Loading…
Loading…
Tender Value
₹1.1 Cr
EMD Value
₹1.1 L
Closing Date
24 Aug 2026, 6:00 pmClosed
Superintending Engineer, Project Implementation Unit, Health & Family Welfare Department.
Supply, Installation, Testing and Commissioning of Modular Operation Theatre at various places in District Surendranagar
331521
2026-27/50/02
Open
Civil Works
Works
Surendranagar
1 document required · 1 mandatory
₹3,600
PIU-General Fund A/c 11-114
₹1.1 L
5 Aug 2026
5 Aug 2026
5 Aug 2026
24 Aug 2026
5 Aug 2026
Name of Work :- Supply, Installation, Testing and Commissioning of Modular Operation
Theatre at various places in District surendranagar.
Sr. No. Description of Items Qty Unit Rate Total Amount
Sr. No. Description of Items Qty Unit Rate Total Amount
Supply, Installation, Testing, and Commissioning (SITC) of 40 mm thick prefabricated modular
operation theater (OT) panels for wall and ceiling system. Panel Core consists of high-pressure
injected rigid Polyurethane Foam (PUF) with a density of 40 Kg/m³ (±2 Kg/m³). Front Skin: 0.8 mm
thick Electro Galvanized Plain (EGP) for durability and impact resistance. Back Skin: 0.8 mm thick
Pre-Painted Galvanized Iron (PPGI) sheet. Panels are fixed to existing brick walls using an SS or GI
1 U-channel substructure. A variable cavity/gap is maintained between the brick wall and the steel panel 431.04 Sq.mtrs 6,550.00
to allow for flush mounting of conduits and equipment like X-ray viewers and surgeon control panels.
The panel surface must be coated with 300 microns Dry Film Thickness (D.F.T.) of anti-bacterial
paint. The paint must be free from toxic agents like formaldehyde, toluene, xylene, and
paradichlorobenzene and as per detailed item specification.
Supply, Installation, Testing and Commissioning of Laminar air flow system. The ceiling filtration
system shall be designed to ensure unidirectional distribution of sterile air in the surgical theatre to
ensure cleanliness of all the area covered by the air flow. Final pressure drop : 600 Pa (maximum).
2 Maximum operating temperature: 60°C . Size of laminar airflow system shall be minimum 8 feet x 8 4.00 Nos. 3,90,000.00
feet and as per detailed item specification.
Supply, Installation, Testing and Commissioning of PVC flooring including Suitable self – levelling
shall be done before PVC Flooring .The flooring should have a mininum thickness 2 mm thick anti-
3 static seamless PVC flooring and as per detailed item specification.
Supply, Installation, Testing and Commissioning of Hermetically sealed doors the door to the should
be a hermetically sealed, single sliding door measuring 2.1 meters in height and 1.5 meters in width
4 CE marked or BIS certified products or FDA or EN certificate or IEC compliance wherever
applicableand as per detailed item specification.
Supply, Installation, Testing and Commissioning of Touch screen control panel the 20" or more. This
control panel shall work as the central control panel for the HVAC controls, instruction board, touch
5 screen and ON/OFF of MOT light. It shall be CE/US FDA/ETL/UL/BIS certified/ listed.The Control 4.00 Nos. 1,95,000.00
Panel shall be able to display the Isolation Panel Alarm Conditions along with MGPS Alarms and as
per detailed item specification.
Sr. No. Description of Items Qty Unit Rate Total Amount
Sr. No. Description of Items Qty Unit Rate Total Amount
Supply, Installation, Testing and Commissioning of Hatch boxes should be equipped with two doors
and the doors shall be operated electrically/motorised.The hatch shall be designed in such a way that
6 only one door shall be openable at one time.Hatch Box material shall be SS 304 grade. Length and 4.00 Nos. 1,15,000.00
width of the hatch box shall be minimum 600mm by 600mm and as per detailed item specification.
Supply, Installation, Testing and Commissioning of LED type Double Film flat panel X-Ray Viewing
panel of miniumum 28" x 17" size. The body shall be of extruded aluminum powder coated with
7 bacteria resistant and disinfectant resistant finish and as per detailed item specification. 4.00 Nos. 41,500.00
Supply, Installation, Testing and Commissioning of double arm moveable pendant for anesthetist
and surgeon. It shall have double moveable arms (any combination) with total coverage of minimum
1800 mm and minimum 330 degree. Each arm shall have ability of horizontal movement. Vertical
movement shall be motorized and the arm height shall remain at a height greater than 6.5 feet above
8 floor level. The pendant shall be European CE Certified with 4 digit notified body number/US 4.00 Nos. 2,84,000.00
FDA/ETL/UL/BIS certified/listed. Weight carrying capacity of the arm shall not be less than 180 kg and
it shall have electromagnetic/pneumatic brakes and as per detailed item specification.
Supply, Installation, Testing and Commissioning of Peripheral Lighting and clean room luminaries with
illuminance of minimum 500 Lux. These shall be minimum 8 in numbers for each MOT and shall be
with highly specular anodized aluminum and optical antiglare system.Luminaries cover shall be made
9 of highly resistant, disinfectant proof laminated safety glass/acrylic with stylish fine-grained 16.00 Nos. 22,500.00
surface.Peripheral lighting shall be done according to IP 65 regulations and as per detailed item
Supply, Installation, Testing and Commissioning of Medical gas lines installation ( per OT).The
medical gas pipeline shall cater to Oxygen (O₂), Medical Vacuum, and Medical Compressed Air (4 bar
10 / 7 bar, as specified),AGSS and nitrous oxide up to the OT pendant from the nearest existing supply 4.00 job 25,000.00
line through the outer passage, as directed by the Engineer-in-Charge and as per detailed item
Supply, Installation, Testing and Commissioning of Double Dome OT Light with Ceiling mounted
having following features and enclosed technical specifications, CE marked or BIS certified products
11 or FDA or EN certificate or IEC compliance wherever applicable and as per detailed item specification.
Total Amount Says
Total Amount Says
Sr. No. Description of Items Qty Unit Rate Total Amount
Sr. No. Description of Items Qty Unit Rate Total Amount
A) Total Tender Amount Rs……………………………
B) Rebate on above tendered amount (if any)……………% (in figure) Rs…………………………
C) Net tendered amount (A-B) Rs…………………………
Note1- All works shall be carried out as per public works department handbook and other specification of division or as Directed
Rate quoted include clearance of site( prior commencement of work and at its close) in all respects and hold good for work under all
condition, site, moisture, weather etc.
Deputy Executive Engineer Executive Engineer
PIU, Surendranagar PIU, Surendranagar
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
01-Make List-4171-06-10-2017.pdf
02-Make List - Civil Items-05-02-2020.pdf
Building-Specification.pdf
Ele-List of Approved Products-FINAL.pdf
GRs and Conditions-11-06-24.pdf
Insurance Clause-03-11-2025.pdf
Standard Specification for Electrical Work.pdf
Performance Bond and Bitumen date.pdf
20-Special Conditions-27-05-2026.pdf
BOQ OT Surendranagar.pdf
Condition.pdf
Make List Dt-15-10-25-6680.pdf
SBD Surendranagar.pdf
Tender Details-50-02.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .