Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹69.9 LAccepted-AOC CHANGANACHERRY GENERAL ELECTRICAL WORK | ERNAKULAM | KERALA | 682001 | L1 | Accepted-AOC L1 | |
| 2 | Rejected-Technical | - | Rejected-Technical L5 | |
| 3 | Rejected-Technical III 246 MANIYATTU BUILDING KURUPPAMPADY P O RAYAMANGALAM ERNAKULAM KERALA 683545 INDIA | ERNAKULAM | KERALA | 683545 | - | Rejected-Technical L3 | |
| 4 | Rejected-Technical | - | Rejected-Technical L2 | |
| 5 | Rejected-Technical | - | Rejected-Technical L4 |
Tender Value
₹74.3 L
EMD Value
₹50,000
Closing Date
25 Mar 2025, 2:00 pmClosed
Superintending Engineer
O/o Superintending Engineer, Kochi Municipal Corporation.
GENERAL-495663/25-Electrification to MRI unit ,Taluk Hospital Fort Kochi
2025_LSGD_752449_1
FCE1-495663/25-MRI UNIT ELECTRIFICATION
Open Tender
Electrical Works
Item Rate
300 days
FORTKOCHI
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,500
₹50,000
23 Jun 2025
19 Mar 2025
26 Mar 2025
19 Mar 2025
25 Mar 2025
19 Mar 2025
Amount
500 KVA USS,320KVA DG
OD496962/2024-2025:Supply, conveyance, installation, testing and commissioning of emergency isolation push button mounted in standard I.P 65 weather proof break glass enclosure to isolate the power supply to the building in case of emergency when the face glass is broken. The push button shall be connected to the trip coil of the 11 kV LB SFU using 1.5 sq:mm 3 core copper cable.
OD496965/2024-2025:Supply,conveyance , installation, testing and commissioning of 80/5A , 15 VA, Cl . 5P10 protection type CT for low set earth fault protection wirh metalic enclosure
OD498000/2024-2025:Supply and providing Three Phase HT TOD Meter
OD496976/2024-2025:Supplying and making outdoor end termination with push-on end termination kit (earthed) for 11 KV grade XLPE cable of 3x150 sq.mm sizes including supply of end sealing kit consisting of stress-cum-semi conducting pad, cap, rain shield, self bonding insulating case, leakage current collector, protective corrugated hose pipe, boot, earth continuity connection (with 3 core kit only), earthing lug (with 1 core kit), adhesive-cum-solvent, PVC (NA) tape, silicon grease, aluminium crimping lug, aluminium oxide cloth, nylon string, copper binding wire, hose clamp and bi-metallic washer etc. as required.
OD496970/2024-2025:Supplying and making indoor end termination with push-on end termination kit (earthed) for 11 KV grade XLPE cable of 3x 300 sq.mm sizes including supply of end sealing kit consisting of stress-cum-semi conducting pad, cap, rain shield, self bonding insulating case, leakage current collector, protective corrugated hose pipe, boot, earth continuity connection (with 3 core kit only), earthing lug (with 1 core kit), adhesive-cum-solvent, PVC (NA) tape, silicon grease, aluminium crimping lug, aluminium oxide cloth, nylon string, copper binding wire, hose clamp and bi-metallic washer etc. as required.
OD496975/2024-2025:Supply, laying and clamping of 1 no. 11 KV grade XLPE cable of 3x300 sq.mm sizes using clamps fabricated from 20 x 3 mm MS flat, spacing of clamps not exceeding 60cms, making good the damages, colour washing etc. as required.
OD497103/2024-2025:SITC of 320 kVA Diesel Generator set complete with integral acoustic enclosure as per existing CPCB IV+ norms and as per technical details given below 1. Engine a) Make of Engine - Cummins/ Kirlosker/Volvo/Caterpillar ) Type of Engine - Diesel Engine c) No. of Cylinders- 6 d) Method of Cooling Liquid cooled with radiator. e) Aspiration -Turbo charged, charge air cooled. f) Design - Suitable for generating set operating. g) Output- As per manufactures standards. 2. Standard accessories with Diesel Engine. a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Mechanical governor g) Fuel filter h) Exhaust silencer i) Exhaust Muffler j) Lubricating oil filter. k) Battery Charger/Generator 3. Engine Instrument Panel with the following items a) Starting switch with key or button. b) Lubricating oil pressure gauge. c) Water temperature gauge. d) RPM Indicator with hour meter. e) Battery charging Ammeter. 4. Safety Controls for Engine. a) Trip for low lubricating oil pressure. b) Trip for high water temperature. 5.Fuel pipe: Oil resistance flexible hoses of 20mm dia or nearest size MS pipe as per manufacturer; standard, 6 Brush less Alternator a) Make - Stamford/Kirlosker/Crompton b) Type - Self exited and self-regulated, brush less c) Capacity ; 320 kVA kVA/ 256 K W @ 0.8PF d) System of Voltage - 3 phase, 415 V, 4 wire system. e) Speed - 1500 rpm f) Voltage regulation band - +/-2.5% of rated voltage g) Frequency - 50 Hz h) Insulation - Class -F/H .The Alternator should confirm to IS 4722. Operation and service manual, spares and tools shall be provided. . 7.Fuel Tank Suitable size built in type integrated with the acoustic enclosure. Fuel connection shall be done as per standards.7. Battery. Suitable size built in type integrated battery with leads and terminals of appropriate AH capacity as per Manufactures requirement. 8. Automatic Battery charger. Push button switch for ON/OFF - 1 set. Metallic DNB - 1No Solid state phase indication lamp for supply ON/OFF with HRC protection Supply of HSD for test run, The standard Electric control panel integrated with acoustic enclosure comprising of the following. a) 400 A,50 KA,4Pole MCCB having adjustable setting, b) Digital Multi function meter with accuracy class 1 to read parameters such as KW, KVA, PF, voltage, Current Frequency etc: c) Digital type single function KWH meter with accuracy class 1, d) LED type phase indication Lamp for indicating the presence of supply on all phases,10.Exhaust Piping Exhaust Piping shall be vent to the top of the nearest tallest building if required . If the pipe cannot be clamped/fixed to the building or any other structure of permanent nature necessary fabricated structures using channel section or angle iron sections of adequate mechanical strength, duly painted with 2 coats of Heat retardant aluminium paint shall be provided for the support of the exhaust pipe. (Additional piping will be measured excluding the standard length of pipe supplied by the manufacture
OD497104/2024-2025:Supply and Providing DG exhaust pipe with B class medium grade MS pipe with & necessary accessories like flanges etc as required and with necessary painting using heat resistant Aluminium paint and providing rain guard on the top 200 mm(including Al cladding)
90.14.1.1:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame)
90.14.2.2:Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD496961/2024-2025:Fabrication, supply & fixing main bus bar system and interconnections with electrolytic grade Aluminium strips/ rigid conductors conforming to IS 1867 (with latest amendments) for bus bar arrangement with single strip per phase supported on finger type bus bar supports of adequate size, spacing between supports not exceeding 50 cm & overhang not exceeding 5 cm including bending to shape, drilling holes, tinning the points of contacts, fixing heat shrinkable PVC sleeves, plated bolts and nuts with plate washers and spring washers, copper sockets for round conductors, etc., as required.
90.14.7:Supply and providing copper earth bus in the panel board
OD496977/2024-2025:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/ equipments including providing suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring, keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required. 1.50 sq. mm single run with required socket 1 12
OD496969/2024-2025:Three phase multifunction meters to read V, A ,PF ,F, accuracy class 1
OD496963/2024-2025:LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour
OD496978/2024-2025:Aluminium anodised Danger Notice Board of size 150 x 100 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour.Aluminium anodised Danger Notice Board of size 150 x 100 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour.
OD496964/2024-2025:20 A fuse holder for BS type blade fuses. 3
OD496968/2024-2025:2 A-16A clip-on offset tag fuse link of size f1 3
OD496974/2024-2025:Aluminium anodised legend plate of size 40 x 20 mm. with inscription of EARTH. 1 1
OD496973/2024-2025:Supply and fixing MC 12 device in the main panel board
90.14.11.4:MCCB AccessoriesSupply and fixing one number earth fault Relay up to 630A to 800A with CBCT.
90.14.8.11:800 A, 4 pole, manual draw out type, microprocessor based ACB with overload , instantaneous SC , delayed SC and ground fault protection 50kA
90.14.11.9:MCCB AccessoriesSupply and fixing auxiliary switch (1 NO + 1 NC) in the existing MCCB of rating up to 630 A.
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
OD496972/2024-2025:Spreader/Terminal adapter Kit Extended terminal for 4 pole MCCB of rating upto 630 A (8 pcs) cat no. CM92004OOOO / Equivalent make
90.14.11.15:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 315-630 A
1.17.10:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.10 x 1.5 sq. mm
90.14.11.13:MCCB AccessoriesSupply and fixing rotary handle, External type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
90.14.11.7:MCCB AccessoriesSupply and fixing 630 - 800A earth fault module of MCCB requiring external CBCT.
90.14.11.8:MCCB AccessoriesSupply and fixing CBCT suitable for 630 - 800A earth fault module.
2.2.1:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.100 Amp, 16 KA, TPMCCB
2.2.5:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.200 Amp, 25 KA,TPMCCB
2.2.9:Providing and fixing following rating and breaking capacity and pole MCCB in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.400 Amp, 35 KA,TPMCCB
OD498023/2024-2025:Supply and providing AMF relay with all accessories
90.12.7.31:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 95 sq mm
90.12.7.33:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 150 sq mm
90.12.7.36:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 300 sq mm
90.12.7.37:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 400 sq mm
9.1.24:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
9.1.26:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 150 sq. mm (50mm)
9.1.30:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
9.1.31:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)
OD497618/2024-2025:Supply and providing earth clamp of 12mm thick
4.1.5:Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.375 mm width X 50 mm depth X 2.0 mm thickness
Capacitor Panel
90.14.1.1:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame)
90.14.2.2:Supply and providing 3mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.2:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardU' section rubber beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
OD496999/2024-2025:LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour
OD497001/2024-2025:Aluminium anodised Danger Notice Board of size 150 x 100 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour.Aluminium anodised Danger Notice Board of size 150 x 100 mm. with inscriptions ( both in English and Malayalam) and conventional Skull and Bone in Red colour.
OD496994/2024-2025:20 A fuse holder for BS type blade fuses. 3
OD497000/2024-2025:2 A-16A clip-on offset tag fuse link of size f1 3
OD496995/2024-2025:Aluminium anodised legend plate of size 100 x 40 mm. with inscription of BUS BAR CHAMBER
OD496991/2024-2025:Aluminium anodised legend plate of size 40 x 20 mm. with inscription of EARTH. 1 1
OD496997/2024-2025:Fabrication, supply & fixing main bus bar system and interconnections with electrolytic grade Aluminium strips/ rigid conductors conforming to IS 1867 (with latest amendments) for bus bar arrangement with single strip per phase supported on finger type bus bar supports of adequate size, spacing between supports not exceeding 50 cm & overhang not exceeding 5 cm including bending to shape, drilling holes, tinning the points of contacts, fixing heat shrinkable PVC sleeves, plated bolts and nuts with plate washers and spring washers, copper sockets for round conductors, etc., as required.
OD497002/2024-2025:Supply & fixing the following accessories in positon and giving connection. 8 stage, 440/ 110 V, 5 A/ 1 A intelligent power factor controller
OD496992/2024-2025:Supply and Fixing of Illuminated Flush head Actuator - Green with legend 'OFF', (Contact - 1 NC) and giving connection etc as required.
90.14.24.46:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.7.5 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel without block reactor.
90.14.24.47:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.10KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel without block reactor.
90.14.24.49:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.15 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel without block reactor.
90.14.24.50:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.20 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel without block reactor.
90.14.24.51:Supply & fixing the following Power Capacitors 3 phase delta connected in positon and giving connection.25 KVAr, 3 phase, 440 V, Metalised Poly Propylene Heavy duty, Box type resin filled Capacitor suitable for APFC panel without block reactor.
OD496996/2024-2025:Providing and fixing following 400/5 A, 5 VA, accuracy class .5, Resin Cast Metering CT in existing panel and giving connection complete
2.10.5:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole and neutral
1.17.29:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 6 sq. mm
2.1.8:Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.400 Amp TP&N
90.14.7:Supply and providing copper earth bus in the panel board
EARHING
OD496989/2024-2025:Supply and providing plate earthing as per IS 3043 with 1200x1200x12 mm GI/CI earth plate, 50 mm GI watering pipe fixed to the earth plate with 25 x 3mm GI clamps, GI funnel with weld mesh, filling required quantity of charcoal including construction of inspection chamber with a bed concrete of 1:4:8 PCC using 40 mm broken stone (10 cm thick), brick work in cement mortar 1:6, plastering the surface of brick masonry and the exposed surface of PCC bed with cement mortar 1:4, 12 mm thick, (the finished inside dimension shall be 450 x 450 x 450 mm) but excluding test joint, earth continuity conductor to the plate, and covering at the top.
OD497637/2024-2025:Earthing with G.I. earth pipe 2 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required
90.16.3.9:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)25 x 3 mm copper strip
90.16.3.11:Supply and clamping the following size of strips on surface of wall/ parapet/ existing cable tray using clamps fabricated from 20 X 3 mm GI flat duly painted or heavy duty GI spacer saddles spacing of clamps not exceeding 1 m, making good the damages, colour washing etc. as required ( for horizontal run)32 x 3 mm copper strip
5.9:Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
5.15:Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.1.3:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required3.15 mm copper conductor ( 10 SWG)
90.16.1.4:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required4.00 mm copper conductor ( 8 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
OD497320/2024-2025:Supply and providing 12x3mm brass bolt and nut with washers on the existing MS box/earth bus etc as required including drilling necessary holes
OD497321/2024-2025:Supply and providing 25x6mm brass bolt and nut with washers on the existing MS box/earth bus etc as required including drilling necessary holes
OD497326/2024-2025:Supply and providing earth clamp of 12mm thick
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.9:Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
OD497305/2024-2025:Reinforcement of RCC work .bend,tied,and and placed in position (plain grill requiring bend cold) using for steel
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
OD496986/2024-2025:Supply and providing 2.5mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 11 KV dielectric strength.
OD496988/2024-2025:Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required.
OD496987/2024-2025:Supply and providing 5 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required.
OD496984/2024-2025:Painting letters or figures of 2.5/4 cm sizes with enamel paint as identification mark to SB, DB, panel board etc as required
OD496985/2024-2025:Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
Electrification
90.2.1.1:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point
OD497342/2024-2025: Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories). Single control light point with 6 A switch , with out ceiling rose (4 light controlled by one switch)
90.2.1.4:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point
90.2.1.6:Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points
90.3.18.2:Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps
90.4.1:Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.4.5.4:Supply, Installation, testing and commissioning of ceiling fan of following sizes including wiring the down rods of standard length (up to 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required. 1200mm sweep - ceiling fan complete with service value minimum 4.0(cub meter/minute/Watt), Air delivery minimum 210(cubic meter/minute), Copper winding suitable for 230V/240V single phase AC supply
OD497585/2024-2025:Supply and fixing ceiling mounded LED Square Ceiling Light (Warm White) lights 18 W High lumen LED 300x300 x4.3cm Philips/Crompton/Havel's/Wipro make
90.4.8:Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
OD497587/2024-2025:Supply , fixing, testing and commissioning on Exhaust fan of the following size ,and, giving connection as required 300mm Light duty with metal leaf double ball bearing
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.14:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 x 2.5 sq. mm
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.27.2:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
90.11.1.12:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+24) - three phase double cover (IP 42/43)
90.11.1.15:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.11.1.20:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required8 way (8+12) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43)
90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
2.10.4:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.1:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps
2.15.2:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
90.12.7.29:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp
90.12.7.40:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp
90.12.7.41:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp
9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.32:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
9.1.34:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 25 sq. mm (28mm)
90.12.7.42:Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp
OD497616/2024-2025:Supply and providing earth clamp of 12mm thick
90.16.1.2:Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required2.65 mm copper conductor (12 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
OD497621/2024-2025:Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
90.15.4.2:Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
OD496980/2024-2025:Amount to be deposited with KSEB/ K.S.E.L.B for scheme approval and energization sanction.(Actual amount will be reimbursed on production of original documents ( Non competitive item)
Kittu Electricals private limited (BID ID -2170350)
candelaengineering corporation (BID ID -2174279)
TECHZONE ENGINEERS PVT LTD (BID ID -2171569)
C.A.K. SOUND (BID ID -2174664)
Bidder Name
Kittu Electricals private limited
ELCON ELECTRICALS
TECHZONE ENGINEERS PVT LTD
candelaengineering corporation
C.A.K. SOUND
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1220314.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .