Institute Engineer
IIT Roorkee
Checking, Repairing, Testing , Commissioning of existing Fire Fighting , Fire Alarm System installed at IIT Roorkee Campus
2020_IITR_597215_1
EW/DI/etender/Fire/IITR/02-1
Open Tender
Electrical Works
Works
60 days
IIT Roorkee
as pervtender
7 documents required · 7 mandatory
₹1,000
Yes
Payable To Registrar IIT Roorkee
₹72,500
Yes
10 Jun 2021
14 Nov 2020
7 Dec 2020
14 Nov 2020
4 Dec 2020
25 Nov 2020
14 Nov 2020 - 20 Nov 2020
Amount
Fire Fighting System
Dismantaling of main fire fighting pump motor set from its existing foundation & repairing and servicing of electric driven pump motor 2280 LPM 70 mtr head DSM type pump i/c alignment of pump and replacement of pump accessories mechanical seal, bronze impeller, shaft sleevs packing nut bolt etc as required and 3 phase motor repairing / replacement of worn out shaft & bushes where ever required complete as per site condition.
Dismantaling of pressurisation pump set from its existing foundation & repairing and servicing of electric driven motor 180 LPM 70 mtr head i/c pump alignment and replacement of pump accessories mechanical seal, bronze impeller,shaft sleevs packing nut bolt etc as required and 3 phase motor repairing / replacement of worn out shaft & bushes where ever required complete as per site condition.
Carrying of B check servicing Diesel Engine driven pump sets 2280 LPM 70 mtr head DSM type pump i/c replacement of defective accessories like thermostat valve, ksealent , oil spray nozzle , piston ring set, liner , piston assly, fuel pipe, valve seat set, cyl. head gasket, lub oil supply pipe, O ring, V built, oil seal, fuel & air filter element, K-oil etc. i/c repairing of cylinder head fuel injection pump, radiator clearing, TC calibration, pump servicing and pump alignment, replacement of mechanical seal of pump accessories and alignment of pump etc. complete as per site condition i/c providing of 02 nos 12 volt battery.
Repairing and replacement of defective/worn-out switchgears and accessories in the existing fire fighting electrical panel, main fire pump, jockey pump and engine start panel, battery charcher i/c rewiring / control wiring of suitable size FRLS copper conductor wire complete as per site condition
Providing & fixing of pressure switch in M.S. pipe lineincluding connection etc. as required.
Repairing and servicing of existing first aid hose reel, wall mounting swinging type complete with drum & bracket of MS construction, spray painted in Post office Red, confirming to IS 884/1995 with upto date amendments complete as required
Replacement of existing damage hose reel pipe in existing hose reel drum with thermoplastic hose pipe type-II, 30 mtr. Long, dia 20mm ISI marked IS : 12585 i/e removing old leak pipe from existing hose reel drum etc as required.
Supplying and fixing 63 mm dia, 15 m long RRL hose pipe with 63 mm dia male and female couplings stainless steel duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required :
Supplying, fixing, testing & commissioning of doubleflanged sluice valve of rating PN 1.6 with non risingspindle, bronze/gun metal seat, ISI marked completewith nuts, bolts, washers, gaskets and conforming to IS780 of following sizes as required
80 mm dia
150 mm dia
Dismentaling repairing and re-fixing of the following size C.I. Sluice valve CI body in the existing pipe line i/c relacment of spendle, disc,chuck nut rubber, gaskets nut bolt washer etc as required for smooth working as per site requirment.
200 mm dia
150 mm dia
100 mm dia
80 mm dia
Dismentaling repairing and refixing of following size CI body non return valve in the existing pipe line i/c relacment of inner flap / rubber gaskets nut bolt washer etc as required.
150 mm dia
80 mm dia
Repairs of existing fire fighting underground pipe line by providing, laying, testing & commissioning of following size 'C' class heavy duty MS pipe 100 mm dia conforming to IS 1239/Part - I/1974 and Part - II / 1979 with upto date amendments, of including fittings like MS elbow flange accessories high pressure rubber insertions nuts and bolts, etc, in ground with single coat of 4 mm thick anti corrosive pipe treatment as per IS 10221 ,including excavation / cutting the RCC (up to existing line) manuaily or using RCC Breaker / drill machine i/c pipe accessories etc.complete as required.
Supplying and fixing Single headed external yard hydrant valve with 1 No. 63 mm dia instantaneous FM Gunmetal/Stainless Steel coupling and cast iron wheel, ISI marked,conforming to IS 5290 (type A) with blank Stainless Steel cap and chain as required.
Dismantaling of fire fighting terrace pump set from the existing base frame i/c disconnecting the electrical connections and suction / delivery pipe lines by cutting the rusted nuts bolts and repairing and servicing electric motor driven 450 LPM 35 mt head pump i/c replacement of pump accessories mechanical seal, bronze impeller,shaft sleevs packing nut bolt etc as required and 3 phase motor repairing / replacement of worn out shaft & bushes where ever required complete as required.
Repairing and replacement of defective/worn-out switchgears and accessories in the existing fire fighting electrical panel, including replace / repair of volt meter, amp meter,current trasformer and cotactor,relay, timer etc as required with rewiring of control wiring of suitable size FRLS copper conductor wire, i/c testing, commissioning etc. complete as required.
Supplying and fixing of ABS shut off nozzle for existing hose reel pipe as required.
Providing & fixing of stainless steel internal hydrant coupling for single headed hydrant valve.
Painting (two or more coats) of existing fire fighting pipe line upto 100 mm dia with primer & PO red paint of approved shed complete as required:
Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia gun metal wheel valve with required accessories, pressure gauge and paintingwith synthetic enamel paint of approved shade as required.
Renewing glass panes of thiknees 4 mm with putty and nails wherever necessaryincluding racking out the old putty:
Fire Alarm System
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
Supplying, installation, testing & commissioning of ceiling/wall mounted loud speaker, 3/1.5 Watt in ABS enclosure complete as required.
Supplying, installation, testing & commissioning of manual call box of ABS type in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
S/F of fire extinguishers ABC type 6 kg capacity (ISI maked IS:2878 & TAC approved) complete with initial charge & wall bracket, alongwith supply of all material and labour for proper completion of work.
S/F of fire extinguishers Co2 type 4.50 kg capacity (ISI maked IS:2878 & TAC approved) complete with initial charge & wall bracket, alongwith supply of all material and labour for proper completion of work.
Refilling and testing of fire extinguishers ABC type 6 kg capacity complete with supply of all materials and labour for proper completion of work.
Refilling and testing of fire extinguishers Co2 type 4.5 kg capacity complete with supply of all materials and labour for proper completion of work
Supplying, installation, testing & commissioning fire alarm sounder with facility to make announcement, mounted in M.S. box (16 SWG) with hinged cover plate & suitable for operation with amplifier i/c line matching transformer etc. complete as required.
Supplying, installation, testing & commissioning of manual call boxes of MS construction in surface/recess with stainless steel chain & hammer assembly complete with glass and push button etc. as required.
Providing & fixing of 2 mm thick aluminium base photo luminescent signage with UV protection size 150 mm x 300 mm complete as required.
Supplying, installation, testing & commissioning of intelligent addressable thermal / smoke detector with rate of rise cum fixed tempreature thermistor complete with base as required
Supplying, installation, testing & commissioning of addressable manual call point complete as required.
Supplying, installation, testing & commissioning of addressable horn cum strobe complete as required.
Providing, fixing, testing & commissioning of 15mm dia quartzoid bulb type sprinklers of rating 68 degreecentigrade with required accessories :
Pendent Sprinkler
Upright Sprinkler
After completion of work as above, complete UG fire fighting & fire alarm system both shall be commissioned & tested as required, for HV Aptt,SAC Building and LHC-2 including prepared a list of inventory (existing item and new item) with external system building wise and handed over after make it operational.
After completion of work as above, complete OH fire fighting & fire alarm system both shall be commissioned & tested as required, for Shivalik , Canal View Aptt and Boys Hostel vigyan Kunj including prepared a list of inventory (existing item and new item) with external system building wise and handed over after make it operational.
PARAMOUNT BUILDING SOLUTION
M/S Priasha Enterprises
SUPER INDIA BUILD PRO PVT. LTD.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .