Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.6 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹20.6 L+₹1.0 L (5.11%)Rejected-Finance 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L2 | Rejected-Finance Being L2 Bidder | |
| 3 | L3₹20.7 L+₹1.1 L (5.62%)Rejected-Finance A 8 SAKHARAM GANESH DAUSKAR SARANI KOLKATA 700 025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | L3 | Rejected-Finance Being L3 Bidder |
Tender Value
Refer Docs
EMD Value
₹42,758
Closing Date
16 Jul 2024, 12:00 pmClosed
Office of the Exe Engr, North 24 pgs EL DIV, PWD,
Office of the Exe Engr, North 24 pgs EL DIV, PWD, kol- 59
Replacement of RAC Machine at various wards under Barasat Government Medical College and Hospital Barasat, North 24 Parganas District. Electrical Work
2024_WBPWD_692337_1
WBPWD/EE/N24/EL/e-NIQ- 105/24-25
Open Tender
MISC ELECTRICAL WORKS
Item Rate
21 days
Barasat
Please refer Tender documents.
4 documents required · 4 mandatory
₹42,758
Office of the Exe Engr, North 24 pgs EL DIV, PWD
1 Sept 2025
12 Jun 2024
18 Jul 2024
12 Jun 2024
16 Jul 2024
19 Jun 2024
18 Jun 2024
Amount
SUB HEAD 1 -- SITC OF AC Supply and delivery of High-wall Split type Air-conditioner machine having the following specification :- Cooling Capacity : 6.6 kW (Minimum) Minimum ISEER : 3.8, BEE levelling - 3 Star (min) [1st July 2022 to 31st December 2024] IS Compliance : IS-1391 (Part-I & Part-II) with all amendments Refrigrant : R410A/ R32 Compressor : Rotary/Scroll with fixed speed Evaporator & Condenser Coil : Copper Operating outdoor temperature : 50ºC and above Power Supply : 230V, 50Hz (±tolerance as per applicable standard) The PCB board of indoor unit should be covered by metallic enclosure. The scope of work is also includes supply of following (i) Necessary refrigerant copper line with nitrile rubber insulation and wrapping tape- 3 mtr. (ii) Necessary 3/4 core copper cable (FRLS type- make- Finolex/Polycab/RR Kabel) - 3 mtr and with 25A plug top with indicator (Legrand/Crabtree/Schneider). (Make- Mitubishi Electric/ O-General/ Zamils).
Supply and delivery of High-wall Split type Air-conditioner having the following specification : Cooling Capacity : 5200 Watt (minimum) Minimum ISEER - 3.8, BEE levelling - 3 Star (min) [1st July 2022 to 31st December 2024] IS Compliance - IS-1391 (Part-I & Part-II) with all amendments Refrigrant : R410A/ R32 Compressor : Rotary/Scroll with fixed speed Evaporator & Condenser Coil - Copper Operating outdoor temperature - 50°C and above Power Supply : 230V, 50Hz (±tolerance as per applicable standard) The PCB board of indoor unit should be covered by metallic enclosure. The scope of work is aIso includes supply of following. (i) Necessary refrigeration copper line with nitrite rubber insulation and wrapping tape - 3 mtr. (ii) Necessary 3/4 core copper cable (FRLS type - make - FinoIex/PoIycab/RR Kabel) - 3 mtr and with 25A plug top with indicator. (Legrand/Crabtree/Schneider). (Make- O-General / Mitsubishi Electric / Zamils)
Installation, Testing & Commissioning of Indoor & Outdoor unit of the above Hi wall Split AC machine after making hole in wall etc as per direction of EIC including supply of required Refrigerant, S&F of necessary fixing arrangement for indoor unit and 40x40x5 mm MS angle iron frame for outdoor unit (or arrangement recomended by Manufacturer), duly painted, laying and making connection of refrigeration pipe, power cable, drain pipe etc as per direction of EIC.
S & F of additional following items for length exceeding 3 mtr. For complete installation and commissioning of above AC machine. (i) Supply & Fixing of extra refrigerant pipe (as requisite dia) with nitrile rubber insulation and wrapping tape (each mtr Refrigerent pipe will include cost of 1 meter liquid pipe line and 1 mtr gas pipe line of required dia and other accessories as required)
S & F of additional following items for length exceeding 3 mtr. for complete installation and commissioning of above AC machine. (i) 2.5 sqmm, 3/4 core copper cable (FRLS type - make : Polycab/Finolex/RR-Kabel)
Supply and Laying Soft Drawn PVC Drain Pipe 19 mm dia with proper supports & brackets as per direction of EIC. (Make- Suprime/ Oriplast)
Supply and delivery of heavy duty Window type Air-conditioner machine having the following specification :- Cooling Capacity : 6050 watt (Minimum) Minimum ISEER : 3.1, BEE levelling - 3 Star (min) [1st July 2022 to 31st December 2024] Refrigrant : R410A/ R32 Compressor : Tropical Rotary with fixed speed Evaporator & Condenser Coil : Copper Operating outdoor temperature : 50ºC and above Power Supply : 230V, 50Hz (±tolerance as per applicable standard) Indoor Airflow Volume : 860 m3/h Moisture Removal : 2.2 I/h The scope of work is also includes supply of following (i) 25A plug top with indicator (Legrand/Crabtree/Schneider). (Make- O-General/Hitachi/Voltas/Carrier) & buy back existing old dismantled 15 nos. 2.0 Ton capacity window type AC machine.
Installation, Testing & Commissioning of the above window AC machine into the existing hole/position in wall etc as per direction of EIC including supply of required Refrigerant and S&F of necessary fixing arrangement or repairing & rectifying incl. painting the existinmg wooden support in wall (if required) and mending good the damages as per direction of EIC.
SUB-HEAD 2 -- MISCELLANEOUS Dismantling of the existing old window/split type RAC machine from its existing position ands shifting the same at safe location as per direction of E.I.C.
S & F of 250V 1-phase Timer DB (equivalent to 12 way SPNDB in size) on wall with double door sheet steel enclosure, neutral bar, din rail, with lP43 protection comprises with 25A DPMCB (C-curve 10kA) and 1 no. 24 hr. Digital time switch (L&T, Crono 67DDTO) and 1 no. 22/25A 2 Pole power Contactor (L&T, MNX- 22 - 2P) complete with internal wiring with suitable size of PVC insulated copper wire with socketting and 2 nos. Connector including 1 no. Toggle switch for auto/manual operation and 1 no. LED indicator lamp and necessary earthing attachment as per direction of EIC. [Make : L&T/ABB/Legrand]
SUB-HEAD 3 -- PVC CONDUIT & COPPER WIRES Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Make- Finolex/ Polycab/ RR Kabel/ KEI) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. 2 x 56/0.3 (4 sqmm) + 1 x 36/0.3 (2.5 sqmm) ECC [1(a-iii) / E- 14]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. b) 2.5 sq mm [9(i) / F-5]
c) 4 sq mm [9(ii) / F-5]
SUB-HEAD 4 -- PLUGS & SOCKETS Supply & Fixing 240 V, 25 A, Modular type AC starter (Make- North West or Brand approved by EIC) with 25A Modular switch type DP MCB (C-Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [17 / E-19]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Make- North West or Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. [5(a)/E-17]
SUB-HEAD 5 -- EARTHING Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. Long With ISI-Medium GI pipe as per GS. [ 2(a)/G-1]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below ground level) complete with cemented brick work (1:6) of 25 cm width duly plastered with cement morter (inside) Cl hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. [3(a)/G-2]
Excavation of soil for installation of Earth Electrode and filling & ramming for Soft Soil. [1(a)/G-1]
Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. [5(d)/G-3]
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. Solid GI wire No. 4 SWG [5(a-i)/G-2]
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall as per GS. [4(a)/G-2]
SKY DECORATIONS PRIVATE LIMITED
MAXCOOL REFRIGERATION CO.
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .