Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹21.8 LAccepted-AOC H1 7 8 IT PARK ROAD NO 4 IPIA KOTA RAJ 324005 | KOTA | RAJASTHAN | 324005 | 1 | Accepted-AOC Lowest Bidder | |
| 2 | 2₹24.2 L+₹5,622 (0.23%)Rejected-Finance | 2 | Rejected-Finance Not the Lowest Bidder | |
| 3 | 3₹26.6 L+₹2.5 L (10.2%)Rejected-Finance | 3 | Rejected-Finance Not the Lowest Bidder | |
| 4 | 4₹27.0 L+₹2.8 L (11.7%)Rejected-Finance | 4 | Rejected-Finance Not the Lowest Bidder | |
| 5 | 5₹27.2 L+₹3.1 L (12.9%)Rejected-Finance | 5 | Rejected-Finance Not the Lowest Bidder |
Tender Value
₹24.5 L
EMD Value
₹49,000
Closing Date
26 May 2021, 6:00 pmClosed
Garrison Engineer Kota
Opp Circuit House, Station Road, Kota - 324001
SPECIAL REPAIR/REPLACEMENT OF PUMPS AND CONNECTED WORKS, POWER FACTOR CONTROL PANEL, EARTHINGS AT VARIOUS E/M INSTALLATIONS AND SPL REPAIR TO BUILDING NO. P-461 (MP HALL) OF CHILDREN SCHOOL AT MILITARY STATION KOTA
2021_MES_441201_1
8518/E8
Open Tender
Electrical and Maintenance Works
Item Rate
183 days
Kota
Class E category b(i)
7 documents required · 7 mandatory
₹500
GE Kota
₹49,000
Yes
21 Jun 2021
7 May 2021
28 May 2021
7 May 2021
26 May 2021
21 May 2021
8 May 2021 - 14 May 2021
Amount
Supply, install, commissioning and testing of open well submersible pump set, electric driven, 415 volts, 3 phase, 50 Hz supply, 36 M head, 13.4 Litre per second discharge (capacity not less than 10 HP), suitable for star delta connection with and including fully automatic star delta starter suitable for pump with accessories like contactor, protection relay range 9-14 Amps etc, complete all as specified and directed.
Supply, install, commissioning and testing of monoblock pump set, electric driven, 415 volts, 3 phase, 50 Hz supply, 18 M head, 7.60 Litre per second discharge (capacity not less than 3 HP), suitable for star delta connection with and including fully automatic star delta starter suitable for pump with accessories like contactor, protection relay range 4-7 Amps etc, complete all as specified and directed.
Supply, install, commissioning and testing of monoblock pump set, electric driven, 415 volts, 3 phase, 50 Hz supply, 28 M head, 6.40 Litre per second discharge (capacity not less than 5 HP), suitable for star delta connection with and including fully automatic star delta starter suitable for pump with accessories like contactor, protection relay range 6-10 Amps etc, complete all as specified and directed.
Supply, install, commissioning and testing of monoblock pump set, electric driven, 415 volts, 3 phase, 50 Hz supply, 40 M head, 9.60 Litre per second discharge (capacity not less than 10 HP), suitable for star delta connection with and including fully automatic star delta starter suitable for pump with accessories like contactor, protection relay range 6-10 Amps etc, complete all as specified and directed.
Lifting of existing unserviceable submersible pump set of any size/capacity from tube well with all PVC/MS column pipe and Supply, install, commissioning and testing of submersible pump set - 08 stage, electric driven, 415 volts, 3 phase, 50 Hz supply, 32 M head, 12.00 Litre per second discharge (capacity not less than 7.5 HP), suitable for star delta connection with and including fully automatic star delta starter suitable for pump with accessories like contactor, protection relay range 9-14 Amps etc, complete all as specified and directed.
Supply, install, commissioning and testing of centrifugal pump set, electric driven, 415 volts, 3 phase, 50 Hz supply, 57 M head, 19.00 Litre per second discharge (capacity not less than 25 HP), suitable for star delta connection with and including fully automatic star delta starter suitable for pump with accessories like contactor, protection relay range 20-32 Amps etc, including providing foundation of the pump set as per manufacturer's instructions, complete all as specified and directed.
Supply and installing pressure booster pump set, 1 HP, 0.75 KW, pressure range 2.2-3.6 kg/Sqcm, auto on-off system, complete with all accessories for fixing, complete all as specified and directed.
Supply, installing, testing and commissioning chlorine pressure feed high pressure single head gear motorised adjustable dozing pump 0-100 PSI (Pressure upto 0-7 Kg), gear motor having output 2U.S. GPD to 40 U.S. GPD, power 230 volts, 50 Hz, RPM-44 with accessories including lead tubing, connecting nuts, injection check valves, clay weight and ferrules, complete all as specified and directed.
Supply and installing altoch dozing system consisting of 40 Litre-100 Litre PE/FRP tank with lid and level gauge alongwith agitator with shaft and blade in SS - 316 (FRP/Epoxy coated/plastic mounted on tank, complete all as specified and directed.
S&F in replacement PVC insulated and PVC sheathed, 1100 volts grade flat type submersible cable with multistranded copper conductor, complete all as specified and directed for the following cross sectional area: - 3 core 6 Sqmm
3 core 10 Sqmm
S&F of PVC insulated and PVC sheathed multicore bright annealed bare copper conductor, 3 core, 2.5 Sqmm, heavy duty cables for voltage grade 1100 volts conforming to IS694:2010 including heavy grade PVC conduit for carrying cable with all fixing arrangement such as clamps, screw, washers etc on wall/surface, complete all as specified and directed.
S&F of HDPE pipes of 75 mm bore, PE-63 having minimum withstand pressure 6Kg/Sqcm and conforming to IS-4984:1995, suitable for submersible pump, complete all as specified and directed.
S&F MS foot valve of 100 mm bore, including rubber seal, nuts, bolts and washers etc, complete all as specified and directed.
Disconnecting and dismantling of existing unserviceable APFC panel and Supply, installation, testing and commissioning of automatic power factor corrector (APFC) panel for 3 phase, 415 volts and 50 Hz system, capacity 100 KVAR with incoming MCCB of capacity 200 Amps 3 pole, 50 KA rating, complete all as specified and directed.
Disconnecting and dismantling of existing unserviceable APFC panel and Supply, installation, testing and commissioning of automatic power factor corrector (APFC) panel for 3 phase, 415 volts and 50 Hz system, capacity 50 KVAR with incoming MCCB of capacity 100 Amps 3 pole, 50 KA rating, complete all as specified and directed. Note for item Nos 15.00 & 16.00: It shall be responsibility of the contractor to maintain power factor of the panels more than 0.95 for a period of two years from the date of completion of the work. If power factor is recorded less than 0.95, penalty @ Rs. 2000.00 per day or part thereof to this effect shall be imposed on the contractor untill the power factor is again maintained more than 0.95 by the contractor.
Supply and laying in replacement, LT 1100 volts grade UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor, 185 Sqmm 3.5 core, laid in trenches/ducts, fixed on wall/inside panel, drawn through pipe all as specified and directed.
Supply and laying in replacement, LT 1100 volts grade UG cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor, 95 Sqmm 3.5 core, laid in trenches/ducts, fixed on wall/inside panel, drawn through pipe all as specified and directed.
Repair to existing unserviceable APFC panels, rewiring of the circuits with appropriate size of copper cable including replacement of unserviceable parts of the panels, complete all as specified and directed. (Supply only of parts of APFC Panels shall be measured and paid separately under appropriate items)
Supply only MPP heavy duty capacitor 20 KVAR
Supply only MPP heavy duty capacitor 10 KVAR
Supply only MPP heavy duty capacitor 5 KVAR
Supply only MPP heavy duty capacitor 2 KVAR
Supply only CT ring type having ratio 100/5 for APFC panel one each for each phase of RYB
Supply only power capacitor switching contactor MO C type having operating voltage 415 volts, 3 phase, 50 Hz and 20 KVAR
Supply only APFC relay 12 stages
Supply only APFC relay 8 stages
Supply only MCB 32 Amps, triple pole
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5M in depth and getting out in hard/dense soil for laying of under ground cables/pipes and foundation etc, complete all as specified and directed.
Returning, filling in soil, including spreading, levelling, watering and well ramming in layers not exc 25 cm. complete all as specified and directed.
Removing excavated material (soil) n exc. 50m distance and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and directed.
M&L dry clean Sand filling in trenches around underground cables for earth cushion, complete all as specified and directed. (Depth of sand shall be measured after punning).
M&L for pulverized fuel Ash-lime bricks (Fly ash bricks - non modular size), class 10, laid dry and flat adjoining each other over sand cushion in trenches as protection to UG cable, complete all as specified and directed.
M&L for Earthing with galvanized steel earth plate electrode of size 600 mm x 600mm x 6.0 mm, buried directly in ground (earth plate not less than 2.25 Mtr below normal ground level) connected to galvanized earth strip of 32x6 mm dia by means of bolts, buts, check nuts and washers of galvanized iron on steel including 40 mm bore light grade GI tubing for protection of earth strip, MS sheet metal funnel with wire mesh, watering pipe medium grade 20 mm bore, charcoal or coke and common salt in alternative layer of 15 Cm compacted thickness all around the electrode with concrete earth pit of PCC 1:3:6 type 75 mm thick precast RCC (1:2:4) type B1 pit cover reinfored with 8 mm dia deformed bar and suitable handle made of 10 mm dia round bar including GI earth strip of 32x6 mm size for extension of earth lead and necessary excavation, earth work, in soft/loose soil and disposal of spolis to a distance not exc 50 Mtr and necessary connection and testing complete all as shown in electrical plate No. 3 and complete all as specified and directed. (Earth lead strip and GI protection pipe beyond 7.50 m shall be measured and paid separately)
All as per item 35 above but using 25x4 mm GI earth strip as earth lead, complete all as specified and directed.
All as per item 35 above but using 4 mm dia GI earth wire as earth lead, complete all as specified and directed.
S&F earth continuity conductor or main earthing lead, fixed to walls on batten of recess or chases or buried in ground or drawn in existing couduit or fixed tompoles or any other indicated situation 4 mm dia Galvanised iron earth wire, complete all as specified and directed.
All as per item 38 above but 25x4 mm GI earth strip, complete all as specified and directed.
All as per item 38 above but 32x6 mm GI earth strip, complete all as specified and directed.
Taking down cement plaster any description/thickness on brick or stone walls etc including raking out joints, hacking for key, scrubbing down with water etc, complete all as specified and directed.
Demolition of cement concrete (unreinforced) of any description and and in any position not otherwise specifically provided for and removing rubbish from premises, complete all as specified and directed.
M&L for 25mm thick plain cement concrete 1:2:4 type B-0 (using 12.50 mm graded stone aggregate) as in flooring/sub base finished rough to receive floor finishes/screed, complete all as specified and directed.
M&L PCC 1:4:8 type D-2, using 40 mm graded stone aggregate, as in foundation, filling, mass concreting etc, complete all as specified and directed.
M&L for joint free non skid ceramic coloured tiles, 7 to 8mm thick (square/rectangular) area of each tile exceeding 0.18 Sqm but not exceeding 0.38 Sqm, in floors etc, set and jointed in neat cement slurry and pointed in coloured cement to match the shade of tiles, laid over and including 15 mm thick screed bed in CM 1:6, complete all as specified and directed.
M&L for non skid ceramic coloured tiles, 7 to 8mm thick (square/rectangular) area of each tile exceeding 0.18 Sqm but not exceeding 0.38 Sqm, on vertical surfaces, set and jointed in neat cement slurry and pointed in coloured cement to match the shade of tiles, laid over and including 10 mm thick CM 1:4 bedding, complete all as specified and directed.
M&L for machine cut kota stone slab as in flooring 17 to 22 mm thick and jointed with grey cement slurry mixed with pigment to match the shade of the slab including grinding, rubbing and polishing, laid over and including 20 mm thick screed bed in CM 1:6, complete all as specified and directed.
M&L for machine cut kota stone slab as in flooring (Except kota stone) and jointed with grey cement slurry mixed with pigment to match the shade of the slab including grinding, rubbing and polishing, laid over and including 20 mm thick screed bed in CM 1:6, complete all as specified and directed. (Kota stone slabs obtained from dismantling shall be reused under this item.)
M&L for machine cut kota stone slab as in skirting, dado, risers etc, 17 to 22 mm thick and jointed with grey cement slurry mixed with pigment to match the shade of the slab including grinding, rubbing and polishing, laid over and including 15 mm thick CM 1:4 backing, complete all as specified and directed.
M&L for rendering 15 mm thick in CM 1:4 on other than fair faces of brick work or stone masonry surfaces, finishing the surface even & smooth without using extra cement, complete all as specified and directed.
Demolition of brick work/stone boulder masonry, built in CM incl all quoins, arches, pillars etc but excluding ashlar facing, dressed stone work and precast concrete articles, complete all as specified and directed.
M&L for cutting out concrete blocks, slabs, brickwork or stone masonry (in alternate course), forming toothings for and bonding new work in mortar into old work, including new materials entering old wall using precast cement concrete blocks made with PCC 1:2:4 type B-1 using 20 mm graded stone aggregate, set in CM 1:4, complete all as specified and directed.
M&L preparation of newly plastered surfaces of walls and applying 1 to 1.5 mm thick wall care putty as per manufacturer's instructions and over it applying two coats of distemper oil emulsion over a coat of primer, complete all as specified and directed.
M&L for applying two coats of cement based paint over a coat of primer on newly plastered surfaces of walls including preparation of surfaces, complete all as specified and directed.
Excavation in post holes (or similar holes) Each n exc 0.50 Cum, getting out, returning filling in and ramming earth or broken rubble mixed with earth around in layers not exceeding 25 cm, watering and removing surplus soil to a distance of n exc 50m and making good surface in soft/loose soil, complete all as specified and directed.
Cutting holes into or through brick walls exceeding one brick but not exceeding two brick thick, built in cement mortor and making good in cement mortor (1:3) or cement concrete (1:2:4) type B1 as required, complete all as specified and directed.
S&F mild steel framed work as in grills, grating etc. with end of bars shouldered and/or riveted, or forged into spikes: framed guard bars: barred iron doors: ladders: frame balusters: walk ways: railing: frame work of water tanks and similar works conforming to Fe-290 Grade-E-165, complete all as specified and directed.
M & L for preparation of new or previously untreated steel surfaces exceeding 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chromate primer, complete all as specified and directed.
M&L brick work with pulverized fuel Ash-lime bricks (old size fly ash bricks), straight or curved on plan exc 6 m mean radius, built in CM 1:6, complete all as specified and directed.
Dismantling of Stone slabs and tiles of any description or thickness in floors etc, laid, bedded and pointed in any mortar, complete all as specified and directed.
M/s Prem Associates
L P Singh and Co.
K B ENTERPRISES
ANNAPURNA ENTERPRISES
TARKESHWAR DASS CONSTRUCTION COMPANY
S.S Enterprises
Pioneer Enterprises
Ganesh Contruction
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .