Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹35.5 LAccepted-AOC | L-1 | Accepted-AOC AOC | |
| 2 | L-2₹39.9 L+₹4.3 L (12.2%)Rejected-Finance | L-2 | Rejected-Finance Highest |
Tender Value
₹32.3 L
EMD Value
₹64,520
Closing Date
13 Aug 2019, 5:00 pmClosed
Ritesh Nandal
Executive Engineer, Elect. Division PWD B and R Br., Ambala Cantt
Construction of Head office building for Directorate of Employment Haryana (Rojgar Bhawan) plot no. I.P. -6, Sec-14, Panchkula (Pdg. 11 KV Sub Station only).
2019_HRY_89695_2
PWD/Elect-KNL/Elect-AMB/16184
Open Tender
Construction Works
Works
120 days
Ambala
Please refer Tender documents.
3 documents required · 3 mandatory
₹5,000
Executive Engineer, Elect. Division PWD Band R Br.
₹64,520
20 Dec 2021
29 Jul 2019
16 Aug 2019
29 Jul 2019
13 Aug 2019
29 Jul 2019
Amount
( c ) Moulded case Circuit breakers. Supply and erection of moulded case circuit breakers on wall or on existing pedestal including bonding to earth and necessary connections. 15 Amp..to 60 Amp.. 415 V ,10 KA 3-phase. 31.12 c (i)
100 Amp..to 220 Amp..415 V,10 KA 3-phase. 31.12 c (ii)
250 Amp. 415 V 35 KA 3 Phase 31.12.c (iii)
500 Amp.. to 600 Amp.. 415 V , 35 KA 3-phase. 31.12 c (v)
(P) Pipe Laying. Supply and erection of pipe for wiring purposes including bends inspection boxes etc. where necessary and painting as required. Galvanised iron pipe 65 mm dia on flushed. 31.21 (xiv)
(Q) Earthing Earthing with GI earth plate 600 mm x 600 mm x 6 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) complete as equired. 31.22(iii)
Earthing with tinned copper earth plate 600 mm x 600 mm x 3 mm thick including accessories and providing masonry enclosures with cover plate having locking arrangement and watering pipe etc. ( but without charcoal or coke and salt ) comlete as equired. 31.22(iv)
Extra for charcoal or coke and salt for G.I. Plate or copper plate earth electrode. 31.22(v)
Pdg. and fixing 25 mm x 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode as required . 31.22(x)
Pdg. and fixing 25 mm x 5 mm copper strip on surface or in recess for connections etc. as required with all labour and material. 31.22(xiv)
Pdg. and fixing 25 mm x 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode as required . 31.22(xi)
Pdg. and fixing 25 mm x 5 mm G.I. Strip on surface or in recess for connections etc. as required with all labour and material. 31.22(xv)
Supply and erection of 20 mm x 3 mm thick G.I. tape fixed with suitable G.I. stapples of same size. 31.22(xix)
Supply and erection of under ground cable ,loose in existing pipe or trenches complete with necessary connections . 240 Sq. mm 3.5 Core Armoured Cable. 31.26 (xxxiii)
150 Sq. mm 3.5 Core Armoured Cable. 31.26 (xxxi)
120 Sq. mm 3.5 Core Armoured Cable. 31.26 (xxx)
95 Sq. mm 3.5 Core Armoured Cable. 31.26 (xxix)
70 Sq. mm 3.5 Core Armoured Cable. 31.26 (xxviii)
25 Sq. mm 3.5 Core Armoured Cable. 31.26 (xxv)
16 Sq. mm 4 Core Armoured Cable. 31.26 (xI)
Supply and erection of suitable compression type brass cable glands for underground Cable. 10 Sqmm to 16 Sqmm Cable 2 to 4 Core . 31.28 (ii)
25 Sqmm to 50 Sqmm Cable 2 to 4 Core. 31.28 (iii)
70 Sqmm to 95 Sqmm Cable 3 to 3.5 Core . 31.28(iv)
120 Sqmm to 185 Sqmm Cable 3 to 3.5 Core 31.28 (v)
240 Sqmm Cable 3 to 3.5 Core . 31.28 (vi)
( T ) Street Light. Supply and erection of prestressed cement concrete pole as per IS : 1678-1960. 11 metres long 152 mm x 203 mm at top and 152 mm x 368 mm at bottom with working load of 360 Kg. burried 2.20 m in ground. 31.30 (VI) (iii)
(X) Miscellaneous . Supply and erection of shock restoration chart in glass frame 31.35 (iv)
Supply, Installation, Testing and Commissioning of wall / free standing floor mounting dust & vermin proof compartmentalized cubical panel made out of 2 mm thick CRCA sheet, required hardware 3 mm thick bakelite sheet provided all along the bus bar and cable tray separating switches compartment and supporting suitable channel duly painted by 2 coat zinc / red oxide primer followed by 2 coats of powder coating in grey or required shade after rising. the panel having PU / Neoprene rubber gasket of not less than 3 mm thickness separate detachable gland plate MS base channel hinged door with inter locking arrangement for equipments / switch wear. Transport acrylic sheet shall be provided in front of bus bar compartment to prevent direct access to bus bar bakelite sheet 3 mm thick for separately cable alley to BBC from switch chamber extended solid copper bars up to cable alleys shall be provided for outgoing connection which shall be paid as extra items. Side walls and cable alley compartments shall be having bolted type doors with detachable extension type structure. The Panel will be complete with control wiring (Copper) and fuse protection. (Only outer area on all sides shall be measured). 31.63
Supply and Fixing of copper bus bar duly tinned by means of SMC / DMC type insulator high tensile nuts and bolts spring washers fixing to same in existing panel including bending, cutting in required shape and size and insulation with color coding heat shrinkable PVC insulation complete in all respect. 31.64
Supply and Fixing of rotary handle for ON / OFF operation of existing MCCB in the LT panel including fixing the same in position with all labour and material to required to complete the job in all respect. Rotary Handle up to 125 Amp.., MCCB 31.66 ( i )
Rotary Handle above 125 Amp.., MCCB ( ii )
S/E of mark double walled corrugated (DWC) HDPE pipe laid 1 Mtr. Below ground level including digging and refilling of earth including cost of suitable size socket / cuppler for HDPE pipe including cost of labour and material required to complete the job in all respect upto the entire satisfaction of Engineer in charge of work. HDPE 90/75 mm outer dia / inner dia 31.67 ( ii )
HDPE 145/123 mm outer dia / inner dia ( iii )
S/E of XLPE (E)11 KV HT aluminum conductor armoured cable ISI mark laid in existing pipe /trenches/surface with all labour and material required to complete the job in all respect upto the entire satisfaction of the Engineer-in-charge of the work. 50 sqmm 3 core XLPE Cable 31.71 ii)
Supply & erection of factory manufactureed cable tray cover made of 16g GI Sheet complete with Fastoner Nuts bots and in position including all petty material required to complete the Job in all respect upto the Entire statisfaction of Engineer in Charge of the work Suitable for 50 x 150 mm 31.82 ii)
Suitable for 50 x 300 mm iii)
Total -A (HSR items): Supply, installation, testing & commissioning of 11KV Oil type Outdoor type transformer 315 KVA capacity, 3Phase, 50Hz alongwith spefication i.e. Copper Double Wound, Oil Immersed, Naturally Cooler, Core type Transformer confirming to IS : 1180, with Latest efficiency level with first filling of Oil as per IS : 335. Output- 315KVA, No load voltage ratio at rated voltage & frequency - 11 / 0.433 KV, Cooling type- ONAN, Off Load tap changer, taping range & step (Plus/ Minus/ Step) - (5%/ 10%/ 2.5%), vector group- Dyn-11, Temp rise at rated load on Ambient- 50 Deg C, Paint Shade to IS : 5 (Epoxy) alongwith rating & diagram plate, earthing terminal (2Nos.), lifting lugs, air release hole with plug, dehydrating silica gel breather, prismatic oil level guage, oil filling hole with plug on conservator, oil conservator with drain plug, thermometer pocket, jacking lugs, bottom drain cum filter valve, top flter valve, 4Nos. bi directional rollers, explosion vent with diaphram, marshelling box, 100mm OTI with alarm & trip, WTI with alarm & trip, buchholz relay with alarm & trip, shutt off valves for buchholz relay (2Nos.) Magnetic Oil level gauge, Radiator - fixed & cable box - HV/ LV side complete in all respect upto the entire satisfaction of Engineer- in- charge of work. Make: Kirloskar, Crompton, Schneider, Siemems. NS-1
11kV, 630A, 20kA/3-sec, Compact VCB Supply, Commissioning , Testing of 11kv, 630 Amps,20KA Indoor non-extensible SF6 gas insulated floor mounted Compact Switchgear with copper bus bars, having All live parts enclosed in robotically welded/hermatically sealed with not less than 2mm thick ,non ferrite non magnetic stainless steel tank filled with SF6 at suitable pressure, with IP class IP67 ,leak rate less than 0.1% per year tested for internal arc 20KA/1 Sec as per latest IEC 62271-200. Make -C&S, Schneider, Siemens. The Compact Switchgear shall comprise of: INCOMER - Direct Cable Entry Module 11kV, 630Amp, Direct Cable Entry Module with associated bushings having Live cable LED indication scheme and cable-box for accomodating trifurcated XLPE cables having size not more than 3Cx185sqmm. OUTGOING - Fixed-Type Vacuum Circuit Breaker 11kV, 630Amp, 20kA/3-sec, Fixed-Type Vacuum Circuit Breaker Module with associated bushings having Live cable LED indication scheme and cable-box for accomodating trifurcated XLPE cables having size not more than 3Cx185sqmm. The breaker shall have motorized Spring-charging Snap-action mechanism with distinct Push Buttons for ON/OFF of Vacuum Interrupters having rated current of 630Amp and breaking capacity of 20kA. The Vacuum Circuit Breaker module shall also have integrated Disconnector-cum-Earthing Switch for ensuring Line-Side earthing for purpose of maintainence and other activities. The Earthing Switch shall be suitably interlocked to ensure that it will not operate unless the breakers are disconnected. Present position of Vacuum Circuit Breaker, including ON/OFF/EARTH shall be distinctly visible at the front-facia via mechanical, true-position, semaphore indications. The breaker shall be accompanied with integrated 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. Relay should have facility to display the maximum loaded phase current also.Relay shall record minimum 5 fault records with time stamping. The complete unit shall be a floor-mounted, standalone unit, along with suitable Gas-Level Manometer with Go/No-Go indication, which can be easily removed to refill the SF6 gas if required in future. Associated 2x12VDC Battery+Charger scheme for motorized spring-charging of VCB, which shall remain suitably charged via 230VAC input provided by the purchased at one point inside the Compact Switchgear. Complete in all respect NS-2
Supply & Erection of Heat shrinkable jointing kit / HT terminal box with tapex joint M-seal make including making necessary connections with transformer and HT metering panel with all required material thimble lugs & soldering compound tape etc. upto the entire satisfaction of Engineer-in-charge of work . Indoor for 50 sqmm , 3 - core (end termination tapex model) NS-3 (i)
Outdoor for 50 sqmm , 3 - core (end termination tapex model) (ii)
Supply & erection of 11KV gang operated switch Rashtriya / Jayshree / BHEL make conforming to IS with latest amendment including suitable size of copper blade erection of same on the existing 'H'pole with the help of 3 Nos. channels of size 75mmx40mmx6mm, 1.8M long fixed with suitable size of MS clamp, nuts and bolts including cost of 6 Nos. 11KV insulator with GI pin, RD fuses and painting with 2 coat of approved paint and one coat of red oxide material required to complete the job in all respect up to entire satisfaction of the Engineer-in-Charge of the works. NS-4
Supply & erection of lighting arrestor model ALPRO / Alastom/ LEMCO make suitable for 11KV 3 Phase 50 HZ ground neutral system comprising of spare gape type queen gap type in series with non linger resistar element house in Horizontally scale poreclam bushing with line and ground terminal along with mounting clamps conforming to ISS 3070 (Part-I) of 1985 with latest amendment with all labour and material required to the complete in all respect up to entire satisfaction of the Engineer-in-Charge of the works. NS-5
Supply of 11KVPin Insulator Brown colour with 11KV Gi Pin Jay Shree make with Disc fitting T&C type complete in all respect with erection of the same upto the entire satisfaction of the Engineer in Charge of work NS-6
Supply & Erection of Rubber mat of size 2mX1m & 12 mm thick suitable for 11 KV complete in all respect. NS-7
Supply & Erection MS bucket stand which including cost of 6 nos. buckets of 9 liter capacity with sand filling including cost of welding & painting of complete stand & buckets with one coat of red oxide and two coats of approved paint of red colour with all labour & petty material to complete the job in all respect upto the entire satisfaction of Engineer-in-charge of work. NS-8
Supply , Erection , testing & comissioning of 11 KV HT Metering Panel ( Box ) complete with 11KV CTs, PT & HT Meter Bidirectional of 0.2 accoracy ( compatible with Solar Power Plant ) as per approved make of UHBVN Panchkula complete in all respect upto the entire satisfaction of Engineer -in Charge of work.consisting of following : i)Cubical panel free standing floor mounting type made of sheet steel 14 G SWG CRCA sheet with channel iron base frame spray painted with strong synthetic grey channel paint as per size & design approved by UHBVN. PANCHKULA Electrical Supply.Out door Type with outer canopy. ii)3 nos. 11 KV CTs 0.2 accuracy of rating as approved by UHBVN Panchkula. Chandigarh Electrical Supply for indoor installation of approved make of UHBVN Panchkula Electrical Supply. iii)1 no. 11 KV PTs 11000/110 volts 0.2 accuracy oil filled suitable for indoor installation of approved make of UHBVN Panchkula Electrical Supply . iv)Digital electronics meter (Bidirectional) 3 Phase 4 wire 11000 / 110 volts 10 VA burden 0.2 accuracy for recording reading of KWH of make and rating approved by UHBVN Panchkula Electrical Supply with push button display operating system for different kind of readings . v)Outer housing fab by 2mm thick CRCA sheet to cover the HT Metering Panel from rain water alongwith agnle iron frame. vi) The cubical panel will be complete in all respect including interconnections , internal wiring with PVC copper cable its testing / approval of all items by UHBVN Panchkula Electrical Supply with a gurantee of one year from the date of commissioning including cost of all labour & material required to complete the job in all respect upto entire satisfaction of Engineer-in-charge of work.. NS-9
Supply , Erection , testing & comissioning of Stey Set for GO Switch complete in all respect i/cost of Disc insulator etc. upto the entire satisfaction of Engineer -in Charge of work. NS-10
Supply , Erection , testing & comissioning of GI Fancing 7.5 Feet High From Finish Floor Level supported with GI Angle/ Channel complete in all repect upto the entire satisfaction of Engineer -in Charge of work. NS-11
Capacitor Panel -95 KVAR NS-12 Supply Installation, testing & commissioning 95 KVAR cubical type free floor mounted front operated Automatic power factor improvement panel fabricated from 16gauge CRCA sheet for load bearing surfaces & 14gauge for non lead bearing surfaces, dust & vermin proof indoor type with hinged lockable door suitable for 415V, 3 Phase, 4 wire, 50 Hz AC supply with seperate cable alley & lockable bus bar chamber duly powder coated as per approved shade after proper sheet treatment. It shall be complete with Aluminium Bus Bar 250Amp. with heat shrinable sleeves, earth i/c supplying & fixing following switch gears & accessories interconnection & marking as specified. The internal control wiring shall be fuse less. All control wiring & meeting protection shall be provided shall be done by MCBs switch board complete as per schematic diagram. All incoming & ourgoing feeders feeders shall be provided with ON/ OFF indication light. Make : Vrindavan Electricals, Kalyani Switchgear, Dhillon Fabricators. INCOMER FEEDER MCCB 250A. TP 36KA =1No. Spreader Terminals =1No. Rotary Handle =1No. Voltmeter with VSS =1No. Ammeter with ASS =1No. RYB Indication Lamp LED =3Nos. 250/5Amp. 15 VA CL-1 Current Transformer =3Nos. 06Amp. Control SP MCB =3Nos. CT Short Link =3Nos. OUTGOING FEEDERS 8 Step APFC Relay =1No. Exhaust Fan =1No. Capacitor Bank 95 KVAR Capacitor Bank 5KVAR =3Nos. MCB 25A. TP 10KA =3Nos. Capacitor Duty Contactor 5KVAR =3Nos. Control MCB 6A. =1Nos. ON /OFF Indicator =6Nos. ON /OFF Push Button =6Nos. Auto Manual Switch =3No. Capacitor Bank 10KVAR = 2Nos. MCB 32A. TP 10KA =2Nos. Capacitor Duty Contactor 10KVAR =2Nos. Control MCB 6A. =2Nos. ON /OFF Indicator =4Nos. ON /OFF Push Button =4Nos. Auto Manual Switch =2Nos. Capacitor Bank 25 KVAR =2Nos. MCB 63A. TP 10KA =2Nos. Capacitor Duty Contactor 25KVAR =2Nos. Control MCB 6A. =2Nos. ON /OFF Indicator =4Nos. ON /OFF Push Button. =4Nos. Auto Manual Switch. =2Nos. FABRICATION & POWDER COATING Fabrication in 1.6/2.0MM. CRCA Sheet Powder Coating in Siemens Gray Shade, 75x40mm.Channel Base Frame, Cable Entry will be Top & Bottom Suitable for Cable ,Lock, Rubber Gasket, hardware etc. BUS BAR & HARDWARE 250A. Aluminium E-91 Grade Main Bus Bar,Load wise Sub Feeder Bus Bar Colour Coated Heat Shrink Bus Bar sleave Nut-Bolt,Washer ,Hardware etc. WIRING & ACCESSORIES Power & Control Wiring will be (ISI 1100V) flamc smoke FRLS PVC Single Core Copper Wire,Copper Lugs, PVC Sleeve, Ferruels Numbers, Hardware & Labour etc. The Panel should be complete in all respect i/c all control / power wiring with necessary labour & pettty material required to complete the job in all respect upto the entire satisfaction of Engineer-in- charge of work.
S/E of Enclosure upto 125Amp. MCCB with all labour and petty material required to complete the job in all recpect upto the entire satisfaction of Engineer in Charge of work as per make of MCCB. NS-13
Ecs Engineering Chd. Pvt. Ltd.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .