EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
RNB ELECTRIC DIVISION KASHMIR ENGINEERING COMPLEX
Installation of Main control panel LED lights and replacement of Damaged electric wiring at DC Residence Kulgam
2025_PWDJK_299444_1
NIT No.243/2025-26 Dt/29/12/2025
Open Tender
Electrical Works
Percentage
15 days
kulgam
Please refer Tender documents.
4 documents required · 4 mandatory
₹300
EXECUTIVE ENGINEER RNB ELECTRIC DIVISION KASHMIR
₹11,221
30 Dec 2025
30 Dec 2025
15 Jan 2026
30 Dec 2025
14 Jan 2026
30 Dec 2025
Supply, installation , testing and commissioning of 3 star rating 2 Ton Inverter type split Air Conditioner (Hot & cold) suitable for operation on AC supply single phase 50Hz 230V with hermetically sealed inverter compressor with air cooled condenser latest R410A/ R-32 refrigerant fan motor, start and run capacitors, relay and over load protector internal unit with one indoor and one outdoor unit. The indoor unit fitted on wall by employing suitable clamps and the outdoor unit will be placed on angle iron stand fitted with nut/bolts outside the room to avoid noise, including standard length of suitable size copper tubing covered with nitrilic foam, topping up with refrigerant for additional length of piping if required, PVC flexible drain pipe, suitable capacity 3 core sheathed/ PVC insulated copper cable and a battery operated wireless remote unit. The job includes repairs to walls wherever the same are cut and the AMC of AC for a period of one year from date of successful commissioning. (Daikin/ Blue Star/ LG/IFB/ eq. make to be approved by EIC).
Supply, installation , testing and commissioning of 3 star rating 1.5 Ton Inverter type split Air Conditioner (Hot & cold) suitable for operation on AC supply single phase 50Hz 230V with hermetically sealed inverter compressor with air cooled condenser latest R410A/ R-32 refrigerant fan motor, start and run capacitors, relay and over load protector internal unit with one indoor and one outdoor unit. The indoor unit fitted on wall by employing suitable clamps and the outdoor unit will be placed on angle iron stand fitted with nut/bolts outside the room to avoid noise, including standard length of suitable size copper tubing covered with nitrilic foam, topping up with refrigerant for additional length of piping if required, PVC flexible drain pipe, suitable capacity 3 core sheathed/ PVC insulated copper cable and a battery operated wireless remote unit. The job includes repairs to walls wherever the same are cut and the AMC of AC for a period of one year from date of successful commissioning. (Daikin/ Blue Star/ LG/IFB/ eq. make to be approved by EIC).
Supply, installation , testing and commissioning of relay type voltage stabilizer suitable for 2 Ton AC operating from input voltage 90-260Volt thereby producing output voltage of 230volts +_ 3%. (5 KVA) V-Guard/ LIV- Guard.
Supply, installation , testing and commissioning of relay type voltage stabilizer suitable for 1.5 Ton AC operating from input voltage 90-260Volt thereby producing output voltage of 230volts +_ 3%. (4 KVA) V-Guard/ LIV- Guard.
Supply and installation of 32A modular plug/socket with 32A DP MCB for AC
Supply, installation, testing and commissioning of 12 Watt LED recessed/ mounted (round or square) Down lighters having aluminum body, minimum 80lm/w, average life 50000 hours, LM79 & LM80 test report should be from Govt. Approved NABL lab / Govt. Of India , Operating temperature -10`C to +45`C. The job includes replacement warranty of fixture if damaged/ burnt out what so ever reason for a period of two years reckoned from the date of successful commissioning/ handing over of site to the intending department. (Havells/ Philips/ Crompton/ Jaguar/Wipro/ eq. make to be approved by EIC). Commercial series (warm)
Supply and installation of frost free double door type 242 ltr. refrigerator with full sized freezer on top, smart inverter compressor.(3 star) LG/ Samsung/ eq. make to be approved by EIC
Supply and installation of 28 ltr. Free standing microwave oven curd making (wire rack type) with child safety lock. LG/ Samsung/ eq. make to be approved by EIC
Supply and installation of free standing dish washer with 13-15 place settings capacity, Eco silence drive, Glass protection, extra dry and hygienic wash. Bosch/IFB/ eq. make to be approved by EIC
Wiring for sub mains along with earth wire in FRLS PVC insulated 660/1100volt grade flexible stranded copper conductor wires in recessed or surface conduiting system, excl. cost of conduits(Havells/ Polycab/ Finolex/ Anchor/KEI/RR or eq.)
2 x 6.0 sq.mm + 1x 6.0 sq. mm wiring for AC points.
4 x 16.0 sq.mm + 2x 6.0 sq. mm Heating Sub main
Supply, installation, testing and commissioning of 63A TPN MCB rating 240/415V, 10 KA “C” curve MCB suitable for inductive load in the MCB distribution board complete with necessary connections. (Havells/ Legrand/ Indo Asian/ Schneider/ eq. make to be approved by EIC)
Supply and fixing of 25 mm dia. Medium class PVC conduit along with accessories in surface / recess, incl. cutting the wall and making good the same or fixed with nails/screws with rawlplugs or as required
SITC of wall/free standing floor mounted (Outdoor type) dust and vermin proof compartmentalized cubical panel for electrical Works, made out of CRCA sheet. Other parameters required as per point(a) Thickness of sheet shall not be less than 1.6 mm up to 600 mm length/width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required. Side walls and cable alley compartment shaving bolted type doors with/without detachable extension type structure (b) Panel shall be duly treated for derusting in 7 tank process with de phosphating and with powder coating of minimum 70 microns on both side of panel in desired shade The panel having PU/Neoprene rubber gasket of not less than 3mm thickness, required hardware, separate detachable gland plate M.S. base channel (min 75mm), hinged door with locking arrangement for equipment/switchgear (c) Interconnection between bus bar and switch gears/cable shall be rigidly supported and made out by flexible copper wires (upto 125 amp) and by solid bus bar (> 125). (d) Only outer area on all sides shall be measured & panel to be fabricated only from CPRI approved fabricator, CPRI Test certificates to be submitted) All as per pre approved by Engineer in charge.
Providing and fixing following rating and breaking capacity and pole MCCB with thermo magnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. (Thermal Magnetic type, Adjustable type)
Normal Incoming
200 Amp, 36 KA, FP MCCB
Aluminum Bus Bar 400 Amp set of 4 strips
ON Load Change Over Switch FP 200 amp. (Front operated)
Aluminum Bus Bar 400 Amp set of 4 strips
Outgoing
100 Amp, 10 KA, TPN MCB
63 Amp, 10 KA, DP MCB
Space for 16 way MCBs
Supply, laying, connecting and commissioning of 70 sq. mm 3.5 core PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade Aluminum LT cable from main panel to LT pole , incl. cost of required al. thimbles duly crimped. ( over head/under ground).
Providing of chemical earthing as per IS standards by way of digging 8 feet pit then embedding 2.5 mtr. Long GI earthing electrode, 60 mm dia. Connecting the plate with main control panel by 10 SWG Copper wire with 1/2” dia. Full thread brass nut and bolts and washers, refilling the pit with chemical compound.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.04 MB
BOQ_971425.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .