Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.7 LAccepted-AOC DOOR NO 2 31 23 SECTOR 7 SBI COLONY MVP VISAKHAPATNAM 530 017 | VISAKHAPATANAM | ANDHRA PRADESH | 530017 | L1 | Accepted-AOC L1 | |
| 2 | L2₹17.9 L+₹16,680 (0.94%)Rejected-Finance FLAT NO 304 SN TOWERS JAGANNADHAPURAM JUNCTION AKKAYYAPALEM VISAKHAPATNAM 530 016 | VISAKHAPATANAM | ANDHRA PRADESH | 530016 | L2 | Rejected-Finance NOT BEING L1 | |
| 3 | L3₹18.0 L+₹21,524 (1.21%)Rejected-Finance | L3 | Rejected-Finance NOT BEING L1 | |
| 4 | L4₹19.5 L+₹1.7 L (9.73%)Rejected-Finance | L4 | Rejected-Finance NOT BEING L1 |
Tender Value
₹18 L
EMD Value
₹36,000
Closing Date
5 Oct 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE No 2 Visakhapatnam
CWE No 2 Station Road Viskhapatnam 04
AS AND AS TO HT 4 POLE STRUCTURE AT NEW ADMIN BLOCK AT INS KALINGA BHEEMUNIPATNAM
2021_MES_466715_2
82533
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Kalinga
class E cat b ii
6 documents required · 6 mandatory
₹500
Yes
GE Kalinga
₹36,000
Yes
25 Nov 2021
9 Sept 2021
8 Oct 2021
9 Sept 2021
5 Oct 2021
18 Sept 2021
9 Sept 2021 - 11 Sept 2021
60 days
Amount
Supply, install, testing & commissioning of factory made 11 KV, 630 Amps, 21 KA for 3 seconds, SF6 insulated, motorized, outdoor, 6 way RMU consisting of 2 Nos VCB incoming, 2 Nos VCB outgoing for feeder and 2 Nos VCB outgoing for transformer complete all as per manufacturers instructions,as specified and as directed and shall comprise of the following: [A] RMU shall be 11 KV, 630 Amps, 21KA for 3 seconds, SF6 insulated, motorized, outdoor, 6 Way RMU, right side extensible with air insulated bus connected metering unit, type tested in line with latest IEC Standards, suitable for operations at a height up to 1000 meters above sea level and at 40ºC ambient temperature without any de-rating,
switchgear and busbar shall all be contained in a stainless steel enclosure [minimum 2mm thick AISI 441 Grade] filled with SF6 at 0.3 Bar [300 hPa] relative pressure, RMU tank shall provide full insulation and switchgear shall be insensitive to the environment with degree of protection of IP67, switchgear operating mechanism shall have an IP2X protection and cable chamber shall have IP3X protection, outer enclosure shall be IP 54 type tested, powder coated with pure polyester based paint, suitable for the site installation conditions, accidental overpressure due to an internal arc is limited by the opening of the safety valve, at the bottom of the metal enclosure, away from the operator, plug in type of extensibility must be provided and coupling busbar should not be exposed to air to avoid oxidation of busbars. Extension of cubicle shall require 450 mm to handle and the gap between the coupled RMU’s must be within 10mm.
[B] Vacuum Circuit Breaker [VCB], comprising of the following: [i] 11 KV, 630 Amps, 21 KA VCB with Manual / motorised spring assisted mechanism and series trip coil – 1 No, [ii] Load break switch with built-in earth switch – 1 No [iii] Position indicator through clear front mimic in line with IEC 62271-103 – 1 No [iv] Self powered relay with O/C, S/C, E/F protection. Relay shall have a front USB / RS485 / RS232 port for laptop Interface / modbus communication, LCD display, 10 event records, 5 fault records, min 2 setting group and keypad for setting parameters for the relay – 1 No [v] CT ratio 200-100/1-1A for incoming, 200-100/1-1A for 2 Nos feeder outgoing and CT ratio 100-50/1-1A, 4 Nos transformer outgoing, class - 1.0, 2.5VA for metering and class 10P10, 2.5 VA for protection – 1 Set [vi] Live cable indicator with indication at the front and three inlets to check the synchronization of phases – 1 No
[vii] cable termination bushing suitable for up to 1 run, 3 core, 300 Sq.mm, XLPE cable – 1 Set [viii] cable termination cover boots [push on type] – 1 Set [ix] Fault Passage Indicator FPI. [x] Circuit breakers shall have two positions: open or disconnected and closed. A separate and independent 3 position earthing switch and disconnector shall be fitted to open and earth the cables in such way that interlocks prevent all unauthorised operations. An operating mechanism shall be used to manually close the circuit breaker and charge the mechanism in a single movement. An independent mechanism shall be fitted for the 3 positions earthing switch and disconnector circuit breaker shall be fitted with a local system for manual tripping by an Integrated push button. There shall be no automatic reclosing. Circuit breaker shall have a min of 2000 mechanical and electrical operations and 50 Nos short circuit operations, disconnector and earth switch shall have a minimum of 1000 [M1] mechanical operations , 100 electrical operations at rated current and 5 Nos operations at rated short circuit current.
[c] Data transmission rates – 300 to 19200 BPS for serial ports for MODBUS and 10/100 MBPS for TCP/IP ethernet ports [d] Use of IEC 60870-5-104 protocol to communicate with the Master Station[s] [e] Use of MODBUS over RS485 interface, protocol to communicate with the MFTs, protection relay. [f] It have required number of communication ports for simultaneous communication with master station[s], MFTs. [g] FRTU shall have the capability of automatic start-up and initialisation following restoration of power after an outage without need of manual intervention. All restarts shall be reported to the connected master stations.
[h] Remote data base downloading of FRTU from master station from SCADA/DMS control center. [i] Internal battery backup to hold data in SOE buffer memory & also maintaining the time & date. [j] Communication with at least four master stations simultaneously on IEC 60870-5-104 [k] RTU shall be capable of acquiring analog values through transducers having output as 4-20 mA, 0-10 mA, 0-+10 mA etc using analog input modules. [l] FRTU shall have one TCP/IP Ethernet port for communication with master station[s] using IEC 60870-5-104 protocol. [m] FRTU shall have one serial RS 485 port for communication with MFTs and connected in daisy chain using MODBUS protocol. Minimum 15 analog values [Including 4 Energy Values] shall be considered per energy meter. [viii] Connection with adjacent modules shall be direct through busbar via metering bushing or through MV cables. VT’s and CT’s from the manufacturer conforming to IEC61869-3 and IEC 61869-2 respectively shall be accepted.
Note: [a] The make of Vacuum Interrupter, FRTU offered shall be of the same make as of the Ring Main unit. [b] An operator situated in front, lateral and rear [A-FLR 21kA – 1 Sec, downwards exhaust, for tank as well as cable compartment] of the RMU switch board during an internal fault shall not be exposed to the effects of arcing. Internal arc type test report for IAC AFLR 21 KA for 1 sec for both tank & cable box shall be for minimum 3 way / 3 function RMU. [c] All operations shall be from front of the RMU, including access to cable bushings. Bushings along the sides or the rear of the RMU are not acceptable. [d] Construction of plinth / foundation for 11KV RMU: The rate quoted is deemed to be including the cost of plinth / foundation.The foundation shall consists of two parallel brick walls built using fly ash brick masonry straight or curved on plan to any radius built in CM (1:6) of length 2.10m, suitable thickness and height as per the manufacturer’s instructions including
over PCC concrete bed of 150 mm thick in PCC (1:4:8) type D-2, (using 40mm graded stone aggregate) over 150 mm thick hardcore of gauge not exceeding 63mm of broken stones or boulders, deposited, spread and levelled in layers not exceeding 15 cm thick watered and rolled, over 150 mm thick sand filling, rendering to brick surfaces with 15 mm thick in CM (1:4) with finishing the top surface even and smooth without using extra cement, applying three coats of white washing including earthwork excavation of pit size 2.10 X 1.20 X 0.60 Metres complete all as per manufacturer’s recommendations, drawings, as specified and as directed. [e] The rate quoted is also deemed to be including the cost of disconnection of HT Cables up to 3 core, 240 Sq.mm from existing 2 Pole / 4 Pole structures, removing of cable loop and reconnection to RMU complete all as directed by the Engineer-in-Charge. [f] End termination joints shall be measured and paid separately. Make :Siemens/ABB/Schenider/BHEL.
Supply, jointing, testing and commissioning of cable jointing kit for 11 KV (Earthed) grade cable for indoor type joint (heat shrinkable) complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 150 sqmm to 185 sq mm complete all as directed. Make : M - Seal/ 3M /Denson / Raychem/Universal.
Supply, jointing, testing and commissioning of cable jointing kit for 11 KV (Earthed) grade cable for indoor type joint (heat shrinkable) complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm complete all as directed. Make : M - Seal/ 3M /Denson / Raychem/Universal.
M&L Earthing complete with copper earth plate electrode 600×600× 3.15 mm thick, buried directly and preferably vertically in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to copper strip of size 20x3mm (up to 7.5 m in length from earth plate ) by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing with DBs including earth work and excavtion in any type of soil, PCC 1:3:6 type C1 chamber and RCC 1:2:4 type B1 cover 40 mm thick, with 8mm dia steel deformed (TMT bars) reinforcement at 150mm c/c both ways, 20 mm dia GI medium grade pipe for watering, water funnel, testing point etc complete all as specified and directed by Eng-in-charge and testing on completion.
Dismantling of 4 pole structure by disconnecting the GOD,DO fuse,lighting arrestor and jumper by loosening nuts and bolts and lowering them safely with the help of chain pulley and dismantling cross arms of MS channel or angle section and stay assembly,etc and lowering it all accessories and making good to the disturbed area complete all as directed by Eng-in-charge. Note : The unit rate quoted shall be deemed to be included for necessary T&P,Crane,Vehicles,etc all as direcred by Eng-in-charge.
MURALI KRISHNA ASSOCIATES
GAGANSRI INFRA
UV POWER TECH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .