality silicon rubber beeding) suitably marked on the
41 outside with the letters "FIRE HOSE" including necessary locking arrangement and Cabinet shall be powder coated and painted with one coat of primer and two coats of Nos. 9,384 7.00
stove enamel paint of approved shade and White Inside .(or as approved by Architect)All accessories need to be confirming to relevant Indian standards.
(Cost shall be inclusive of providing break glass box containing key for the cabinet and fabricated suitable size fresh angles and required supports as shown in the drawing).
Supplying, installation testing and commissioning of Wall Mounted first aid fixed type fire hose reel for installation with internal hydrant with M S construction spray
painted in post office red conforming to IS 884 with up to date amendments complete with the following as required.
with water hose High pressure braided rubber suitably reinforced 25 mm size & 40 meter standard lenght conforming to IS-444 Type 2 with 5 mm tapering branch gun metal
42 nozzle , set 7,659 35.00
Connection from riser 40mm diameter gun metal stop valve and Pipe and socket etc. Hose to be fixed type wall mounted drum & recessing into hose cabinet to suit location
including fixing with lead anchor fasteners & bolts & nuts complete as required. ( Including drum and fixing type arrangement ) etc. complete.
All accessories need to be confirming to relevant Indian standards.
Supplying, installation testing and commissioning of stand Mounted first aid fixed type fire hose reel for installation with External hydrant with M S construction spray
painted in post office red conforming to IS 884 with up to date amendments complete with the following as required.
with water hose High pressure braided rubber suitably reinforced 25 mm size & 40 meter standard lenght conforming to IS-444 Type 2 with 5 mm tapering branch gun metal
43 Connection from riser 40mm diameter gun metal stop valve and Pipe and socket etc. Hose to be fixed type wall mounted drum & recessing into hose cabinet to suit location set 9,108 7.00
including fixing with lead anchor fasteners & bolts & nuts complete as required. ( Including drum and fixing type arrangement ) etc. complete. All accessories need to be
confirming to relevant Indian standards.
(Cost shall be inclusive of fabricated suitable size fresh angles and required supports as shown in the drawing).
Supplying, installation testing and commissioning of orifice plate made out of 8 mm thick Gun metal with orifice of required size to be fitted between flange & hydrant
valve to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.
44 All accessories need to be confirming to relevant Indian standards. Each 2,001 42.00
Supply, Installation, testing & commissioning of forged brass 25 mm dia screwed inlet single acting air release valve with 25 mm dia ball valve on inlet side and
pressure gauge with isolating cock.
45 All accessories need to be confirming to relevant Indian standards. Nos. 2,415 6.00
Supplying, installation testing and commissioning of Gunmetal short branch pipe The Branch shall have 63mm Male Instantaneous Inlet, suitable for use with 63 mm size
Fire fighting hoses and 20 mm bore bore Solid Jet Nozzle conforming to IS 903 suitable for interconnect hose pipe coupling complete as required.
46 All accessories need to be confirming to relevant Indian standards. NOS. 3,312 42.00
Supplying, installation testing and commissioning of gun metal Tripple purpose Nozzle conforming to IS 2871
with option of projecting water in form of straight stream (Jet) hollow jet or full, protective spray, and shall have facility of complete shut‐off. Nozzle shall have 63mm Male
47 Instantaneous Inlet, and discharge outlet shall have rubber ring for protection, and fixed teeth for giving good quality spray. NOS. 4,250 1.00
All accessories need to be confirming to relevant Indian standards.
Item no. Item Description Unit Rate Total Qty. Amount
Providing and supplying ISI standard R.C.C pipes (of sulphate Resisting Cement) in standard lengths of NP3 class and 200 diameter suitable for either collar joints or
rubber ring joints including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to department stores, stacking
Note : One coller should be supplied with each full length plain ended RCC pipe, cost included in rates. One rubber ring should be supplied with each full length socketed
48 pipe, cost included in rates. Rmt 505 39.00
Lowering, laying and jointing R.C.C pipes in C.M. 1:1 1/2 of 200 diameter in proper position, grade and alignment at all level as directed by Engineer-in-charge including
conveyance from stores to site of work, labour, giving hydraulic testing as per ISI code.
Providing and supplying ISI standard R.C.C pipes (of sulphate Resisting Cement) in standard lengths of NP3 class and 300 diameter suitable for either collar joints or
rubber ring joints including all taxes, insurance, transportation, freight charges, octroi, inspection charges, loading, unloading, conveyance to department stores, stacking
Note : One coller should be supplied with each full length plain ended RCC pipe, cost included in rates. One rubber ring should be supplied with each full length socketed
49 pipe, cost included in rates. Rmt 874 11.00
Lowering, laying and jointing R.C.C pipes in C.M. 1:1 1/2 of 200 diameter in proper position, grade and alignment at all level as directed by Engineer-in-charge including
conveyance from stores to site of work, labour, giving hydraulic testing as per ISI code.
Providing and fixing of pump trigger system only for Fire Hydrant Main Pump as per requirement and specification consisting of following items Including all required
material and labour, terminations, etc. Complete.
50 Pump On / Off switch: per set Nos. 1,104 35.00
Total of FIRE PIPING AND ACCESSORIES
C PUMP & ACCESSORIES
Supplying, installation, testing and commissioning of Electrical driven main centrifugal fire pump suitable for automatic operation and consisting of following, with cast
iron casing & bronze impeller & internal parts, stainless steel shaft, mechanical seal confirming to IS1520. make as approved by ISO and Local fire authority , complete with
coupling, coupling guard necessary M.S. fabricated Common base frame, foundation bolts, RCC foundation, antivibration paidetc. as required and as per site conditions
and instructions of site engineer-in-charge including proper fixing, The electrical motor for the pump should comply as per Specification. Suitable cement concrete
foundation duly plastered with anti vibration pads. and capable of discharging design flow and head against all losses complete.
The scope shall also include suitable HP squirrel cage induction electrical TEFC motor, synchronous speed 2900 RPM, suitable for operation on operated on 3-phase , 415-
Volts, 50 Hz,AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.with ‘B’ class winding, make as
approved by Local fire authority. The pump shall be capable of giving not less than 150% discharge at a head not less than 65% of the rated head. Motor to be of
51 continuous rating etc. complete. set 3,75,050.00 2.00
Each incomer and Outgoing feeder should be capable for protection against Overload, Short Circuit and Phase reversal condition and shall be capable to communicate with
BMS . System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in the controller and BMS. System should be equipped
with dry running protection. Indication of all type of faults / on-off status / electrical paraMtrs.s shall be available on panel and central IBMS monitors. On-off operation for all
pumps shall be available on BMS system.
Main Pump - Motor : Discharge : 2280 LPM, Head 100 mtr.- For Hydrant and Sprinkler
Item no. Item Description Unit Rate Total Qty. Amount
Supplying, installation, testing and commissioning of Diesel engine driven centrifugal fire pump suitable for automatic operation and consisting of following, with cast
iron casing & bronze or phosphor bronze internal parts, stainless steel shaft,make as approved by ISO and Local fire authority , complete with coupling, coupling guard
necessary M.S. fabricated Common base frame, foundation bolts, RCC foundation, antivibration paid etc. as required and as per site conditions and instructions of site
engineer-in-charge including proper fixing, Suitable cement concrete foundation duly plastered with anti vibration pads. and capable of discharging design flow and head
against all losses complete.
The scope shall also include synchronous speed 2900 RPM, water cooled with radiator , diesel engine of speef matching the pump speed, conforming to relevant IS
standard complete with auto starting mechanism, wired for automatic start of the water pump on drop of pressure in the system. 12 / 24 Volt electric starting equipment,
with battery & battery charger, necessary wiring, diesel tank, exhaust pipe extended up to out side as per site condition and instruction of site enginner-in-charge. duly
52 insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop set 6,85,111.00 1.00
solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. M.S fabricated
The pump should confirm to relavant stsandards and approved by Local fire authority.
Pumping System shall be capable to communicate with BMS . System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed
in the controller and BMS. Indication of on-off status paraMtrs.s shall be available on panel and central IBMS monitors. On-off operation for all pumps shall be available on
Pump - Diesel Engine : Discharge : 2280 LPM, Head : 100 mtr- Standby Pump
Supplying, installation, testing and commissioning of Electrical driven Jockey (Pressurization) centrifugal fire pump Horizontal / vertical suitable for automatic operation and
consisting of following, with cast iron casing & bronze impeller & internal parts, stainless steel shaft, mechanical seal confirming to IS1520. make as approved by ISO and
Local fire authority , The scope shall also include necessary coupling, coupling guard necessary M.S. fabricated Common base frame, foundation bolts, RCC foundation,
antivibration paid etc. as required and as per site conditions and instructions of site engineer-in-charge including proper fixing, The electrical motor for the pump should
comply as per Specification. Suitable cement concrete foundation duly plastered with anti vibration pads. and capable of discharging design flow and head against all
losses complete.
The scope shall also include suitable HP squirrel cage induction electrical TEFC motor, synchronous speed 2900 RPM, suitable for operation on operated on 3-phase , 415-
Volts, 50 Hz,AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.with ‘B’ class winding, make as
53 approved by Local fire authority. set 1,54,454.00 2.00
Each incomer and Outgoing feeder should be capable for protection against Overload, Short Circuit and Phase reversal condition and shall be capable to communicate with
BMS . System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in the controller and BMS. System should be equipped
with dry running protection. Indication of all type of faults / on-off status / electrical paraMtrs.s shall be available on panel and central IBMS monitors. On-off operation for all
pumps shall be available on BMS system
.Jockey Pump - Motor : Discharge : 180 LPM, Head : 100 mtr For Hydrant and Sprinkler System
Supplying, installation, testing and commissioning of Electrical driven terrace Booster pump suitable for automatic operation and consisting of following, with cast iron
casing & bronze impeller & internal parts, stainless steel shaft, mechanical seal confirming to IS1520. make as approved by ISO and Local fire authority, complete with
coupling, coupling guard necessary M.S. fabricated Common base frame, foundation bolts, RCC foundation, antivibration paid etc. ,as required and as per site conditions
and instructions of site engineer-in-charge including proper fixing, The electrical motor for the pump should comply as per Specification. Suitable cement concrete
foundation duly plastered with anti vibration pads. and capable of discharging design flow and head against all losses complete.
The scope shall also include suitable HP squirrel cage induction electrical TEFC motor, synchronous speed 2900 RPM, suitable for operation on operated on 3-phase , 415-
Volts, 50 Hz,AC supply with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325.with ‘B’ class winding, make as
54 approved by Local fire authority. Emergency start / stop push button station weather proof type and make as approved by Local fire authority. set 81,311.00 2.00
Each incomer and Outgoing feeder should be capable for protection against Overload, Short Circuit and Phase reversal condition and shall be capable to communicate with
BMS . System should be capable to compensate for frictional losses at lower flows. All alarms should be displayed in the controller and BMS. System should be equipped
with dry running protection. Indication of all type of faults / on-off status / electrical paraMtrs.s shall be available on panel and central IBMS monitors. On-off operation for all
pumps shall be available on BMS system.
Booster Electric Pump - Motor : Discharge : 900 LPM, Head : 35 mtr.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
AMCFS_Vol_1_Technical_Bid_General_Terms_and_Conditions_RANIP.pdf
AMCFS_Vol_2_DTS_and_Drawings_Ranip-1-250.pdf
AMCFS_Vol_2_DTS_and_Drawings_Ranip-251-500.pdf
AMCFS_Vol_2_DTS_and_Drawings_Ranip-501-684.pdf
Volume_3_Financial_Bid_Ranip.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .