Loading…
Loading…
Tender Value
₹2.4 Cr
EMD Value
₹2.7 L
Closing Date
22 Apr 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
ELE.TENDER
15 conditions · 4 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or "V" whichever is less V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover.
Tender should have valid "A" class electrical contractor license issued by electrical inspector to state Government with the offer. If "A" class electrical contractor license has been expired , tender should submit receipt of renewal electrical contractor license issued by electrical inspector to state Government with offer also .At the time of contract agreement , contractor must submit valid "A" class electrical contractor license issued by electrical inspector to state Government, If tender have not submit the valid "A" class electrical contractor license the offer will be summarily rejected.
Technical Eligibility Criteria, for the tender value above 50 lac - The tenderer must have successfully completed any of the following during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: Three similar works costing not less than the amount equal to 30% of advertised value of the tender, or Two similar works costing not less than the amount equal to 40% of advertised value of the tender, or One similar work costing not less than the amount equal to 60% of advertised value of the tender. It will be necessary to enclose certificate in this regard duly attested by competent authority along with tender document for the work. The contractor not qualifying the above eligibility criteria or not submitting the certificates for the same, the offer will be summarily rejected.
Definition Of Similar Work : - Following work will be considered similar nature work:- 1.1 Electrification of service building. 1.2 Electrification of staff quarters 1.3 Electrification of offices 1.4 Electrification of Road and colony lighting. 1.5 Rewiring of quarters and service building. 1.6 Earthing arrangement ( Plate & Pipe earthing) for quarters, service building, LT/HT panel etc. 1.7 Installation testing and commissioning of electrical sub-station. 1.8 Laying of H.T Cables. 1.9 Laying of L.T. Cables.
19 conditions · 1 needing a document upload
Payment of Tender Papers & Earnest Money:- Payment of tender document & earnest money cost, in respect of e-tendering should be accepted through net banking or payment gateway only. Note:- Fixed Deposit Receipt (FDR) will not be accepted as EMD for tenders invited on IREPS (e-tender portal). No tender will be considered without deposit of full earnest money and tender fee along with the tender.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Any clarification required by the tenderer may be obtained from Dy. CEE, Mechanical Workshop,Izzatnagar-243122, NORTH EASTERN RAILWAY.
Partnership firm : The tenderer shall submit (i) a copy of partnership deed and (ii) a copy of power of attorney (duly registered as per prevailing law) in favour of an individual to sign the tender documents and create liability against the firm.
INDIAN RAILWAY STANDARD GENERAL CONDITION OF CONTRACT is available on the Indian Railways website. Tenderers are requested to visit the website and be aware of the Terms and Conditions of GCC.
The Earnest Money of the Unsuccessful Tenderer[s] as here in before provided will be returned to the Unsuccessful Tenderer[s] but the Railway shall not be responsible for any loss or depreciation that may happen to the Earnest Money for the due performance of the stipulation to keep the offer open for the period specified in the offer or to the Earnest Money while in their possession, nor be liable to pay interest thereof. The Earnest Money Amount will be directly credited to the Accounts of Unsuccessful Tenderer[s] as early as possible after the tender case is finalised.
Any notes appearing in the Schedule of Items, Quantities and Rates will take precedence over Additional Special Conditions of Contract and also GENERAL CONDITIONS OF CONTRACT and STANDARD SPECIFICATIONS. The Railway will take for granted that Tenderer[s] has/have acquainted himself/themselves with all terms and words used in the tender before submitting the tender.
Bank Guarantee [BGs] to be submitted by contractors as Performance Guarantee should be sent directly to the concerned authorities by the issuing bank under Registered post AD.
Bidders are not required to re-upload the tender document/NIT under his digital signature.
The Earnest Money deposited with the tender of successful tenderer will be retained as part of security deposit which will be 5 percent of the value of work awarded. The balance amount of security deposit will recovered on account bill of the work @ 6 percent till it reached up to 5 percent of the value of work including earnest money.
Before submitting a tender, the tenderer will be deemed to have satisfied himself by actual inspection of the site and locality of the works, that all conditions liable to be encountered during the execution of the works are taken into account and that the rates he enters in the tender forms are adequate and all inclusive to accord with the provisions in Clause-37 of the Standard General Conditions of Contract for the completion of works to the entire satisfaction of the Engineer. (ii) Tenderer will examine the various provisions of The General Goods and Services Tax Act, 2017 (CGST)/Integrated Goods and Services Tax Act, 2017(IGST)/Union Territory Goods and Services Tax Act, 2017(UTGST)/ respective state's State Goods and Services Tax Act, (SGST) also, as notified by Central/State Govt. & as amended from time to time and applicable taxes before bidding. Tenderers will ensure that full benefit of Input Tax Credit (ITC) likely to be availed by them is duly considered while quoting rates. (iii) The successful tenderer who is liable to be registered under CGST/IGST/UTGST/SGST Act shall submit GSTIN along with other details required under CGST/IGST/UTGST/SGST Act to railway immediately after the award of contract, without which no payment shall be released to the contractor. The contractor shall be responsible for deposition of applicable GST to the concerned authority. (iv) In case the successful tenderer is not liable to be registered under CGST/IGST/UTGST/SGST Act, the railway shall deduct the applicable GST from his/their bills under reverse charge mechanism (RCM) and deposit the same to the concerned authority.
The contract shall be governed by the provision of Indian Railways Standard General Conditions of Contract-2022 (Latest) with correction slips up to the date of uploading of tender.
The successful bidder shall have to submit a Performance Guarantee (PG) within 21 (Twenty one) days from the date of issue of Letter of Acceptance (LOA). Extension of time for submission of PG beyond 21 (Twenty one) days and up to 60 days from the date of issue of LOA may be given by the Authority who is competent to sign the contract agreement. However, a penal interest of 12% per annum shall be charged for the delay 22nd beyond 21(Twenty one) days, i.e. from day after the date of issue of LOA. Further, if 60th the day happens to be a declared holiday in the concerned office of the Railway, submission of PG can be accepted on the next working day. In all other cases, if the Contractor fails to submit the requisite PG even after 60 days from the date of issue of LOA, the contract is liable to be terminated. In case contract is terminated railway shall be entitled to forfeit Earnest Money Deposit and other dues payable against that contract. In case a tenderer has not submitted Earnest Money Deposit on the strength of their registration as a Start up recognized by Department of Industrial Policy and Promotion (DIPP) under Ministry of Commerce and Industry, DIPP shall be informed to this effect. The failed Contractor shall be debarred from participating in re-tender for the work.
Tenderer is to abide by the provisions of Payment of Wages Act & Minimum Wages Act in terms of clause 54 and 55 of Indian Railway General Condition of Contract. In order to ensure the same, an application has been developed and hosted on website www.shramikkalyan.indianrailways.gov.in. Tenderer shall register his firm/company etc. and upload requisite details of labour and their payment in this portal. These details shall be available in public domain.
Tenderer is to abide by the provisions of Payment of Wages Act & Minimum Wages Act in terms of clause 54 and 55 of Indian Railway General Condition of Contract. In order to ensure the same, an application has been developed and hosted on website www.shramikkalyan.indianrailways.gov.in. Tenderer shall register his firm/company etc. and upload requisite details of labour and their payment in this portal. These details shall be available in public domain. While processing payment of any "On Account Bill" or "Final Bill" or release of "Advances" or "Performance Guarantee / Security deposit", tenderer shall submit a certificate to the Engineer or Engineer's representative that "I have uploaded the correct details of contract labours engaged in connection with this contract and payments made to them during the wage period in Railway's Shramik kalyan Portal at "www.shramikkalyan.indianrailways.gov.in till .......Month ....... Year" (As per Railway Board Letter No. 2018/CE-I/CT/4 dated 17.10.2018)
Electrical work in connection with Augmentation of Wagon POH infrastructure from 60 to 120 wagons at mechanical workshop/Izzatnagar.
L-WS-IZN-OT-2025-26-06-8
L-WS-IZN-OT-2025-26-06-8
Open
Works - General
6 Months
Bareilly, Uttar Pradesh
₹0
₹2.7 L
22 Apr 2026
23 Mar 2026
8 Apr 2026
228 items across 2 schedules
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | Above/ 22392377.06 Below/P | ||
| — | 200.00 | — | — | ||
| All work pertaining to Horizontal Directional Drilling (HDD )/Boring and trench less cabling. It includes supply, transportation and insertion of self-lubricated HDPE pipe of minimum 8 mm thick and 125 mm outer dia conforming to IS4984/1995 and laying of various cables in HDPE pipe as permissible depending on cable size boring under the track/road will be crossed. the depth of horizontal boring should be minimum 1.65 mtrs from rail flange/road level. Note:- The bore and the laying of cable in the bore under the track/road as per direction of engineer in-charge at site. 2. XLPE LT Cable will be supplied by the railway at concern SSE store depot.. | — | — | — | 2,17,508 | |
| — | 30.00 | — | — | ||
| Supply, making, testing and commissioning of Pipe Chemical Gel GI earthing arrangement with 3000 mm length earth electrode, earth electrode outer shell dia. 50 mm, earth electrode inner shell dia. 25 mm, inner shell thickness 3.25 mm, Terminal size 32/10 mm galvanization Outer shell 80-100 microns, inner shell 200-300 microns and conductive material filled complete in all respect and also making of earth pit with masonry work like bricks, mortar and cement with cover plate 16 SWG MS sheet cover plate having locking arrangement including supply, laying & connecting GI earthing strip size 25 mm x 5 mm. from earth pit terminal to equipment/sub- station (Per earthing length approx 5 meters) | — | — | — | 3,44,991.6 | |
| — | 15.00 | — | — | ||
| Supply, making, testing and commissioning of pipe earthing arrangement with G.I. pipe 'B' class 40 mm dia. 4.5 meter long including all accessories and supply and making masonry enclosure with cover plate of 16SWG MS sheet having locking arrangement, watering pipe, salt, charcoal etc. as per Drg. attached DY.CEE/Ws/IZN/01-2026 to achieve earth resistance less than 8 ohms and connecting the equipment with GI wire of 6SWG. Earthing shall be done on the basis of code of practice for earthing as per IS:3043/1987. | — | — | — | 38,950.05 | |
| — | 1500.00 | — | — | ||
| Supply and recessing/fixing of PVC conduit pipe 25 mm dia 2 mm thick confirming to IS:9537/Part-III/1983 reaffirmed-2007 (Latest version) with all accessories, bend, metal junction box 3/4 way, clamp etc including fixing on the M.S structure/ making chase, plastering/ clamping etc as per site requirement. Make-Poly Cab, Precision, Finolex, Presto Plast. | — | — | — | 60,000 | |
| — | 2000.00 | — | — | ||
| Supply, connecting, testing and commissioning of 0.75sqmm (Const. detail 24/0.20) cable multistranded copper conductor single core PVC (Type-C2) insulated having FRLS properties suitable for working voltage up to and including 1100 volts AC duly ISI marked as per IS:694/90,copper conductor as per IS:9130/1984 and PVC insulation as per IS:5831/1984 or latest and drawn in laid recessed/surface PVC conduit pipe for wiring of light/fan/exhaust fan circuit sub main/main as per direction of Engineer in charge at site. Wiring to be done as per IS732: 1989 or latest. Make-Grandlay Electricals (India) Delhi, Cable Corporation of India Ltd. Fort Gloster Industries Ltd., Universal Cable Co., Asian Cables, Polycab, Finlox, Havell's, KEI, Syska, Anchor, Rallison. | — | — | — | 24,000 | |
| — | 3500.00 | — | — | ||
| Supply, connecting, testing and commissioning of 2.5 sq.mm (Const. detail 36/0.30) cable multistranded copper conductor single core PVC (Type-C2) insulated having FRLS properties suitable for working voltage up to and including 1100 volts AC duly ISI marked as per IS:694/90,copper conductor as per IS:9130/1984 and PVC insulation as per IS:5831/1984 or latest and drawn in laid recessed/surface PVC conduit pipe for wiring. of light/fan/exhaust fan circuit sub main/main as per direction of Engineer in charge at site. Wiring to be done as per IS732: 1989 or latest. Make-Grandlay Electricals (India) Delhi, Cable Corporation of India Ltd. Fort Gloster Industries Ltd., Universal Cable Co., Asian Cables, Polycab, Finlox, Havell's, KEI, Syska, Anchor, Rallison. | — | — | — | 1,05,000 | |
| — | 1500.00 | — | — | ||
| Supply, connecting, testing and commissioning of 4.0 sq.mm (Const. detail 56/0.30) cable multistranded copper conductor single core PVC (Type-C2) insulated having FRLS properties suitable for working voltage up to and including 1100 volts AC duly ISI marked as per IS:694/90,copper conductor as per IS:9130/1984 and PVC insulation as per IS:5831/1984 or latest and drawn in laid recessed/surface PVC conduit pipe for wiring. of light/fan/exhaust fan circuit sub main/main as per direction of Engineer in charge at site. Wiring to be done as per IS732: 1989 or latest. Make-Grandlay Electricals (India) Delhi, Cable Corporation of India Ltd. Fort Gloster Industries Ltd., Universal Cable Co., Asian Cables, Polycab, Finlox, Havell's, KEI, Syska, Anchor, Rallison. | — | — | — | 63,000 | |
| — | 2500.00 | — | — | ||
| Supply, connecting, testing and commissioning of 6.0sqmm cable multistranded copper conductor single core PVC (Type-C2) insulated having Heat Resistant Flame Retardant PVC Insulated Industrial cables Single Core HRFR PVC Insulated Industrial Grade Copper conductor (Unsheathed) Flexible Cables, 1100 Volt Conforming to IS 694, copper conductor as per IS:9130/1984 and PVC insulation as per IS:5831/1984 or latest and drawn in laid recessed/surface PVC conduit pipe for wiring of light/fan/exhaust fan circuit sub main/main as per direction of Engineer in charge at site. Wiring to be done as per IS732: 1989 or latest. Make-Grandlay Electricals (India) Delhi, Cable Corporation of India Ltd. Fort Gloster Industries Ltd., Universal Cable Co., Asian Cables, Polycab, Finlox, Havell's, KEI, Syska, Anchor, Rallison. | — | — | — | 2,82,350 | |
| — | 3700.00 | — | — | ||
| Supply, connecting, testing and commissioning of 10.0 sq.mm (Const. detail 84/0.30) cable multistranded copper conductor single core PVC (Type-C2) insulated having FRLS properties suitable for working voltage up to and including 1100 volts AC duly ISI marked as per IS:694/90,copper conductor as per IS:9130/1984 and PVC insulation as per IS:5831/1984 or latest and drawn in laid recessed/surface PVC conduit pipe of light/fan/exhaust fan circuit sub main/main as per direction of Engineer in charge at site. Wiring to be done as per IS732: 1989 or latest. Make- Grandlay Electricals (India) Delhi, Cable Corporation of India Ltd. Fort Gloster Industries Ltd., Universal Cable Co., Asian Cables, Polycab, Finolex, Havells, KEI, Syska, Anchor, Rallison. | — | — | — | 6,95,600 | |
| — | 2000.00 | — | — | ||
| Supply, connecting, testing and commissioning of 1.5 sq.mm 2 core PVC insulated and PVC Round Sheathed, Multicore Annealed Bare Copper Conductor (flexible) industrial cable for Voltage Grade 1100 Volt, Conforming to IS 694 : 2010 for connecting of ceiling fan and other fittings. Make-Grandlay Electricals (India) Delhi, Cable Corporation of India Ltd. Fort Gloster Industries Ltd., Universal Cable Co., Asian Cables, Polycab, Finolex, Havells, KEI, Syska, Anchor, Rallison. | — | — | — | 1,46,000 | |
| — | 25.00 | — | — | ||
| Supply & fixing of Metal box 4 Module (Rectangular type) made of 1.0 mm G.I. sheet in the wall including cutting of wall, fixing of Module box in the wall and making good by cement. Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electri, L&T. | — | — | — | 1,750 | |
| — | 25.00 | — | — | ||
| Supply & fixing of modular mounting frames with cover plates for 4 Modules (Horizontal type).Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electric, L&T. | — | — | — | 2,250 | |
| — | 100.00 | — | — | ||
| Supply & fixing of Metal box 6 Module (Rectangular type) made of 1.0 mm G.I. sheet in the wall including cutting of wall, fixing of Module box in the wall and making good by cement. Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electri, L&T. | — | — | — | 8,000 | |
| — | 100.00 | — | — | ||
| Supply & fixing of modular mounting frames with cover plates for 6 Modules (Horizontal type). Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electric, L&T. | — | — | — | 7,500 | |
| — | 30.00 | — | — | ||
| Supply & fixing of Metal box 8 Module (Rectangular type) made of 1.0 mm G.I. sheet in the wall including cutting of wall, fixing of Module box in the wall and making good by cement. Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electri, L&T. | — | — | — | 2,700 | |
| — | 30.00 | — | — | ||
| Supply & fixing of modular mounting frames with cover plates for 8 Modules (Horizontal type). Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electric, L&T. | — | — | — | 3,000 | |
| — | 350.00 | — | — | ||
| Supply & fixing of Metal box 12 Module (Rectangular type) made of 1.0 mm G.I. sheet in the wall including cutting of wall, fixing of Module box in the wall and making good by cement. Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electri, L&T. | — | — | — | 38,500 | |
| — | 350.00 | — | — | ||
| Supply & fixing of modular mounting frames with cover plates for 12 Modules (Horizontal type). Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electric, L&T. | — | — | — | 42,700 | |
| — | 100.00 | — | — | ||
| Supply, installation, testing & commissioning of 3 plate Ceiling rose ISI marked as per IS:371/1999 including connections, testing and commissioning as per site requirement. Make- Anchor, SSK (top line), Precision (Prime), Legrand, Indo Asian (Glint & Elvira). | — | — | — | 1,800 | |
| — | 1200.00 | — | — | ||
| Supply, fixing, connecting, testing & commissioning of Modular type switch 6-10 Amps (1-way), single module suitable for operation on 120V to 250V, 50Hz, AC supply. Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electric, L&T. | — | — | — | 1,02,000 | |
| — | 800.00 | — | — | ||
| Supply, fixing, connecting, testing & commissioning of Modular type socket 6-10 Amps 3pin, double module suitable for operation on 120V to 250V, 50Hz, AC supply. Make- Anchor- Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electric, L&T. | — | — | — | 88,000 | |
| — | 450.00 | — | — | ||
| Supply, fixing, connecting, testing & commissioning of Modular type switch 16-20 Amps (1-way), single module suitable for operation on 120V to 250V, 50Hz, AC supply. Make- Anchor-Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electric, L&T. | — | — | — | 63,000 | |
| — | 450.00 | — | — | ||
| Supply, fixing, connecting, testing & commissioning of Modular type socket 16-20 Amps 5/3pin,double module suitable for operation on 120V to 250V, 50Hz, AC supply. Make- Anchor- Roma, Anchor-Woods, Indo asian (Glint &Elvira) Havells-Crab Tree, Siemens, Schneider Electric, L&T. | — | — | — | 90,000 | |
| — | 200.00 | — | — | ||
| Supply and fixing of modular blanking plate single module on the module plate as per direction of engineer in-charge at site. Make- Anchor-Roma, Anchor-Woods, Indo Asian (Glint & Elvira) Havells-Crab Tree, Siemens, Schneider Electri, L&T. | — | — | — | 4,000 | |
| — | 50.00 | — | — | ||
| Supply, fixing, connecting and commissioning of Electric ceiling fan 1200 mm sweep with BLDC motor 5 star rated as per IS: 374 (V2)/2019 or latest, Power Consumption less than 24-26 watt, Air delivery more than 220 Cum per minute, speed 350 rpm, double ball bearing, 03 Nos blades, blade thickness size 1.1 mm power factor 0.9 complete with all accessories like- Nut, bolts ,Clamp and down road and speed regulator remote control etc as required suitable for operation on 230 volts, 50 Hz AC supply. Guarantee period will be 03 years. | — | — | — | 1,31,500 | |
| — | 10.00 | — | — | ||
| Supply, installation, testing and commissioning of Exhaust fan 380 mm sweep, 1400 rpm metallic body heavy duty with louvers shutter on the wall grouting of MS Nut and bolt 3/8" dia, connection with PVC insulated flexible copper conductor complete in all respect. Exhaust fan shall conforming IS: 2312/1967(latest version). | — | — | — | 21,500 | |
| — | 36.00 | — | — | ||
| Supply, fixing, connecting and commissioning of bus bar chamber (size 450Wx 300Dx 600H) double door & canopy with best quality powder coating made by 1.6 mm CRCA sheet complete with 100 Amps aluminium bus bar phase & neutral 20x5 mm, 4 way suitable for 415 volts 50 Hz AC supply with heat shrinkable sleeve & SMC /DMC support and 01 No. MCCB 100 Amps four pole 36 KA thermal magnetic released based including RYB indication. | — | — | — | 9,13,320 | |
| — | 3.00 | — | — | ||
| Supply, fixing, connecting and commissioning of bus bar chamber (size 450Wx 300Dx 600H) double door & canopy with best quality powder coating made by 1.6 mm CRCA sheet complete with 200 Amps aluminium bus bar phase & Neutral 20x10 mm , 4 way suitable for 415 volts 50 Hz AC supply with heat shrinkable sleeve & SMC /DMC support and 01 No. MCCB 200 Amps four pole 36 KA thermal magnetic released base including RYB indication. | — | — | — | 97,350 | |
| — | 210.00 | — | — | ||
| Supply, installation, testing & commissioning of Metal clad plug & Socket DBs with 16A, 220V (1P+N+E) DP MCB with enclosure etc. at suitable place as per direction of engineer in- charge at site for welding point & for connection of other machines in shop in all respect. | — | — | — | 4,71,450 | |
| — | 150.00 | — | — | ||
| Supply, installation, testing & commissioning of Metal clad plug & Socket DBs with 32A, 440V (3P+N+E) TP MCB with enclosure etc. at suitable place as per direction of engineer in- charge at site for welding point & for connection of other machines in shop in all respect. | — | — | — | 7,05,000 | |
| — | 40.00 | — | — | ||
| Supply, installation, testing & commissioning of Metal clad plug & Socket DBs with 63A, 440V (3P+N+E) TP MCB with enclosure etc. at suitable place as per direction of engineer in- charge at site for welding point & for connection of other machines in shop in all respect. | — | — | — | 2,64,000 | |
| — | 400.00 | — | — | ||
| Supply and fixing of MS sheet frame made by 1.6 mm thick of size 375 X mm X 375 mm for fixing of industrial type Plug and socket enclosure 16/32/63 Amps IP 40 protection with MCB on the MS column as per direction of engineer in charge at site. | — | — | — | 2,30,000 | |
| — | 500.00 | — | — | ||
| Supply & welding / fixing of fabricated M.S. angle support size 40 x 40 x 5 mm duly painted with 04 slots of 10x 18 mm size duly red oxide primered. Standard length 450 mm long centre distance between slots /conductor 50mm required at entry one meter on straight run. | — | — | — | 89,760 | |
| — | 500.00 | — | — | ||
| Supply, fixing & connecting testing and commissioning of 125 Amps capacity 04 bars DSL M-type or V type, resistance -0.00193 ohm of G.I RYBG minimum voltage 600 volts, Type of insulation- PVC carbonate sleeve including joint with suitable bolted joints with suitable bolts, joints, joint cover end cap, power feed kit. | — | — | — | 6,09,975 | |
| — | 18.00 | — | — | ||
| Supply, fixing & connecting of current collector set capacity 125 Amps with nylon shoe holder, structure - metallic, mounting distance from conductor-127 mm and mounting bracket- 25 Sq.mm bar one meter cable to feed the supply of EOT crane | — | — | — | 39,619.8 | |
| — | 500.00 | — | — | ||
| Supply, installation, connecting, testing and commissioning of 4 pole hanger clamps for DSL bars suitable for 1100 volts AC Supply as per site requirement. | — | — | — | 90,060 | |
| — | 9.00 | — | — | ||
| Dismantling of existing over head copper wire of erecting and CRS shop as per direction of engineer in charge at site and handed over to the SSE/Elect/PM (including bracket insulator clamps etc.) | — | — | — | 90,000 | |
| — | 600.00 | — | — | ||
| Laying of 01 No. XLPE L.T. cable 1100 volts 4 core of size up to 240 Sq.mm direct in the ground at a depth of 01 metre below ground level & 350 mm wide including excavation of cable trench, sand cushioning protective with second-class bricks approx 10 bricks per Mtrs & refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trenches per IS: 1255/1983. Note:- XLPE L.T Cable will be supllied by the railway. | — | — | — | 66,216 | |
| — | 1000.00 | — | — | ||
| Laying of 01 No. additional XLPE L.T. cable 1100 volts 4 core of size up to 240 Sq.mm direct in the ground above made trench (Vide item No. 46) at a depth of 01 metre below ground level & 350 mm including excavation of cable trench and sand cushioning protective with second- class bricks approx 10 bricks per mtrs & refilling of cable trench with solid earth consolidating by ramming by 270 mm above the surrounding level over trenches per IS: 1255/1983. Note:- XLPE L.T Cable will be supllied by the railway. | — | — | — | 42,570 | |
| — | 1500.00 | — | — | ||
| Laying, Fixing and connecting of 4 core, 25/95/120/240/300 Sq. mm XLPE (LT) cable with the help of M. S. clamp on the wall as well as on the M.S structure as per site requirement. | — | — | — | 21,945 | |
| — | 35.85 | — | — | ||
| Design, Manufacturing, supply, fixing, connecting & commissioning of cubical type LT. switch board panel of size (2.0 m x 1.5 m x 0.8 m) made by CRCA sheet 2.0 mm sheet and supply & providing of sub copper bus-bar for connecting bus coupler MCCB 800 Amps, and main copper bus bar to outgoing MCCBs fedders, outgoing MCCBs will be connected with aluminium lugs through cable glands and wiring of meter, indication lamp etc as required with suitable for size of copper conductor cable. The switch board panel & accessories shall conform to as per CPWD's "General specification for Electrical works, chepter-7/2023" with the following accessories:- Note:- 03 Nos L.T Panel (2.0 m x 1.5 m x 0.8 m) | — | — | — | 2,07,815.28 | |
| — | 6.00 | — | — | ||
| Supply, fixing, connecting & commissioning of incoming L.T ACB 4 Pole, 800 Amps. with microprocessor released IPR 1+ Draw out type, Rated Ultimate Short circuit breaking capacity Ics =100 % Icu at 415 Volts 65 KA conforming to IS/IEC 60947-2. ACB will be connected with bus bar separaters of suitable size with nuts, bolts and washer including aluminium lugs with nuts, bolts and washer for connecting incoming/outgoing cables. Note: Make acceptable ABB , L&T, Seimens, Havells and Scheneider | — | — | — | 20,08,680 | |
| — | 100.00 | — | — | ||
| Supply, fixing, testing and commissioning of Main copper bus- bar 1000 Amps with insulator crimping socket making of proper holes in the bus bar, suitable for operation on 415 volts, 50 Hz., AC supply and crimping of all type aluminium crimping socket with nut, bolts & washer then connection of cables complete in all respect. Note: Make acceptable ABB , L&T, Seimens, Havells and Scheneider | — | — | — | 77,600 | |
| — | 3.00 | — | — | ||
| Supply, installation, testing and commissioning of MCCB 630 Amps, 04 poles, braking current 45 kA, at 415 Volts, 50 Hz, adjustable thermal released range 100 %., Ics =100 % Icu including hardware and insulator as required conforming to IS/IEC 60947-2. ( As Bus coupler). MCCB will be connected with main bus bar, bus bar separaters of suitable size with nuts, bolts and washer including aluminium lugs with nuts, bolts and washer for connecting bus bars. Note: Make acceptable ABB , L&T, Seimens, Havells and Schneider | — | — | — | 1,66,365 | |
| — | 12.00 | — | — | ||
| Supply, installation, testing and commissioning of outgoing MCCB 400 Amps, 04 poles, braking current 36 kA, at 415 Volts, 50 Hz, adjustable thermal released range, Ics = 100 Icu % including hardware and insulator as required conforming to IS/IEC 60947-2. MCCB will be connected with bus bar separaters of suitable size with nuts, bolts and washer including aluminium lugs with nuts, bolts and washer for connecting bus bars/outgoing cables. Note: Make acceptable ABB , L&T, Seimens, Havells and Scheneider | — | — | — | 4,60,200 | |
| — | 12.00 | — | — | ||
| Supply, installation, testing and commissioning of outgoing MCCB 200 Amps, 04 poles, braking current 25 kA, at 415 Volts, 50 Hz, thermal released range 200-250 Amps., Ics = Icu 100 % including hardware and insulator as required conforming to IS/IEC 60947-2. MCCB connected with bus bar separaters of suitable size with nuts, bolts and washer including aluminium lugs with nuts, bolts and washer for connecting bus bars/outgoing cables. Note: Make acceptable ABB , L&T, Seimens, Havells and Scheneider | — | — | — | 2,28,000 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing and commissioning of Outgoing MCCB 100-125 Amps, 04 poles, braking current 25 kA, at 415 Volts, 50 Hz, adjustable thermal released range, Ics =100 % Icu including hardware and insulator as required conforming to IS/IEC 60947-2. MCCB will be connected with bus bar separaters of suitable size with nuts, bolts and washer including aluminium lugs with nuts, bolts and washer for connecting bus bars/outgoing cables. Note: make acceptable ABB , L&T, Seimens, Havells and Scheneider | — | — | — | 34,800 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing and commissioning of LED Multifunction Meter, accuracy class 1 with RS-485, input voltage measurement range 17-520 VAC, Aux supply 90-300 VAC, flush mounted 96 x 96 mm, Parameters: V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Events( High -Low), Neutral Current, K Factor. (For Incomming). | — | — | — | 56,790 | |
| — | 108.00 | — | — | ||
| Supply, installation, testing and commissioning of RYB LED Indication lamps for incoming and outgoing feeders. | — | — | — | 7,020 | |
| — | 95.00 | — | — | ||
| Supply, installation, testing & commissioning of heavy duty bracket type 700 mm sweep air circulator fan single phase RPM 1400 ± 5% , three blades suitable for 230V, 50Hz without regulator AC supply having air replacement 370 CM per minutes, the propeller should be cast aluminium. Yellow & confirming to IS:2997/64 with amendment 1 to 5 air circulating fan should be wall mounting /MS piler mounting. The air-circulating fan will be mounted/fixed on MS piler (in shop shed) with M.S. flats 50 x 6 mm clamps including bolts , nuts & washers etc complete in all respect. Make- Khaitan, Usha, Bajaj, Crompton, Polar, Orient, Havell's, GE | — | — | — | 6,12,920.05 | |
| — | 160.00 | — | — | ||
| Supply, fixing , testing & commissioning of LED Pit Light luminaire of 16 Watt (as per CAMTECH specification) complete with Power Factor > 0.9, input Voltage 48 V AC+10%,Frequency Range 50 Hz, LED matrix 12 LED matrix, Approximate light output 1300-1400 lumens, LED Driver- High brightness driver system, Source- PWM constant current, Reverse polarity protection, Short circuit protection, Open circuit protection, Material and insulation of driver - Fire retardant material (ABS & Polycarbonate), Diffuser- P12 prismatic polycarbonate & toughened glass, Tj (Junction temperature) - Less than 90 degree centigrade of each LED after continuous operation of 12 hours, The whole luminaire fixture shall be provided with high impact resistance i.e.IK10, The whole luminaire fixture shall ensure tightness level of IP67 and all accessories of luminaire shall be prewired upto the terminal block and the connecting lead shall be 3 core (phase, neutral & earth), PVC insulated of suitable size and minimum 1.0 metre long. Note:- LED pit light luminaire should be fixed on the wall with the help of suitable size of aluminium clamp, rawal plug with screw as per direction of engineer incharge at site. | — | — | — | 4,32,000 | |
| — | 2.00 | — | — | ||
| Design, supply, installation, connecting, testing and commissioning of step down 3.0 KVA transformer wall/pole mounting type, input voltage single phase 220 volts ± 10%, 50 Hz, AC supply and output voltage 48 volts ± 10%, AC supply with volt meter, ampere meter, indication lamp, high & low voltage and short circuit protection including made by CRCA sheet 1.6 mm thick with hinged cover locking arrangement and making hole in the bottom for cable entry with cable glands and supply & fixing of cable connector terminals etc as required as per site requirement. Note:- Step down transformer fixed on the wall/pole mounting with the help of suitable size of M.S Clamps including nut, bolts & washer as per direction of ingineer inchareg at site. | — | — | — | 44,000 | |
| — | 25.00 | — | — | ||
| Supply, making, testing and commissioning of Pipe Chemical Gel GI earthing arrangement with 3000 mm length earth electrode, earth electrode outer shell dia. 50 mm, earth electrode inner shell dia. 25 mm, inner shell thickness 3.25 mm, Terminal size 32/10 mm galvanization Outer shell 80-100 microns, inner shell 200-300 microns and conductive material filled complete in all respect and also making of earth pit with massonary work like bricks, mortar and cement with cover plate 16 SWG MS sheet cover plate having locking arrangement including supply, laying & connecting GI earthing strip size 25 mm x 5 mm. from earth pit terminal to equipment/sub- station (Perearthing length approx 5 meters | — | — | — | 2,87,493 | |
| — | 2.00 | — | — | ||
| Supply, Installation, Testing and Commissioning 16 - Meter long .High Mast lighting system complete with the following work : - 1.1 supply of 16 - meter high mast system : - The mast shaft shall be in two section Hot dip Galvanized inside and outside in single dip , suitable for wind velocity as per IS : 875 Part 3. There shall be only one longitudinal seam weld per section and no circumferential weld ,It shall also include accessories for high mast including head frame, 2 Point suspension system with stainless steel wire rope, trailing cable , connector ,6 mm dia double drum winch, galvanized lantern carriage arrangement suitable for 8 luminaries LED type symmetrically arranged . the mast shall have an integral power tool motor , manual handle junction box at the base compartment for its operation. 1.2 supply of foundation bolts manufactured from special steel. along with nuts, washer anchor plates & common template (set 01) 1.3 supply , fixing testing and commissioning of LED flood light fixture 250- watt power factor not less than 0.95 and LED driver should be constant voltage & current, and fitting should be IP 66 - 08 Nos. LED fitting shall conform to BIS specification No. 10322 (Pt.5/sec, 1)/2012 or latest. 1.4 Supply of LED type single dome aviation 21 Supply, fixing, connecting double module obstruction light. 1.5 Design & making of outdoor stand mounted feeder pillar control panel with 63 Amps TPN MCB Incomer, single dial time switch, 45 Amps TP contractor for the automatic switching of luminaries, power tool control with 02 no. 9 Amps contractors and raise lower push button, incoming 35 mm & outgoing 16 & 2.5 mm 2 terminals. (set 01) 46.1:-Supply and making of 02 nos. chemical Gel GI Pipe earthing arrangement with 3000 mm length earth electrode, earth electrode outer shell dia. 50 mm, earth electrode inner shell dia. 25 mm, inner shell thickness 3.25 mm, Terminal size 32/10 mm galvanization Outer shell 80-100 microns, inner shell 200-300 microns and conductive material filled complete in all respect and also making of earth pit with massonary work like bricks, mortar and cement with cover plate 16 SWG MS sheet cover plate having locking arrangement including supply, laying & connecting GI earthing strip size 25 mm x 5 mm. from earth pit terminal to high mast. 46.2:-2. Erection Part:- 2.1 Design construction & erection of suitable shallow foundation with M20 concrete for the high mast considering the safe soil bearing capacity at site as 10 T/ sq.mtr at 2 mtr depth. with all material & labour (Job-01). 46.3:-2.2 Erection of the high mast with the help of suitable equipment and wiring of luminaries with all wiring material like PVC insulated, PVC sheathed flexible cable of suitable copper conductor, cable lugs, MCB etc and all labours. 46.4:-(Successful Tenderer shall submit WARRANTEE GUARANTEE (WG) @ 10% of the Contract Value of this item in the prescribed proforma before claiming the payment for this item.) Note: High Mast and LED flood light fixture 250 Watt shall be guaranteed/warranted for a period of 60 months from the date of commissioning for satisfactory performance. | — | — | — | 7,91,492 | |
| — | 2.00 | — | — | ||
| Making of hexagonal platform foundation with Rail post and including all accessories for high mast lighting tower in yard and good siding as per CEE's Drg No. L/CEE/GKP/2010/2 as enclosed with all materials. Note:-1.Only rail pole will be supplied by therailway.2. Cutting of rail post 1750 mm length (each) is included in the scope of work. | — | — | — | 20,512 | |
| — | 400.00 | — | — | ||
| Supply, laying and fixing of Hot Dip Galvanized as per IS: 2629/4759 perforated type cable tray of sizes 100 mm x 200 mm x100 mm, 2.0 mm thick with coupler including nuts, bolts, washers on the existing strucure for cable laying. Note :- Make acceptable Aditya steel Industries, Hutaib Electricals, ELCON Global, Super Cable Tray and JP Shine Electrical. | — | — | — | 2,56,000 | |
| — | 400.00 | — | — | ||
| Supply, laying and fixing of Hot Dip Galvanized as per IS: 2629/4759 perforated type cable tray cover of size 15 mm x 205 mm x15 mm, 1.2 mm thick on the above item including nut, bolts & washer tec. as required. Note:- Make Aditya steel Industries, Manibhadra Electrical Pvt.Ltd. | — | — | — | 1,22,400 | |
| — | 50.00 | — | — | ||
| Supply, laying and fixing of Hot Dip Galvanized as per IS: 2629/4759 perforated type cable tray Tee 200 mm x 100 mm 2.0 mm thick with coupler including nuts, bolts, washers on the existing structure for cable laying. Note:- Make acceptable Aditya steel Industries, Hutaib Electricals, ELCON Global, Super Cable Tray and JP Shine Electrical. | — | — | — | 96,000 | |
| — | 200.00 | — | — | ||
| Supply, laying and fixing of Hot Dip Galvanized as per IS: 2629/4759 perforated type cable tray elbow bend of sizes 100 mm x 100 mm x100 mm, 2.0 mm thick with coupler including nuts, bolts, washers on the existing strucure for cable laying. Note:- Make acceptable Aditya steel Industries, Hutaib Electricals, ELCON Global, Super Cable Tray and JP Shine Electrical. | — | — | — | 96,000 | |
| — | 200.00 | — | — | ||
| Supply, laying and fixing of Hot Dip Galvanized as per IS: 2629/4759 perforated type cable tray cover of size 15 mm x 105 mm x15 mm, 1.2 mm thick on the above item including nut, bolts & washer tec. as required. Note :- Make acceptable Aditya steel Industries, Hutaib Electricals, ELCON Global, Super Cable Tray and JP Shine Electrical. | — | — | — | 35,200 | |
| — | 200.00 | — | — | ||
| Design, Fabrication, Supply and Fixing of supporting clamps made by 40 mm X 40 mm x 5 mm MS angle iron including greenish grey paint for holding of Hot Dip Galvanized/Powder coated perforated type cable tray of 200 mm widths x100 mm height x 2500 L, 2.0 mm thickness with cover plate on the existing structure including welding of MS angle iron frame as per drawing on existing structure, nuts & bolts etc. for fixing of cable tray on the existing structure as per direction of engineer inchagre at site. | — | — | — | 2,50,000 | |
| — | 6.00 | — | — | ||
| Supply, fixing, connecting & commissioning of TPN distribution board 4 way shall conforming to IS:8623-12 & 3,IEC61439-1 &3, IK for double door made by CRCA sheet steel, powder coated, provided with 100 Amps insulated phase bus bars /Neutral bar/Earth bar, colour coded inter connecting wire set, cable ties, planking plates ,circuit identification lable with provision for 4 pole MCCB as incomer, DP as sub incomer and SP MCB as outgoings. IP 43 with metal door including supply , fixing and connecting of 01No. MCB 4 pole - 63 Amps "C" Curve, 06 Nos. MCB DP - 20 Amps. "C" Curve and 12 Nos.- MCB SP 10 amps. "C" Curve. | — | — | — | 1,75,170 | |
| — | 3.00 | — | — | ||
| Design, Fabrication, Supply, Installation, Testing and commissioning of Automatic Power Factor Correction Panel 200 KVAR suitable for operation on 3 phase 415 Volt, 50 Hz. AC supply, Super heavy duty cylindrical capacitor - 03 Nos. - 50 KVAR, 01 Nos.-25 KVAR, 01 No. - 10 KVAr and 03 Nos.- 5 KVAR, Main incoming MCCB 400 Amps., breaking capacity-35 KA, Icu =100 % Ics including hardware and insulator as required conforming to IS/IEC 60947-2 and connecting of incoming and outgoing cables with suitable size of aluminium lugs, nuts, bolts and washer etc.as required. Note:- The APFC Panel shall conforming to IEC:61921/IS:16636 ( For 01 No for new shed & 02 Nos for erecting shop) Make:- Havells L&T and Schenieder | — | — | — | 17,09,100 | |
| — | 160.00 | — | — | ||
| Supply, Installation, Testing and commissioning of High bay LED luminaires 100 watt, Next generation, energy saving, environment friendly & robust high bay LED with PDC housing suitable for ceiling (Surface/Suspended) mounting with system efficacy 12000 lm, Efficacy > 120 lm/ Watt, Beam angle 120 degree, power factor > 0.95, Ingress protection: IP:66, colour rending index > 70, THD < 10 % , operating temp. range -10 degree to 50 degree centigrade suitable for operation on 140 volts to 270 volts ,50 Hz AC Supply with the following protection;- Over voltage & under voltage protection, Short circuit protection, Reverse polarity protection , Over temperature protection & Built in Surge protection. complete with hardware for mounting in the workshop shed. Make:- Havells, Bajaj, Philips, Goldwyn and Schneider. Note:- High mast LED luminaires should be fixed on the shed structure with the suitable size of M.S Clamps, nuts, bolts and washer etc.required. | — | — | — | 22,40,000 | |
| — | 7.25 | — | — | ||
| Design, Manufacturing, supply, fixing, connecting & commissioning of cubical type LT. switch board panel of size (1.5 m x 1.0 m x 0.8 m) made by CRCA sheet 2.0 mm sheet and supply & providing of sub copper bus-bar for connecting bus coupler MCCB 800 Amps, and main copper bus bar to outgoing MCCBs fedders, outgoing MCCBs will be connected with aluminium lugs through cable glands and wiring of meter, indication lamp etc as required with suitable for size of copper conductor cable. The switch board panel & accessories shall conform to as per CPWD's "General specification for Electrical works, Part-IV Substation-2013" with the following accessories:- | — | — | — | 42,026.8 | |
| — | 15.00 | — | — | ||
| Supply, fixing, testing and commissioning of Main copper bus- bar 300 Amps with insulator crimping socket making of proper holes in the bus bar, suitable for operation on 415 volts, 50 Hz., AC supply and Crimping of all type aluminium crimping socket then connection of cables complete in all respect. | — | — | — | 11,640 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of outgoing MCCB 200 Amps, 04 poles, braking current 25 kA, at 415 Volts, 50 Hz, thermal released range 200-250 Amps., Ics = Icu 100 % including hardware and insulator as required conforming to IS/IEC 60947-2. MCCB will be connected main bus bar with bus bar separaters of suitable size with nuts, bolts and washer including aluminium lugs with nuts, bolts and washer for connecting bus bars. Note: Make acceptable ABB , L&T, Seimens, Havells and Scheneider | — | — | — | 19,000 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing and commissioning of Outgoing MCCB 63 Amps, 04 poles, braking current 25 kA, at 415 Volts, 50 Hz, adjustable thermal released range, Ics =100 % Icu including hardware and insulator as required conforming to IS/IEC 60947-2. MCCB will be connected main bus bar with bus bar separaters of suitable size with nuts, bolts and washer including aluminium lugs with nuts, bolts and washer for connecting bus bars. Note: Make acceptable ABB, L&T, Seimens, Havells and Scheneider | — | — | — | 34,800 | |
| — | 1.00 | — | — | ||
| Supply, installation, testing and commissioning of LED Multifunction Meter, accuracy class 1 with RS-485, input voltage measurement range 17-520 VAC, Aux supply 90-300 VAC, flush mounted 96 x 96 mm, Parameters: V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Events( High -Low), Neutral Current, K Factor. (For Incomming). | — | — | — | 9,465 | |
| — | 21.00 | — | — | ||
| Supply, installation, testing and commissioning of RYB LED Indication lamps for incoming and outgoing feeders. | — | — | — | 1,365 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing and commissioning Vertical Filing Cabinet 4 Drawer VFC of size Length 47 CM Depth 62 CM Height 132 CM. Features : - Smooth drawer movement with precision telescopic slider mechanism • An anti-rebound mechanism to prevent the drawer from coming out after it is pushed in • An anti-tipping mechanism that allows only one drawer to be opened at a time to prevent toppling over of the cabinet. Make Godrej | — | — | — | 1,45,956 | |
| — | 6.00 | — | — | ||
| Supply, installation, testing and commissioning (Level 6 & above office) of Revolving Chair Godrej make Model Premier and mid back with fixes arm, height adjustable, rotatable and free moving wheels.Note:- For Dy CEE/IZN office. | — | — | — | 61,596 | |
| — | 5.00 | — | — | ||
| Supply, testing and commissioning of Compressed air Duster 48000RPM 2 speed copper motor, Air Blower, Air Spray portable Black , power full motor 500 watt, complete with 300 ml rubbing alcohol & repair screw driver set 110 in 1. | — | — | — | 19,225 | |
| — | 2.00 | — | — | ||
| Supply, installation, Testing and commissioning of 500 KVA Capacity, 11/0.415 KV, 3 phase, 50 HZ., indoor type copper wound transformer, Delta/Star DYn11, ONAN cooled with off circuit tap changer having range -5 % to + 10% in steps of 2.5 each with first filling of oil complete in all accessories transformer should be Energy Efficiency Level-2 as per IS:1180 (Part-I) 2014 with latest amendments. Note:- Transformer incoming termination kit will be connected with suitable size of bus bar separator including nuts, bolts and washer etc as required and outgoing cable will be connected with suitable size of aluminium lugs with nuts, bolts and washer etc. as required. | — | — | — | 53,10,000 | |
| — | 2.00 | — | — | ||
| Jointing, connecting & commissioning of heat shrinkable indoor type end termination kit for 11 KV X.L.P.E. (H.T.) Aluminium conductor cable 3 core 70 sq. mm.as direction of Engineer In- charge at site complete in all respect. Note:-Heat Shrinkable outdoor type termination Kits will be supplied by the railway at site. | — | — | — | 4,880.48 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
Transformer500KVASpecification.pdf
ATTACHMENT
SpecialTermsandConditionsfor60to120wagon_2.pdf
ATTACHMENT
GCC_April-2022.pdf
ATTACHMENT
Correctionslip1.pdf
ATTACHMENT
FormofcompletioncertificateofElectricalwiringinstallation.pdf Form of completion certificate
ATTACHMENT
PipeEarthingdrawing.pdf
ATTACHMENT
TechnicalspecificationofHighmast60to120.pdf
ATTACHMENT
LTPanelspecification.pdf
ATTACHMENT
FormofcompletioncertificateofElectricalwiringinstallation.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .