Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.7 LAccepted-AOC 26 740 35 KESARI HOUSE NEAR RICO INDUSTRIAL AREA DEVIPURA SIKAR RAJASTHAN 332 001 | SIKAR | SIKAR | RAJASTHAN | 332001 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹47.1 L+₹10.2 L (27.7%)Rejected-Finance | L2 | Rejected-Finance other than L1 | |
| 3 | L3₹47.5 L+₹10.7 L (29.0%)Rejected-Finance DOOR NO 68 2963 E3 MANDAKKARA ROAD AYYAPPANKAVU ERNAKULAM KERALA 682 018 | ERNAKULAM | ERNAKULAM | KERALA | 682018 | L3 | Rejected-Finance other than L1 |
Tender Value
₹37 L
EMD Value
₹74,000
Closing Date
10 Sept 2024, 6:00 pmClosed
CWE AF TRIVANDRUM
CWE AF TRIVANDRUM HQ SAC IAF COMPLEX AKKULAM THURUVIKKAL POST TRIVANDRUM 11
Provn of mobile transformer 500KVA trolley mounted with LT HT cable and augmentation of HT Electric distribution system by replacing GOS with RMU at HQ SAC U under GE AF Trivabdrum
2024_MES_663992_1
CWE(AF)/TVM/82491 E8 Mobiletransformer at GE AF TVM
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Trivandrum
Class D Category b(ii)
7 documents required · 7 mandatory
₹500
GE AF Trivandrum
₹74,000
Yes
16 Oct 2024
4 Jul 2024
14 Sept 2024
4 Jul 2024
10 Sept 2024
18 Jul 2024
5 Jul 2024 - 10 Jul 2024
Amount
SCHEDULE 'A'
Supply, & installation, testing and commissioning out door type, trolley mounted step down transformer, 11KV/ 433 Volts ( At no load) AC 3 ph, 50 Hz, energy efficient level - 2 confirming to IS 1180 (Part-I), capacity 500 KVA , core type, double copper wound, oil immersed, naturally cooled, oil natural- air -natural (ONAN), Class A insulation lamination CRGO(M-4 grade) with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side( LV) in accordance with vector group Dyn- 11 with natural brought out on secondary side (LV) and having tappings at +/- 2.5% to +/- 5% on HV side to be changed by means of hand operated off load tap changer gear. The maximum temperature rise should not exceed 45 degree C (IS 1180) in oil and 55 degree C in HV /LV windings when measured by resistance method after continuous full load run on an ambient temp of 45 degree C and shall also comprise of the following:- (a) 01cable box chamber on HV side( primary) consisting of 03 Nos bushing with copper rods complete with nuts and washers, with 01 No cable gland suitable for HT cable. (b) 01 cable End box on LV side( secondary) consisting of 04 Nos bushing with copper rods complete with nuts and washers, with 01 No cable gland suitable for LT cable. (c ) Oil conservator tank with filter type drain plug and oil level gauge.
(d) Dehydrating breather with first fill of silica gel. (e) Explosive vent, thermometer pocket on tank cover, oil level gauge, oil drain filter valve, lifting hucks, oil filling hole with cap/ plug with connection plate complete. Air release valve plug at four Nos plate soil cast steel detachable rollers. (f) 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120 degree C for monitoring temperature of oil (OTI) and winding (WTI) with metal guard having maximum perimeter temperature reading indicator with resetting device. (g) 02 Nos earthing terminals on tank cover to facilitate fixing of 50 x6 mm GI earth strip for earthing of body. Rating plate and terminal marking plate. (h) Extra bushing for natural, in the LT cable box for providing independent set of earthing for natural. (j) First fill of new and unused transformer oil, IS- 335 marked (make: savita / Power Oil) filtered and tested up to 60 KV die electric strength at 2.5 mm air gap between testing electrodes.
Supply and fabrication of 04 wheelers trolley for 500 KVA transformer fabrication with C channels frame work in outer body with carrying capacity of 5Ton with toiling hook in front side and full disc rotation handbreak mechanism sockabsoberbs,leaf set etc.with suitable hub and disc fitted in MS square rod and complete with MS based plate anof 5 mm thick in top along with trolley along with power cable and earthing materials(both side copper lugs fitted flexible copper brraded jumper minimum 04 meter each for earthing for 04 Nos )Storage space in storage with locking system fencing, hand jackie 04 Nos, wheels spanners and hand air pump etc. including of 02 coat of synthetic enamelled paint over a coat of anti corrosive paint complete as per directed. Note: Quoted rates are inclusive of complete trolley with suitable size tyre with tube, capable to wear the load of 500KVA including trolley's weight
Supply install testing and commissioning of of RMU 11kV, 630A, 21kA, Motor operated, Compact, Outdoor, both side Extensible, Non drawout type, + CCVV+ (2nos. Load Break Switch (OD) incomer and 2Nos.Vaccum Circuit Breaker (VL) Outgoing) SAFEPLUS-XT compact gas insulated Ring Main Unit, All live parts enclosed in a robotically welded stainless steel tank of IP 67 class of protection. With Battery and Battery all as specified including necessary foundation as per OEM / KSEB standards . STANDARDS AND MECHANICAL DATA "Metal Enclosed switchgear: IEC 62271-200, General Purpose switches: IEC 60265-1, Disconnectors and Earthing switches: IEC 62271-102, Switch Fuse Combination: IEC 62271-105, Circuit Breakers: IEC 62271-100, Common clauses: IEC 60694, Pressure of SF6 gas: 1.4 bar at 20 °C Cable bushings: DIN 47636 Temperature class: -25 °C - +40 °C Outdoor Degree of protection: - SF6 tank: IP 67 - Front cover: IP 2X - Cable cover: IP 3X - Enclosure: IP54 Busbars: 240 mm2 Cu Earth bar (external): 120 mm2 Cu - Bolt dimension: M10 Thickness of Stainless Steel Tank: 2.5 mm Colours: - Front cover: RAL 7035 - Side and cable cover: RAL 7035 - Enclosure: IS 632"
ELECTRICAL DATA – 12 kV - 28kV-1min "Nominal voltage: 11 kV Rated frequency: 50 Hz Rated current busbars: 630 A Rated current cable switch disconnector: 630 A Short time withstand current: - Cable switch disconnector with interface C(400-bolt) bushing: 21 kARMS 3 sec. - Vacuum circuit breaker with interface C (400-bolt) bushing: 21 kARMS 3 sec. Rated current for transformer T-off:630 A Impulse withstand voltage: To earth and between phases: 75 kV Insulation level: - Power frequency 1 min: 28 Kv A01 C,A02 C– Load Break Switch Module Safe plus C is a cable switch module with a three-position load break switch and earthing switch, busbars, interlocking and earth bar. 1 Safe plus type C: Cable switch 12kV, 630A 1 Manometer (Only in A01 C) with Remote Gas monitoring 1 Snap action mechanism for Motor operation; Control Voltage 24V DC 1 Cable cover standard with Interlocking 1 Cable bushings interface C (400 bolted), 630 A, standard 1 Capacitive voltage indication fixed type VPIS 9-15 kV 1 Aux. switch for load break switch position 2NO + 2NC 1 Cable support bars, standard for 1-way unit 3 Terminal Protector (BOOT) 1 Short Circuit + Earth Fault Indicator (Only in A01 C Module)
A01 C,A02 C– Load Break Switch Module Safe plus C is a cable switch module with a three-position load break switch and earthing switch, busbars, interlocking and earth bar. 1 Safe plus type C: Cable switch 12kV, 630A 1 Manometer (Only in A01 C) with Remote Gas monitoring 1 Snap action mechanism for Motor operation; Control Voltage 24V DC 1 Cable cover standard with Interlocking 1 Cable bushings interface C (400 bolted), 630 A, standard 1 Capacitive voltage indication fixed type VPIS 9-15 kV 1 Aux. switch for load break switch position 2NO + 2NC 1 Cable support bars, standard for 1-way unit 3 Terminal Protector (BOOT) 1 Short Circuit + Earth Fault Indicator (Only in A01 C Module)
A03,– Vacuum Circuit Breaker Module Safe plus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earth bar and stored spring energy mechanism. 1 Safe plus type V: Vacuum circuit breaker 12kV, 630A 1 Bushings outside cone interface C for connection of external busbars 1 Stored energy mechanism for Motor operation; Control Voltage 24V DC 1 Cable cover standard with Interlocking 1 Self-Powered O/C and E/F protection relay with RS485 port C&S Make 1 Cable bushings interface C (400 bolted), 630A 1 Aux. switch for vacuum circuit breaker position 2NO + 2NC 1 Capacitive voltage indication fixed type VPIS 6-12 kV 1 Cable support bars, standard for 1-way unit 3 Ring core current transformer type 100/1 A, 2.5VA, 5P10 for Protection
A04,– Vacuum Circuit Breaker Module Safe plus V is a Vacuum circuit breaker module with vacuum circuit breaker, three position isolator/earthing switch, busbars, interlocking, earth bar and stored spring energy mechanism. 1 Safe plus type V: Vacuum circuit breaker 12kV, 630A 1 Bushings outside cone interface C for connection of external busbars 1 Stored energy mechanism for Motor operation; Control Voltage 24V DC 1 Cable cover standard with Interlocking 1 Self-Powered O/C and E/F protection relay with RS485 port C&S Make 1 Cable bushings interface C (400 bolted), 630A 1 Aux. switch for vacuum circuit breaker position 2NO + 2NC 1 Capacitive voltage indication fixed type VPIS 6-12 kV 1 Cable support bars, standard for 1-way unit 3 Ring core current transformer type 100/1 A, 2.5VA, 5P10 for Protection Additional equipment delivered separately or mounted in respective panel. 1 Operating handle 1 2 x 12 V DC Battery and Battery charger.
Supply and fix cable jointing kit for 11 KV grade cable for outdoor straight through joint Heat shrink type complete with jointing material and accessories suitable for 3 core XLPE armoured, Al conductor cables, earthed system of size 120 sqmm -185 sqmm all as specified and as directed
Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm -185 sqmm all as specified and as directed
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 150 sqmm all as specified and as directed
Excavation in trenches in hard/dense soil not exceeding 1.5m wide and not exceeding 1.5 metre in depth for laying of cable and not exceeding 10 Sqm on plan for poles, struts, stays etc. and not exceeding 1.5 m in depth and getting out complete all as specified.
Returning and filling of excavated soil up to a depth of 30 cm after riddling the excavated soil for Cushioning of cable and refilling of trench with normal excavated soil all as specified and directed :-
Removing excavated material to a distance not exc 50 mtrs and depositing where directed at a level n.exc 1.5 mtr above the starting point.
Supplying and laying un-reinforced precast concrete cable cover, class HVP,type 1 with peak, size 300mm x 180mm x 40mm
Supply and lay in trenches/under roads/crossings or fixed to wall/pole, GI tubing light grade of 80 mm dia for protection of UG cables including taking out old unserviceable pipes and remove from site :- Note : Payment for excavation and earth work shall be paid for separately under relevant items of Schedule.
Supply, laying and testing cable XLPE insulated , screened , PVC bedded, galvanized steel strip or wire armoured , electric power cables (heavy duty ) with stranded aluminium conductor , 11kV grade of size 3 core 120 Sqmm
Supply, laying and testing cable XLPE insulated , screened , PVC bedded, galvanized steel strip or wire armoured , electric power cables (heavy duty ) with stranded aluminium conductor , 11kV grade of size 185 sq mm 3 core
Supply, laying and testing cable XLPE insulated , screened , PVC bedded, galvanized steel strip or wire armoured , electric power cables (heavy duty ) with stranded aluminium conductor , 11kV grade of size 240 sq mm 3.5 core
Supply, laying and testing cable XLPE insulated , screened , PVC bedded, galvanized steel strip or wire armoured , electric power cables (heavy duty ) with stranded aluminium conductor , 11kV grade of size 150 sq mm 3 core
M&L for earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm thick, buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with top edge of the plate not less than 1.5 mtrs below normal ground level, connected to 20 x 3 mm copper strip as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 in SSR connected to earting test point all as specified or indicated complete with excavation & earth work, PCC pit in cement concrete 1:2:4 type B1 with CI cover plate having suitable handle (10mm MS Rod) 20mm dia GI medium grade watering pipe with GI funned with wire mesh 40mm bore GI pipe (light grade) for protection of earth lead conductor all as directed and testing on completion.
Dismantling of 4 poles structure made of concrete poles alongwith GOS/DO / MS Brazings/ insulators any type and taking old old earthing pit & removing debris form site all as specified and making good existing surfaces after removing the HT pole from its existing position and shifted out of the site / station.
Taking electric supply shutdown from KSEBL and remove carefully the existing defective CT/PT Unit from over head structure and HT TOD meter from Meter Box depositing to MES Store Yard Note : The quoted rates are inclusive of the T&P , labour and safety equipments including electric supply shutdown, disconnecting all 11KV connections and HT ST joint kit of suitable size for existing cable etc.
Supply, Fix & Connect 11 KV Cast Resin Current Transformer (CT) suitable for indoor applications Ratio 10 /5A, Class 0.2S, Burden 10 VA as per IEC 61869 - 2:2012, BIS 16227-2 and as per KSEBL Specifications IL12/28/75 KV ,STR :13.1 KA/sec
Supply, Fix & Connect 11 KV/110 V (3 Phase ) Cast Resin Potential Transformer (PT) suitable for indoor applications Class : 0.2, Burden 25 VA as per IEC 61869 -3:2011, BIS 16227-3 and as per KSEBL Specifications IL12/28/75 KV , VF-1.2 Cont
Supply, Fix & Connect HT 11 KV TOD Meter 3 phase, 4 wire, (10/5A, 11 KV/110V)/( 15/5A, 11 KV/110V), Class : 0.2S, DLMS type and , including fixing arrangements/ necessary wiring materials and Test Terminal Box if any as per site requirement complete as per KSEB specifications. Make : L&T Note: 02 TOD meter of different range as mentioned in Description
Testing of HT new CT/PT Unit at TMR Division, Trivandrum by KSEBL and necessary sealing including Testing Fees, transportation to & fro, loading, unloading complete
Testing of HT new TOD Meter at TMR Division, Trivandrum by KSEBL and necessary sealing, including Testing Fees, transportation to & fro, loading, unloading complete
Supply, Fix & Connect 11 KV Cast Resin Current Transformer (CT) suitable for indoor applications Ratio 15 /5A, Class 0.2S, Burden 10 VA as per IEC 61869 -2:2012, BIS 16227-2 and as per KSEBL Specifications IL12/28/75 KV ,STR :13.1 KA/sec
Supply, Fix & Connect 11 KV/110 V (3 Phase ) Cast Resin Potential Transformer (PT) suitable for indoor applications Class : 0.2, Burden 25 VA as per IEC 61869 -3:2011, BIS 16227-3 and as per KSEBL Specifications IL12/28/75 KV , VF-1.2 Cont
Supply, install, testing and commissioning of outdoor type totally enclosed water proof HT Metering Panel consisting of the following :- a) Arrangements to measure the parameteres from 1No. 11 KV/110 V (3 Phase ) Cast Resin Potential Transformer (PT) suitable for indoor applications Class : 0.2, Burden 25 VA as per IEC 61869 -3:2011, BIS 16227-3 and as per KSEBL Specifications IL12/28/75 KV , VF-1.2 Cont. b) Arrangements to measure the parameteres from 3Nos. 1Phase 11 KV Cast Resin Current Transformer (CT) suitable for indoor applications Ratio 5 /5A, Class 0.2S, Burden 10 VA as per IEC 61869 -2:2012, BIS 16227-2 and as per KSEBL Specifications IL12/28/75 KV ,STR :13.1 KA/sec c) 1No. Emergency push button, 1No. LBS ON & OFF indication & control MCBs. d) Bottom entry cable chamber for incoming & outgoing. e) 1No. Test terminal block with complete metering wiring and provision for mounting HT TOD meter. f) 2No. Space heater with thermostat. g) 1Set 50x10mm Alu. Bus bar with colour coded heat shrinkable sleeves, DMC supports & sealing bush etc. All the above assembled in powder coated CRCA sheet steel enclosure with sealing facility and including necessary Foundation as per KSEB standards .
Fixing only TOD meter taken out from items ser No 19 including internal connection.
Total of Schedule 'A'
ABM ELECTRICALS (BID ID -3081263)
ELAN ENGINEERS (BID ID -3091598)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .