Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.8 LAccepted-AOC D NO 35 14 13 1 RP PETA GAVARA KANCHARAPALEM VISAKHAPATNAM 530008 | VISAKHAPATNAM | VISAKHAPATNAM | ANDHRA PRADESH | 530008 | L1 | Accepted-AOC being lowest bidder | |
| 2 | L2₹33.5 L+₹48,278 (1.46%)Rejected-Finance FLAT NO 304 SN TOWERS JAGANNADHAPURAM JUNCTION AKKAYYAPALEM VISAKHAPATNAM 530 016 | VISAKHAPATANAM | ANDHRA PRADESH | 530016 | L2 | Rejected-Finance not being L1 bidder | |
| 3 | L3₹34.6 L+₹1.6 L (4.77%)Rejected-Finance MIG 330 MADHAVADHARA VUDA COLONY VISAKHAPATNAM 530 018 | VISAKHAPATANAM | ANDHRA PRADESH | 530018 | L3 | Rejected-Finance not being L1 bidder | |
| 4 | L4₹36.2 L+₹3.1 L (9.49%)Rejected-Finance | L4 | Rejected-Finance not being L1 bidder | |
| 5 | L5₹36.6 L+₹3.5 L (10.6%)Rejected-Finance 15 15 KHERIYA BHAN PURANI CHAWANI GWALIOR GWALIOR GWALIOR MADHYA PRADESH 474010 | GWALIOR | MADHYA PRADESH | 474010 | L5 | Rejected-Finance not being L1 bidder |
Tender Value
₹44 L
EMD Value
₹88,000
Closing Date
27 Jun 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Garrison Engineer Utility-I Visakhapatnam
Garrison Engineer Utility-I Near Samudrika Naval Base Post Visakhapatnam -530 014
SPL REPAIR FOR REPLACEMENT OF 4 POLE AND 2 POLE STRUCTURES WITH RMUS AT MEGHADRIGEDDA, WATER SUPPLY STATION UNDER GE (U-I) VISAKHAPATNAM
2024_MES_658180_1
8655/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Garrison Engineer Utility-I Visakhapatnam
As per NIT
6 documents required · 6 mandatory
₹500
Garrison Engineer Utility-I
₹88,000
Yes
16 Jul 2024
6 Jun 2024
29 Jun 2024
6 Jun 2024
27 Jun 2024
21 Jun 2024
Amount
Supply, install, testing & commissioning of 3 way RMU ( 2 incoming + 1 outgoing), 12 KV, 630 A, outdoor, extensible type, SF6 insulated, consisting of 02 Nos, 630A VCB, fixed, non draw out type as incoming and 01 No, 630A VCB as outgoing, conforming to following specifications:- (A) RMU shall be floor mounted, 11 KV, 630 Amps, 21 kA for 3 Seconds, SF6 Insulated, Motorized, Outdoor extensible type, RMU with Air Insulated Bus Connected Metering unit, Type tested in line with latest IEC Standards, suitable for operations at a height up to 1000 Meters above sea level and Ambient Temperature range from 5ºC to 50ºC without any de-rating. Switchgear and Busbar shall be contained in a Stainless Steel Enclosure [made out of min 2 mm thick SS 304 Grade sheet] filled with SF6 at 0.3 Bar [300 hPa] Relative Pressure, RMU Tank shall provide Full Insulation and Switchgear shall be insensitive to the environment with Degree of Protection of IP67, Switchgear Operating Mechanism shall have an IP2X Protection and Cable Chamber shall have IP3X Protection, Outer Enclosure shall be IP 54 type tested, Powder Coated with Pure Polyester Based Paint, suitable for site installation conditions, Accidental Overpressure due to an Internal Arc is limited by the opening of the safety valve, at the bottom of the metal enclosure, away from the operator, Plug in type of extensibility must be provided and coupling busbar should not be exposed to air to avoid oxidation of busbars. Extension of cubicle shall require 450mm to handle and the gap between the coupled RMU’s must be within 10mm. Make of RMU / VCB / Vacuum Interrupter / Relays / FRTU : ABB / Transguard / Siemens / Schneider (Contd...)
(B) Each Vacuum Circuit Breaker [VCB] shall comprising of the following:- [i] 11 KV, 630 Amps, 21 kA / 3s, 3 Pole Motorized VCB (Non draw out type) with 3 pole manual disconnector and 3 pole manual earth switch, Motorized Spring Assisted Mechanism and Series Trip Coil – 1 No. [ii] Self Powered Relay with O/C, S/C, E/F Protection. Relay shall have a Front USB for Laptop Interface, LCD Display, 10 Event Records, 5 Fault Records, min 2 setting group and keypad for setting parameters for the relay – 1 No [iii] Resin Cast ring core Protection CT, Plate mounted type : 100-50/1A, 5P10, 2.5 VA-01 Set. [iv] Resin Cast ring core Metering CT, Plate mounted type : 100-50/1A, Cl. 1.0, 2.5 VA-01 Set. [iv] Live Cable Indicator with indications at the Front and Three Inlets to check the Synchronization of Phases – 1 No [v] Making capacity - 52.5 kAp [vi] Cable Termination Bushing suitable for up to 1 Run, 3 Core, 240 Sq.mm, XLPE Cable [vii] Cable Termination Cover Boots [Push on type] [viii] Circuit Breakers shall have Two Positions: Open or Disconnected and Closed. A separate and independent 3 Position Earthing Switch and disconnector shall be fitted to open and earth the cables in such way that interlocks prevent all unauthorized operations. An operating mechanism shall be used to manually close the circuit breaker and charge the mechanism in a single movement. An independent mechanism shall be fitted for the 3 Positions Earthing Switch and Disconnector Circuit breaker shall be fitted with a local system for manual tripping by an Integrated Push Button. There shall be no automatic reclosing. Circuit Breaker shall have a min of 2000 Mechanical and Electrical Operations and 50 Nos Short Circuit Operations, Disconnector and Earth Switch shall have a minimum of 1000 [M1] Mechanical Operations, 100 Electrical Operations at rated current. (C) Air Insulated Bus Connected Metering Unit comprising the following:- [i] Air Insulated Enclosure with necessary Bus Connection – 1 No [ii] PT 11KV / √3 / 110V / √3, 50 VA, Class-1.0 – 1 Set [iii] Multi Function Meter, Digital Type [Displaying A, V, PF, Hz, KVA, KW, KVAR, KWH, KVARH etc. Class 1.0 / 0.5] with RS485 Port for Communication in Modbus Protocol. - 01 Set (Contd...)
[iv] R / Y / B Indicating Lamps – 1 Set [v] 11 KV / 230V AC, Class 1, 500VA Control Transformer – 1 No [vi] Battery and Battery Charger, 12 Ah, [I/P-230V AC, O/P - 24V DC] – 1 No (D) Space Heater with thermostat (E) 2 x 8 Window Alarm Annunciator and Hooter Notes:- [a] An operator situated in front, lateral and rear [A-FLR 21 kA – 1 Sec, Downwards Exhaust, for Tank as well as Cable Compartment] of the RMU Switch board during an internal fault shall not be exposed to the effects of Arcing. Internal Arc Type Test Report for IAC AFLR 21 kA for 1 Sec for both Tank & Cable Box shall be for minimum 3 Way / 3 Function RMU. [b] All operations shall be from front of the RMU, including access to cable bushings. Bushings along the sides or the rear of the RMU are not acceptable. [c] Construction of Plinth / Foundation for 11KV RMU: The rate quoted is deemed to be including the cost of Plinth / Foundation and nothing extra shall be paid on this account. The foundation shall consists of Two Parallel Brick Walls built using bricks straight or curved on plan to any radius built in Cement Mortar 1:6 of length 2.10m, of suitable thickness and height as per the manufacturer’s instructions over PCC Concrete Bed of 150mm thick in PCC 1:4:8, Type D-2, using 40mm graded stone aggregate over 150mm thick Hardcore of gauge not exceeding 63mm of broken stones or boulders, deposited, spread and leveled in layers not exceeding 15 cm thick watered and rolled, over 150mm thick Sand Bed, rendering to brick surfaces, 15 mm thick in Cement Mortar 1:4, and finishing the top surface even and smooth without using extra cement, applying Three coats of white washing including earthwork excavation of pit size 2.10 X 1.20 X 0.60 Metres complete all as per manufacturer’s recommendations, as specified and as directed. [d] The rate quoted is also deemed to be including the cost of disconnection of HT Cables up to 3 Core, 240 Sq.mm from existing 2 Pole / 4 Pole Structures, removing of cable loop and reconnection to RMU after new end termination complete all as specified and as directed by the Engineer-in-Charge. [e] End termination joints shall be measured and paid separately. [f] The make of RMU / VCB / vacuum interrupter / Relays offered shall be of same make. Different makes shall not be accepted.
All as per Sl Item No 1.00 to 1.02 above but 5 way RMU (1 incoming + 4 outgoing) including epoxy resin cast CT plate mounted type : 100-50/1A with rating class 5P10, 2.5 VA for protection CT and Cl 1.0, 2.5 VA for metering CT -01 Set
M&L cable jointing kit for 11 KV (Earthed) grade 3 core XLPE armoured aluminium conductor cable of size 185 sqmm for straight through, heat shrink type joint with jointing material and accessories complete all as specified and directed. Note:- (i) The cost of excavation is deemed to be included in the unit rate quoted against this item. Make:- 3M / Denson / Raychem
M&L cable jointing kit for 11 KV (Earthed) grade 3 core XLPE armoured aluminium conductor cable of size 185 sqmm for indoor termination, heat shrink type joint complete with jointing material and accessories complete all as specified and directed. Make:- 3M / Denson / Raychem
Dismantling and taking down existing 4 pole structure complete including ACSR conductors, Gang operated air break switches, lightning Arrestors, DO fuses, cross arms, insulators and all other accessories, breaking concrete foundation, removing debris outside MD Land and making good the disturbed surface to match with the existing, complete all as specified and as directed.
All as per Sl Item No. 5.00 above but existing 2 pole structure.
M&L earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6 mm thick buried directly in ground in vertical position (earth pit not less than 2.25 m deep below the normal ground level) with top edge of the earth plate not less than 1.5 m below normal ground level, connected to earth lead of galvanised iron strip 32 x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel, all as shown in electrical plate No. 3 of SSR Part-I connected to earthing test point complete all as specified and directed. Note:- The unit rate shall also include for earth work in any type of soil, PCC 1:3:6 type C1 chamber, RCC 1:1.5:3, type A1 cover slab, 50 mm thick reinforced with 8 mm dia TMT bar @ 140 mm C/C both ways, 10 mm dia plain bar lifting handle embedded in cover slab, Main earthing lead from earth electrode to test point upto 7.5 m length, 20 mm bore medium grade GI watering pipe, 40 mm bore GI light grade earth lead protection pipe, funnel, wire mesh, copper lugs, charcoal and common salt in alternate layer etc.
MURALI KRISHNA ASSOCIATES
M/s.DSRK CONSTRUCTIONS
UV POWER TECH
AUTOMATION AND SWITCHGEAR PANELS
LAKSHMI SAI CONSTRUCTIONS
M/S SRI VENKATA BHAVANI CONSTRUCTIONS
AYYAPPA CONSTRUCTIONS
PRAHJVAL CONSTRUCTIONS
MONITOR ENGINEERING WORKS
suresh electricals
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .