Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.1 LAccepted-AOC MOTHER TERESA ROAD ZOO TINIALI GUWAHATI 781024 | GUWAHATI | KAMRUP METRO | ASSAM | 781024 | ₹21.1 L Quoted ₹22.0 L | L1 | Accepted-AOC Reasonable rate |
| 2 | L2₹24.9 LRejected-Finance | ₹24.9 L | L2 | Rejected-Finance Quoted amount higher than L1 |
| 3 | L3₹26.2 LRejected-Finance | ₹26.2 L | L3 | Rejected-Finance Quoted amount higher than L1 |
| 4 | L4₹26.5 LRejected-Finance | ₹26.5 L | L4 | Rejected-Finance Quoted amount higher than L1 |
| 5 | L5₹27.8 LRejected-Finance | ₹27.8 L | L5 | Rejected-Finance Quoted amount higher than L1 |
| Sl No | Description | Qty | Unit | M/S TAPAN KUMAR RAY L2 | NAGALAND AGENCIES CO L5 | M/S M P Sharma L3 | MS AFTAB LASKAR L4 | M/S LUIT CONSTRUCTION L1 | M/S SUBHAM ENTERPRISE L6 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Materials and labour for earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with copper strip of 20 x 3mm size by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation in hard/dense soil, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down of unserviceable earthing complete all as specified and as directed.
Notes:-
(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item.
(ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. | 8 | Each Set | 19,000 ₹1.5 L | 25,000 ₹2 L | 19,990 ₹1.6 L | 19,800 ₹1.6 L | 18,000 ₹1.4 L | 20,500 ₹1.6 L |
| 2.00 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI strip of size 25x4mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed.
Notes:-
(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item.
(ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. | 12 | Each Set | 9,000 ₹1.1 L | 11,000 ₹1.3 L | 8,990 ₹1.1 L | 8,930 ₹1.1 L | 450 ₹5,400 | 12,500 ₹1.5 L |
| 3.00 | Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised wire of 4mm dia by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 15mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down of unserviceable earthing complete all as specified and as directed.
Notes:-
(i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item.
(ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department. | 4 | Each Set | 9,000 ₹36,000 | 10,000 ₹40,000 | 8,990 ₹35,960 | 8,950 ₹35,800 | 450 ₹1,800 | 13,000 ₹52,000 |
| 4.00 | Supply & Fix Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required Copper earth strip 20 x 3 mm with saddles/fasteners/insulators and fixing screws etc including taking down unserviceable earthing complete all as specified | 25 | Rm | 500 ₹12,500 | 700 ₹17,500 | 495 ₹12,375 | 397 ₹9,925 | 450 ₹11,250 | 750 ₹18,750 |
| 5.00 | Supply & Fix Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required Aluminium earth strip 25 x 3 mm with saddles/fasteners/insulators and fixing screws etc including taking down unserviceable earthing complete all as specified | 45 | Rm | 300 ₹13,500 | 425 ₹19,125 | 495 ₹22,275 | 400 ₹18,000 | 500 ₹22,500 | 635 ₹28,575 |
| 6.00 | Supply & Fix Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI earth strip 25 x 4 mm with saddles/fasteners/insulators and fixing screws etc including taking down unserviceable earthing complete all as specified | 125 | Rm | 600 ₹75,000 | 300 ₹37,500 | 580 ₹72,500 | 933 ₹1.2 L | 630 ₹78,750 | 610 ₹76,250 |
| 7.00 | Material & Labour in replacement of test terminal block made of gun metal or phosphorus bronze size 75mmx75mmx25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head screws complete all as specified and as directed. | 8 | Each | 780 ₹6,240 | 980 ₹7,840 | 896 ₹7,168 | 1,000 ₹8,000 | 800 ₹6,400 | 1,350 ₹10,800 |
| 8.00 | Supply & Fixing in replacement of air termination single pointed aluminium rod 12mm dia 300mm long for lightning protection complete all as specified and as directed. | 10 | Each | 400 ₹4,000 | 425 ₹4,250 | 364 ₹3,640 | 410 ₹4,100 | 325 ₹3,250 | 350 ₹3,500 |
| 9.00 | Supply & Fixing in replacement of air termination single pointed copper rod 12mm dia 300mm long for lightning protection complete all as specified and as directed. | 8 | Each | 500 ₹4,000 | 615 ₹4,920 | 593 ₹4,744 | 630 ₹5,040 | 530 ₹4,240 | 1,050 ₹8,400 |
| 10.00 | Supply and fixing steel tubular swaged pole, type 410 SP 31 (Overall length 9.00 meter) conforming to IS-2713 (Part 1 to 3) 1980 complete with cast iron base plate, finial taper plug, bolts, nuts and washers, screws. Pole shall be painted with two coat of black bituminous throughout internally and externally upto planting depth and the remaining external portion shall be painted with two coats of aluminum paints over a coat of red oxide primer including painting from bottom to 1.2m height alternative with 30cm red and white strip and writing pole no with black paint on yellow background complete all as specified and as directed.
Note:
(a) Earth work and PCC shall be measured and paid separately under relavent items of schedule 'A'/BoQ.
(b) Design / drawing of HT pole and dimension is to be obtained from OEM/auth dealer/supplier and same is to be got approved from AGE(I) before placing order to the manufacturer. | 6 | Each | 14,000 ₹84,000 | 17,500 ₹1.1 L | 13,965 ₹83,790 | 14,300 ₹85,800 | 13,300 ₹79,800 | 16,500 ₹99,000 |
Updated dates
Tender Value
₹26 L
EMD Value
₹52,000
Closing Date
24 Jan 2026, 6:55 pmClosed
COL AMIT CHAUBEY
HQ 137 Wks Engr PIN 914137 c/o 99 APO
REPAIR/ MAINTENANCE OF EXTERNAL ELECTRIC DISTRIBUTION SYSTEM AND CONNECTED WORKS AT AIZWAL MIL STN UNDER GE SILCHAR
2025_MES_745127_1
8110/E8
Open Tender
Civil Works
180 days
Silchar
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE Silchar
₹52,000
Yes
16 Mar 2026
18 Dec 2025
31 Jan 2026
18 Dec 2025
24 Jan 2026
10 Jan 2026
Materials and labour for earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with copper strip of 20 x 3mm size by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation in hard/dense soil, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down of unserviceable earthing complete all as specified and as directed. Notes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connected with GI strip of size 25x4mm by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 40mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down old unserviciable earthing set all as specified and as directed. Notes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.
Materials and labour for earthing complete with galvanised iron earth plate electrode 600 mm x 600 mm x 6 mm thick, burried directly and preferably vertically in ground, earth pit not less than 2.25 Mtr deep below ground level with top edge of the plate not less than 1.5 m below ground level connetced with galvanised wire of 4mm dia by means of nuts, bolts, check nuts and washers made of galvanised iron or steel earthing lead to be protected by galvanised iron pipe of 15mm bore (light grade) and other end connected to earthing test point or lightening arrestor or main controlling switch as directed including providing funnel with 20mm bore galvanised iron pipe (medium grade), wire mesh, charcoal or coke and common salt in alternate layer of 15cm (compacted thickness) all round the earth electrode, concrete earth pit in PCC (1:3:6) type C-1 (with 20mm graded aggregate), 50mm thick precast RCC (1:2:4) cover slab (re-inforced with 8mm dia TMT bar @ 15 cm C/C bothways and suitable handle made of 10mm dia) including necessary earth work in excavation, returning filling and removal of surplus earth upto a distance not exceeding 50 m etc all as shown on electrical plate No. 3 of MES Schedule Part-I(2009) complete including testing on completion including taking down of unserviceable earthing complete all as specified and as directed. Notes:- (i) Main earthing strip from earth plate electrode to rest point upto length of 7.5 meters length shall deemed to be included in the unit rate quoted against this item. (ii) On testing after completion if the desired resistenance is not obtained the contractor shall redo the earthing without any extra cost to the department.
Supply & Fix Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required Copper earth strip 20 x 3 mm with saddles/fasteners/insulators and fixing screws etc including taking down unserviceable earthing complete all as specified
Supply & Fix Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required Aluminium earth strip 25 x 3 mm with saddles/fasteners/insulators and fixing screws etc including taking down unserviceable earthing complete all as specified
Supply & Fix Earth continuity conductor or main earthing lead fixed to wall on battenor recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required GI earth strip 25 x 4 mm with saddles/fasteners/insulators and fixing screws etc including taking down unserviceable earthing complete all as specified
Material & Labour in replacement of test terminal block made of gun metal or phosphorus bronze size 75mmx75mmx25mm drilled and screwed including 3 Nos 8mm dia 25mm long hexagonal head screws complete all as specified and as directed.
Supply & Fixing in replacement of air termination single pointed aluminium rod 12mm dia 300mm long for lightning protection complete all as specified and as directed.
Supply & Fixing in replacement of air termination single pointed copper rod 12mm dia 300mm long for lightning protection complete all as specified and as directed.
Supply and fixing steel tubular swaged pole, type 410 SP 31 (Overall length 9.00 meter) conforming to IS-2713 (Part 1 to 3) 1980 complete with cast iron base plate, finial taper plug, bolts, nuts and washers, screws. Pole shall be painted with two coat of black bituminous throughout internally and externally upto planting depth and the remaining external portion shall be painted with two coats of aluminum paints over a coat of red oxide primer including painting from bottom to 1.2m height alternative with 30cm red and white strip and writing pole no with black paint on yellow background complete all as specified and as directed. Note: (a) Earth work and PCC shall be measured and paid separately under relavent items of schedule 'A'/BoQ. (b) Design / drawing of HT pole and dimension is to be obtained from OEM/auth dealer/supplier and same is to be got approved from AGE(I) before placing order to the manufacturer.
Supply and fixing steel tubular swaged pole, type 410 SP 55 (Overall length 11.00 meter) conforming to IS-2713 (Part 1 to 3) 1980 complete with cast iron base plate, finial taper plug, bolts, nuts and washers, screws. Pole shall be painted with two coat of black bituminous throughout internally and externally upto planting depth and the remaining external portion shall be painted with two coats of aluminum paints over a coat of red oxide primer including painting from bottom to 1.2m height alternative with 30cm red and white strip and writing pole no with black paint on yellow background complete all as specified and as directed. Note: (a) Earth work and PCC shall be measured and paid separately under relavent items of schedule 'A'/BoQ. (b) Design / drawing of HT pole and dimension is to be obtained from OEM/auth dealer/supplier and same is to be got approved from AGE(I) before placing order to the manufacturer.
Supplying, Laying connecting & testing XLPE insulated, PVC sheathed, armoured HT electric power UG cable (heavy duty with stranded aluminum conductor) of size 95 Sqmm, 3 core, 11000 Volts(Earthed) grade, conforming to IS-7098 (Part-II) laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed. Note : Earth work, precast cable cover protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule 'A'/BoQ.
Supplying, Laying connecting & testing XLPE insulated, PVC sheathed, armoured HT electric power UG cable (heavy duty with stranded aluminum conductor) of size 95 Sqmm, 3.5 core, 11000 Volts(Earthed) grade, conforming to IS-7098 (Part-II) laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed. Note : Earth work, precast cable cover protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule 'A'/BoQ.
Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 70 sqmm 3.5 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed. Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule 'A'/BoQ.
Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 50 sqmm 3.5 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed. Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule 'A'/BoQ.
Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 25 sqmm 4 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed. Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule 'A'/BoQ.
Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 16 sqmm 4 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed. Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule 'A'/BoQ.
Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 10 sqmm 4 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed. Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule 'A'/BoQ.
Supplying, laying / fixing, testing and commissioning of electric cable, grade aluminium conductor XLPE insulated, 10Sqmm, 2 core, 1100 volt earthed grade, Un-armoured cables conforming to IS-7098 (Part-I)-1988, stranded, XLPE insulation, PVC tape inner sheath laid in trenches, passing through ducts, etc. fixed on poles, etc. including taking out old damaged cable complete all as specified and as directed. Note: Excavation/earthwork, bricks, sand cushioning and GI pipe will be measured and paid separately.
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for foundations, manholes, etc. or for laying cables/pipes, erecting poles, etc. not exceeding 10sqm on plan and getting out in soft / loose soil complete all as specified and as directed.
All as per item No 21 above but depth exc 1.5m but n.exc 3m complete all as specified and as directed.
Returning, filling in, including, spreading, leveling, watering and well ramming in layers not exceeding 25cm deep as in any type of soil complete all as specified and as directed.
Removing excavated materials to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point in any type of soil including spreading in low lying area and leveling complete all as specified and as directed
Materials and labour for sand filling around the cable with approved quality coarse sand for sand cushioning of Under ground cable including spreading and punning down to 18 cm thickness complete all as specified and as directed.(Compacted thickness shall be measured)
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1, with peak, size 300mm x 180mm x 40mm in trenches on cable as cable protection across the length of the cable (width wise)complete all as specified and as directed.
Materials and labour for brick protection cover to underground cables with sub class ‘B’ over burnt brick of size 23 X 11.5 X 7.5 cm, (locally available best quality), laid dry and flat abutting each other with gaps not exceeding 10mm complete all as specified and as directed.
Supply and laying GI tubing 80mm bore light grade with fittings laid in trenches for protection of HT/LT underground cables/ roof conductor including taking down old unserviceable pipes complete all as specified and a
s directed. .
Supply and laying GI tubing 50mm bore light grade with fittings laid in trenches for protection of HT/LT underground cables/ roof conductor including taking down old unserviceable pipes complete all as specified and as directed. .
Supply and laying GI tubing 40mm bore light grade with fittings laid in trenches for protection of HT/LT underground cables/ roof conductor including taking down old unserviceable pipes complete all as specified and as directed. .
Material and Labour for PCC 1:3:6 type C-2 using 40 mm graded crushed stone aggregate for errection of Stay rod, filling and mass concrete etc all as specified and directed by Engr-in-Charge.
Supply and fixing in repair of 415V 10KA 'C' curve miniature circuit breaker (MCB) of TPN 63 to 100Amps current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and as directed.
Supply, fixing, commissioning & testing of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, Electric power cable (heavy duty) with aluminium conductors, 1100 volts, grade cross sectional area 16 sqmm 2 core laid through duct/ pipe / in trench etc. with cable glands & suitable size of aluminium lugs including taking down of unserviceable cable complete all as specified and as directed. Note : Earth work, brick protection and sand cushioning and GI Pipe Shall be measured and paid separately under relavent item of schedule 'A'/BoQ.e
Material and labour for HT 11 KV (Earthed) grade heat shrinkable jointing kit outdoor type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 70 to 95 sqmm including taking down of unserviceable jointing kit complete all as specified and as directed.
Material and labour for LT 1.1 KV (Earthed) grade heat shrinkable straight through jointing kit complete with jointing material and accessories suitable for 4/3.5 core XLPE armoured aluminium conductor cable of size 10 to 16 sqmm including taking down of unserviceable jointing kit complete all as specified and as directed.
Material and Labour for PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate for coping of pole, filling of road cutting and mass concrete etc complete all as specified and directed by Engr-in-Charge.
Material and labour for testing earth resistance between conductor and earth value for buildings and lightning conductors including writing date of testing and next due date with synthetic enamel paint in approved fonts over the earth pit complete all as specified and as directed. Note: (i) Testing shall be done from testing agencies approved by the GE. (ii) Test certificates shall be submitted in duplicate to claim any payment against the item. (iii) Periodicity of testing on each earthing shall be twice within currency of contract or as directed by the Engineer-in-charge. (iv) Two numbers of testing in one earthing shall be measured as one unit for payment purposes.
Set of three
Material and labour for LT 1.1 KV (Earthed) grade heat shrinkable straight through jointing kit complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 25 to 50 sqmm including taking down of unserviceable jointing kit complete all as specified and as directed.
Material and Labour for draining out old transformer oil and supply, filling/ topping up oil of transformer oil of dielectric strength not be less than 60kV and conforming to IS-335 of 1993 up to desired levels as required for transformers at different locations complete all as specified and as directed.
Material and labour for LT 1.1 KV (Earthed) grade heat shrinkable straight through jointing kit complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 95 sqmm including taking down of unserviceable jointing kit complete all as specified and as directed.
Material and labour for LT 1.1 KV (Earthed) grade heat shrinkable straight through jointing kit complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 70 to 95 sqmm including taking down of unserviceable jointing kit complete all as specified and as directed.
Supply and fixing breather assembly including silica gel, indicating type, 4 to 6mm standard size of the particle, blue colour for transformer of capacity from 63 to 150kVA including removing of old unserviceable breather complete all as specified and as directed.
Material & Labour for preparation of old surfaces of transformers, any type (power or distribution) of capacity upto and including 100 to 150kVA (in situ) outdoor type, installed at various locations, by cleaning, scrapping, rubbing/ polishing etc. and spray painting with two coats of Duco paint (Grey) and writing the SM MES No of transformer on body of transformer with synthetic enamel paint (of approved tint) in suitable font and size (as approved) complete all as specified and as directed
Supply and fix in repair of drain valve of transformer 100 KVA to 150 KVA of existing make complete all as specified and as directed.
Material & Labour for preparation of surfaces viz. scrapping old paints, smoothening, etc. and painting to steel tubular poles, 9m high, with two coats of synthetic enamel paint upto a height of 1.5m from ground, in alternate stripes in black & yellow, including painting of pole coping with synthetic enamel paint (black tint) and writing (font 1/2"x3") pole numbers with white synthetic enamel paint on circular base, marking of HT/LT, painting of balance portion of pole, cross arms, brackets with two coats of aluminum paint with all necessary staging, safety precautions, etc. as required complete all as specified all as directed.
Supply & fixed in repairs of 4 pole onload change over switch, 415V, 50Hz with SS enclosure of 100A capacity fixed to panel board with necessary arrangement including nuts, bolt, lugs, glands, etc. complete all as specified and as directed.
Supply & fixed in repairs of MCCB 4 pole 35kA, 250A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed.
Supply & fixed in repairs MCCB 4 pole 35kA, 200A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed.
Supply & fixed in repairs MCCB 4 pole 35kA, 160A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed.
Supply & fixed in repairs MCCB 4 pole 25kA, 125A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed.
Supply & fixed in repairs MCCB 4 pole 25kA, 100A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed.
Supply and fix in repair of cross arms. Bracings, support channel, backplate hooks etc fabricated from structural steel, sections (MS Channel) of required size and shape including nuts, bolts,washers, welding, bending , cutting cold or hot, drilling holes for inserting bolts as indicated and directed including painting with one coat of red oxide primer and two coats of silver aluminium paint complete all as specified.
S & F in reapir of Cable Route Indicator made of CI Disc, 150mm dia, with inscription of HT/LT Cable fixed to MS angle of size 40 X 40 X 6mm, 450mm long with bolts & nuts, duly grouted in PCC, 1:3:6, Type C1 complete including necessary excavation and earth work complete all as specified and as directed.
Supply & fixed in repairs MCCB 4 pole 16kA, 63A, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed.
The panel shall be fixed with angle iron frame made of angles of size 40X 40 X 5mm at Corners and ISMC of suitable size for base, embedded 600 mm below ground level in PCC 1:2:4, Type B–1 using 20mm grade stone aggregate, 600 mm above ground level complete including connecting up with existing incoming and outgoing cables etc. and comprising the following : [a] MCCB, 125 Amps, FP, 25KA, 415 Volts, 3 Phase, AC, 50 Hz – 1 No. [Incoming] [b] Aluminium bus bar 400 Amps for phases and 300 Amps for Neutral of suitable size and length duly insulated with colour code. [c]Multifunctioning meter (Next Gen) - 01 No [d] Colour Coded LED Phase Indicating Lamps for each Phase – 1 Set. OUTGOING :- (a) MCCB 4 Pole 63 Amps, 16 KA Breaking capacity - 03Nos
Supply and fix in repair of brass terminal stud with nuts, check nuts, oil seal and washer for HT side suitable for 100/150kVA transformer complete all as specified and as directed.
(b) MCB SPN 32A, 10 KA Breaking capacity - 04 Nos.
M&L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, for LT, 20x15cm size ncluding dismanting old unserviceable plate complete all as specified and as directed.
M&L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, for HT, 20x15cm size ncluding dismanting old unserviceable plate complete all as specified and as directed.
Supply & fixed in repairs MCCB 3 pole 16kA, 32-40 Amps, 415V, 50Hz, with thermal magnetic release setting, fixed to panel board with necessary arrangement including nuts, bolt, lugs, etc. complete all as specified and as directed.
Supplying, laying / fixing, testing and commissioning of electric cable, grade aluminium conductor XLPE insulated, 6Sqmm, 2 core, 1100 volt earthed grade, Un-armoured cables conforming to IS-7098 (Part-I)-1988, stranded, XLPE insulation, PVC tape inner sheath laid in trenches, passing through ducts, etc. fixed on poles, etc. including taking out old damaged cable complete all as specified and as directed. Note: Excavation/earthwork, bricks, sand cushioning and GI pipe will be measured and paid separately.
M & L for preparation of old painted surface of LT Panel/Distribution box installed at E/M Installations at Aizawl Mil Stn area of any size by removing all dirt, dust,etc and painting complete surface including connected accessories such as angle Iron channel etc of any description with one coat of synthetic enamel paint of approved colour including writing of identification complete all as directed by Engineer-in-Charge.
M&L hard core of gauge n.exc 63mm deposited spread and leveled in layers n.exc 15cm thick, watered and rammed to true surface broken stone or boulders or aggregate around 4 pole , 2 pole structure and transformer etc. complete all as per directed by Engr-in-charge.
Supply and fixing in repair of 415V 10KA 'C' curve miniature circuit breaker (MCB) of TP 32 to 63Amps current carrying capacity in the DB complete with connection testing and commissioning complete all as specified and as directed.
Supply and fixing in reapir of 240V, 10KA 'C' curve miniature circuit breaker (MCB) of SPN and current carrying capacity 32 Amps in the MCB DB complete with connection testing and commissioning complete all as specified and as directed.
Material and Labour for (cold bitumen) for filling/repair of road cutting with road patch material ready mix liquid asphalt with chemicals, anti striping agents, graded aggregates and additives laid in layers of 50mm and compacted with rammer or a wooden mallet complete as per manufacturer instructions and as directed by Engr-in-Charge.
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.30 MB
8110tenderdocx.pdf
Tender Documents • 1.49 MB
BOQ_834349.xls
BOQ • 0.30 MB
Download all tender documents and submit your bid