Bill of Quantities
I. No. Qty Items Unit Rate Per Amount
Civil Work Estimate
1 Demolition & Dismantling work
Demolition of RCC work using Hydra
Breacker including stacking of servicable
materials and disposal of unservicable
materials with all lead and lift.Removal Of
Existing Building Foundation and Super
Structure If Any.
Demolition of Brick work and stone
masonry including stacking of serviceable
materials and disposal of unserviceable
b 115 materials with all lead and lift.(ii) In 544.95 Cu.M.
Cement Mortar.Removal Of Existing
Building Foundation and Super Structure
Dismentaling of sheet roofing including
ridges, Hips, Valleys, Gutters etc.
c stacking of serviceable materials and
disposal of unserviceable materials with
all lead and lift.
i 10 (i) G.I.sheet roofing. 47.25 Sq.mt
ii 5 (ii) A.C. sheet roofing. 53.55 sq.mt
Dismentling steel work including
d 2000 distempering and stacking the materials 3.63 Kg.
with all lead and lift.
Dismentling doors, windows, ventilators
etc. (wood or steel) shutters including
chowkhats architraves, hold fasts and
e 2 185.85 Each
other attachment etc. complete and
stacking them with in all lead and lift.
(i)Notexceeding 3 Sq.M. in area.
Removing & Scrapping of Old
deteriorated Plaster of any thickness from
Masonary / R.C.C. member including
stacking of serviceable material &
disposal of un serviceable from site of
work with all lead & lift.
Dismentaling any type tiled of stone floors
laid in mortar including stacking of
g 50 serviceable materilas and disposal of 47.25 Sq.M.
unserviceable materials with all lead and
Excavation for foundation including
sorting out stacking of useful material &
2 disposing of excavated stuff upto 50 mt.
lead. Loose & Soft soil.Excexuted With
Mechanical Effort
a 2309 up to 1.5 mt. depth 115.92 Cu.M.
b 1972 1.5 to 3.0 mt. depth. 128.52 Cu.M.
c 1864 3.0 to 5.0 mt. depth 141.11 Cu.M.
Add extra for Disposing off the excavated
d 100 stuff of above items for lead of (A) 50 m 17.28 Cu.M.
Add extra for Disposing off the excavated
e 100 stuff of above items for lead of (B) 100 m 34.56 Cu.M.
Providing and installing cast in situ single
under reamed piles of specified diameter
and length below pile cap, excluding the
cost of Concrete, steel reinforcement but
f including the cost of boring with bentonite
solution and the length of the pile to be
embedded in pile cap etc. all complete.
(Length of pile for payment shall be
measured upto to the bottom of pile cap) :
i 20 400 mm dia. Piles 638.83 Rmt.
ii 20 450 mm dia. Piles 705.03 Rmt.
Extra over single under ream for
providing additional bulbs in under
reamed piles, under specified diameter
excluding the cost of Concrete, steel
reinforcement (only the nos. of extra
bulbs are to be paid).
t 2 400 mm dia. Piles 813.05 Each
ii 2 450 mm dia. Piles 1103.43 Each
Provdg. & laying cement concrete 1:5:10
(1 cement : 5 course sand : 10 hand
3a 1 broken aggregates 40 mm nominal size) 2492.52 Cu.M.
and curing complete, excluding cost of
form work in foundation & Plinth.
Provdg. & laying cement concrete 1:3:6
(1 cement : 3 coarse sand : 6 hand
3b broken stone aggregates 40 mm nominal
size) and curing complete excluding cost
of form work in
625 (A) Foundation and plinth 2976.00 Cu.M.
Supplying of graded hand brocken stone
3c 231 size of 90 mm to 127 mm at site (Rubble 609.82 Cu.M.
Labour charges for spreading the spouls
90 mm to 127 mm thick layer good earth
filling in voids correcting the grade &
camber comp. with rolling, watering, incl.
preparing thesurface by brushing for
removing all loose or dirts ect.comp.
Provdg. & laying cement concrete 1:4:8
(1 cement : 4 coarse sand : 8 hand
4 5 broken stone aggregates 40 mm nominal 2653.67 Cu.M.
size) and curing complete excluding cost
of form work in foundation& plinth.
Filling available excavated earth
(excluding rock) in trenches, plinth, sides
of foundations etc. in layers not
exceeding 20 cm. in depth consolidation
each deposited layer by ramming and
Conveyance charges of earth lime,
6 murrum, building rubbish, manure,
garbage, sludge, excavated rock, fly ash,
aggregate of any kind etc. comp.
a 100 Conveyance charges 0 km to 1 km 46.63 Cmt
b 100 Conveyance charges 0 km to 2 km 60.69 Cmt
c 6000 Conveyance charges 0 km to 5 km 100.44 Cmt
d 6000 Extra For Lead on Above Item Above 5 9.26 Cmt
e 6000 Extra For Lead on Above Item Above 6 9.26 Cmt
f 6000 Extra For Lead on Above Item Above 7 9.26 Cmt
g 6000 Extra For Lead on Above Item Above 8 9.26 Cmt
Extra For Lead on Above Item Above
Filling in plinth with sand under floors
including watering, ramming,
consolidating, compacting and dressing
etc. completed.
Filling in foundation and plinth with
murrum or selected soil in layers of
7b 150 cm. thickness including watering, 286.20 Cmt
ramming and consolidating etc.
Brick work using common burnt clay
building bricks having crushing strength
8 not less than 35 kg/Sq. cm. in cement
mortar 1:6 (1 cement : 6 fine sand)
conventional brick
a 109 (a) in foundation & Plinth 3981.21 Cu.M.
b 532 Super structure Upto Floor Two Level 4253.46 Cu.M.
c 567 Super structure Above Floor Two Level 4293.55 Cu.M.
I.Half brick masonry in common burnt
clay building bricks having crushing
strength note less than 35 Kg/Sq. Cm. in
cement mortar 1:4 (1 cement : 4 coarse
sand) using conventional brick in Super
structure upto floor Four level
a 476 All Floor Level 646.70 Sq.M.
Providing and laying controlled cement
concrete of M-25 Grade and curing
complete, Excluding the cost of form
work, Scaffolding, cost of reinforcement
for reinforced concrete work For any
Height up to any FloorLevel.
a 54 Foundations,Raft,Footings,Mass concrete 4238.04 Cu.M.
b1 2 RCC Retaining wall at All Floor 4519.88 Cu.M.
Tie-Beam, Lintel , Beam- Bracket, Stair
Case & Landing, Coping ,Slab, balcony,
weather shed, loft , any cantilever etc All
Columns,Pillars, posts and struts at All
Providing and laying controlled cement
concrete of M-20 Grade and curing
complete, Excluding the cost of form
work, Scaffolding, cost of reinforcement
for reinforced concrete work For any
Height up to Floor Four Level.
a 10 Foundations,Raft,Footings,Mass concrete 3977.88 Cu.M.
Tie Beam , Lintel , Beam- Bracket
b1 175 Coping ,landing, Slab, balcony, weather 4460.36 Cu.M.
shed, loft , any cantilever etc at All Floor
c1 3 Column at All Floor 4558.20 Cu.M.
d1 1 Stair Case All Floor 5418.91 Cu.M.
Providing and laying in position Ready
Mixed M250 grade concrete for reinforced
cement conctere work , using cement
content as per approved Design Mix
manufactured in fully automatic batching
plant and transported to site of work in
transit mixer for all lead having
continuous agitated mixer, manufactured
as per mix design of specified grade for
reinforced cement concrete work
including pumping of R.M.C. from transit
mixer to site of laying with all lead and lift,
excluding the cost of centering shuttering
finishing and reinforcement including cost
of admixtures in recommended
proportions as per IS: 9103 to accelerate/
retard setting of concrete, improve
workability without impairing strength and
durability as per direction of the Engineer
- in charge. Without Fly Ash (Min cement
level as per latest IS 456 shall be
maintained) (Cement level 450 kg )
Providing and laying in position Ready
Mixed M200 grade concrete for reinforced
cement conctere work , using cement
content as per approved Design Mix
manufactured in fully automatic batching
plant and transported to site of work in
transit mixer for all lead having
continuous agitated mixer, manufactured
as per mix design of specified grade for
reinforced cement concrete work
including pumping of R.M.C. from transit
10.4 10 mixer to site of laying with all lead and 4793.10 Cu.M.
lift, excluding the cost of centering
shuttering finishing and reinforcement
including cost of admixtures in
recommended proportions as per IS:
9103 to accelerate/ retard setting of
concrete, improve workability without
impairing strength and durability as per
direction of the Engineer - in charge.
Without Fly Ash (Min cement level as per
latest IS 456 shall be maintained)
(Cement level 400 kg )
Drilling suitable holes in reinforced or
plain cement concrete with power driven
drill machine to a minimum depth of
80mm upto 250mm in RCC beams,
lintels, columns and slabs to introduce
10.5 steel bars for sunshades/balconies
including fixing the steel bars in position
using Hilti Chemical HY200-R but
excluding the cost of reinforcement, all
complete as per direction of Engineer-In-
8 mm Dia in 80 mm Deep & 12 mm Dia
10 mm Dia in 100 mm Deep & 14 mm Dia
12 mm Dia in 120 mm Deep & 16 mm Dia
16 mm Dia in 160 mm Deep & 20 mm Dia
d 90 608.63 Each
20 mm Dia in 200 mm Deep & 25 mm Dia
25 mm Dia in 250 mm Deep & 32 mm Dia
Providing and laying controlled cement
concrete 1:2:4( 1cement : 2 coarse sand :
4 Graded stone aggregate 20 mm
11 nominal size ) and curing complete,
Excluding the cost of form work and
reinforcement for reinforced concrete
a 4 Foundations, footings, base of 3923.53 Cu.M.
columns,grade slab and mass concrete.
slab, landing shelves, Balconies, lintels,
b 1 beams, girders, and cantilever, up to 4012.47 Cu.M.
aany floor level.
P/A Trimix with dewatering machine and
floater machine on constructed R.C.C.
c 1535 54.00 Sqmtr
work incl. cost of machine and labour etc.
comp. as directed.
Making 15 mm Groove in R.C.C work on
d 550 road and filling it with poly sulfied selant 30.00 Rmt
and finished it good incl. all labour
charges etc. comp. as directed
Providing and laying and fixing 25 mm
thick expansion joint by hydrocell semi
rigid UV resistance with high performance
e 14 738.13 Sqmt
laminated closed cell polythene foam joint
filler in sheet foam as directed, etc.
Providing form work in ordinary timber
planking so as to give a rough finish
including centering, shuttering, strutting
and propping etc. height of propping and
centering below supporting floor to celling
not exceeding 4 M & removal of the same
for in situ reinforced or plain concrete
a 1029 (A) Foundation, footings, bases of 171.68 Smt
columns etc. and mass concrete.
b 3359 (B) Flat surface such as soffits of slabs, 252.00 Smt
landing and the like
c 1443 (C) Vertical surfaces such as walls (any 229.95 Smt
thickness) partitions.
(D) Columns, pillars, posts & struts.
d 2480 (1) Square, rectangular, polygonal in plan 297.68 Smt
e 20 (2) Circular or curved in plan. 422.10 Smt
(H) (1) Sides and soffits of beam,
haunchings cantilevers, girders,
bressumers, Coping and lintels not
exceeding 1 M in depth.
(2) Sides and soffits of beam, haunchings
g 10 cantilevers, girders, bressumers and 259.88 Smt
lintels exceeding 1 M in depth.
h 118 (L) chullah hoops, weather sheds, 155.78 Smt
chhajas, carbels etc including edges.
(M) Staircase with-sloping or stepped
i 400 soffits incl. risers & strings excluding 242.55 Smt
Extra for additional height of propping and
centering where the height of propping
and centering exceeds 4 .O M between
j 100 supporting floor to ceiling including 386.48 Smt
temporary brick or stone pillars for
supporting as required. (i)Height more
than 4.0 M.and upto 5.0 M.
Providing T.M.T Fe 500D bar
reinforcement for R.C.C. work including
bending, binding and placing in position
complete up to any floor level..
a 293942.5 All Floor Level 75.46 Kg.
Providing and laying polished Kota stone
slab (Polished / River Finish, Green
colour ) flooring over 20 mm. (average)
thick base of cement mortar 1:6 (1
cement : 6 coarse sand) or lime mortar
1:1.5 laid over and joined with grey
cement slurry including rubbing and
polishing complete.25 mm th.
Providing and laying polished Kota stone
slab 25 mm. thick in Platform ,Riser of
Stair , Skirting, Tread , dado and pillars
laid on 10 mm. thick cement mortar 1:3 (1
cement : 3 coarse sand) jointed with grey
cement slurry including rubbing and
polishing and MAking groove where it is
Required etc. compl
Providing and laying white/Colur glazed
tiles 6 mm thick in flooring treads of steps
and landing laid on a bed of 12 mm thick
cement mortar 1:3 (1 cement : 3 coarse
sand) finished with flush pointing in white
Providing and layingWhite / Colour glazed
tiles of size 600 mmx300mm x 8 mm /
300 mmx 450mm x 8 mm in skirting,
17 290 risers of steps, Floor and dedo on 10 mm. 1426.95 Sq. M.
thick cement plaster 1:3 (1 cement :
coarse sand) and jointed with white
Providing and laying marble stone slab
flooring over 20 mm. (Average) base of
cement mortar 1:6 (1 cement: 6 coarse
18 2 sand) or L.M. 1:1.5 laid and jointed with 2194.63 Sq. M.
grey cement slurry including rubbing and
polishing complete: (A) Marble slab
Providing and laying Vitrified tiles 8 to
mm thick , 24'' x 24'' in flooring treads of
steps and landing laid on a bed of 12mm
thick cement mortar 1:3 (1-cement : 3-
coarse sand) finishing with flush pointing
in white cement.
Providing and laying Vitrified tiles 8 to
mm thick , 24'' x 24'' in skrting risers of
19b 4340 steps and dedo on 10mm thick cement 1130.15 Sq. M.
plaster 1:3 (1cement : 3-coarse sand) and
jointed with white cement slurry
P & L 24" x 24" vitrified 8 mm thick tile
20 mm (average) base of cement mortar
1:6 ( 1cement: 6 coarse sand) on new
surface or fixing on existing flooring by
adhesive material including dismentaling
of existing flooring and jointed with color
cement slurry including finised with flush
pointing & cleaning the surface etc.
complete for Antiskid
Providing and Fixing 18 mm thick
concrete base exposed brick cladding
including surface waterproffing, polymer
19d 68 modified tile adhesive and polymer 3574.35 Sq.M.
modifies tile grout ( grey / white) with
neccesary scafolding etc compl. As per
direction of engg. Incharge.
Providing and Laying Tactile Tile (For
Vision Impaired Persons as per
Strandards) of Size 300x300x9.8 mm
Having with Water Absorption less than
0.5% and Confirming to is:15622 of
Approved Make in all Colours and
Shades in for Outdoor floors such as
19e 160 footpath, Courtyard, Multi models 1663.72 Sq.M.
Location etc., laid in 20 mm Thick Base of
Cement Mortar 1:4 ( 1 Cement :
Course Sand) in all Shapes & pattern
including Grouting the Joints with White
Cement mixed with Matching pigment etc.
Complete as per Direction of Engineer-in-
Providing and laying Ceramics tiles 6 to
8 mm thick in flooring, treads of steps,
20 10 landing and dedo on 12 mm. thick cement 960.47 Sq. M.
plaster 1:3 (1 cement : 3 coarse sand)
and jointed with white cement slurry.
Providing & Laying 18 mm thick Mirror
polish granite For flooring , counter , stair
-riser , tread , skirting , dedo , Jambs etc.
machine cut or chiselled on bed of
cement mortar 1:1 pointing with neat
cement slurry incl. moulding, Making
grooves where it is required etc. comp. as
per instruction of engineer in charge.
Provdg. 20 mm. thick Finish / Mala
cement plaster in single coat on fair side
22a of brick / concrete walls for interior
plastering upto any Floor level and
finished even and smooth in C.M.1:4.
i 6106 All Floor Level 190.58 Sq.M.
Provdg. 20 mm. thick Finish / Mala
cement plaster in single coat plastering
b on ceilings, Beam side and sofits of stairs
upto any Floor level and finished even
and smooth in C.M.1:4.
i 3952 All Floor Level 215.15 Sq.M.
Providing & fixing 23 cm wide chicken
c 1518 mesh jali with nails & then application of 292.59 Sq.mt
15 mm plaster on R.C.C. & masonary
joints as per dir. of engg. In charge.
Providing and mixing water proofing
materials in cement mortar in proportion
d 250 recommended by the manufacturer. etc. 48.77
comp. as per instruction of engineer in
Providing 20 mm th. Double coat Sand
face / Mala Cement Plaster on Walls upto
any Height Above Ground level consisting
23a 3350 of 12 mm th. Backing coat of C.M. 1:3 ( 1 297.68 Sq.M.
cement : 3 Ssand ) & 8 mm th. Finishing
coat of C.M. 1:1 ( 1 cement : 1 sand ) ets.
White / Color washing with lime on
undecorated wall surfaces (two coats) to
give an even shade including thoroughly
brooming the surface to remove all dirt,
dust mortar drops and other foreign
Providing & Applying 3 mm thick External
Wall Rustic Type Texture as per Design
& Make as Approved by Consultants /
Engineer in Charge. Work Includes All
Necessary Scaffolding Work upto Any
Finishing walls with Acrylic Smooth
exterior paint of required shade :New
work (Two or more coat applied @
ltr/10 sqm over and including priming coat
of exterior primer applied @ 2.20 kg/10
P./L. METALIC HERITAGE SURFACE
Providing and fixing of HERITAGE
textured homogeneous wall finishing
system from BAKELITE HYLAM LTD or
equivalent make consisting of a two
component system of (25 kgs per Pack)
made of 92% silica particles coated with
fade resistant pigments, 100% acrylic
polymer bonding agent (5kgs per pack)
24d 25 with the applied thickness of the coating 637.38 Sq.M.
being between 0.8mm-1.2mm to be
applied on acured, smooth level plaster
without keying, as per the
shades/combinations approved, as per
the manufacturer directions, for usages,
tobe applied by an approved applicator of
the manufacturer, as per the directions /
supervision of the engineers in charge, all
complete. Includes All Necessary
Scaffolding Work upto Any Height.
Wall Painting (two coats) with plastic
emulsion / Oil paint of approved brand
and manufacture and of shade required
on undecorated wall surfaces to give an
even shade, over and including a priming
25a 6500 coat with alkali resistance primer of 78.44 Sq.M.
approved brand and manufacture after
thoroughly brushing the surface free from
mortar droppings, and other foreign
matter and also including preparing the
surface even and sand -papered smooth
Extra over above item for every
subsequent coat of of wall painting with
plastic emulsion / Oil paint of approved
Applying two coats of Birla (white cement
based) or Asian (acrylic lapy-putty) or
equivalent & two coats of primer of
approved brand and manufacture on new
wall surface to give an even shade
including thoroughly brushing the surface
free from mortar dropping and other
foreign matter and sand papered smooth.
Providing & Laying & Jointing glazed
stoneware pipes incl. excavation up to
mt.,refilling, trasporting the pipe to work
site, unloading, lowering in trenches,
laying and jointing the pipes in c.m. 1:1
incl. all jointing materials such as cement,
sand, hemp, bitumen as dire. testing the
pipe line to a head of 1.5 mt. and
hydraulic test as dire incl. watering
trenches, spreading , and carting away of
surplus earth within 100 mt.lead as dire.
a 130 23 cm dia. 344.64 Rmt
Providing & Laying & Jointing glazed
stoneware pipes incl. excavation up to
mt.,refilling, trasporting the pipe to work
site, unloading, lowering in trenches,
laying and jointing the pipes in c.m. 1:1
incl. all jointing materials such as cement,
sand, hemp, bitumen as dire. testing the
pipe line to a head of 1.5 mt. and
hydraulic test as dire incl. watering
trenches, spreading , and carting away of
surplus earth within 100 mt.lead as dire.
b 25 15 cm dia 211.05 Rmt
c 15 10 cm dia. 288.23 Rmt
Constructing brick masonry chamber for
under ground C.I. Inspection chamber
and bends with bricks having croshing
strength not less than 35 Kg. Cm2 in C.M.
1:5 C.I. cover with frame (Lightduty)
455mm x 610 mm intenal dimensions
total weight of cover with frame to be not
less than 38 Kg. (Wt. of cover 23Kg.) and
27 18 Wt. of frame 15Kg.) (R.C.C.top slab with 3863.85 No.
1:2:4 mix (1-cement:2-coarse sand:4-
graded stone aggregate 20mm size)
foundation concrete 1:5:10 inside plaster
15 mm thick with cement mortar 1:3
finished smooth with a floating coat of
neat cement on walls and bed concrete
etc. complete.(i) Inside dimensions
mm x 610 mm and up to 850 mm deep
Constructing Manhole with R.C.C. top
slab in 1:2:4mix (1-cement: 2-coarse
sand:4-graded stone aggregate 20 mm
nominal size) foundation concrete 1:3:6
mix (1-cement:3-coarse sand:6-Brick bats
40+50mm size) inside plastering 15mm
thick with Cement Mortar 1:5 (1-
Cement:5-coarse sand) finished with a
floating coat of neat cement and making
channels in cement concrete 1:2:4 mix (1-
Cement:2 -Coarse sand:4-stone
aggregate 20 mm nominal size) finished
smooth complete including curing and
festing (i) Inside size 900mm x 1200mm
and up to 1.5M. deep including C.I. cover
with frame size 560 mm diameter total
weight of cover and frame to be not less
than 128kgs. (Wt. of cover 64Kg. and Wt.
of frame 64Kg.) (A) With 230 mm thick
walls of brick masonry using brick having
crushing strength not less than
35Kg./Sq.cm. in Cement Mortar 1:5 (1-
Cement: 5-Coarse sand) (2)B type depth
up to 1.50 Metre
Providing and fixing white vitreous china
flat back or wall corner type lipped front
urinal basin of 340x280x470 mm sizes
respectively with standard flush pipe,
Waster Pipe, Waste Coupling, PVc
Connection and G.I clamps complete,
including painting of fittings and brackets,
cutting and making good the walls and
floors wherever required : Cera Model
No. S4020103 or Equivalent
Providing and Fixing of C.P. Brass BIB
Cock of 15 mm Dia of Jaquar make
florentine series model no. 5047n or
equivalent make with all necessary
fittings. as approved by Engineer - in -
Providing and fixing brass screw down
Angle stop tap.(A) 15mm dia. Of Jaquar
make florentine series modelno. 5053n or
equivalent make with all necessary
fittings. as approved by Engineer - in -
Providing and fixing C.P. brass shower
d 10 rose with 15mm or 20mm inlet Shower 279.37 No.
Arm.(A) 100mm dia. Each
Provding and Fixing of autoclosing
pressmatic pillar cock / bib cock with all
necessary fittings of Polished Bright
Chrome Finish of Jaquar make model no.
031L65 or equivalent make as approved
by Engineer in Charge. Rate including of
cost of labour, material etc. in complete
Providing and Fixing of C.P. Brass Two
Way Bib Cock of 15 mm Dia of Jaquar
make model no. 041kn or equivalent
make approved make with all necessary
fittings. as approved by Engineer - in -
Providing and Fixing of C.P. Brass urinal
Valve Auto Closing System With Full Built
in Control Cock & Wall Flange of 15 mm
g 20 Dia of Jaquar make model no. 077 or 2568.08 No.
equivalent make approved make with all
necessary fittings. as approved by
Engineer - in - charge.,
Providing and Fixing of C.P. Brass Pillar
Cock Auto Closing System with Elbow
Operated Extended Lever of 15 mm Dia
h 30 of Jaquar Make Model No,031 MED or 3723.48 No.
Equvalent Approved Make & Model with
all necessary fittings. as approved by
Engineer - in - charge.,
Provdg. & laying S.W. Gully trap with C.I.
garting brick masonry chamber & water
tight C.I. cover with frame of 300 mm x
300 mm size ( inside) with standard
weight. sqare mouth trap size 150 x100
Providing erecting and fixing double
31 2000 coated ISI water tank of required capacity 3.91 Litre
each with all necessary fittings and
connection etc. complete on terrace
Extra rate over item of excavation of earth
for excavation of asphalt pavement/RCC
of thickness up to 0.20 meter including
32 20 demolishing the asphalt carpet, metal, 71.43 Sq.M.
soiling / cutting Reinforcement etc.comp.
with stacking the material as directed.-up
to 0.20 meter thickness
Providing and fixing PVC SWR Nahni trap
IS 14735 for drain - 100 mm diameter
with jali of the
33 55 following nominal diameter of self 565.43 No.
cleansing design with C.I scread down or
hinged grating including the cost of
cutting and making good the walls.
Provdg. And fixing Concealed / Open to
wall, ceiling & floor in true line and level
UPVC pipe Schedule- 40 of make as
approved by engg. incharge. pipe shall be
fix on wall with the help of clamp at every
34a twi meter center to center of shall be
concealed as directed in cluding
neccesarry fitting etc. in cluding testing of
pipe and jointd and fixing the same with
adhesive solvent , including cost of all
materials of following nominal bore
ii 600 25 mm 90.93 Rmt
iii 15 32 mm 117.97 Rmt
iv 320 40 mm 146.65 Rmt
Providing and fixing concealed center
point to wall ceiling & floor CPVC (SDR
13.5) PIPE having National Sanitation
34b Foundation (NSF) seal for potable water
of following dia. nominal bore tube fittings
and clamps including making good the
wall, ceiling and floor etc. complete
i 5 15 mm 165.21 Rmt
ii 5 20 mm 202.97 Rmt
iii 5 25 mm 247.25 Rmt
iv 5 32 mm 330.36 Rmt
v 5 40 mm 437.66 Rmt
vi 5 50 mm 647.30 Rmt
Provdg. And fixing to wall ,ceiling and
floor 10.00 kg. F/Sq.Cm2 working
pressure polythelene pipes of the
35 following outside diameter, low, density,
complete with special flange compression
type fittings, wall clips etc. making good
wall ceiling and floor.
b 130 (A) 75mm dia 274.68 Rmt
c 400 © 110 mm dia 332.91 Rmt
Providing and fixing water closet
squatting Pan ( Indian type W.C. Pan)
36 8 size 580mm (A)VitreousChina. (I)Long 1351.15 No.
pattern = White colour with Trap and Pair
Providing and fixing white vitreous china
extended wall mounting water closet of
Cera Make S1043101 Carat Model Or
Equivalent Model With EWC Soft Close
Seat Cover, Chair Bracket, nuts, bolts
and gasket etc complete.
Providing and fixing chromium plated
brass half trun flush cock of approved
quality including fixing in pipe line etc.
Providing and fixing Health Faucet of
Jaquar make model no. 573 oe
c 28 equivalent make as approved by engg. In 1543.36 No.
charge with flexible tube upto 1 metre
long etc. complete.
Providing and fixing 24"x18"x8" Carysil
Elegance or Equivalent Make of Single
38a 2 Bowl Sink S.S. Matt Finish With Waste 7960.60 No.
Coupling, Waste Pipe,etc. cutting and
making good the walls wherever required.
Providing and fixing Under counter Wash
basine including 15 mm C.P. Brass Pillar
tap, 32 mm C.P. Brass Waste of
Standard make, Include All Accessaries,
b 18 Cutting & Making good the wall / granite 6641.14 No.
Wherever Required in White Color :
Model S2030101 of Cera Clair Series or
Equivalent make Waash basine of size :
Providing and fixing Wall Hung wash
basin Including 32 mm C.P. brass waste
of standard pattern, Include All
c 20 Accessaries, cutting and making good 3825.20 No.
the walls / granite wherever require:In
White Color : Cera Cadal Or Equivalent
Make Wash basin of size 515 x 410 mm
Providing and Fixing White Vitreous
China Laboratory Sink with C.I. Brackets,
C.P. Brass Chain with Rubber Plug,
mm C.P. Brass Waste and 40 mm C.P.
d 4 Brass Trap with Necessary C.P. Brass 5581.19 No.
Unions Complete, Including Painting of
Fittings and Brackets, Cutting and Making
Good to Wall / Granite Wherever
Required: Size 600 x 450 x 200 mm
Provdg. & fixing 600mm x 450 mm
Bevelled edge mirror of superior glass
39a 35 mounted of .6 mm th. A.C. sheet or 825.48 No.
plywood sheet and fixed to wooden pluge
with C.P. brass screws and washers.
Provdg. & fixing C.P..Brass towal rail
complete with C.P. brass brackets fixed
to wooden plugs with C.P. Brass
screws.(600 mmx 20 mm size)
Providing and fixing ball valve (brass) of
41 approved quality, High or low pressure,
with plastic floats complete :
i 14 15 mm dia 886.22 No.
ii 1 20 mm dia 1099.94 No.
iii 40 25 mm dia 1552.93 No.
iv 20 40 mm dia 3312.60 No.
v 5 50 mm dia 4613.48 No.
42a Providing and fixing Full Way valve (HEX)
with wheel of approved quality :
i 6 15 mm Full Way valve (HEX) 1461.17 No.
ii 1 20 mm Full Way valve (HEX) 1924.61 No.
iii 12 25 mm Full Way valve (HEX) 2535.55 No.
iv 1 32 mm Full Way valve (HEX) 3377.64 No.
v 10 40 mm Full Way valve (HEX) 4661.10 No.
vi 5 50 mm Full Way valve (HEX) 6675.14 No.
Providing and Fixing of C.P.Brass Pillar
Cock of 15 mm Dia of approved make
with all necessary fittings. as approved by
Engineer - in - charge.,
b 10 Providing fixing of SS grab bar with all 1937.24 No.
hardwares for Physically Handicap toilet.
Providing and laying integral cement
based water proofing treatment including
44a 850 preparation of surface as required for 1150.48 Sq.M.
treatment of roofs, balconies, terraces etc
consisting of following operations:
(a) Applying a slurry coat of neat cement
using 2.75 kg/sqm of cement admixed
with water proofing compound conforming
to IS. 2645 and approved by Engineer-in-
charge over the RCC slab including
adjoining walls upto 300 mm height
including cleaning the surface before
(b) Laying brick bats with mortar using
broken bricks/brick bats 25 mm to
mm size with 50% of cement mortar 1:5
(1 cement : 5 coarse sand) admixed with
water proofing compound conforming to
IS : 2645 and approved by Engineer-in-
charge over 20 mm thick layer of cement
mortar of mix 1:5 (1 cement :5 coarse
sand ) admixed with water proofing
compound conforming to IS : 2645 and
approved by Engineer-in-charge to
required slope and treating similarly the
adjoining walls upto 300 mm height
including rounding of junctions of walls
(c) After two days of proper curing
applying a second coat of cement slurry
using 2.75 kg/ sqm of cement admixed
with water proofing compound conforming
to IS : 2645 and approved by Engineerin-
(d) Finishing the surface with 20 mm thick
jointless cement mortar of mix 1:4 (1
cement :4 coarse sand) admixed with
water proofing compound conforming to
IS : 2645 and approved by Engineerin-
(e) The whole terrace so finished shall be
flooded with water for a minimum period
of two weeks for curing and for final
test.“All above operations to be done in
order and as directed and specified by
the Engineer-in-Charge :and shall be
guaranteed for minimum period of
years after handing over the completed
building by the main contractor to be
finished as directed. Stamp paper
guarantee 10 years to be furnished
before receiving any payment from the
With average thickness of 120 mm and
minimum thickness at khurra as 65 mm.
Providing and laying broken chine mosaic
flooring for terrace using 12 mm to 20 mm
broken pieces of glazed tiles to be laid
over cement mortar 1:3 to plain or slope
and to be tempered to bring mortar creme
out upto surface using white cement
including rounding off junctions and
extending them upto 15 cm along the
wall,clearing with water and oxalic acid
etc. as directed.
Providing and applying fibre reinforced
elastomeric liquid water proofing
membrane with resilient acrylic polymers
having Sun Reflectivity Index (SRI) of
on top of concrete roof in three coats
@10.76 litre/ 10 sqm. One coat of self-
priming of elastomeric waterproofing
liquid (dilution with water in the ratio of
c 490 3:1) and two coats of undiluted 562.40 Sq. M.
elastomeric waterproofing liquid (dry film
thickness of complete application/system
not less than 500 microns). The operation
shall be carried out after scrapping and
properly cleaning the surface to remove
loose particles with wire brushes,
complete in all respect as per the
direction of Engineer-in-Charge.
Filling in Sunken Portion with good
Quality Aerated light weight concrete
block having crushing strength not less
than 35 kg/sqcm and where directed by
d 63 the Architect / Engineer-in-charge, in 4559.61 Cmt
sunk in layer. including watering,
ramming where it is required etc.
complete, as directed by the Architect /
Engineer-in-charge .
Providing and laying cement concrete
flooring ( I.P.S.) 1:2:4 (1-cement : 2-
coarse sand : 4-graded stone aggregate
20mm nominal size) laid in one layer and
finished with a floating coat of neat
cement. (B) 50mm thick.
Providing and fixing M.S. grills/ Gate of
required pattern to wooden/ Granite
frames of windows etc. with M.S. flats at
required spacings and frame alround,
square or round bars with round headed
bolts and nuts or by screws all complete
as per the structural designs and
directions of Engineer in charge
Providing & Fixing Structural steel work (
Confirming to IS 4923-1997) riveted,
bolted or welded in builtup for all type
sections, in framed work, including
b 2000 cutting, hoisting, fixing in position and 126.68 Kg.
applying a priming coat of approved steel
primer all complete as per the structural
designs and directions of Engineer in
Applying priming coat over new steel and
other metel surface after and including
preparing the surface by throughly
cleaning, oil, grease, dirt and other
c 700 34.34 Sqmt
foreign matter and scoured with brushes
fine steel wood, scrapers and sand paper
with ready mixed priming paint brushing
Painting two coats (excluding priming
coat) on new steel and other metal
surface with enamel paint, brushing,
d 700 interior to give an even shade including 86.94 Sqmt
cleaning the surface an even shade
including cleaning the surface of all dirt,
dust and other foreign matter.
Providing & Fixing 1.2 mm Thick S.S.-304
Grade 900 mm to 1150 mm High S.S.
Railing having Hand Rail Member of
mm Dia., 4 No. of Horizontal Pipe of
e 120 mm Dia. & Baluster Suppprt of 40 mm 2270.21 R.Mtr.
Dia. At Every Third Step as per Detail
Given. Rate Includes All Work Complete
as per Description & as per Direction of
Engg. in Charge.
Providing and fixing in position collapsible
steel shutters with vertical channels
20x10x2 mm braced with flat iron
diagonals 20x5 mm size with top &
47a 75 bottom rails of T-iron 40x40x6 mm with 5391.23 Sq. M.
38 mm dia. Steel pulleys complete with
bolts , nuts , locking arrangement
stoppers , handles including applying a
priming coat of red lead paint.
Providing corrugated 0.80 mm (22
gauge) thick G.I. sheets roofing fixed with
galvanized iron ‘J’ or ‘L’ hook bolts, and
b 5 nuts 8 mm. dia with bitumen and G.I. 719.93 Sq.M.
limpet washers filled with white lead
complete excluding the cost of purlines,
rafters and trusses.
Providing valleys 900 mm. overall in plain
1.6 mm. thick G.I. sheet Class – 3 fixed
c 2 with ‘J’ or ‘L’ hook bolts and nuts 1042.78 Sq.mt.
galvanized from ‘J’ or ‘L’ hook bolts and
bitumen washers complete.
Providing and fixing rolling shutters of
approved make made of 80 mm wide
M.S. laths inter-locked together through
their entire length and jointed together at
the ends by end locks mounted on
48a 9 specially designed pipe shaft with bracket 3468.72 Sq.M.
plates, guide channels and arragements
for inside and outside locking with push-
pull operation including the cost of hood
cover and spring etc. complete.(A)
Shutters having width below 3.5 M.
Providing and fixing rolling shutters of
approved make made of 80 mm wide
M.S. laths inter-locked together through
their entire length and jointed together at
the ends by end locks mounted on
b 12 specially designed pipe shaft with bracket 4450.51 Sq.M.
plates, guide channels and arragements
for inside and outside locking with push-
pull operation including the cost of hood
cover and spring etc. complete. (B)
Shutters having width 3.5 M. and above
Providing and fixing 27mm domal Series -
1.2 mm Th. Alluminium Section Three
track Sliding window With Metalic Powder
49a 155 Coating and 4 MM Clear Glaas(Non 6373.85 Sq. M.
Tuffen) Include All Accessaries and
Fixture etc. complete as per the direction
of Engineer-in-charge.
Providing and fixing 27mm domal Series -
1.2 mm Th. Alluminium Section Two track
Sliding window With Metalic Powder
b 46 Coating and 4 MM Clear Glaas(Non 4999.10 Sq. M.
Tuffen) Include All Accessaries and
Fixture etc. complete as per the direction
of Engineer-in-charge.
ALUMINIUM DOOR WORK
Providing and fixing Aluminium Door work
(Single Shutter OR Double Shutter with or
without fix glass) made from Jindal or
equivalent make Powder Coated (50
micron pure polyester coating )
,aluminium section frame built up
standard tubular and other section of
approved make confirming to IS 733 and
IS 1285 , member size with shutters of
horizontal member , vertical member
Confirming to IS733 and IS 1285 fixed
with rawl plug abd screws or fixing clips
or with expansion hold fasteners including
necessary filling up of gaps at junctions at
top bottom and sides with required PVC/
c 51 Neoprene felt, 8/12 mm toughened glass 5401.70 Sq. M.
of approved make etc. Aluminum sections
shall be smooth, rust free, straight.mitred
and jointed mechanically wherever
required including Door Hardware such
as cleat angles aluminum snap beading
for glazing /paneling, CP Brass/ Stainless
steel screws, Stoppers, heavy duty floor
hing, S.S. Hinges, aldrop , Locking
system, heavy duty Floor Springs, Pivot
and fixtures and transparent silicon
sealant glass fixing to frame as per
details all complete as per architectural
drawings and the direction of Engineer in
Charge. rate incl. all type of alumnium
sections for doors as per the detail
Architectural dwg.
Providing and fixing standared extruded
of alluminium section of size 63 mm x
38.10 mm x 1.2mm (Section:2434, @
50 a 20 Wt.0.643Kg/mt ) with colour anodized 1163.92 Sq. M.
alluminium frame for ventilation with
mm thick frosted glass as details etc
complete for Ventilation
Providing and fixing standared extruded
of alluminium section of size 63.50 x
38.10 x 1.95 mm ( Section no:
@Wt 1.094 Kg / Rmt with colour anodized
alluminium frame with 5 mm thick
transparent bronze colour tinted float
glass as details etc complete for Fix
Providing Fixing 1.2 mm thick Alluminium
Section Partition -Fully Glazed / Partly
Panelled Partly Glazed / Fully Panelled
Having Size of Section of 2.1/2 x 1.1/2
with 4 mm Compact Sheet / 5 mm thick
Glass Fixing with 4 mm thick EPDM
Rubber etc. Complete as per Direction of
Consultant / Engg.incharge.
Providing Fixing 1.2 mm thick Alluminium
Section Partition Door -Fully Glazed /
Partly Panelled Partly Glazed / Fully
Panelled , frame Having Size of Section
of 2 .1/2 x 1 .1/2 and Door Section
Having Size of Tips Vertical 1 .3/4 x
.3/4, Top Rail 4 x 1 .3/4, Middle Rail
.3/4 x 1 .3/4, Bottom rail 4 x 1 .3/4 with
mm Compact Sheet / 5 mm thick Glass
Fixing with 4 mm thick EPDM Rubber
Including Lock, Handle, Door Closer,
Door Stoper, Stopper etc Complete as
per Direction of Consultant /
Providing and fixing Structural Glazing
with using the 17 Micron anodised of
approved colour alluminium section as
transium, mullium of size 63mm x 38mm
x 2 mm with using 6 mm thick reflective
structural glass of approved make, colour
/ Tinted, toughned and shade and fixed
with silicone sealant and spacer tap and
at corner sealed neoprene foam dust and
Air sealed gasket mirred including
scaffolding, cleaning of glass
etc.complete at all heights anf lifts with all
necessary fitting and fixtures, anchore
51a 8 fasteners, necessary M.S. or Aluminium 3953.75 Sq.mt.
brackets, suitable design for openable or
sliding window as per Architectural
drawing and as directed by Engineer-in-
charge. Grooves between the glasses to
be filled with sealant of Dow corning -
structural sealant 995, weather sealant
789. The entire facade should be water
proof. The mullions are to be connected
to bracket by SS-304 nut bolts.
Measurement shall be given as per actual
execution of the work. (Rate are included
providing & fixing of MS structure steel
work wherever Required)
Providing and fixing ISI marked 35 mm
thick flush door shutters conforming to IS
: 2202 (Part I) decorative type, core of
block board construction with frame of 1st
class hard wood and well matched teak
ply veneering with vertical grains or cross
bands and face veneers on both faces of
shutters with 1.00 mm thick Decorative
52a 68 Laminated Sheet on both faces of 4332.15 Sq.mt.
shutters including ISI marked Stainless
Steel butt hinges, bright /matt finished
125 mm Stainless Steel handles of
approved quality & make, ISI marked
oxidised M.S. door latches / Aldrop
Conforming to IS:5930 with necessary
screws etc. complete as per direction of
Engg. incharge.
Providing wood work in frames of Doors,
windows cleare story windows and
othersimilar works wrought, framede and Cu.Decim
fixed in position. (A) Indian Teak Wood
Providing & Fixing Fluted Glass Partition
and Door Using 16 x 45 mm Powder
Coated Alluminium Section with 8 mm
Thick Fluted Toughened Glass Including
Lock, Handle, Floor Spring, Connector,
Silicon and All Other Accessaries
including Making Pit etc Complete as per
Direction of Consultant / Engg.incharge.
Providing & Fixing Profile Shutter Using
16 x 45 mm Powder Coated Alluminium
Section with 5 mm Thick Fluted
d 200 Toughened Glass, Concealed Handle 14838.39 Sq.mt.
Section and Hinges Including All
Accessaries etc Complete as per
Direction of Consultant / Engg.incharge.
Providing and fixing of approved make
Clean room doors. Doors should be
finished in Powder Coating with thickness
of 60 microns approx. in desired Shades.
The manufacturer company must be ISO
9001-2015 certified. The door frame is a
Single rebate profile of minimum size
105mm X 57 mm made out of 1.2 mm
minimum thick galvanized steel sheet.
The frame is finished with Powder
Coating in desired Shade. Frame having
provisions and necessary Arrangement
e 75 for receiving appropriate hardware like 10705.16 Sq.mt.
lock and hinges. The door leaf shall be a
minimum 46mm thick fully flush double
skin door with vision lite of DGU Glass of
Size 300 x 300 mm x 6 mm . The door
leaf shall be manufactured from 1.0 mm
thick galvanised steel sheet. Door
Includes SS 304 Hinges, D type Pull
Handle-SS 304, Mortise Deadlock with
cylinder - 70mm both side key , Flush
type tower bolt, Door Seal , Door Closer
etc. Complete as per Standard
Providing and fixing of approved make
radiation-proof lead line door with
galvanised steel. Recommended lead
door design should be a sandwich-type
panel with both sides GI Sheet with a
minimum 2mm Lead infill. Doors should
be finished in Powder Coating with
thickness of 60 microns approx. in
desired Shades. The manufacturer
company must be ISO 9001-2015
certified. The door frame is a Single
rebate profile of minimum size 105mm X
57 mm made out of 1.2 mm minimum
thick galvanized steel sheet & with 2mm
f 19 lead infill. The frame is finished with 27488.83 Sq.mt.
Powder Coating in desired Shade. Frame
having provisions and necessary
Arrangement for receiving appropriate
hardware like lock and hinges. The door
leaf shall be a minimum 46mm thick fully
flush double skin door without vision lite.
The door leaf shall be manufactured from
1.0 mm thick galvanised steel sheet. Door
Includes SS 304 Hinges, D type Pull
Handle-SS 304, Mortise Deadlock with
cylinder - 70mm both side key , Flush
type tower bolt, Door Seal , Door Closer
etc. Complete as per Standard
Providing and fixing 35 mm th. Shutters
for doors windows & clearstory windows
incl. wood frames as specified 12 cm. x
53 7cm. size incl. anodised alluminium
fixtures and fastenings including primer
coat of approved quality and two coats of
oil paint etc. complete.
a 3 Fully glazed 4788.50 Sq. M.
b 3 Fully panelled 5478.89 Sq. M.
c 3 Partly panelled and partly glazed 5133.69 Sq. M.
Providing and Fixing FRP FRAME size
125 x 65 mm and 35 mm thick FRP
shutter with wood grain raised pannel
design finish shutter having extra
reinforcement on sides and edges and in
polish finish The core of the shutter is to
be filled up with injected fire extingushing
grade.polyurethane foam done in situ
along with embedded wooden pieces for
stiffering and also for tacking hinges and
fixtures. The whole FRP frame and
shutter is to be water proof.weather
proof,tennite proof and resistance to mild
acid/ Alkali, Rates are to be inclusive of
S.S. hinges with necessary screws and
brass fixtures and fasening.
Making connection to the ex.M.H.in
running sewer incl. Dewatering and other
required machinery etc. of following dia
pipes at any convenient time. All
damaged work shall be well repaired as
per instructions. etc..complete.
a 1 For Pipe 150 mm to 300 mm diameter 1339.29 No.
b 1 For Pipe 400 mm to 600 mm diameter 2232.14 No.
Making connection of galvanised Mild
steel distribution branch with galvanised
56 1 mild steel main 50mm to 80mm nominal 600.08 No.
bore by providing and fixing tee including
cutting and threading the pipes complete
Providing throating or plaster drip,
57a 2000 grooves and moulding to Wall , R.C.C. 41.25 Rmt
chajja and slab.
Providing & Laying cement vatta 10 cm x
10 cm in size quarter round in c.m. 1:1 (
57b 180 1 cement, 1 coarse sand) laid in one 23.45 Rmt
layers finishing with a floating of neat
cement watering etc complete as dire.
Carring out plinth treat ment to post
construction/ existing structure by
spraying chemical solution for termite
control treatment including labour and
material consist ment withI.S.I
specification. Using Chlordene and
Chiorpur files 20EC. As Per 6131_ paret-
II Consentration Weight one percent is
recommended i.e one litre 20EC chemical
emulsion with19 liter give1%
concrentration inclusive of one litre
chemical emulsion appication at the rate
of 5 Litre chemical/ Sqm of surface is
recommended as per I.S
Carring out timber treatment to all wood
work including drilling holes and spraying
oil based chemical solution on surface of
timber work for termite control including
labour and material etc. complete. Using
Chlordene 20EC. As Per 6113_part III
Consentration Weight 1.00 percent is
recommended one litre chemical
emulsion dillute with 9 liter of kerosene
precent concentration. Total dillute
concrentration will be10litre inclusive of
the litre chemical emulsion application
0.75/Litre chemical per one Sqmt printed
two coat wood surface.
Paver Block Providing and laying shot
blasted Non - interlocking, Paver blocks
of specified thickness, size, grade of
concrete and colour machine made and
blasting by automatic shot blasting
machine and high density of as per
approved sample of approved make for
footpath, parking areas, service
lanes,cross over and other areas as
mentioned in the drawing. Including
providing and laying 50 mm thick averave
bedding layer of coarse sand below paver
block as per required grading and
specification. Laid paver block shall be
mechanically compacted. The work of the
paving blocks shall be executed in line
60 200 and level by skilled mason of flooring 758.93 Sq.mt.
work only. Small size of paver block with
same specification shall be used at
residue or at end. It should be laid in such
a way that the no cutting of the paver
block to be necessary. If cutting of paver
block shall be required , than cut by
machine only and laying to be done by
skilled flooring mason. The finished
surface of the paver block shall have
coarse sand Texture Finish. Pave blocks
shall be compacted and shall be re-laid if
necessary. Actual laid area shall be
measured and paid without any wastage.
(A) 80 mm thick M-35 grade Grey Paver
block of size 200mm x 200mm. As per
SProviding and fixing pre-cast concrete
kerb stone of gray cement based
concrete block 30cm length,30cm height
and 15cm thick of M250 grade concret as
per approved design and including
excavation for fixing in proper line and
level,filling the joint with C:M 1:3
(1cement:3fine sand) etc complete.
Providing and fixing double action
hydraulic floor spring of approved brand
and manufacture conforming to IS :
having brand logo embossed on the body
/ plate with double spring mechanism and
door weight upto 125 kg, for doors,
including cost of cutting floors,
62a 35 embedding in floors as required and 4558.89 No.
making good the same matching to the
existing floor finishing and cover plates
with brass pivot and single piece M.S.
sheet outer box with slide plate etc.
complete as per the direction of Engineer-
in-charge. With stainless steel cover plate
minimum 1.25 mm thickness
Providing and fixing aluminium extruded
section body tubular type universal
hydraulic door closer (having brand logo
with ISi, IS : 3564, embossed on the
b 40 body, door weight upto 36 kg to 80 kg 1626.10 No.
and door width from 701 mm to
mm), with double speed adjustment with
necessary accessories and screws etc.
Designing, fabricating, testing, installing
and fixing in position Curtain Wall with
Aluminium Composite Panel Cladding,
with open grooves for linear as well as
curvilinear portions of the building , for all
heights and all levels etc. including:
(a) Structural analysis & design and
preparation of shop drawings for pressure
equalisation or rain screen principle as
required, proper drainage of water to
make it watertight including checking of
all the structural and functional design.
(b) Providing, fabricating and supplying
and fixing panels of aluminium composite
panel cladding in pan shape in metalic
colour of approved shades made out of
4mm thick aluminium composite panel
material consisting of 3mm thick FR
grade mineral core sandwiched between
two Aluminium sheets (each 0.5mm
thick). The aluminium composite panel
cladding sheet shall be coil coated, with
Kynar 500 based PVDF / Lumiflon based
fluoropolymer resin coating of approved
colour andshade on face # 1 and polymer
(Service) coating on face # 2 as specified
using stainless steel screws, nuts, bolts,
washers, cleats, weather silicone sealant,
backer rods etc.
(c) The fastening brackets of Aluminium
alloy 6005 T5 / MS with Hot Dip
Galvanised with serrations and serrated
washers to arrest the wind load
movement, fasteners, SS 316 Pins and
anchor bolts of approved make in SS
316, Nylon separators to prevent bi-
metallic contacts all complete required to
perform as per specification and drawing
The item includes cost of all material &
labour component, the cost of all mock
ups at site, cost of all samples of the
individual components for testing in an
approved laboratory, field tests on the
assembled working curtain wall with
aluminium composite panel cladding,
cleaning and protection of the curtain wall
with aluminium composite panel cladding
till the handing over of the building for
occupation. Base frame work cost for
ACP cladding is included in this item rate.
The Contractor shall provide curtain wall
with aluminium composite panel cladding,
having all the performance characteristics
all complete , as per the Architectural
drawings, as per item description, as
specified, as per the approved shop
drawings and as directed by the
Engineer-in-Charge. However, for the
purpose of payment, only the actual area
on the external face of the curtain wall
with Aluminum Composite Panel
Cladding (including width of groove) shall
be measured in sqm. up to two decimal
Providing and Fixing Box type metal
letters forming composite box made from
1mm thick stainless steel plate of grade
304 having brush finish of following font
64 size to be fixed at Main Gate in english
and or Gujrati and including fixing
charges. etc. complete as per direction of
Engg. incharge. for Payment Purpose
Height of Letter will be measured.
a 960 Upto 300 mm Height 93.85 R. Inch
Providing and Fixing MURAL made out of
2mm thick s.s. plate grade 304, including
making necessary design as per Architect
dwg. Through laser cutting including
connection to the R.C.C./Masonary with
necessary frame,anchor
fastnuts,M.S.Plate etc. complete as per
direction of Engg. incharge.
Providing and Fixing Sinage - internal and
external signage boards with Vinyle Text
65b 20000 on ACP sheet / 2 mm th. S.S. Plate etc. 9.38 Sq.Inch
complete as per direction of Engg.
Providing and fixing retro Reflective Hi
Intensity Micro Prismatic Grade Board
using 2mm Aluminum / 4mm ACP, angle
iron 75 x 75 x 6mm. Descaling and
degreasing the board as per requirement
using epoxy reflactive process by screen
painting as directed etc. complete
including transporting and fixing in C.C.
1:2:4 with necessary excavation curing
etc. complete as per I.R.C. 67-2012
design. A warranty for 7 years for the
Retro reflective sheeting from original
manufacturer & a certified copy of 3 year
outdoor exposure test report from third
party test lab for the product offered shall
be submitted by contractor. (B)Class B
Type-4(MDR/ODR) retro reflective
Road marking with hot applied
thermoplastic paints with reflectorising
glass beads on bitumin surface providing
and laying a hot applied thermoplastic
compound 2.5 mm thick including
reflectorising glass beads @ 250gms per
sqm area, thickness of 2.5mm is
excluding of surface applied glass beds
as per IRC:35-2015. The finished surface
to be level, uniform and free from streaks
and holes. zebra patta /bump patta
65d 230 lane/center line/ edge line/cut patta. The 364.08 Sqmt
white color marking should provide
liminance coefficinet on cemend road
shalll be min 130 mcd/m2/lux and Asphalt
road shall be min 100 mcd/m2/lux during
the service life during the day time. The
marking should meet the performance
criteria for night time reflectivity, wet
reflectivity and skid resistance as
mentioned in the section-15 of IRC
352015. Warranty for the Retro reflectivity
should be two years.
CAT EYE/Pavement Marker(MNC two
nail) made out of acrylic
StreneAcrylonitrile or hi-impact poly
Steren fitted with moulded of
metheacrylate(MNC)reflector cube corner
reflector design,filled with tightly adhering
pooting compound as per ASTMD-788
65e 10 size 11.5x7x1.60 cms or 10x10x1.75 cms 160.71 Nos.
provided with bituminous adhesive in
sufficient quantity with each unit fixing
with two shrank .Reflector on both
side.Co efficient of lumination as per
specification and compressive strenth
tones at 23 degree centigrade etc.B)
Double side lenses.
Providing and fixing eco-friendly light
weight calcium silicate false ceiling tiles
having T egular edge & 15mm Thick
Densified edges on the Tile Periphery for
Extra Strength The Light weight calcium
66a 1910 silicate ceiling tiles shall have, light 1632.63 Sq.mt.
reflection 85% non-combustible as per
B.S.476 part IV, 100% humidity
resistance and also having thermal
conductivity 0.043° w/m KC. for the best
thermal Insulation.
The Light weight calcium Silicate tile
shall be of approved texture Fine
fissured/ Spintone/ Cosmos having NRC
value of 0.5 & Globe having NRC value of
0.75 NRC or equivalent of size 595X595
mm to be laid on true horizontal level
suspended inter locking metal grid of hot
dipped galvanized steel sections
(galvanizing @ 120 grams per sqm
including bothside) consisting of main ‘T’
runner suitably spaced at joints to get
required length and size of 24X38 mm
made from 0.30 mm thick (minimum)
sheet, 1200 mm centre to centre, and
cross ‘T’ of size 24X28 mm made out of
0.33 mm (Minimum) sheet spaced
mm along spaced between main ‘T’ at
600 mm centre to centre to form a grid of
1200X600mm and secondary cross ’T’ of
length 600mm and size 24x28mm made
of 0.30 mm thick (Minimum) sheet to be
interlocked at middle of the 1200X600mm
panel to form grid of size 600X600mm
resting on periphery walls / partitions on a
perimeter wall angle pre-coated steel of
size (24X24X3000mm made of 0.40mm
thick (minimum)
sheet with the help of rawl plugs at
450mm centre to centre with 25mm long
dry wall screws @ 230mm interval and
laying 15mm thick Densified edges light
weight calcium silicate ceiling tiles of
approved texture (Fine Fissured/
Cosmos/Spintone) in the grid including,
cutting /making opening for services like
diffusers, grills, light fittings, fixtures,
smoke detectors etc., wherever required,
Main ‘T’ runners to be suspended from
ceiling using G.I. slotted cleats of size
25X35X1.6mm fixed to ceiling with
12.5mm dia and 50mm long dash
fasteners, 4mm G.I. adjustable rods with
galvanized steel level clips of size
85X30X0.8mm, spaced at 1200mm
centre to centre long main ‘T’ bottom
exposed with 24mm of all T-sections shall
be pre-painted with polyester baked paint,
for all heights,
, as per specifications, drawings and as
directed by engineer-incharge.Note:- Only
calcium silicate false ceiling area will be
measured from wall to wall. No deduction
shall be made for exposed frames/
opening (cut outs) having area less than
0.30 sqm. The calcium silicate ceiling
tiles shall have NRC. Value of
(Minimum) for Fine fissured/ Spintone/
Cosmos and 0.75 NRC for Globe, light
reflection 85% noncombustible as per
B.S. 476 part IV, 100% humidity
resistance and also having thermal
conductivity. 0.043° w/m KC.for the best
thermal Insulation
Providing and fixing single layer water
proof gypusm board 12.5 mm thick of the
make New good Group Co.Ltd. or
equivalent & New good Group Co.Ltd.
company sections using water proof
board of size 1220 mm x 1830 mm x
mm suspended by G.I suspender of size
25 mm x 3 mm with intermediate channel
of size 18mm x40mm x0.80mm at
mm center to center ceiling section of
size 40mmx 35mmx 0.55mm at 457 mm
center to center and perimetre chanel A
of size 20mm x 27mm x 30mm x 0.50mm
at edges & drops including paper taps
and sofit cleat, anchor fastener, scoch
bolt connecting cleat joining compound
top coat on ceiling including making
necessary opening for light fitting, diffuser
etc. complete as per detail drawing as
Providing and Fixing 6 mm thick Lexan
Polycarbonate multi wall roofing sheet
fixed with hilti screw and rubber silicon
sealer and alluminium strip of size 50 x
mm etc complete as directed by Engineer
Manufacturing,testing ,supplying
loading,,transporting to work site,loading
unloading lowering in trenches,laying and
68 jointing RCC NP3 class pipes in C:M 1:1
including all jointing materials such as
cement,sand,hemp bitumen as directed
testing the pipe line to a head of 1.5 mt
and hydraulic test as directed etc comp.
a 175 300 mm Diameter 616.07 Rmt
b 10 450 mm Diameter 806.25 Rmt
Constructing Bombay Pattern Type Catch
x 0.60 depth up to 1 mt including
excavation, B.B.C.C.
(1:5:10), 23 cms thick brick maso. wall in
69 20 the prop. of CM 3125.00 No
(1:6) with 40 mm thick IPS flooring in the
bottom and 15 mm thick cement plaster
inside the catch pit in the proportion of
CM (1:3) with out jali etc. comp. as
CatchPit Jali Fixing P/F FRC catch pit jali
with frame 600mm x 600mm clear
opening etc. comp.. As directed by
engineer in charge.
PERCOLATION WELL
71 120 Drilling of pilot bore hole in Alluvial Strata 694.64 Rmt
by direct Rotary Rig of 250 mm.
72 120 Reaming 400 mm 212.50 Rmt
73 1 Electro Logging charges with carting 16071.43 Job
Providing and Installing 200 mm dia
74 60 IS:12818 upvc Casing Pipe "CM" class 1193.75 Rmt
Providing and Installing 200 mm dia
75 1 IS:12818 upvc End Cap, with Air Vent 669.64 Set
200 mm dia Regular with 1.5 mm sloted
size cage type trapezoidal shape wire
wound little carbon galvanized screen
confirming to IS:8110
77 10 Supply of Pea sized Gravel 2029.46 Cmt
78 1 Air Vent of 50 mm Bend 401.79 Unit
79 120 Lowering and Removing of Dropline up to 147.32 Rmt
80 1 Air Compressor 60 CFM/150 PSI 22205.36 Ls
Estimate For Civil Work With Total Rs.
Percolation Well
I. No. Qty Items Unit Rate Per Amount
Electrical Work Estimate
1 INTERNAL WIRING
Point wiring for Light / Bell with 2-1.5
sq.mm & earth wire of 1.5 sq.mm
(Green) both are of ISI marked 1.1 KV
grade ZHFR/HRFR PVC insulated multi
strand copper wires up to 10 mtr length
in below type of pipe erected with 6A
Modular type switch / bell push &
accessories and earth continuity of
following type, erected on PVC /
Metallic/Wooden box, single mounting
base frame covered with
textured/metallic/white front plate
modules erected on / in wall / ceiling as
per pipe erected, with necessary Lamp
holder/ceiling rose / H.D.Connector as
(f) with medium class Rigid PVC pipe and
340 accessories erected concealed in 505.05 Pt
wall/ceiling complete
Point wiring for FAN with 2-1.5 sq.mm &
earth wire of 1.5 sq.mm (Green) both are
of .ISI marked 1.1 KV Grade
ZHFR/HRFR PVC insulated multi strand
copper wires up to 10 mtr length, in below
type of pipe erected with 6A Modular
type switch and hum free EME four or
more step type electronic fan regulator
1.2 with separately mounted and
accessories with earth continuity of
following type erected on PVC /
Metallic/Wooden box, single mounting
base frame covered with
textured/metallic/white front plate
modules erected on / in wall / ceiling as
per pipe erected. with necessary ceiling
rose / H.D.Connector as directed.
(f) with medium class Rigid PVC pipe and
180 accessories erected concealed in 701.40 Pt
wall/ceiling complete
Point wiring for secondary light point with
2-1.5 sq.mm & earth wire of 1.5 sq.mm
(green) both are of ISI marked 1.1 KV
grade ZHFR/HRFR PVC insulated multi
strand copper wires, in below type of
pipe to be erected complete with earth
continuity and necessary connection with
primary light with accessories erected on
Metal / PVC / wooden box covered
covered with appropriate front plate
modules erected on / in wall / ceiling for
open / concealed wiring. with necessary
Lamp holder / ceiling rose /
H.D.Connector as directed.as per pipe
erected with following type of
Note:- Maximum up to 6 mtrs length,
excess will be considered as Mains for
Secondary Point.
(f) with medium class Rigid PVC pipe and
260 accessories erected concealed in 174.30 Pt
wall/ceiling complete
Point wiring for Individual Plug with &
earth wire of 1.5 sq.mm (Green) both are
of ISI marked 1.1 KV grade ZHFR/HRFR
PVC insulated multi strand copper wires
up to 10 mtr length, in below type of pipe
1.4 erected complete with Modular type
switch & 5 pin Plug erected on PVC /
Metallic/Wooden box covered with
appropriate front plate modules erected
on / in wall / ceiling as per pipe erected
with following type of accessories.
[I] For 6A Plug and 6 a switch with 2-1.5
1.4.1 115 sq.mm Cu. Wire from nearby 530.25 Pt
switchboard/mcb db board
(f) with medium class Rigid PVC pipe and
accessories erected concealed in
wall/ceiling complete
[II] For 16A Plug and 16 amp switch with
1.4.2 110 2-2.5 sq.mm Cu. Wire from mcb db 774.90 Pt
(f) with medium class Rigid PVC pipe and
accessories erected concealed in
wall/ceiling complete
[III] For 16A Plug and 16 amp switch with
1.4.3 12 2-4 sq.mm Cu. Wire with 2.5 sq.mm ( 906.15 Pt
green) earthing wire from mcb d b board.
(f) with medium class Rigid PVC pipe and
accessories erected concealed in
wall/ceiling complete
Point wiring for on board Looped Plug
with 6A Modular type switch & 5 pin
socket erected on PVC / Metallic/Wooden
1.5 235 box, single mounting base frame covered 255.00 Pt
with textured / metallic/white front plate
modules erected on / in wall / ceiling
with following type accessories
Point wiring for Two Way Controlled Light
Point with 2-1.5 sq.mm & earth wire of
1.5 sq.mm (green) both are of .ISI
marked 1.1 KV grade ZHFR/HRFR PVC
insulated multi strand copper wires
erected in below type of pipe with 6A
Modular type switches and following type
of accessories erected on PVC /
Metallic/Wooden box, single mounting
base frame covered with textured /
metallic/white front plate modules erected
on / in wall / ceiling as per pipe erected.
with necessary batten/angle holder or
ceiling rose or H.D.Connector as directed.
(f) with medium class Rigid PVC pipe and
18 accessories erected concealed in 627.90 Pt
wall/ceiling complete
Providing following type of Modular Type
Accessories mounted with PVC /
metallic/Wooden box, single mounting
base frame covered with textured /
metallic/white front plate , modules
erected with necessary connections as
per site situation directed by Engineer In
1.7.2 40 (2) One No 5 pin plug 150.00 E.a.
1.7.3 90 (7) Blank Plate Single 25.00 E.a.
1.7.4 20 (8) Computer RJ-45 socket 159.00 E.a.
1.7.5 45 (9) 16 Amp. SP one way switch 179.00 E.a.
1.7.6 45 (10) 6/16Amp. Universal socket 198.00 E.a.
pole Modular MCB Switch
Pole Modular MCB Switch
Supplying and erecting approved make
suitable panel indicator LED type lamp,
lens cover, complete erected with
necessary connections.
Providing and erecting ISI mark Medium
class RIGID PVC PIPES of following size
complete to be erected on/in wall or
ceiling erected with necessary PVC
fittings & Junction boxes fixed with
adhesive solution & Clamps with following
dia of pipes, in approved manner as
Providing & erecting PVC Corrugated
1.9 Flexible Conduit with required nos. of
coupling, PVC bushes, Check-nuts etc.
complete of following sizes.
providing and erecting Mains with ISI
marked electrolyte stranded copper
conductor, Non PVC Zero Halogen free
fire retardant insulated copper conductor,
1.10 insulated wire (HRFR) conforms to IS-
694, erected in existing pipe with 1.5sq.
mm copper conductor of same
specifications for earth continuity of
following size.
In Existing medium class Rigid PVC pipe
and accessories
providing and erecting Mains with 1.1 KV
grade FRLS PVC insulated ISI marked
stranded Copper conductor wire in
following type of pipe to be erected in / on
wall / ceiling with 2.5 sq. mm copper
conductor FRLS PVC insulated stranded
wire of green colour for earth continuity of
(A) with medium class Rigid PVC pipe
and accessories
1.11.1 240 (c) 2 wire 10 sq. mm (use earth wire of 4 234.00 Mtr
1.11.2 40 (h) 4 wire 6 sq. mm 258.00 Mtr
(i) 4 wire 10 sq. mm (use earth wire of
providing and erecting Mains with ISI
marked, 1.5KV grade electrolyte multi
stranded, annealed copper conductor
with heat resistant PVC insulated
conforms to IS 694, IEC - 227 erected in
existing pipe of following size
(Specifically for control panel, relays,
power switchgears, motor starters &
control wiring) with required size of
copper lugs, nuts and bolts if required.
1.12.1 25 (e) One wire 6.00 sq. mm 56.00 Mtr
1.12.2 40 (f) One wire 10.00 sq. mm 91.00 Mtr
1.12.3 10 (g) One wire 16.00 sq. mm 141.00 Mtr
1.12.4 10 (h) One wire 25.00 sq. mm 234.00 Mtr
1.12.5 20 (i) One wire 35.00 sq. mm 298.00 Mtr
1.12.6 20 (j) One wire 50.00 sq. mm 466.00 Mtr
1.12.7 20 (k) One wire 70.00 sq. mm 663.00 Mtr
1.12.8 40 (l) One wire 95.00 sq. mm 910.00 Mtr
Supplying and erecting Flexible PVC
1.13 insulated multi strand multi core 1.1 kv
grade ISI marked copper wires of
following size to be erected as directed.
e) 1.50 Sq.mm 3 core round PVC
h) 2.50 Sq.mm 3 core round PVC
k) 4.00Sq.mm 4 core round PVC
Supplying & erecting M.S. Box having
Gauge painted with red oxide or Heavy
duty PVC box erected flushed on wall or
concealed in wall with necessary
plastering & finishing as directed of
following size.
Supplying & erecting 20 Amp 10 KA
‘C Curve’ single pole MCB with 20 Amp.
1.15 Plug socket, company fabricated powder
coated sheet steel enclosure erected as
directed with connection.
1 [A] Metal Clad Socket with metal clad top 522.00 E.a.
SUB - TOTAL OF INTERNAL WIRING
Switchgears , Panels , MCBDBs &
Providing and erecting Approved make
Three pole moulded case circuit breaker
having breaking capacity ICU of 25 K.A.
at 415 V having normal current rating up
to 25 A to 100A. with Fixed thermal &
magnetic release suitable to work on A.C.
supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
3 ICS=100% of ICU only 5832.20 No
Providing and erecting Approved make
Three pole moulded case circuit breaker
having breaking capacity ICU of 25 K.A.
at 415 V having normal current rating up
to 25 A to 100A. with Fixed thermal &
magnetic release suitable to work on A.C.
supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
2 ICS=100% of ICU only 5302.00 No
Providing and erecting Approved make
Three pole moulded case circuit breaker
having breaking capacity/strength ICU of
35 K.A. at 415 V. having normal current
rating 125A.with Fixed thermal &
magnetic release suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
3 ICS=100% of ICU only 6510.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. at
415 V. having Normal current rating
200A.with Microprocessor
release,Adjustable Overload Settings
from 0.25 to 1 In (in steps of
0.01),Conforms to IS/IEC 60947-2,
suitable to work on A.C.supply 50 c/s.
with all internal connections, spreader
tinned copper & complete erected in
existing 16 G.M.S.housing
2 ICS=100% of ICU only 23288.45 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA.
and above at 415 V . having normal
current rating 250A. with variable thermal
& magnetic release suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
1 ICS=100% of ICU only 20739.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 50 KA
and above at 415 V having Normal
current rating 400A. with variable
Thermal & magnetic release suitable to
work on A.C.supply 50 c/s. With all
internal connections, spreader tinned
copper & complete erected in existing
G.M.S. housing.
1 ICS=100% of ICU only 27476.90 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 50 K.A.
and above at 415 V having normal
current rating up to 630A. with
Microprocessr release Adjustable
Overload Settings from 0.25 to 1 In (in
steps of 0.01) ,Conforms to IS/IEC
60947-2, suitable to work on A.C.supply
50 c/s. with all internal connections,
spreader tinned copper & complete
erected in existing 16 G.M.S. housing
1 ICS=100% of ICU only 40447.75 No
Providing and erecting Approved make
Earth fault Relay suitable to mount with
inter connection suitable to following size
of moulded case circuit breaker having
CT ratio & MCCB rating as following
along with shunt trip 220V AC. with all
internal connections & complete erected
in existing M.S.housing..
Design, fabrication, assembling, supply,
installation, testing and commissioning of
cubicle type, wall / Floor mounted LT
panel suitable for 415 V 3 phase, 4 wire
50 Hz AC supply system fabricated in
compartmentised design from CRCA
sheet steel of 2 mm thick for frame work
,Doors and partitions IP 42 and covers,3
mm thick for gland plates i/c cleaning and
finishing complete 9 tank process in
house facility for powder coating in
approved shade, extendable type FP
aluminium alloy busbars of high
condectivity, DMC/SMC busbar supports,
entire panel shall have a common copper
earthbar of size 25mm X 5 mm OR 50 x
6mm aluminium at the rear with 2 Nos.
earth studs, solid connection from main
busbar to switchgears with require size of
aluminium busbar & control wiring with
1.5 sqmm FRLS insulated copper
conductor cable, cable alleys, cable gland
plates i/c accessrories as per
specification and providing switchgears,
metering instruments etc. for following
panel.G.A.Drawing to be approved by
EIC or consultant. ( Outgoing connectors
must be nut-bolt type. Outgoing mains for
63Amp MCBs must be of 4 x 16sqmm cu
flexible wires).Incomers Mains for MCBs
shall be always from the busbars.
( a ) Providing cable clamps / supports
within distribution boards cable alley.
( b ) All hinged door shall be earthed
through 2.5 sq mm tinned b raided copper
( c ) Pad locking of MCCB’s handles in
“OFF” Position.
( d ) All the C.T.s should be auto short
( e ) All the MCCB's should be with rotary
( f ) All incoming and outgoing air circuit
breakers shall be placed on middle
portion of the vertical in single tier
( g ) Any descripancy found in SLD & Boq
, it should be brought in the notice of the
client / consultant, and the decision will
be taken final by Client / consultant.
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. at
415 V. having normal current rating
2.2.1 125A. with Fixed thermal & magnetic
release suitable to work on A.C.supply
c/s. with all internal connections, spreader
tinned copper & complete erected in
existing 16 G.M.S. housing.
4 ICS=100% of ICU only 7976.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. at
415 V. having Normal current rating
200A.with variable Thermal & magnetic
release suitable to work on A.C.supply
c/s. with all internal connections, spreader
tinned copper & complete erected in
existing 16 G.M.S.housing. Overload
release Range: 84 - 125Amp
1 ICS=100% of ICU only 16061.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. at
415 V. having Normal current rating
200A.with variable Thermal & magnetic
release suitable to work on A.C.supply
c/s. with all internal connections, spreader
tinned copper & complete erected in
existing 16 G.M.S.housing. Overload
release Range: 125 - 160Amp
1 ICS=100% of ICU only 16061.00 No
Providing and erecting Approved make
Three pole moulded case circuit breaker
having breaking capacity/strength ICU of
35 K.A. and above at 415 V. having
Normal current rating 200A.with variable
2.2.4 1 Thermal & magnetic release suitable to
work on A.C.supply 50 c/s. with all
internal connections, spreader tinned
copper & complete erected in existing
G.M.S. housing.Overload release Range:
1 ICS=100% of ICU only 15421.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA.
and above at 415 V . having normal
current rating 250A. with variable thermal
& magnetic release suitable to work on
A.C.supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
1 ICS=100% of ICU only 20739.00 No
Providing and erecting Approved make
Three pole moulded case circuit breaker
having breaking capacity ICU of 25 K.A.
at 415 V having normal current rating up
to 25 A to 100A. with Fixed thermal &
magnetic release suitable to work on A.C.
supply 50 c/s. with all internal
connections, spreader tinned copper &
complete erected in existing 16 G.M.S.
3 ICS=100% of ICU only 5302.00 No
Providing and erecting Approved make
Four pole moulded case circuit breaker
having breaking capacity ICU of 50 K.A.
and above at 415 V having normal
current rating up to 630A. with
Microprocessr release Adjustable
Overload Settings from 0.25 to 1 In (in
steps of 0.01) ,Conforms to IS/IEC
60947-2, suitable to work on A.C.supply
50 c/s. with all internal connections,
spreader tinned copper & complete
erected in existing 16 G.M.S. housing
1 ICS=100% of ICU only 37658.25 No
providing and erecting Approved make
Earth fault Relay suitable to mount with
inter connection suitable to following size
of moulded case circuit breaker having
CT ratio & MCCB rating as following
along with shunt trip 220V AC. with all
internal connections & complete erected
in existing M.S.housing..
providing and erecting Miniature circuit
breaker single pole 0.5A to 2A system
2.2.9 20 and having breaking capacity 10 KA to 268.00 No
be erected in existing box. confirming to
IS 8828/1996 with ISI Mark
providing and erecting Miniature circuit
breaker single pole 6A to 25A suitable to
operate on 240 V A.C. system and having
breaking capacity 10 KA to be erected in
existing box. confirming to IS 8828/1996
Providing & erecting 240 V MCB double
pole switch for motor & inductive load
2.2.11 (C Curve) having 10 KA breaking
capacity & confirms to IS : 8828 in
existing box having following capacity
Providing & erecting 415 V MCB Four
Pole for Motor & Inductive Load (C
2.2.12 Curve) having 10KA breaking capacity &
confirms to IS :8828 in existing box
having following capacity
Providing and erecting following
2.2.13 additional parts for panel mounting
(A)Extended operating rotary handle with
2.2.13a 10 pad lock with three position trip,off,on 865.00 No
suitable for 25A to 250 A panel mounting
(B)Extended operating rotary handle with
pad lock with three position trip,off,on
suitable for 400A to 630 A panel
Supplying and erecting approved make
panel mounting type Digital Voltmeter
having 3 digits LED display, 0 to 750 AC
Volts range erected on existing panel
board with all connection, wiring etc .with
manufacturers calibration certificate.
Supplying and erecting approved make
panel mounting type Digital Ammeter
having 3 digits LED display, external CT
operated, calibrated for 0 to 1000 Amps
suitable to operate on 500 Volt AC
erected on existing panel board with all
connection, wiring etc .with
manufacturers calibration certificate.
Supplying and erecting Ammeter /
Voltmeter selector switch for 3 phase AC
Supply 500 V on existing panel board
with necessary connections.
Providing & erecting L.T. Current
Transformer with bar primary 50/5 to
1000/5 ratio 15 VA burden erected in
existing CRCA box duly secured with
insulating materials connected to the
Supplying & erecting approved make
Power Factor Meter 150mm dia
flush/projection type/ balanced &
unbalanced load to work with
2.2.18 1 appropriately provided CT’s 100/5A to 5052.00 No
400/5A ratio & other accessories
complete erected in M.S. box &
connected to the circuit by means of PVC
copper Core leads.
Supplying and erecting approved make
suitable panel indicator LED type lamp,
lens cover, complete erected with
necessary connections.
Providing and erecting metallic vitrified
danger notice board as per language
2.2.20 4 suggested by engineer incharge for 69.00 No
MEDIUM VOLTAGE installation to be
erected as per IS-2551.
Providing and erecting required size
2.2.21 8 Aluminium strip for earthing of H.T. , OCB 223.00 KG
/ ACB / Transformer, LT panel board,
Motors etc. using copper clamp.
Providing and erecting required size
Copper strip for earthing of H.T. OCB /
ACB/ Transformer, LT panel board,
Motors etc. using copper clamp.
providng and erecting Approved make
energy meter 3 phase 4 wire unbalanced
2.2.23 3 load 500 V. 5 to 10A complete erected as 2179.00 No
directed with necessary earth wire.Class-
Providing , erecting , fabricating the M.S.
structure as per requirement on site
incorporating proper size of M.S.
angles,square,round, flats, bars,
channels, sections complete with cutting,
2.2.24 250 welding, grinding & finishing duly painted 77.00 Kg
with one coat of red oxide with erection
on site as per direction of engineer in
charge with necessary grouting,
cementing, plastering & finishing
Supplying and erecting triple pole &
neutral 440V/ 500V panel mounting
Aluminium Busbars with four equal Nos.
of bus having current density not more
than 0.8 Amp. / sq.mm (Rated current /
cross section area) duly wrapped with
colour insulating tape for phase sequence
of following current carrying capacity,
erected with necessary bus bar supports
/insulators, main cable socket to each
busbar,erected in existing cubical panel
with necessary connections.
2.2.25a 10 (A) Suitable for 100 Amp. Capacity 654.00 RnMtr
2.2.25b 18 (B) Suitable for 200 Amp. Capacity 1027.00 RnMtr
2.2.25c 18 (C) Suitable for 300 Amp. Capacity 1455.00 RnMtr
2.2.25d 30 (E) Suitable for 630 Amp. capacity 3031.00 RnMtr
Providing & erecting weather proof, dust
& vermin proof, floor mounted front
operated indoor type cubical panel board
necessary IP-42 and above protection as
per approval from engineer incharge
made from 14 SWG thick CRC M.S.
sheet for outer body & doors, 16 SWG
2.2.26 thick CRC M.S.sheet for internal
partitions with necessary accesories
supporting angles/ flats channel
including cutting, bending, drilling,
welding, riveting with internal partitions &
cable alley as per requirements &
instruction of engineer-in-charge with
supplied switch gears, BUSBARS,
suitable size of inter connecting PVC
copper wire / copper-aluminium strips,
rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments,
earth bus & earth bolts, foundation flange
- bolts-base Plates, sufficient nos. of
hinged doors, handles with locking
arrangement and rubber gasket,heavy
duty end terminal connection,danger
notice board,necessary
ventilation,earthing strip complete. The
Panel shall be painted with epoxy powder
(The rates excludes the cost of
switchgears, bus bars, inter connecting
mains & Copper Aluminium strips,
meters, Fuses etc. The dimension shall
be measured excluding base beams) The
panel shall be supplied with following
approved manufacturers with following
(B) The standard companies switch gear
shall be used and only manufacturers at
CPRI approved factory
12 (i) with 350mm depth 14755.00 Sqmtr
Supplying & erecting XLPE(IS:7098)(I)-88
ISI unarmoured copper cable 1.1 KV
grade to be erected as directed of
following size.
2.2.27a 40 (N) 4 core 16 Sq. mm 721.00 Mtr
2.2.27b 50 (M) 4 core 10 Sq. mm 568.00 Mtr
2.2.27c 12 (L) 4 core 6 Sq. mm 361.00 Mtr
2.2.27d 90 (C) 2 core 6 Sq. mm 202.00 Mtr
2.2.27e 20 (B) 2 core 4 sq.mm 130.00 Mtr
providing and erecting Mains with ISI
marked, 1.5KV grade electrolyte multi
stranded, annealed copper conductor
with heat resistant PVC insulated
conforms to IS 694, IEC - 227 erected in
existing pipe of following size
(Specifically for control panel, relays,
power switchgears, motor starters &
control wiring) with required size of
copper lugs, nuts and bolts if required.
2.2.28a 300 (a) One wire 1.00 sq. mm 12.00 Mtr
2.2.28b 120 (b) One wire 1.50 sq. mm 17.00 Mtr
2.2.28c 100 (c) One wire 2.50 sq. mm 27.00 Mtr
Design, Supplying, installing, testing of
factory fabricated ready made Three
phase APFC Panel Cubical Panel
fabrication should be type tested as per
IEC 61921, 61439:1&2 Capacitor Duty
Contactor for switching as per following
Steps Incomer Switch of MCCB type
Icu=Ics=50KA at 400/440 Volts, with OC,
SC, internal earth fault protection Incomer
Switch of MCCB type Icu=Ics=50KA at
400/440 Volts, with OC, SC, internal earth
fault protection,Copper tinned insulated
Busbar,Cubical panel should be indoor
type with IP 43 and IK 10,Metalized
2.3 polypropylene film tye3-phase 528-
550Volt Capacitor,De tuning Reactor for
each capacitor,Panel having Short Circuit
and Overload protection,Each step
Capacitor having suitable MCB with Sc,
OL, internal earth fault relay,Each stage
having Stage Contactor (Capacitor load
rating),PF regulator master controller
having suitable steps with LCD display,
Rs 485 Communication port, Indication
LED Lamps for main incomer and ON-
OFF for each capacitor bank,MS Chanel
for Floor mounting, Cable entry as per
site situation,Cooling fans for panel, (
Supplying & erecting approved make IP
55 grade Company fabricated Timer
Panel of following capacity for switch On-
Off street lights on time scheduling basis
made from 16G CRCA sheet duly epoxy
power painted inside and outside with
2.4 hinged doors and locking arrangement
consisting of suitable size of 4 Pole MCB
and 4 pole contactor (cat-III)with analog
time switch, auto manual switch of same
make and suitable input and output
Bakelite terminals and with door earthing
approved by Engineer in charge.
MCBDBs and MCBs
providing and erecting Miniature circuit
breaker single pole 6A to 25A suitable to
operate on 240 V A.C. system and having
breaking capacity 10 KA to be erected in
existing box. confirming to IS 8828/1996
Providing & erecting 240 V MCB double
pole switch for motor & inductive load
2.6 (C Curve) having 10 KA breaking
capacity & confirms to IS : 8828 in
existing box having following capacity
Providing & erecting 415 V MCB Four
Pole for Motor & Inductive Load (C
2.7 Curve) having 10KA breaking capacity &
confirms to IS :8828 in existing box
having following capacity
Sheets steel powder coated enclosure
2.8 4 suitable for incorporating One/Two nos. 175.00 E.a.
Providing and erecting Sheet Steel
powder coated MCB distribution board -
flush / surface mounted fitted with busbar,
neutral link, earth bar and DIN rail,
2.9 Conforms to IS 8623-1 & 3, IEC 61439-1
& 3 without MCB to house appropriate
nos. of MCBs.(The DBs should be used
of same company of MCB to be used)
(A) single phase incoming and horizontal
single phase outgoing
(b) sheet steel double door (IP-43)
2.9.1 6 (i)4 way ( concealed manner ) 747.60 E.a.
2.9.3 6 (iii)8 way ( concealed manner ) 1369.20 E.a.
2.9.5 32 (iv)12 way ( concealed manner ) 1773.60 E.a.
(B) three phase incoming and single
2.10 phase horizontal type outgoing Per
phase isolation type (PPI)
(b) sheet steel double door
2.10.1 14 (i)4 way ( concealed manner ) 2779.20 E.a.
2.10.3 7 (ii)6 way ( concealed manner ) 3462.00 E.a.
2.10.5 5 (iii)8 way ( concealed manner ) 4054.80 E.a.
Supplying & erecting Sheet Steel powder
coated Cable end termination Box to be
mounted on Top or Bottom of the MCB
Distribution Box for housing/covering
Extra wires & Cables, suitable for
following size of MCB DB Box.
(G) Three Phase 8 Way ( concealed
2.11.2 2 (G) Three Phase 8 Way 683.00 E.a.
Providing and erecting Sheet Steel
powder coated Vertical MCB distribution
board (VTPN) - flush / surface mounted
double door (IP54) fitted with copper
insulated busbar, isolated neutral bar,
2.12 earth bar and DIN rail, Conforms to IS
8623-1 & 3, IEC 61439-1 & 3, suitable for
250 AMP TPN MCCB + RCCB as
incomer and three phase outgoing as per
following .(The DBs should be used of
same company of MCB to be used)
2.12.1 1 (A)4 way outgoing 9149.00 E.a.
2.12.2 3 (B)6 way outgoing 9823.00 E.a.
Providing & erecting 415 V MCB three
Pole for Motor & Inductive Load (C
2.13 Curve) having 10KA breaking capacity &
confirms to IS :8828 in existing box
having following capacity
providing and erecting Approved make
ELCBs / RCCBs conforming to IS:
and having sensitivity of 30 mA and Short
Circuit withstand capacity of 10 KA and
suitable for operation on single phase
V,50Hz. having characteristic of quick
action & tripping with all advance feature
& do not incorporate any electronic
component. for following Max. rating
erected as directed
Providing and erecting metallic vitrified
danger notice board as per language
2.15 55 suggested by engineer incharge for 69.00 E.a.
MEDIUM VOLTAGE installation to be
erected as per IS-2551.
Providing & erecting Medium Voltage
2.16 20 Danger Notice Board sticker as per 26.00 E.a.
language suggested by engineer
incharge of standard size as per IS-2551
SUB - TOTAL OF Switchgears , Panel
Follow IS code :3043 is the guideline
for the earthing
Providing and erecting required size HOT
3.1 340 deep Galvanised iron strip for earthing of 77.00 KG
H.T. , OCB/ ACB/ Transformer LT panel
board, Motors etc. using proper clamp.
Providing and erecting required size
Copper strip for earthing of H.T. OCB /
ACB/ Transformer, LT panel board,
Motors etc. using copper clamp.
3.3 15 Providing and erecting Annealed bare 787.00 KG
Copper wire 8 to 16 SWG.
3.4 80 Providing and erecting HOT deep 77.00 KG
Galvanised iron strip wire 8 to 16 SWG.
Supplying & erecting earth pit of minimum
bore dia.150mm size approved make
Earthing Electrode consisting Pipe-in-
Pipe Technology as per IS 3043-1987
made of corrosion free hot dipped
G.I.Pipes having Outer pipe dia of
50mm having 80-200 Micron galvanising,
Inner pipe dia of 25 mm having 200-250
Micron galvanising, connection terminal
dia of 12mm with constant ohmic value
surrounded by highly conductive
compound with high charge dissipation
3.5 suitable for following type of applications
with chamber and heavy duty
cover.(approved make OEM has to
submit test certificate) & having back
filling compound of (B) Inner chemical
(CCM Compound)- Resistivity:- 0.2 W/
meter testing as per IEC 62561-2017,
Voltage drop:- < 1 volt at no load & dry
form, Sulphar content:- <2%(C) Back fill
Compound :- Earthing compound should
be capable to retain moisture for long
time Necessary test report must be
(a) For Electrical Installation up to 440V in
3.5.1 4 Length of pipe - 1 Mtr 4546.00 E.a.
Back filling compound - 1 Nos Bag of
(c) For Electrical Installation covering
Transformer Neutrals, Lightning arrester
Earthing, A.C.Plant & Sensitive Computer
System(like Automation, SCADA) i.e
independent Earthing in normal soil.
Length of Pipe : 3.00 mtrs
Back filling Compound :2 nos Bags of
Supply, installation,testing and
commissioning of Chemical Earthing with
UL Certified 17.2mm Dia. X 3000mm
Long 254 Micron-Copper bonded M.S.
Rod manufactured as per IEC 62561-2
with 25Kg Bentonite powder plus " U "
bolt rod clamp complete with Lockable
high performence chamber suitable &
tested for 5000T capacity with SS
Hardware.or equivalent
Supplying & erecting funnel type earthing
having earth plate of following size burred
in specifically prepared earth pit 3 mtr.
below ground with 40 kg. charcoal and
salt with alternate layers of charcoal &
salt, 20mm.dia. G.I. pipe with Funnel with
a wire mesh for watering & bricks
masonry block, C.I. Cover complete as
3.7 per para 7.3 of IS 3043 with necessary
length of double Galvanised Iron / copper
earth wire No 6 SWG bolted with lug to
the plate and covered in 12 mm dia. G.I.
pipe 2.5 mtr long complete connected to
the nearest switch gear with end socket
as per direction & duly tested by earth
tester confirming to IS (As per drawing)
with following specification
(C) with 60 x 60x 0.315 cms. Copper
SUB - TOTAL OF Earthing
4 CABLES, Cable Termination and cable
Providing and erecting XLPE(IS:7098)(I)-
88 ISI armoured cable multistrand
Aluminium conductor for 1.1 KV. to be
laid on wall with necessary clamps or in
existing trench / pipe of following size of
Providing and erecting XLPE (IS:7098)(I)-
88 ISI armoured cable multistrand / Solid
Aluminium conductor for 1.1 KV. to be
laid on wall with necessary clamps or in
existing trench / pipe of following size of
4.2.1 65 (a) 4 core 4 Sq. mm 116.00 Mtr
4.2.2 400 (b) 4 core 6 Sq. mm 125.00 Mtr
Providing and erecting XLPE (IS:7098)(I)-
88 ISI armoured cable multistrand
Aluminium conductor for 1.1 KV. to be
laid on wall with necessary clamps or in
existing trench / pipe of following size of
4.3.1 95 (d) 4 core 16 Sq. mm 152.00 Mtr
Providing and erecting XLPE(IS:7098)(I)-
88 ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing
trench / pipe at road crossing or floor of
following size of cable.
4.4.1 35 (C) 3 core 6 Sq. mm 392.00 Mtr
4.4.2 75 (D) 3 core 10 Sq. mm 495.00 Mtr
Supplying & erecting XLPE(IS:7098)(I)-88
ISI unarmoured copper cable 1.1 KV
grade to be erected as directed of
following size.
40 (I) 3 core 16 Sq. mm 557.00 Mtr
Providing and erecting XLPE(IS:7098)(I)-
88 ISI armoured cable multistrand / Solid
Copper conductor for 1.1 KV. to be laid
on wall with necessary clamps or in
existing trench / pipe at road crossing or
floor of following size of cables.
4.5.2 35 (B) 4 core 4 Sq. mm 361.00 Mtr
4.5.3 70 (C) 4 core 6 Sq. mm 505.00 Mtr
Providing and erecting XLPE(IS:7098)(I)-
88 ISI armoured cable multistrand
Copper conductor for 1.1 KV. to be laid
on wall with necessary clamps or in
existing trench / pipe at road crossing or
floor of following size of cables.
4.6.1 80 (D) 8 core 2.5 sq.mm 315.00 mtr
Making trench in soft soil of suitable width
of 90 cm deep for laying cable or locating
4.7 280 the fault all over the run and back filling 55.00 Mtr
the same and making the surface as
Covering of cable with second class
bricks or cement tiles laid cover the cable
4.8 40 crosswise & also on both sides with 139.00 Mtr
covering of 7. 5 Cm. layer of sand above
& below cable (16 bricks per meter)
( A )Making trench in Hard Murrum / Tar
Road of suitable width of 90 cm or
required depth for laying any size of
cable or locating the fault all over the run
and back filling the same and making the
surface as normal ground.
4.10 5 (B) If additional machinery like hammer 354.00 Mtr
driller or JCB use [Add]
Drilling the road without breaking the road
surface (Asphalt) for laying of cable for
4.11 feeding power supply by making up to
following size of holes at both ends
4.11.1 5 (A) Up to 100 mm bore dia 488.00 Mtr
4.11.2 5 (B) Up to 150 mm bore dia 610.00 Mtr
Supplying following size of Light duty “A”
4.12 Class G.I . Pipe & erecting as directed by
Engineer-in-charge.
10 (A) 25 mm dia 171.00 Mtr
Providing & laying. R.C.C. Hume pipe for
cable to be laid 90 cm. below ground
across the road crossing or on floor with
necessary material in an approved
manner and making the ground as per
Providing & laying approved make
Double walled corrugated pipes (DWC) of
polyethylene(conforming to IS 14930 II
4.14 )with necessary connecting accessories
of same material at required depth in
existing trench for laying of cable. below
ground / road surface for enclosing cable
4.14.1 80 (A)50 mm outer dia 62.00 Mtr
4.14.2 300 (B)63mm outer dia 73.00 Mtr
4.14.3 50 (C))90 mm outer dia 95.00 Mtr
4.14.4 40 (D)120 mm outer dia. 136.00 Mtr
Providing & laying approved make ISI
marked Rigid PVC pipe having 6Kg / cm2
(Class-3) to be erected at road crossing
on or floor as directed for laying of cable.
The pipes as following size of dia &
weight per 6 mtr.
4.15.1 5 (D) 75 mm inner Dia. (5.5 Kg/6RMT) 124.00 Mtr
4.15.2 5 (F) 110 mm inner Dia. (11.63 Kg/6 RMT) 234.00 Mtr
Providing and, fixing heavy duty flange
type brass cable gland with rubber ring
4.16 for PVC insulated armoured cable
complete with out going tails, insulating
tape etc for following size of cables.
Providing and, fixing heavy duty flange
type brass double compression type
cable gland with rubber ring for PVC
insulated armoured cable complete with
out going tails, insulating tape etc for
following size of cables.
Solder less crimping type Aluminium lugs
conforming to IS suitable for cable of
4.18 following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut
bolts in an approved manner.
Solder less crimping type Copper lugs
conforming to IS suitable for cable of
following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut
bolts in an approved manner.
Providing and fixing approved make
Perforated C type cable tray. Made from
sheet steel. The cable tray should be
single or double bended as per required
and as per IS 2062/1079 and shall be
coated with hot dip galvanizing as per IS
2629/4759. with max 17.5% perforation
with coupler plate / Fish plate and GI
hardware like nut - bolt and washers etc.
erection with necessary support(
included) as per Specification and as per
instruction of engineer in charge..
SUB - TOTAL OF Cables,Cable
Terminations & Cable Trenches
5 Light Fixtures & Fans
Supply , Installation, testing and
commissioning of pre-wired, LED
fitting/post top luminaries etc of all types,
complete with all accessories and tube
etc. directly on ceiling/ wall, including
connection with 1.5 sq. mm FRLS PVC
insulated, flexible, copper conductor,
single core cable with flexible conduits
and coupler and earthing etc. as required.
Note:- The LED Light fixtures should
comply all international standards third
party ( LM 79 for complete fixture, LM
for individual LED ). The Manufacturer /
Channel Partner of the Manufacturer has
to submit 4- Years unconditional free
Replacement Guarantee for complete
Supplying and erecting LED indoor
fittings with LEDs of wattage 0.2 Watt to
0.5 Watt assembled on single MCPCB,
with housing used as a heat sink shall be
made of thick sheet Steel conforming to
IS: 513/CRCA/ aluminium die cast
powder coated and high U.V. & corrosion
resistance with diffuser with company
mark/name 160V to 270V, Power Factor
more than 0.95, THD < 15%,CCT 3000 K
to 6500K, Luminaire efficacy>
lumens/watt , LED driver efficiency >
%( fitting required LM-79 & LM-80
Certificates)(NOTE: Below description
have shown ranges of Wattage capacity
of LED fittings.The Engineer incharge
may select any wattage capacity between
the ranges shown.)
( A ) Tube Light with integral / non integral
5.1.1a 10 (iii) 18-20 Watts, Surge - 2KV,IP-20, 293.00 No
conventional 2/ 4 feet
5.1.1b 55 (v) 36-40 Watts, Surge-2 KV, IP-20, 530.00 No
conventional 4 feet
(B) LED Panel Light with provision for
5.1.2 Plane front frame with translucent cover
fixed to housing complete.IP20
5.1.2a 30 (i)up to 8 Watts,4" x 4", Surge-2 KV 271.00 No
5.1.2b 235 (iii) 12-15 watts, 6" x 6", Surge-2 KV 462.00 No
5.1.2c 110 (iv) 18 to 20 watts, 8" x 8", Surge- 2 KV 607.00 No
5.1.2d 120 (vi) 36 watts, 24" x 24", Surge- 2KV 1777.00 No
5.1.3 (G) Spot Light 425 Lumens, Surge-2KV
5.1.3a 10 (a) 3 to 7 Watts 805.00 No
5.1.4 12 (H) Mirror Light 9 Watts, wall mounted 309.00 No
minimum 1 feet long
(I) Adjustable spot light with COB led
5.1.5 having aluminium reflector of following
5.1.5a 4 (ii) 12 Watts 957.00 No
5.1.5b 4 (iii) 15 Watts 1087.00 No
Providing & erecting Approved make
Power Saving 50 Watt Ceiling Fan with
double ball bearing ISI mark with
Condenser 230 volt A.C. 50 Hz
mm sweep complete having 3blades with
aluminium blades with , canopy & 30 cm.
down rod erected with earthing.(Make
shall be approved by Engineer in charge))
Providing & erecting Approved make
Ceiling Fan with double ball bearing ISI
mark with condenser A.C.230V 50c/s.
5.3 50 1400 mm. sweep complete, canopy 1721.00 No
erected on existing hook or clamp with
earthing [ Make shall be approved by
Engineer in Charge]
Providing & erecting Approved make
Ceiling Fan with double ball bearing with
Condenser 230 volt A.C.50 Hz. 900 mm
sweep complete having 3 Aluminium
blades, canopy erected complete. [ Make
shall be approved by Engineer in Charge]
Supplying and erecting approved make
oscillating type medium duty bracket fan
with Aluminium Blades A.C. 23OV. 50cy/s
wall mounted with height adjustment and
5.5 6 rotary tilting device complete with guard, 2329.00 No
mounting accessories kit, pull cord for
speed and oscillation flexible Core plug
top complete erected with lead wires as
directed. 400MM.
Supplying & erecting approved make low
noise decorative exhaust fan having size
5.6 48 200mm with 1350 RPM with square 1687.00 No
frame ABS body with inbuilt lowers &
Supplying & erecting fan hook box of
mm M.S. round bar bounded to the RCC
bars up to 50mm length each side and
5.7 180 pierced through a 16 Gauge M.S. box / 107.00 No
Heavy Duty PVC box complete erected
concealed in Ceiling with necessary
5.8 180 Providing 2.5mm.thick laminated acrylic 18.00 No
sheet to cover the fan hook or Fan box.
Supplying and erecting 19 / 20 mm.
nominal bore Medium Class M.S. Pipe
5.9 180 down rod erected duly painted for fan 107.00 Mtr
complete with proper insulation without
leakage and earthing.
Supplying & erecting single phase
approved make industrial exhaust fan
suitable for medium duty ring mounted
low noise operation suitable for medium
duty having following dia size and
maximum speed in RPM
1 [D] 450 mm dia 900 RPM 3306.00 No
5.11 1 Providing suitable M.S. louver shutter of 365.00 No
the Exhaust fan.
Supplying & erecting electro galvanised
G.I. wire micro mesh jali cover of grade
5.12 1 304 required size with suitable wooden 628.00 Sqmtr
frame duly fitted in wall outside of exhaust
fan for insect protection.
Providing and erecting PVC body surface
or pendent mounting LED Bulk type
watt Lighting Fitting with electronic driver.
And lumen output from luminaire 720lm
5.13 6 input voltage range 90-300VAC , 50Hz 780.00 No
cool white(3000 to 6500k), inbuilt driver, -
20degC to +60degC working
temperature, AL frame with Beam Angle
SUB - TOTAL OF Light Fixtures & Fans
6 External lighting
Supply , Installation, testing and
commissioning of pre-wired, LED fitting
/post top luminaries etc of all typesof
external lights, complete with all
accessories and tube etc. directly on pole
/ pole bracket , including connection with
1.5 / 2.5 sq. mm FRLS PVC insulated,3
core flexible, copper conductor, with
flexible conduits and coupler and earthing
etc. as required.
Supplying and erecting LED street light /
Flood light fittings with High power White
LEDs wattage of 3 Watt and above
assembled on single MCPCB, efficiency
more than 130 lm/w and corrosion free
High pressure die cast aluminum housing
with smooth finish powder coated and
heat sink extruded aluminium with
diffuser and Polycarbonate optics/ lenses,
with toughened glass with company
6.1 mark/name engraved or embossed 160 to
270 V,Power Factor more than 0.95, THD
< 10 %, CCT 3000 K to 5700K,Uniformity
ratio >0.45, Luminaire efficacy>
lumens/watt . LED driver efficiency >
%.( fittings required LM-79 & LM-80
certificates)(NOTE: Below description
have shown ranges of Wattage capacity
of LED fittings.The Engineer incharge
may select any wattage capacity between
the ranges shown.)
(A) Street Light (IP-65), Surge protection -
4KV /5000K integral and 10 kv non
6.1.1 integral ,Light must have 440VAC line
supply protection. It should withstand
hours for 440VAC line supply.
(f) Above 60 watts to 90 watts ( Required
(B) Flood Light (IP-65), Surge -
4KV/5000K ,Light must have 440VAC line
supply protection. It should withstand
hours for 440VAC line supply
6.1.2.a 12 (c) Above 60 watts to 90 watts 6028.00 No
6.1.2.b 4 (v) above 120 to 160 watts 8370.00 No
Supply of approved make frp/grp pole
having followiing specifications :
FRP/GRP pole made by centrifugal
moulding process using thermoset resin
polyester/epoxy resin system having
minimum glass content 45.0%.The pole
should be in one pieceand tapered round
in shape,having smooth outside surface
finish and should be totally fre from
corrosion as well as non conductive and
shock proof. Pole should be provided with
FRP/GRP base bracket dully fabricated
from metal(M.S) and dully claded with
FRP/GRP material to avoid any metal
exposer and painted with PU paint.
Pole should mechanical properties i.e
Specfic gravity (ASTM D 792) 1.3‐1.8
Kg/m3, 2. Glass Content % by weight
absorption (ASTM D 570) <0.5%,
Tensile Strength(ASTM D 638) 200+/‐
50Mpa, 5. Flexural strength (ASTM D
790) 250+/‐50Mpa, 6. Compressive
Strength (ASTM D 695) 200+/‐50MPa,
Yeild Strength(ASTM D638) 250 +/‐
Pole should be flame retardant as per IS
6746.Resin used shall be UV resistance
and pigmented. Pole should be painted
with first coat of epoxy primer and then
two coat of highly weather resistance
polyurethen paint to ensure proper
addhesion of the paint.Minimum
thickness shall be 80 to
micron.Defelection of the pole shall not
exceed more than 10.0 % of the length of
the pole for the given load.Pole should be
generally made as per the dimensional
data,performance criteria and some
interchagebility features of poles as per
the standard ANSI C123.20 latest version
of ASTM D 923/01 including cable
termination box with necessory
accessories.The size of pole and type of
installation with foundation , Anchor Base
& Internal junction box as per the
manufacturer details and site requirement
. The cost of 6 Mtr & 10 Mtr pole's Flood
light mounting ring is included.
(3) 'B' class (Heavy Duty) frp/grp pole
suitable for base plate mounting
[D] Overall Length of 6.0 meter, Average
thickness : 7mm, Top/Bottom Outside
Dia. 76/176mm +/‐2.Weight of Pole
16 Kg approx. (Without base) Metal Anchor 16815.00 E.a.
Base dully frp claded (Size : 340 Ø *
12mmthk , Mounting hole PCD 285mm *
6 nos. of 20 Ø hole)
Providing FRP/GRP arm bracket of
6.3 having 15˚ arm with 50 mm OD pipe *5
mm thk,1000mm long from pole centre
6.3.1 13 (a) Single arm bracket 1882.00 No
6.3.2 1 (b) Double arm bracket 2390.00 No
Supplying & erecting sintex make SMC
press moulded composite FRP. loop-in,
loop-out approx. 2mm thick box complete
with bakelite connector strip 4way &
6.4 2 hinged doors having locking 472.00 No
arrangements with mounting clamp with
nuts, bolts & washers suitable for erection
on wall ( c)150mm x 125mm x 100mm
Providing cement concrete.for foundation
or for concrete filling in 1:2:4 ratio with
6.5 7 to 25 mm stone metal duly plastered with 5077.00 CU Mtr
necessary curing for pole muffing or any
B' class galvanised iron pipe 32 mm
outside dia 45 cms long duly welded on
20 cms x 20 cms x 3 mm thick M.S. base
6.6 2 plate, erected on wall or corner for 340.00 No
mounting street light luminaire with
necessary hardware materials duly
SUB - TOTAL OF External Lighting
Supplying & erecting approved make
Automatic liquid level controller 6A. with
sensor testing as per instruction of
7.1 1 Engineer in charge on site complete with 2332.00 Job
wiring connection with existing wires
with copper conductor from pump to
upper and lower tank.
Supplying and erecting Flexible PVC
7.2 insulated multistrand multicore 1.1 kv
grade ISI marked copper wires of
following size to be erected as directed.
e) 1.50 Sq.mm 3 core round PVC
Providing and erecting ISI mark Medium
class RIGID PVC PIPES of following size
complete to be erected on/in wall or
ceiling erected with necessary PVC
fittings & Junction boxes fixed with
adhesive solution & Clamps with following
dia of pipes, in approved manner as
Providing & erecting water cooler having
storage capacity 150 Ltr. & cooling
capacity 150 Ltr.per hour @ an ambient
temp of 45˚ C. The outlet temp. of the
7.4 4 water should drop by 15˚C within a hour, 55340.00 No
The water cooler should be comprising of
hermetically sealed compressor, fan
motor, condensing unit, water tank
surrounded by evaporating, coil,
thermostats, relay etc.complete with
necessary inlet & outlet connection. The
body of water cooler will be made from
Stainless Steel.
Supplying and erecting water filter cum
purifier with ultra violate technology.
7.5 4 (Aquaguard / waterdoc model or 5371.00 No
equivalent symphony/ crystal/videocon
Providing & erecting open well horizontal
mono block pump set with cast iron body,
complete for three phase submersible
[D] For 5 HP 3 phase open well horizontal
mono block pump set suitable for
LPM to 310 LPM @ 10 to 42 Mtr head
suitable for 50/65 mm dia delivery pipe
[C] For 3 HP 3 phase open well horizontal
mono block pump set suitable for 85 LPM
to 270 LPM @ 11 mtr to 33 mtr head
suitable for 50/65 mm dia delivery pipe
Supplying & erecting approved make
motor control cubical panel (Direct - on -
line) made from 16 G. CRCA sheet duly
epoxy powder painted inside and outside
with hinged doors and locking,
arrangement consisting of suitable size of
ON- OFF isolator (AC - 3/23duty) main
fuses, single phasing preventer,
indicating lamps for R- Y - B phases,
overload relay, Automatic water level
controller, Ammeter, Voltmeter each with
two way selector switch incoming, wires
duly socket crimped, main contactor &
overload relay, start - stop push buttons,
to be erected on angle iron frame
grouted on wall as directed. The isolator,
overload relay & contactors will be of L &
T, Siemens or BCH make only.
2 (a) DOL up to 5.0 H.P. 7646.00 No
Charges for doing liasioning work for
obtaining the necessary clearances from
the Electrical inspector / competent
Authorities for the total Electrical
installation,co-ordinating with various
agencies including getting highrise
permission. All necessary drawings,
calculations, test certificates, etc. as
7.8 1 required by these authorities shall be 10000.00 No
prepared and furnished by the EPC
Vendor. Any modification/rectification as
required by these authorities shall be
carried out by theEPC Vendor at free of
cost. The fees required to be paid to
these authorities for inspection shall be
borne by Owner on production of
documentary evidences.
online Un-interruptible Power Supply
Supplying and erecting approved make
online Un-interruptible Power Supply
system comprising flat cum-boost charger
with IGBT base rectifier & Inverter &
sealed maintenance free SMF batteries.
The charger having operating capacity for
input 160-270V AC & inverter having
output 230V,50 Hz Ac with 0.8 load
power factor with battery, over/under
voltage output with over load & short
circuit protection equipment. The system
housed in CRC sheet duly powder coated
paint with following power backup.with
MS painted batteries stand, 10%
Overload capacity for momentary load.
3 [H} 10 KVA with 1Hr Backup 265597.00 No
Supplying and erecting horizontal /
vertical mounting type storage water
heater with copper container housed in
M.S./S.S. body insulated with glass wool /
puff complete with heating
elements,adjustable thermostats 300C to
850C, indicating lamp, safety valve,
fusible plug, etc.complete erected with
coach bolts, nuts. washers &
6 (C)25 Ltr. with 2 KW. heating element 11342.00 No
Premium category
Providing & erecting fibre reinforced PVC
flexible pipe with brass locking nuts &
washers & clips at both ends complete
erected without leakage
SUB - TOTAL OF MISC. Work
8 PASSENGERS ELEVATOR
Supply ,installing , commissioning and
testing of Stretcher Lift ( Hospital lift )
15/16 passengers (MRL LIFT) as per R
& B S.O.R ( Category - Premium ) having
following specifications:- G+3 Floor
Supplying, Erecting, Testing &
Commissioning the passenger lift having
following main features:
[1] GEAR LESS LIFT DRIVE comprising
of High Starting torque Lift 3 phase 440 V
A. C. Permanent Magnet Synchronous
motor of proper rating with high efficiency
[2] Micro processor based / PLC,
ACVVVF, vector control drive with
encoder feedback closed loop system
shall be used for lift car and door
operation which shall be full collective
selective operation hall call demand
response, UP/DOWN hall stops, Main,
Up/ Down Contactor with overload and
phase reversal relay and safety controls.
[3] Car with M S platform with bracings of
adequate size and to sustain the impact
load cabin + passenger with safety factor
of fire for steel and side panels of
Stainless steel of sheet of grade
duty. Car ceiling will be S.S. finishes with
aesthetic appearance with LED ceiling
lights. Car flooring shall be of anti skid
PVC with choice of colour of engineer in
charge. Car doors shall be of stainless
steel grade 304, hairline finish with centre
opening / telescopic automatic doors. Car
panel will also be S.S. 304 finished with
emergency stop device, mechanical door
safety device, facility of auto/ attended
mode. All car panel buttons and all floor
switches must be with brail language as
[4] All landing doors must be fire rated for
2 hour shall be fully automatic centre
opening/ telescopic opening made of
hairline finish steel grade of 304 with key
holes and infrared curtains with Unlocking
facility from outside
[5] Appropriate battery operated
emergency light in the car along with
alarm switch shall be provided. Also,
Emergency Light & Fan should start
immediately without any Time Delay as
soon as power fails.
[6] Digital scrolling indicator system for
up-down arrow along with floor position
indicator shall be provided inside the car
and at all floors.
[7] Full height infra red curtain with
multiple cross / crossing light beams shall
[8] Automatic Rescue Device (ARD) shall
be provided accordingly of passenger
capacity with Manual Rescue Operation (
Manual Cranking Facility).
[9] Audio visual indication in the lift car
showing over loading shall be provided
such that doors kept open till excess load
[10] Spring buffers/PU Buffers shall be
[11] Car fan as per passenger capacity
with automatic sleep timer shall be
[12] Voice annunciator with suitable
music shall be provided in lift car.
[13] Self diagnostics system for
operational and safety parameters shall
be provided in control panel.
[14] Mechanical over speed governor with
governor calibration as per actual site
parameters and submission of calibration
certificate submission, door key holes in
the floor doors, fireman switch shall be
[15] Lift machine hoisting arrangement in
the lift machine room and monkey ladder
for lift pit should be provided by the lift
agency, along with the other steel
structure works, foundations for the
[16] In the hoist way fascia plate shall be
provided without any extra cost, where
ever required as / if directed by engineer
[17] Permanent wiring with necessary
safety devices like RCCB in all circuit,
Over Voltage Under Voltage protection
and THD eliminator in circuit for lift
machine room and lift well with proper
numbers of light points, with fixtures,
exhaust fan and plug points shall be
provided by the agency. Only 3 phase
Power Supply shall be made available by
department in lift machine room.
Necessary Earthing as per Lift Act/Rules
shall be arranged by Lift Agency.
[18] Any civil/ electrical works for
additional and alteration in lift shaft and
machine room related to erection of lift
shall be made by lift agency without any
extra cost. (granite/marble fixing around
all landing door openings are not in lift
agency’s scope.)
[19] Agency has to provide all working
drawings and documents and liaison
services for obtaining all necessary
permission from lift inspector and other
[20] acrylic transparent licence/display A4
size holder in lift car
[20A] As per statutory requirement of
Govt. Of Gujarat lift & escalator act
lift agency has to provide
1. Car top safety barricade
2. Push & talk communication system.
3. Fireman's switch operation at Ground
4.carrying out third party lift inspection
during/after lift erection and provide report
by third party authorized by concern
licensing authority 5.agency has to
provide third party insurance upto
completion of free maintenance period
and submit the document for the same.
[21] Car Panel Operating Buttons with
floor position indicator/buttons must be of
Auto Glow type clearly visible when view
from inside cabin.
[22] For Physically Handicapped person
Full Length Handrails of hairline finish
steel grade of 304 should be provided at
appropriate height on the Rear & Side
Wall Panels in Lift Car.
[23] With Necessary KVA rating voltage
controlled Stabilizer suitable for your
controller, drive and all equipments of lift.
[24] Necessary rating of DP Elcb and FP
Elcb required for lift is in scope of work
which rating is sugested by CEICED
Department (electrical Inspector)
(B) SPECIAL FEATURES
DESCRIPTION OF LIFTS for PREMIUM
1. Advanced control system dual 64 bit
embedded microprocessor with CANBUS
Serial Communication mode including
Regenerative power efficient operation,on
site programming facility, Anti nuisance,
Pte-opening, BMS/RMS with necessary
online real time monitoring system having
necessary connectivity for remote
monitoring & other suitable supporting
hardware & software devices to fulfil the
2. Floor Indication LCD Display with call
registration & brail mark with arrival gong
and hall lantern & TFT Screen in the car
with MP3 Voice Announcer.
3. CAR Panel should be Scratch
resistive SS Moonrock finish / Hair Line /
Honeycomb for car and all Doors, All
landing doors must have fire rating up to
2 hours and car door must have multi-
level crisscross beam door protection.
4. To & fro communication system &
wiring (i.e. car , control room & guard
room ) and Each elevator are equipped
with remote monitoring system.agency
has to provide mobile app and user id
and password for monitoring
15/16 Passengers, Stretcher Lift Ground
plus 3 upper floor with Rated Speed of
AMC LOGO design as per given by
department to be embossed inside the lift
car wall opp. To door.
(C) With General PLUS ADDITIONAL
2 SPECIAL FEATURES attached herewith. 2003064.00 No
SUB TOTAL of Passengers Elevator
Providing and erecting approved make
split air-conditioning unit consisting of
copper condensing unit with fan motor,
hermetically sealed rotary compressor
with accessories etc. duly connected
separately erected evaporating unit and
9.1 blower motor with its accessories by
means of extra supplied proper insulated
copper tubing,drain PVC pipes suitable
for ( cost includes powder coated Stand,
Eco Friendly green gas charging, 15A
plug top & Remote Control) with
necessary core cutting.
(1)For ISEER Range (KWH/KWH)(3.1 to
3.99) Premium Category
9.1.1 1 [a] For 0.8 to 1.0 Ton Capacity 38986.00 No
9.1.2 9 (b) for 1.5 ton capacity 51923.00 No
9.1.3 12 (c) for 1.7 to 2.0 ton capacity 58706.00 No
9.1.4 2 (d) for 2.2 to 2.5 ton capacity 68449.00 No
Supplying and installing MS angle
powder coated / Painted standard type of
wall/floor stand mount for outdoor unit of
split AC of following capacity, erected
with necessary hardware materials as
(A) 25mm*25mm*3mm thick M.S angle
9.2.1 10 suitable for upto 2 TR. Capacity of ac 1305.00 No
(B) 35mm*35mm*5mm thick M.S angle
9.2.2 14 suitable for above 2 TR to 4 TR Capacity 1496.00 No
Supplying and erecting insulated pair of
9.3 580 soft copper tubing including power and 956.00 RMT
control cable,necessary PVC drain pipes
for Split AC machine up to 4 TR capacity
Rigid UPVC drain pipe of 10 Kg/cm2.
9.4 rating with 9 mm thick.nitrile rubber
Supplying & fixing 50mm thick TF quality
9.5 142 expanded polystyrene for underdeck 409.00 Sqmtr
insulation on slab/wall /shaft exposed to
sun/atmosphere as per specifications.
SUB TOTAL of HVAC WORK
10 D.G.SET AND ATS PANEL
Supplying and erecting, commissioning
and testing of Diesel Generating set
confirming to IS: 4722:1968 & BS:5514
having continuous rating, 3 phase,
volts, 50 cycles A.C. supply comprising of
a totally enclosed air/water cooled diesel
engine with multi-cylinders developing
suitable BHP not less than following
capacity at 1500 RPM with 10% overload
for one hour in 24 hours with standard
accessories like fly wheel, lubricating oil
cooler, "A" class governor, heavy duty
fuel wheel and lubricating oil filter, oil bath
air filler, lubricating oil pressure gauge,
end exhaust manifold, standard set of
tools with adjustable spanners, screw
drivers, cylinder head to cover, joint
cylinder head to exhaust, element lube oil
filter, 12 / 24 volts electric starting
equipment complete with standard heavy
duty battery, dynamo, cut-outs, ammeter,
necessary wiring, pressure gauge, starter
etc and heavy duty Residential type
exhaust silencer (With DEF System) and
vertical hot air duct both
logged with asbestos rope, save oil trays,
exhaust piping of required length,
standard wall/floor mounted fuel with level
indicator and piping and drip proof
alternator, self excited, self regulated,
screen protected, with excitation system,
capable of delivering the rated system
output at 415 volts, 3 phase, 0.8 PF,
Hz, 4 wire, running at 1500 RPM,
conforming to IS-4722- 1968 with voltage
regulation +/- 5% of rated voltage from
no load to full load. Both the engine and
alternator fitted on a common fabricated
steel base plate with antivibration
mounting engine and alternator both
connected to each other by flexible flange
coupling and with floor/wall mounted
control panel box comprising of voltmeter
ammeter, selector switches, ACB /
MCCB / MCB of adequate capacity,
indicator lamps duly wired with HRC
fuses. The alternator & control panel shall
be connected with provided suitable
capacity armoured cable and complete
with Acoustic enclosure (canopy) made
out of 16 SWG CRCA Sheet, sound
absorbing material Rockwool of
density & 100 mm thick conforming to
IS:8183 / PU Foam of 40 Density - at
least 40 mm. The resin bonded rockwool
covered from inside the canopy by
perforated sheet with 3/4 mm holes,
sound level not more than 75 dB at a
distance of 1 mtr, as per PVCT norms.DG
set should have in built fuel tank capacity
of minimum 8 hrs of continous running
capacity on full load . Erection,
commissioning and satisfactory testing as
per requirement with first filling of fuel
(minimum up to the 80% of fuel tank
capacity), oil, etc. with guarantee /
Warrantee of complete system for Two
years. & with obtaining all necessary
certificate from Electrical Inspector. The
Capacity and Ratings of DG sets are as
below. (As per new CPCB4+ Emission
norms Engine With - Turbo Charger,
EGR (Exhaust Gas Recirculation), CRS
(Common Rail Fuel System), DOC
(Diesel Oxidation Catalyst), SCR
(Selective Catalytic Reduction),
Integrated wiring harness connected to
1 (O) Continuous rating of 160 KVA ,BHP 1382776.00 Each
not less than 197 BHP
Providing & erecting approved make ATS
panel suitable for following size of
phase, 415 V., 50 cycles, A.C. diesel
generating set complete of scope as
detailed below:
1) Power module: Motorised Changeover
switch with ATS controller, Auxiliary
contactor with NO & NC contacts with
Automatic Battery Charger, indicating
lamps for Generator ON, Mains ON, Load
and suitable control terminals and power
terminals with neutral earthing studs.
(F) ATS Panel for 160 KVA 3 phase DG
SUB TOTAL of D.G.SET & ATS Panel
I. No. Qty Items Unit Rate Per Amount
CCTV System Work Estimate
Final specification and block diagram
shall be submitted by CCTV camera
SITC of 1/2.8" CMOS 3MP IP Fixed Lens
IR rugged DOME Camera having
progressive scanning system , Pixels
3MP (2304 x 1296),Lens 2.8 mm, Fixed,
F1.4, Minimum Illumination color / BW:
Color: 0.002 Lux @ F1.6, BW 0 Lux IR
ON,IR Distance 40 Mtrs,Wide Dynamic
Range 130 Db,Privacy Masking Off/On (5
Areas),Local Storage Micro
SD/SDHC/SDXC card slot (2TB),Gain
Control 0 ~ 100%,Angle of View (H x V)
H:87.2° V:49.1°,Ethernet 10 Base-T/100
Base-TX Ethernet (RJ-45),Protocols:IPv4,
IPv6, TCP/IP, HTTP, HTTPS,
RTSP/RTP/RTCP, IGMP/Multicast,
SMTP, SNMP, DHCP, NTP, DNS, DDNS,
CoS, QoS,802.1X, UPnP,
mDNS(Bonjour), UDP, ICMP, ARP, TLS,
SFTP,Body Material Aluminium +
Polycarbonate,Number of Video Streams
4,Ingress Protection IP66, IP67, Event
Notifi cation HTTPS, HTTP, SMTP,
ONVIF, Bit Rate 100 K ~ 6 Mbps
Certificates: FCC PART 15, CE (EN
55032), ICES-003,CE (EN 55035),UL
listed to UL/CSA 62368-1, BIS IS
(Part 1)/IEC 69050-1,RoHS, REACH,
WEEE,BIS ER, STQC
SITC of 1/2.8" CMOS 3MP IP Fixed Lens
IR rugged Bullet Camera having
progressive scanning system , Pixels
3MP (2304 x 1296),Lens 3.6 mm, Fixed,
F1.4, Minimum Illumination color / BW:
Color: 0.002 Lux @ F1.6, BW 0 Lux IR
ON,IR Distance 50 Mtrs,Wide Dynamic
Range 130 Db,Privacy Masking Off/On (5
Areas),Local Storage Micro
SD/SDHC/SDXC card slot (2TB),Gain
Control 0 ~ 100%,Angle of View (H x V)
H:87.2° V:49.1°,Ethernet 10 Base-T/100
Base-TX Ethernet (RJ-45),Protocols:IPv4,
IPv6, TCP/IP, HTTP, HTTPS,
RTSP/RTP/RTCP, IGMP/Multicast,
SMTP, SNMP, DHCP, NTP, DNS, DDNS,
CoS, QoS,802.1X, UPnP,
mDNS(Bonjour), UDP, ICMP, ARP, TLS,
SFTP,Body Material Aluminium +
Polycarbonate,Number of Video Streams
4,Ingress Protection IP66, IP67, Event
Notifi cation HTTPS, HTTP, SMTP,
ONVIF, Bit Rate 100 K ~ 6 Mbps,
Certificates: FCC PART 15, CE (EN
55032), ICES-003,CE (EN 55035),UL
listed to UL/CSA 62368-1, BIS IS
(Part 1)/IEC 69050-1,RoHS, REACH,
WEEE,BIS ER, STQC
Supply , Installation , Testing and
commissioning of 32 Channel NVR
(Network Video Recorder) Embedded
Linux based for recording upto 32CH at
1080P, 960fps with 04 nos. SATA HDDs
minimum 40TB storage or more
(recording requirement all cameras
recording at 2MP, 25fps for 30 days),
H.265 HEVC/H.264/MJPEG codec
decoding, Front Panel with LEDs
Indication for Power & HDDs Status,
nos. USB, ONVIF S, Time Sync with
NTP, Encrypted Streaming & Control, 2-
Way Audio Line & Out, PTZ Operation
Pan, Tilt, Zoom, Support, Pre & Post
Alarm Recording Support,
Recording/Evidence Clip Export to USB,
16 Channel Synchronous Playback,
1.3 1 Playback control i.e Play, Pause, Stop, 66202.00 No
Fast Forward, Backward, Speed Control,
Timeline & Zoom; Snapshot, Web Client,
Central Monitoring Software, iPhone;
iPad; Android based Mobile clients,
02HDMI & 01VGA Output, 04 On Board
HDDS each up to 10TB, Alarm Input (16
nos.), Alarm Output (04 nos.),
RS232/485, eSATA, 256 Mbps
throughput, NDAA Section
Compliant, Operating Temperature –10°C
to 55°C, Certification : Certifications:
ONVIF compliant, UL/CSA 62368-1, CE
(EN 50130-4), FCC Part 15, EN
NDAA & RoHS (EN63000) compliant.
Including fixing accessories and cable
termination with required
connectors/Jack, complete in all respect
as per instruction of engineer in-charge.
Supply Installation Testing &
1.4 2 Commissioning of 8TB Surveillance 25150.00 No
Supply, Installation, Testing and
Commissioning of 43 inch, Professional
LED Display Cum Commercial TV with
Android 11 & Inbuilt play store, UHD
resolution, 400 nits brightness, It's 24*7
usage, 50,000 hours life, 3 years
warranty, Android 11 with inbuilt play
store, Inbuilt wifi, Landscape / Portrait
mode, Inbuilt Bluetooth, 2 GB / 16 GB
Memory, Inbuilt SOC with HDMI cable
Providing and erecting ISI mark Medium
class RIGID PVC PIPES of following size
complete to be erected on/in wall or
ceiling erected with necessary PVC
fittings & Junction boxes fixed with
adhesive solution & Clamps with following
dia of pipes, in approved manner as
CAT 6 UTP Cable
Supplying & erecting approved make LAN
1.7 cable of following size in existing pipe as
1.8.1 1 Supply, Installation, Testing & 12053.57 No
Commissioning of 9U wall mount rack.
1.8.2 2 3U wall mount Rack 5025.01 No
SITC of 24 x 10/100/1000BASE-T PoE
ports 4 x Gigabit RJ45/SFP Combo ports
Advanced L2 switching and security
features L2+ Static Routing Optional
“standard mode” or “surveillance mode”
management user interface 193 W PoE
budget (Including Five year free
maintenance with guarantee)
SITC of 8 x 10/100/1000BASE-T PoE
ports 2 x Gigabit SFP ports Advanced L2
switching and security features L2+ Static
Routing Optional “standard mode” or
surveillance mode” management user
interface 65W PoE budget
[Approved by Competent Authority i.e. not
Below the rank of Executive Engineer ]
Supply, Installation Testing &
Commissioning 5 Mtr. HDMI Interface
1.11 1 Cable as per the detailed Specifications 820.00 No
supports transmission of 4K Signals as
per the detailed Specifications
Supply, installation, fixing, testing and
commissioning of PVC Junction box for
1.12 28 CCTV Camera, IP65, outdoor application. 440.00 No
Junction Box size will be as per vendor's
requirement and site condition.
SITC of Patch Panel Cat 6 UTP Keystone
Type- 24 Port-Fully Loaded (Including
Five year free maintenance with
SITC of Jack Cat 6 Keystone UTP
1.14 28 (Including Five year free maintenance 160.00 No
with guarantee)
SITC of CAT6 UTP 24AWG PATCH
CORD:1M,Plug 30U' Snag less
(Including Five year free maintenance
with guarantee)
SUB -TOTAL OF CCTV SYSTEM
2 LAN NETWORKING
Supplying and laying UPVC cable
trunking system comprising unplasticised
polyvinyl, chloride rigid material with
ignition free and flame proof confirming
BS with necessary end caps Internal and
external bend, flat bends, coupler, tee
etc..All necessary accessories and
measuring of following sizes
2.1.1 5 (2) 100 mm x 50 mm trunking 424.00 Mtr
2.1.2 5 (4)100 mm x 50 mm trunking with TWIN 1309.00 Mtr
compartment With clip in divider
Supply & installation of surface mounted
U PVC snap-on adaptable trunking
raceways, fabricated out of U-PVC to Off-
White or approved shade as per IS 733 of
thickness 2.0mm for the base and sides
with all accessories like removable
covers, joints ,height spacer,angles
complete with necessary bends, suitable
sized junction boxes and tees etc,
(a)Size: 50x80mm PVC Raceways for
5 Power & Data with 2 compartments 1052.00 Mtr
above specifications.
Supply & installation of modular type
accessories for U PVC snap-on
adaptable trunking/Pop up Box with
required items erected with necessary
connection. As desired by Engineer In
2.3.1 4 i) 6 A SP 1 Way Switch 204.00 No
2.3.2 2 ii) 16A SP 1 Way Switch 351.00 No
2.3.3 4 iv) 6A universal socket shuttered 347.00 No
2.3.4 2 iv) 6/16 A universal socket shuttered 458.00 No
2.3.5 2 vi) Cat-6 LAN Socket 561.00 No
Supplying & erecting approved make
Telephone Cable electrolytic copper
conductor PE insulation twisted in two
pairs, & wrapped with FRLS PVC tape &
2.4 sheathed with FRLS PVC or HFFR outer
Jacket suitable for telephone wiring &
confirming to C-DOT erected in existing
pipe. of following size of conductors &
nos.of pairs. With necessary connections.
(b) Armoured [Jelly Filled]
40 1) Ten Pairs 124.00 Mtr
2.5 LAN NETWORK
SITC of CAT6 UTP 24AWG PATCH
CORD:1M,Plug 30U' Snag less
(Including Five year free maintenance
with guarantee)
SITC of CAT6 UTP 24AWG PATCH
CORD:2M,Plug 30U' Snag less
(Including Five year free maintenance
with guarantee)
SITC of 24 x 10/100/1000BASE-T ports
x Gigabit RJ45/SFP Combo ports
Advanced L2 switching and security
features L2+ Static Routing Optional
“standard mode” or “surveillance mode”
management user interface
SITC of Patch Panel UTP Keystone-
Port- Unloaded (Cat 5e,Cat 6 & Cat 6 A )
(Including Five year free maintenance
with guarantee)
Providing & erecting main Distribution
(MDF) indoor type, back mounted frame
as per DoT standard approved with krone
1 (a) Suitable for 10 pair 985.00 E.a.
Providing & Erecting Netwrok rack with
following capacity with Necessary cooling
2.8 fan,Cable manager,6A PDU,equipment
rack with necessary mounting
Supplying & erecting approved make LAN
2.9 cable of following size in existing pipe as
Providing & Erecting approved make
following size of TV Co-axial flexible
cable comprising inner conductor of solid
bare copper insulated with Foam PE &
Secondary conductor made of poly -
Aluminium film bonded Al. Braids @
suitable coverage overall sheathed with
black PVC insulation.
SUB -TOTAL OF LAN NETWORK
I. No. Qty Items Unit Rate Per Amount
FIRE FIGHTING SYSTEM
Design,Drawing,
Supply,installing,testing and
commissioning of FIRE HYDRANT
1 Internal / External Hydrant
Supplying, Installation, Testing and
Commissioning of electric driven main
1.1.1 Hydrant fire pump suitable for automatic
operation and consisting of following:
complete in all respect as required.
a) Horizontal type, single stage,
centrifugal, end suction pump of cast iron
body & bronze impeller with stainless
steel shaft, mechanical seal to ensure a
minimum pressure of 3.5 kg/sq. cm. at
highest and farthest outlet at specified
2 flow of 2280 lpm at 65 Mtr. head 230151.00 Set
conforming to IS 1520.with suitable size
of footvalve confirming to IS
Pressure rating PN2 , preventing entry of
foreign body to pump through suction
pipe, perfectly flat seating surfaces for
b) Suitable HP Squirrel cage induction
motor, TEFC, suitable for opertion on
415 volts, 3 phase 50 Hz. AC with IP
class protection for enclosure, horizontal
foot mounted type with Class - 'F'
insulation, conforming to IS-325.
c) M.S. fabricated Common base plate,
coupling, coupling guard, foundation bolts
etc. as required.
d) Suitable cement concrete foundation
duly plastered with anti vibration pads.
The pump shall be capable of giving not
less than 150% discharge at ahead not
less than 65% of the rated head.
Supplying, Installation, Testing and
Commissioning of electric driven
pressurisation pump suitable for
automatic operation and consisting of
following: complete in all respect as
a) Horizontal type, single stage,
centrifugal, end suction pump of cast iron
body and bronze impeller with stainless
steel shaft, mechanical seal at specified
flow of 180 lpm at 56/70 m. head
conforming to IS: 1520.with suitable size
of footvalve confirming to IS
Pressure rating PN2 , preventing entry of
foreign body to pump through suction
pipe, perfectly flat seating surfaces for
b) Suitable HP Squirrel cage induction
motor TEFC type suitable for operation
on 415 volts, 3 phase 50 Hz. AC with IP
55 Class of protection for enclosure,
horizontal foot mounted type with Class F'
insulation, conforming to IS :
c) M.S. fabricated Common base plate,
flexible rubber coupling, coupling guard,
foundtion bolts etc. as required.
d) Suitable cement concrete foundation
duly plastered with anti vibration pads.
1.1.3 ENGINE DRIVEN PUMP
Supplying, Installation, Testing and
Commissioning of diesel engine driven
1 main fire pump suitable for automatic 506181.00 Set
operation and consisting of following:
complete in all respect as required
a) Horizontal type, single stage,
centrifugal, end suction pump of cast iron
body and bronze impeller with stainless
steel shaft, mechanical seal to ensure a
minimum pressure of 3.5 kg/sq. cm at
highest and farthest outlet at specified
flow of 2280 lpm at 65 m. head
conforming to IS
b) Suitable HP, 1500 /1800 RPM water
cooled with radiator, diesel engine
conforming to relevant BS & IS standard
complete with auto starting mechanism,
12/24 volts electric starting equipment,
180 AH lead acid battery with battery
stand, exhaust pipe extended upto 6 m.
outside pump house duly insulated with
50 mm thick glass wool with 1.0 mm.
thick aluminium sheet cladding,
residential silencer, instruments and
protection as per specification, stop
solenoid for auto stop in the event of fault
with audio indications, painted with post
office red colour etc. as required.
c) One 200 Ltr capacity day oil storage
tank fabricated from 3 mm thick M.S.
plates. Tank shall be provided with inlet,
outlet, overflow, air vent, drain
connections, filling connection & level
indicator. Tank shall be mounted on a
suitable steel structure (Painted with
coats of red oxide paint). Tank shall be
provided with two or more coats of
synthetic enamel paint outside over two
coats of red oxide primer.
d) M.S. Fabricated Common base plate,
coupling, coupling guard, foundation bolts
etc. as required.
e) Suitable cement concrete foundation
duly plastered with anti vibration pads.
1.2 FIRE PANELS
FIRE CONTROL PANEL FOR Main
1 Hydrant pump and Jockey pump and 341210.00 No
Diesel Engine pump.
Fabrication, Supplying, Installation,
Testing & Commissioning of electrical
control panel of cubical construction, floor
mounted type, fabricated out of 2mm
thick CRCA sheet, compartmentalised
with hinged lockable doors, dust and
vermin proof, powder coated of approved
shade after 7 tank treatement process,
cable alley, inter-connection, having
switchgears and accessories mounting
and internal wiring, earth terminals,
numbering etc. complete in all respect,
suitable for main fire pump, pressurisation
pump complete as per CPWD
specification with following in coming and
Outgoings, suitable for operation on
415V, 3 phase, 50Hz Ac Supply with
enclosure protection class IP 42 as
required :suitable for operation on 415 V,
3 phase, 50 HZ, AC supply with
enclosure protection class IP 42 as
A. Incoming Feeder:-
(i) 1 No of 200 A,35KA, 415V,FP MCCB
with Thermalmagnetic Based Releases
having O/C, S/C ,E/F protection, Digital
ELR 96x96mm with CBCT, FP Spreader
Terminals 1 set= 8 Pcs, Extended Rotory
Handle for MCCB, 240V AC Shunt Trip
(ii) LED type indicating Lamp with suitable
rating 2 Amp SP MCB:- 1 Set (each set
comprise of R,Y,B)
(iii) Digital type 3 phase Multi function
Meter with suitable rating of MCB &
Nos. of single core epoxy resin cast type
CTs of 200/5 Amps, 10 VA, CL
ratings -1 Set.
415 V, 200 Amps, FP Aluminium Busbars
with Heat shrinkable color code insulation
OUTGOINGS:-( All outgoing feeders for
pumps should have digital Ammeter with
selector switches and LED type
ON,OFF,Trip indicating Lamps )
1 sets - 125 A, 25kA TPN MCCB,
Ics=100% Icu, with fully automatic
Star/Delta starter suitable for 50 HP pump
with overload protection, current sensing
type single phase preventor complete
with all acceessories and internal wiring
required for automatic operation,selector
switch for local/remote, auto/manual/OFF
1 sets - 125 A, 25kA TPN MCCB,
Ics=100% Icu, with fully automatic
Star/Delta starter suitable for 50 HP pump
with overload protection, current sensing
type single phase preventor complete
with all acceessories and internal wiring
required for automatic operation,selector
switch for local/remote, auto/manual/OFF
1 no.63A,16KA MCCB
Ics=100%,Extended Rotry handle with
TM release having O/C & S/C protection
with 10 HP fully automatic star/ delta
starter , current sensing type, Single
Phase Preventer, ON/OFF Push Button &
LED type Indicating lamps complete with
all accessories and internal wiring
required for automatic operation, selector
switch, for local/remote, auto/manual
Diesel Engine Control.
Control for Diesel Engine comprising:
i) Auto/Manual selector switch &
attempt starting device, timers and relays
as required, push buttons, start/stop in
ii) LED type Indication lamp for High/Low
Lub. Oil pressure, High Water Temp and
Engine ON indication.
iii) Battery charger suitable for 12 V/24 V
DC with boost and trickle selector switch,
0-30 V DC volt meter, 0-20 Amp DC
iv) All standard relays, accessories for
automatic operation of diesel engine,
wiring with 1.5 sq mm PVC insulated
copper wire between various sensors and
system controller / starter, suitable size
cable for battery charging etc. as
System Controller
Designing, Supply, Installation, Testing
and Commissioning of system controller
to control operation of Main Electric Fire
Pump, Diesel Pump, Pressurisation
Pump, Terrace Pump in sequence as per
specification consisting of relays, timers,
sensors, annunciation window for fault
indication, control wiring complete as
3 NOS. 25A DP MCB " C " Curve
1.3 PRESSURE GAUGES AND PRESSURE
Providing, fixing, testing and
1.3.1 2 commissioning of Pressure Switch with 1329.87 Set
Providing and fixing in position the
1.3.2 3 industrial type pressure gauges with gun 967.73 Set
metal / brass valves complete as required
Providing, laying, testing &
commissioning of 'C' class heavy duty MS
Pipe conforming to IS 1239 i/c fittings like
elbows, tees, flanges, tapers, nuts bolts,
gaskets etc., in ground including
1.4 excavation and providing cement
concrete blocks as support, anticorrosive
treatment with coaltar/asphalt tape as per
IS 10221, refilling the trench etc. of
following sizes complete as required .(
35 100MM Dia 2300.63 Mtr
Providing, laying, testing &
commissioning of 'C' class heavy duty MS
pipe conforming to IS 3589/IS
including Welding, fittings like elbows,
tees, flanges,tapers, nuts bolts, gaskets
etc. and fixing the pipe on the wall/ceiling
with suitable clamp/support frame and
painting with two or more coats of
synthetic enamel paint of required shade
complete as required :
1.5.9 5 200mm Dia ( wall thickness 6.3mm ) 4938.01 Mtr
Supplying and fixing Single headed
internal / External hydrant valve with
No. 63 mm dia instantaneous FM
Gunmetal/Stainless Steel coupling and
cast iron wheel,ISI marked, conforming to
IS 5290 (type A) with blank
Gunmetal/Stainless Steel cap and chain
16 Single headed Stainless steel 5549.04 No
Providing, fixing, testing and
commissioning of Wall mounting swing
type first aid Fire Hose Reel with drum,
1.7 15 hanging bracket, 30 M x 25 mm dia high 10499.50 No
pressure hose reel tubing as per IS:884
with shut nozzle and ball valve and all
required accessories.
Supplying, Installation, Testing and
commissioning of weather proof Fire
Hose cabinet size 900x 600x300mm to
house fire hydrant & hose, including
all other related accessories fabricated
1.8 15 from M.S. sheet (16 Gauge) of fully 4726.50 No
welded construction having front door
with locking arrangement, partially glazed
with 4 mm thick glass. Cabinet shall be
powder coated & painted with post office
Providing ISI marked RRL (IS : 636, type‐
A) fire hose pipe 15 meter long and
mm dia with ISI marked (IS : 903)
1.9 30 Stainless steel male and female coupling 4020.55 No
bound and rivetted to hose pipes with
copper rivets and copper wire complete
Providing Stainless steel ISI marked
mm. dia. male Instantaneous pattern
short branch pipes with 20 mm dia.
1.10. 16 Nozzle as per IS : 903, suitable for 10 1502.28 No
Kg/sqcm operating pressure and suitable
for interconnections to hose pipe coupling
Supplying and fixing of fire brigade
connection of cast iron body with gun
metal male instantaneous inlet couplings
complete with cap and chain as reqd. for
suitable dia MS pipe connection
conforming to IS
1.11.1 1 2 way - 100 mm dia M.S. Pipe 6094.09 No
1.11.2 1 4 way - 150 mm dia M.S. Pipe 12631.09 No
Providing, fixing, testing and
1.12 1 commissioning of 25 mm dia Air Release 1949.25 No
Valve and Ball Valve assembly on top of
each riser for Air release system.
Providing, fixing, testing and
1.13 1 commissioning Pressure Relieaf Valve 4940.68 No
25mm dia with Ball Valve.
Supplying and fixing orifice plate made
out of 6 mm thick stainless steel (Grade
304) with orifice of required size to be
1.14 12 fitted between flange & landing valve of 1932.76 No
external and internal hydrants to reduce
pressure at the outlet to the level of
kg/cm2 complete as required.
Supplying, fixing, testing and
commissioning of butterfly valve of PN
1.6 rating with bronze/gunmetal seat duly
ISI marked complete with nuts, bolts,
washers, gaskets conforming to IS
of following sizes as required :
Providing, installation, testing and
commissioning of non-return valve of
1.16 following sizes confirming to IS:5312
complete with rubber gasket, GI bolts,
nuts,washers etc.as required :
Providing, installation, testing and
commissioning of stainless steel Y-
1.17 strainer fabricated out of 1.6 mm thick
stainless steel, Grade 304, sheet with
mm dia holes with stainless steel flange.
Supply, Installation, Testing and
1.18 11 Commissioning of Brass. Ball Valves with 737.27 No
all fittings required. 25mm size
Supplying and erecting Flexible PVC
1.19 insulated multistrand multicore 1.1 kv
grade ISI marked copper wires of
following size to be erected as directed.
f) 1.50 Sq.mm 4 core round PVC
SITC of fire pump start stop push buttons
SITC of 4 Zone standalone Fire Alarm
control Panel, 16X2 Character LCD
Display, provision for zone wise contact
1.21 1 and sounder. Panel does not have 12300.00 No
provision to connect Repeater Panel.
Approval: CE Mark.(Including Five year
free maintenance with guarantee)
Providing and erecting ISI mark Medium
class RIGID PVC PIPES of following size
complete to be erected on/in wall or
ceiling erected with necessary PVC
fittings & Junction boxes fixed with
adhesive solution & Clamps with following
dia of pipes, in approved manner as
Supply, Installation, Testing and
Commissioning of Single action Manual
Pull Station.Shock and Vibration
Resistant, pull Down Lever Remains
Down Until Reset. Shall be Polarity
Insensitive (with all mounting accessories
, complete with Junction Box for mooting
on Surface, Cable lugs at Ends, cable
compression glands, cable tags and
Supply, Installation, Testing and
Commissioning of Conventional Sounder
cum strobe having tone settings with
range of 95dbA and field selectable
1.24 8 15/30/75/110 candelas.(with all mounting 1201.75 No
accessories , complete with Junction Box
for mooting on surface, cable lugs at
ends, cable compression glands, cable
tags and Ferruling.)
CABLES AND TERMINATIONS
Providing and erecting XLPE(IS:7098)(I)-
88 ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing
trench / pipe at road crossing or floor of
following size of cable.
1.25.1 36 (B) 3 core 4 Sq. mm 285.00 Mtr
1.25.2 10 (G) 3 core 6 Sq. mm 392.00 Mtr
Providing and erecting XLPE(IS:7098)(I)-
88 ISI armoured cable multistrand Copper
conductor for 1.1 KV. to be laid on wall
with necessary clamps or in existing
trench / pipe at road crossing or floor of
following size of cable.
Providing and erecting XLPE(IS:7098)(I)-
88 ISI armoured cable multistrand
Copper conductor for 1.1 KV. to be laid
on wall with necessary clamps or in
existing trench / pipe at road crossing or
floor of following size of cables.
Providing and, fixing heavy duty flange
type brass cable gland with rubber ring
1.28 for PVC insulated armoured cable
complete with out going tails, insulating
tape etc for following size of cables.
1.28.2 8 (C) 2 to 4 core 10 Sq. mm 38.00 No
1.28.3 2 (D) 2 to 4 core 16 Sq. mm 47.00 No
Solder less crimping type Copper lugs
conforming to IS suitable for cable of
following size evenly crimped with high
pressure tool & connected to switchgear
terminals with brass/cadmium plated nut
bolts in an approved manner.
Providing and fixing approved make
Perforated C type cable tray. Made from
sheet steel. The cable tray should be
single or double bended as per required
and as per IS 2062/1079 and shall be
coated with hot dip galvanizing as per IS
2629/4759. with max 17.5% perforation
with coupler plate / Fish plate and GI
hardware like nut - bolt and washers etc.
erection with necessary support(
included) as per Specification and as per
instruction of engineer in charge..
Supply, installation,testing and
commissioning of Chemical Earthing with
UL Certified 17.2mm Dia. X 3000mm
Long 254 Micron-Copper bonded M.S.
Rod manufactured as per IEC 62561-2
with 25Kg Bentonite powder plus " U "
bolt rod clamp complete with Lockable
high performence chamber suitable &
tested for 5000T capacity with SS
Hardware.or equivalent
1.32 SEWAGE PUMPS
2 Supplying, Installation, Testing and 19676.50 No
commissioning Sewage water
submersible pumping sets of CI casing &
impeller, SS shaft, including with inbuilt
water level sensors for operating the
pumps automatically and all accessories
suitable for operation on 220 V-240 V,
single phase, 50 Hz. AC supply etc. as
> 10 mm solid handling capacity,Minimum
Capacity - 50 LPM,Minimum Head
Charges of Preparing Design , Drawings
,Testing of Fire Fighting System with
necessary Approval from Local Fire
authority.( Including Pre-NOC and NOC
from Fire authority. ) The fees required to
be paid to these authorities for inspection
shall be borne by AMC ( owner ) on
production of documentary evidences.
Providing, fixing, testing and
1.34 commissioning of below Auto Glow
1.34.2 8 Fire Equipment: 4" X 12" 514.97 No
1.34.3 8 In case of Fire, do not use lift, use 650.00 No
staircase: 8" x 8"
1.34.4 8 Fire Lift 4"X12" 514.97 No
1.34.5 8 Fire Extinguishers 8"x 4" 480.00 No
1.34.6 8 Floor Sign": 4" X 12" 514.97 No
1.34.7 8 Fire Hydrant 4” X 12” 514.97 No
1.34.8 8 Fire Hose Reel.4” X 12” 514.97 No
1.34.9 8 DCP Extinguisher 8"x 4" 480.00 No
1.34.10 8 CO2 Extinguisher 8"X 4" 480.00 No
Providing, fixing, testing & commissioning
of 15mm dia quartzoid bulb type
sprinklers of rating with required
1.35.1 140 Pendent Sprinkler 57°C standard 362.25 No
response (K-80) UL Listed
1.35.2 5 Pendent Sprinkler 68°C standard 471.50 No
response (K-80) UL Listed
Supplying, installation, testing &
commissioning of sprinkler flexible pipe
(UL Listed) of stainless steel complete
with 15 NPT on reducer thread with
maximum working pressure of 175 PSI
test pressure of 875 PSI (Burst) with
branch line (Inlet) 25mm NPT male
thread to sprinkler head (Outlet) 15mm
NPT female thread with reducer, nipple,
side brackets,center bracket, stockbar of
following sizes complete as required etc
of following sizes as required:
Providing fixing, testing and
1.37 2 commissioning of Drainning & Testing 4939.25 No
Assembly 25mm dia with Sight Glass
Union joint , Ball Valve & Drain Valve.
SUB-TOTAL OF FIRE HYDRANT
2 FIRE EXTINGUISHERS AND
LIGHTNING ARRESTER
2.1 FIRE EXTINGUISHER
FIRE EXTINGUISHER Supplying,
Installation, Testing and commissioning of
Dry Chemical Powder (DCP) 6 Kg Fire
Extinguisher Mono Ammonium
Phosphate Powder 40, Stored Pressure
2.1.1 8 Type, Pressure Gauge, Controllable 2724.25 No
discharge mechanism Class A, Rating 3A
& Class B rating 21B as per IS 15683 ISI
MARK (ABC Dry Chemical Powder - MAP
40%)fitted with required accessories
including wall suspension brackets.
Supplying, fixing, testing and
commissioning of CO2 type Fire
Extinguisher of capacity 4.5 kg filled with
Co2 Gas as per IS 15222 with controll
discharge mechanismfitted with Hose &
Horn applicable on Class B fire rating
21B confirms to IS 15683, bearing ISI
mark. Co2 Cylinder as per IS
Providing & fixing of ISI marked water
CO2 type Portable fire extingusher,9 LTR
capacity, Hydraulic test pressure 35Kgf/
cm2, Discharge range 2 Mtr,Average
discharge time: Min. 13Sec,Fire Rating
3A,Grade: IS:15683.
Providing & fixing of ISI marked, Squeeze
Grip Cartridge Type water CO2 type
Portable fire extingusher,9 LTR capacity,
2.1.4 1 Hydraulic test pressure 35Kgf/ cm2, 4200.00 No
Discharge range 2 Mtr,Average discharge
time: Min. 13Sec,Fire Rating 3A,Grade:
Providing,fixing, testing and
commissioning of 10Kg Modular type fire
extinguisher having Nitrogen expellant
,ceiling mounted,Sprinkler Nozzle is gas
tight the release temperature is adjusted
with sprinkler imported bulb set at
57 degree C or 68 degree C ,coverage
area 4 to 5 sqmtr,
2.2 LIGHTNING ARRESTER
SITC of Vertical Air Termination Solid
aluminium with Base- 10 mm dia and
1000 mm long. Air Termination Base
tested for conditioning, Ageing Test &
Lightning impulse current withstand test:
100 kA of 10/350µs waveform in an
accredited Third party laboratory as per
6.3 & 6.4 of IEC 62561-1 2017 protocol
with MAST 34mm dia 3000 mm long-
Cold Galvanized
SITC of 8 mm dia solid Aluminium
Conductor for roof top mesh grid and
tested as per IEC 62561- 2 conducted in
the Govt. accredited thirty party
laboratory to meet the requirement of
IS/IEC 62305 with Required Accessories
- Aluminium Holding clamp at every 1 mtr
distance, Aluminium/SS cross splicer at
every crossing of Alu. conductor,
Expansion piece with connectors at every
2.2.2 165 20 mtr distance, Aluminium straight 297.00 Mtr
Splicer to connect conductors. All
Accessories should be tested as per IEC
62561-1 2018 Cl. 6.3 for conditioning &
Ageing Test & 6.4 for Lightning impulse
current withstand test: 100 kA of
10/350µs waveform(Ageing & Electrical
test ) conducted in a sequence manner &
tested in the Govt. accredited Third party
laboratory to meet the requirements of
SITC of Galvanized Steel Flat 25x6 mm
thickness from earth electrode directly in
ground as required. Zinc coating:
2.2.3 125 g/m square (Approx:70 micron coating) 153.00 Mtr
tested and used exclusively for lightning
protection earthing system and ring
equipotential bonding.
SITC of 14.2 mm dia 3 mtr long Earth
electrode of High tensile steel electrode
with 250 micron copper bonding & 1 bag
of Carbon fill Based environment friendly
backfill tested as per IEC 62561-7 in
NABL accredited Laboratory and suitable
stainless Steel double sided clamp. Eco
Friendly rust proof heavy duty weather
proof Polyethylene Earth Pit Chamber
with following dimensions :254 mm dia
(top), 330 mm dia (bottom) & 260 mm
Heat / FIRE RESISTANT COATING OF
CABLE: Supply and apply intumescent
based coating Hilti 678on cables / bunch
cables & cable tray for at least 1 mtr in
every 14 Mtrs for horizontal runs and to
entire length of vertical runs. The coating
shall have a density in the range of 1.2 to
1.4 Kg / L. The coating shall be non-toxic,
asbestos and halogen free and shall have
good mechanical strength. The coating
shall comply with IEC 332 part 3 (1992).
The product shall carry test certificate for
mold resistance rating of 0 as determined
by ASTMG21-96. The product should
have a VOC content of approx... 60g/l as
2.3 20 per LEED 2009 and should not have any 3690.00 Kg
de-rating effect on the cable.
Manufacturer should submit relevant
certificates for mentioned attributes.
Coating shall be carried out by approved
machine spraying system which will yield
uniform thickness and better finish. Fire
stop installation shall be done by Hilti
Accredited Fire stop Specialty Contractor
(HAFSC) and in accordance with
guidelines. Firestop specialty Contractor
need to submit work completion
certificate along with installation report
through Hilti documentation Software
CFS DM for periodic inspection &
maintenance purpose.
FIRE STOP FOAM Hilti CP 620 on both
sides of wall, with minimum 2 Hours fire
rating when tested in accordance with UL
1479 / ASTM-E 814, for horizontal
openings in floors or slabs made of
concrete / masonry or Gypsum after
passing service lines like cable trays or
cables / cable bundles. The expanding
foam expands seven times its volume to
fill the cavity at the time of dispensing the
material and shall fully cure within two
minutes after dispensing. The product
shall be age tested as per Dafstb and
DIBT Standards. The product shall
provide water tightness when tested for
W rating as per UL standards and shall
carry test certificate for sound insulation
of 50 dB when tested in accordance with
ASTM E 90. The product shall carry test
certificate for mold resistance rating 0 as
determined by ASTM G21-96 and shall
have a VOC content of approx... 1.3g/l as
per LEED 2009. The product shall be
tested in accordance with IEC 60068-2-
57: 1999-11 (Environment Testing) as per
Part 2-57: Test for Vibration-Time –
history method and VERTEQQII for
seismic zone 4. The system shall be UL
listed & classified and product shall bear
the UL and FM approval logo on the
packing. If none of UL test certificate
comply with actual application, an EJ
document prepared by a qualified
personnel and based on nearest third
party tested & approved systems like UL
test certificates & in accordance with IFC
guidelines shall be produced by
manufacturer. A Fire stop submittal shall
be produced by manufacturer, in
accordance with approved passive fire
protection method statement, for
technical approval. Fire stop installation
shall be done by Hilti Accredited Fire Stop
specialty Contractor (HAFSC) and in
accordance with Hilti guidelines and UL
system test certificates along with
installation report through Hilti
documentation Software CFC DM for
periodic inspection & maintenance
SUB TOTAL of FIRE EXTINGUISER &
Lightning Arrester
FIRE DETCTION & FIRE ALARM
Supply, Installation, Testing &
Commissioning of Microprocessor based
Networkable Analogue Addressable Fire
Alarm Control Panel. The Panel shall be
compliant with EN54-2, EN54-4 and
approved by LPCB. The Fire Alarm
Control Panel shall have inbuilt 2 loops
and expandable capacity upto 8 loops.
The Panel must have Full colour 800 x
480 LCD with resistive touch screen and
automatic backlight dimming. The Panel
must also have the capability to take
Addressable Intelligent Wired and
Wireless Devices on same loop. Each
loop shall have a capacity of
analogue Addressable devices and
Base sounders/Base Sounder Beacons.
The panel shall have an event log of
minimum 10,000 events @ 1 second
resolution, Filterable and Printable. The
Panel shall have Three access levels.
Panel shall support upto 5000 Cause &
Effects entries, with upto 20,000 inputs
controlling & 20,000 Controlling outputs
across the network. The Panel shall have
capability for Peer to Peer networking
through RS485 network card. The Panel
must have 4 inbuilt programmable
sounder circuits, each circuit rated at
2.5A.The Panel must have inbuilt
programmable inputs and 5 inbuilt
programmable relay outputs. The Panel
shall have up to sub-addressable
programmable Inputs/Outputs via optional
RS485 COMMS serially connected
expansion cards. The Panel shall have
240 V AC power supply along with
automatic Battery Charger. The Panel
shall be fully expandable via common
plug in loop driver boards. The user shall
have a choice of using the panel with
5.25 Amp or 10.25 Amp power supply
unit which is inbuilt in the FACP and
should be approved to EN54-4. The
Panel shall have configurable via USB
port to PC or memory stick. The Panel
shall have dedicated RS232 serial port for
optional printer. Approved by LPCB
SITC of Analogue Addressable Multi-
Sensor which is fully compatible with
Analogue Addressable Protocol,having
removable high performance chamber
with Twin fire LED's allow 360 degree
viewing, User selectable sensitivity
3.2 130 modes 1% to 4.5% obs/m, Incorporate 3597.20 No
Optical and dual Heat elements, lock
mechanism (sensor to base),
Electronically addressed, Pulsing/non-
pulsing controlled from panel. Approved
by LPCB & VdS. (Including Five year free
maintenance with guarantee)
SITC of Analogue Addressable Multi-
Heat Sensor which is fully compatible
with Analogue Addressable
Protocol,having removable high
performance chamber with Twin fire
LED's allow 360 degree viewing, User
selectable sensitivity modes 0 to
3.3 8 degree Celsius, Incorporates Fixed 3498.30 No
Temperature and Rate Of Rise Heat
elements, lock mechanism (sensor to
base), Electronically addressed,
Pulsing/non-pulsing controlled from
panel. Approved by LPCB (EN54: Part 5)
(Including Five year free maintenance
with guarantee)
SITC of sensor common mounting base,
includes stainless steel contacts, slim
profile - only 8mm, quick connection via
3.4 138 square cable clamps, facility for remote 354.20 No
indicator, Approved by LPCB (Including
Five year free maintenance with
Supply,Instllation,Testing and
Commissioning of Fault isolator Module
capable of monitoring shorted loop circuit
3.5 11 and automatically restore 2477.10 No
communications when shorted conditions
are corrected (Including Five year free
maintenance with guarantee)
Supplying, installation, testing &
commissioning of response indicator on
3.6 50 surface/recessed MS Box having two 193.20 No
LED, metallic cover complete with all
connections etc as required.
SITC of Manual Call Point approved to
EN54-11:2001, Approved by LPCB Easy
3.7 8 to install, push-fit wiring terminals 4191.75 No
(Including Five year free maintenance
with guarantee)
SITC of Analogue addressable loop
powered Base Sounder, variable sound
output 50 ~ 98 dB(A) (±2 dB(A)) output at
1 metre, 51 user-selectable tones (all
3.8 8 tones EN54-3 compatible), Auto 7442.80 No
shutdown feature prevents noise-
pollution, Approved by LPCB & VdS
(Including Five year free maintenance
with guarantee)
Supplying & laying of 2x 1.5 sqmm fire
alarm armoured cable, 600/1000V rated
with annealed copper conductor having
XLPE insulation, steel wire armouring
& FRLS outer sheath complete as
SUB -TOTAL OF FIRE DETECTION&
I. No. Qty Items Unit Rate Per Amount
LANDSCAPING WORK :
LAYING OUT LAWN – After excavating
soil upto 30 cm. depth & removing
unwanted stuff, stones etc. Preparing soil
for planting by supplying and mixing
inch river fine site and 0.5 cmt FYM
maximum 100 sqmt of lawn area and
1 100 doing termicide @ 1 fit / 100 sqmt area 85.00 Sq.mt.
and planting selection 1 type / approved
lawn grass at maximum 6 cm x 6 cm
distance and maintain it upto 120 days.
Maintainance include all operations i.e.
watering, grass cutting, gap filling,
applying of fertizer if require etc.
Supplying, Spreading and leveling of
2 40 good earth like firtile soil as directed etc 575.00 Cmt.
Supplying, Spreading and leveling of
3 10 good quality river Kap Filling 100 mm as 575.00 Cmt.
directed etc comp.
Supply and Planting saplings of Hedge
plants like kadvi mahendi, karmda,
dyuranta, nikodeviya etc. specifies bag
size is 4 inch x 6 inch, well established &
free from disease at site. as per the
Supply and Planting saplings of Ficus
panda, Ficus benjamina, Ficus
benjamina variegated, Ficus longisland
bag size is 13 inch x 13 inch, well
branched, well established & free from
disease at site as per the instructions
Supply and Planting saplings of (Jasud,
Ixora, Ticoma Gaudi-chaudi, Gultora,
Jetropha, Haemeliya, Chandani, Mogaro,
Galfemia, , Allamenda, Desi Gulab,
Euphorbia mili, Jasud Hybrid, Chandani
double, Madhukamini, Madhumalti,
Ticoma Capensis, Ixora draft, Nikadevia,
English Karen etc.) having height of
minimum 2.00 to 2.5 ft. and bag size is
inch x 10 inch, well branched, well
established & free from disease at site as
per the instructions.
Supply and Planting saplings of Golden
Bamboo having height of minimum 5 to
7 30 6 ft. and bag size is 8 inch x 10 inch, well 45.00 Nos
branched, well established & free from
disease at site as per the instructions.
Supply and Planting saplings of
Palm(Botal palm,foxtel) having height of
minimum 10.00 to 12.00 ft. and bag size
is 21 inch x 21 inch, well branched, well
established & free from disease at site as
per the instructions
Supply and Planting saplings of champa
(deshi) having height of minimum 8 to
10 ft. and bag size is 15 inch x 16 inch,
well branched, well established & free
from disease at site as per the
Supply, Spreading and leveling of Brick
10 5 dust (Chharu) particle size having 1300.00 Cmt
Supply Saplings and Planting of trees
species as specified ( Alstonia scholaris,
Erythrina indica, Jacaranda
mimosifolia,Delonix regia , Anthocephalus
cadamba, Spathodea companulata,Neem
(Azadirachta indica), Lagerstromia
speciosa , Tabebuia argentea, Cordia
sebestena, Mimusops elengi, Bauhinia
blakeana, Kigelia pinnata, Cassia fistula,
Banyan, Ficus religiosa, Peltophoroum,
Bottle brush, Silver Oak, Billi, Mahagony,
Pendula, Desi Asopalav,Sevan, Badam,
Ficus infectoria, Pinkesiya, Millingtonia
hotensis, Rain Tree, Bakm limdi, kasid,
Ashok tree, parkia, Tabebuia Rosea,
millettia, etc.) having height of minimum
7.00 to 8.0 ft. and bag size is 13 inch x
13 inch, well branched, well established &
free from disease at site as per the
Supplying insecticides at site well packed
in bottle of 20 litre. weight including
12 50 royalty and carriage with all leads and lifts 300.00
(product to be brought in company sealed
I. No. Qty Items Unit Rate Per Amount
Furniture Work ( Curtains and
Cupboard Shutter)
Proviging and Fixing Storage Shutter
made out of 50mm X 25 mm Indian
Teakwood Frame and 18 mm Ply Board.
With 1 mm thick laminate finish in the
front and 0.8 mm thick Laminate on Back
Side with 12 mm thick Indian teakwood
beading. The scope also include
1 10 providing and fixing s.s. finish hardware 6805.00 Sq.mt.
as per the Requirement. The rate include
cost of all labour, material and with all
hardware like handle, magnate, tackels,
adhesive, screws, etc.for satisfactory
completion of this items.All Exposed
Wood Work shall have malamine polish
Meeting Table Ovel M4 ( 1355 MM WIDE
Providing and supplying meeting table
ovel in shape of size 1355 mm Wide as
shown in drawing.The top made out of
mm thk.ply wood with laminate top as
shown in drawing.20 mm thick teak wood
beading is provided all around table top
2 6 with 5 mm groove in the center. The top 11879.04 RMT
is supported by 2 nos. of vertical square
box made out of 19 mm thick ply board of
size 300mm x 300mm rest on the wooden
base of size 400mm x 400mm x 40mm as
shown in drawing.The rate includes cost
of all labour,material and with necessary
tools,tackles,adhesive,screws,etc.for
satisfactory completion of this item.
Providing & Fixing Sun Control Reflective
3 500 Type Film / Frosted Film as Selected by 646.37 Sq.mt.
Architect/ Engg. In Charge For Glass
Doors / Windows etc. as Directed.
Providing & Fixing in Position Vertical
Roller Blinds with Minimum 3 % and
Maximum 5 % Light Transperace Screen
Fabric Incuding Providing & Fixing of
Powder coated G- Channel at the Topof
Window with necessary Screw , Cleats
etc. and PVC Roller ( Weight Pipe) and
PVC Chain For Up and Down Movement
4 450 of Blinds etc. of Approved Make and as 1372.03 Sq.mt.
per Drawings / Instruction of Engg. in
Charge For All Colors and Shades. Rates
Includes all Lead and Lift For All Floor
Level, All Height , All Material
Accessories, Fixing , Scaffolding , Labor
etc. Complete in All Respects. All
Required Accessories & Material must be
From Same Manufacturer.
Cubical track for cubical curtain :- supply
and installation of heavy duty Aluminium
cubical track size 20mm wide x 30 mm
high, made of aluminium Extruded with
white powder coating complete with
continous PVC liner, nylon giders and
hooks , plastic end cap, connecting
bridge, overlapping joint connector, Wall
bracket with matching screws to make up
cubicle approx. height to 2100 mm
clearance from floor level at approx.
mm spacing with all accessories of
approved brand/make along with
alluminium Extruded hospital curtain's
track system with shite powder coating
with all accessories as per approved
sample. All required accessories and
materials must be from same
manufacturer. This Item is Excluding
Cubicle Curtain :- Supply & Installation of
Water Repellant, Antimicrobial Cubicle
Curtain with High Strength18" Oval net at
Top as Approved by Consultant / Engg. In
Charge. Eyelets on Curtains & Hooks and
All other Required Accessories, Fixing
Scaffolding, Labor etc. Complete in All
Respects. All Required Accessories &
Material must be From Same
Total of Furniture Work ( Curtains and Total Rs.
Cupboard Shutter)
Signature of Bidder
Special Condition For Tenderers
• Scope includes Complete Demolition of Super Structure & Sub Structure up to
Foundation Level of Existing Old Buildings in the Said Plot Under Development as
Instructed by Engg. In Charge & Then Disposal of Serviceable & Un Serviceable
Material including Cleaning & Levelling of Entire Plot. The Total Project Includes
Demolition of Existing Units and Site Clearance. The Total Responsibility and
Liability of This Demolition Works Including Site Clearance Shall Be of The
Contractor. This Demolition and Debris Removal Includes all Hidden Foundation
also at Locations Where New Foundation or New Work is To Be Done.
• Contractor Has to Visit Site with representative of A.M.C. Before Quoting Amount in
Tender. The Contractor Shall Not Be Paid For Any Dismantling, Demolition, Carting
The Debris And/ or Any Expenses Incurred For Site Clearance.
• Contractor shall have to Pay Premium Amount to A.M.C. For Disposal of Serviceable
Goods Like Old Reinforcement, Old Wooden Doors/Windows, Iron Work,
Copper/Alu. Wiring, Bricks etc. Which shall be Quoted in Part-A of Financial Bid.
• For Consideration of Lowest Eligible Bidders , Premium Amount as Mentioned
Above i.e. Part-A shall be Deducted From e-Tender Amount For Construction Work
i.e. Part-B , Quoted by the Contractors.
• The Lowest Eligible Bidder shall have to Deposit Premium Amount for the
Serviceable Goods at the Time of Submission of Security Deposit.
Signature of contractor Additional City Engineer (NORTH ZONE)
Seal Ahmedabad Municipal Corporation
AHMEDABAD MUNICIPAL CORPORATION
ENGINEERING DEPARTMENT- CENTRAL ZONE
Name of Work : CONSTRUCTION OF C.H.C. BUILDING AT F.P. NO. 189, T.P.S.NO. 11 (BAPUNAGAR) IN
SARASPUR- RAKHIYAL WARD, NORTH ZONE, AHMEDABAD.
FINANCIAL BID (Online Only)
Demolition of Existing Structure
Sr.No. Description Amount
Quoted Premium Amount For Serviceable Material (Which is Payable to
1 A.M.C. at The Time of Depositing Security Deposit by the Lowest Eligible
Amount in Words Rupees :
Sr.No. Description Amount
1 Amount For Civil Work Rs.9,13,15,328.20
2 Amount For Electrical Work Rs.1,56,58,757.95
3 Amount For CCTV & ELV Work Rs.
4 Amount For Fire Fighting System Work Rs.
5 Amount For Landscaping Work Rs.
6 Amount For Furniture Work ( Curtains and Cupboard Shutter) Rs.
I/We am/are willing to carry out work at ______% above / below (should be written in figures and words)
the estimated cost mentioned above.
Estimated cost put to tender : Rs. 11,51,71,975.19 Estimated cost put to tender : Rs.
Add_____% above : Rs ___________ Deduct_____% below : Rs __________
In words : Rupees _______________________ In words : Rupees_____________________
Net Tender Amount For Consideration of Lowest Eligible Bidders
Sr.No. Description Amount
1 Net Amount For Cost of Civil , Electrical, Fire Fighting, O&M, Landscaping
and Interior & Furniture Work i.e. Part-B Rs.
2 Quoted Premium Amount Payable to A.M.C. i.e. Part-A Rs.
3 Net Tender Amount i.e. (Part-B -
Net Tender Amount in Words Rupees :
Signature of contractor Additional City Engineer ( N.Z. )
Seal Ahmedabad Municipal Corporation
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
NZ_RAKHIYAL_CHC_Final Price Bid Vol.-II_Dt.25-03-2026.pdf
NZ_RAKHIYAL_CHC_Vol-1 Part B TS_Civil Work Dt. 25-03-2026.pdf
NZ_RAKHIYAL_CHC_Vol-1 part-C Electrical Specification.pdf
NZ_RAKHIYAL_CHC_Vol-1 part-D CCTV Work Specification.pdf
NZ_RAKHIYAL_CHC_Vol-1 part-E Fire Fighting Specification.pdf
TENDER DRAWING SARASPUR RAKHIAL CHC.pdf
NZ_RAKHIYAL_CHC_Vol-1 part A Tender Document.pdf
Download all tender documents and submit your bid