| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹4.0 CrAdmitted-Finance | -15.00% | ₹4.0 Cr | L1 | Admitted-Finance |
| 2 | L2₹4.3 Cr+₹23.7 L (5.89%)Admitted-Finance | -9.99% | ₹4.3 Cr+₹23.7 L (5.89%) | L2 | Admitted-Finance |
Tender Value
₹4.7 Cr
EMD Value
₹9.5 L
Closing Date
10 Feb 2026, 1:00 pmClosed
Director (Planning and Design), HRBC
ST. GEORGES GATE ROAD (MUNSHI PREM CHAND SARANI) KOLKATA-700 021
Construction of Nonadanga Fire Station at Kolkata district G1 storeyed building with foundation of G3 storeyed building
2026_HRBC_991030_1
HRBC/03/2nd Call/DIRPLDN/25-26
Open Tender
CIVIL WORKS
Percentage
365 days
Nonadanga
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹9.5 L
HRBC BHAVAN
27 Feb 2026
20 Jan 2026
12 Feb 2026
20 Jan 2026
10 Feb 2026
31 Jan 2026
30 Jan 2026
Civil Works
Foundation (Pile & Pile Cap)
Providing Bored Cast-in-situ M25 grade R.C.C. pile in position as per specifications in all kinds of soil including cost of boring using drilling mud to stabilize the bore and flushing the bore of excess mud with freshly prepared drilling fluid by using pumps prior to placing concrete by tremie pipe in one continuous operation and including the cost of all materials and labour for placing of concrete and also including the cost of mobilization and hire charges of all equipment necessary for boring, welding of reinforcement cage as necessary and lowering of reinforcement cage, preparation and placing of concrete, including the cost of concrete but excluding the cost of reinforcement and labour for bending binding etc. complete as per Drawing and Technical Specifications and removal of excavated earth with all lifts and lead upto 1000 m. Work to be executed as per IS: 2911 (Part II Sec 2). Using tripod, winches Pile diameter - 500 mm. (The rate of providing the temporary steel casing up to 3m is included)
Providing MS casing pipe around RCC cast-in-situ bored piles of different diameters in position including cost of all materials, fabrication, handling etc. complete as per direction of Engineer-in-Charge.
Integrity testing of Pile using Low Strain / Sonic Integrity Test / Sonic Echo Test method in accordance with IS 14893 including surface preparation of pile top by removing soil, mud, dust & chipping lean concrete lumps etc. and use of computerized equipment and high skill trained personal for conducting the test & submission of results, all complete as per direction of Engineer-incharge. a) Within 50 km. radius from Raj-Bhavan (50% of total piles)
Performing Vertical load test on single Pile in accordance with IS:2911(Part-IV) by hydraulic jacks on pile/piles with 1.5 times the design load including preparation of the head of piles with concrete of required strength for receiving the jacks with all ancillary arrangements for setting up gauges, construction of suitable platforms, keeping the loads and dismantling and removing all arrangement etc. complete as per IS specification and direction of Engineer-in-charge i) Testing load up to 100 T.
Ordinary cement concrete (mix1:2:4) with graded stone chips (20mm nominal size) excluding shuttering & reinforcement if any, in ground floor as per relevent IS codes. Pakur variety. (Below pile cap )
Cost of empty boring as per specification in all kind of soil for providing RCC cast in situ pile above of cut off level including cost of mobilisation and hire charges of all equipments necedssary for boring using drilling mud to stabilised the bore. Using tripod, winches Pile diameter - 500 mm.
Supplying & laying Polythene sheet (150gm/sqm.) in foundation or in foundation trenches.- For below Pile Cap
Batch Mixed concrete of M 25 Grade with well Graded stone chips of 20 mm nominal size containing designed quantity of cement per Cu. M of Wet concrete produced in computerised batching plant under controlled condition using approved super plasticizer designing concrete mix following I.S 10262 and I.S. 456 transporting the mix with agitation in transit mixer to work site depositing the mix on a platform erected for the purpose at required level of concreting and then placing the mix in its final location of form work compacting and curing the same complete as per specification and direction of the Engineer-in charge including hire charges of computerised batching plant, transit mixer with all accessories vibrators etc. inclusive of all other incidental charges in this connection complete but excluding cost of hire charge of platform and its supporting staging which would be paid through separate item. Consumption of cement will not be less than 300 Kg of cement per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula.Pakur Variety.With approved concrete pump. - For Pile Cap
Hire and labour charges for shuttering with centering and necessary staging upto 4 m using approved stout props and thick hard wood planks of approved thickness with required bracing for concrete slabs, beams and columns,lintels curved or straight including fitting, fixing and striking out after completion of works (upto roof of ground floor). (When the height of a particular floor is more than 4 m the equivalent floor height shall be taken as 4 m and extra for works beyond the initial 4 m ht. shall be allowed for every 4 m or part thereof) Steel shuttering or 9 to 12 mm thick approved quality ply board shuttering in any concrete work - For Pile Cap
Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction. For work in foundation, basement and upto roof of Ground Floor/ upto 4 m. Tor steel Fe 500 (JSW/JSPL/SHYAM/SRMB/BMASL/ELECTROSTEEL/SSL). -For Pile + Pile Cap+Tie Beam
Removal of mud sluge slurry liquid earth obtained during pilling work from the working site and disposal of the same beyond the KMC/Municipal or any suitable area with conformity of MC rules using tanker including loading and unloading the same with piump, clearing the site complete in all respecxt as direction of EIC. For 500 mm pile.
Dismantling RC floor roof beams etc including cutting rods and removing rubbish as directed within a lead of 75m including stacking/bending of steel bars - In Ground Floor including roof- For Pile
Batch Mixed concrete of M 20 Grade with well Graded stone chips of 20 mm nominal size containing designed quantity of cement per Cu. M of Wet concrete produced in computerised batching plant under controlled condition using approved super plasticizer designing concrete mix following I.S 10262 and I.S. 456 transporting the mix with agitation in transit mixer to work site depositing the mix on a platform erected for the purpose at required level of concreting and then placing the mix in its final location of form work compacting and curing the same complete as per specification and direction of the Engineer-in charge including hire charges of computerised batching plant, transit mixer with all accessories vibrators etc. inclusive of all other incidental charges in this connection complete but excluding cost of hire charge of platform and its supporting staging which would be paid through separate item. Consumption of cement will not be less than 300 Kg of cement per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula.Pakur Variety.With approved concrete pump. - For Tie Beam
Earth work in excavation of foundation trenches or drains, in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading or stacking the spoils within a lead of 75 m. as directed. The item includes necessary trimming the sides of trenches, leveling, dressing and ramming the bottom, bailing out water as required complete. Depth of excavation for additional depth beyond 1,500 mm. and upto 3,000 mm. but not requiring shoring. -For Pile Cap+Tie Beam
Hire and labour charges for shuttering with centering and necessary staging upto 4 m using approved stout props and thick hard wood planks of approved thickness with required bracing for concrete slabs, beams and columns,lintels curved or straight including fitting, fixing and striking out after completion of works (upto roof of ground floor). (When the height of a particular floor is more than 4 m the equivalent floor height shall be taken as 4 m and extra for works beyond the initial 4 m ht. shall be allowed for every 4 m or part thereof) -For Tie Beam 25 mm to 30 mm wooden shuttering without staging in foundation
Filling in foundation or plinth by silver sand in layers not exceeding 150 mm as directed and consolidating the same by thorough saturation with water, ramming complete including the cost of supply of sand. (payment to be made on measurement of finished quantity) Do by-Fine Sand - Below Tie Beam
Super- Structures (above Foundation)
Antitermite treatment to the top surface of the consolidated earth within plinth walls with chemical emulsion by admixing chloropyrefos emulsifiable concentrates (1% concentration) with water by weight at the rate of 5 liter per sq.m. of the surface before sand bed or subgrade is laid. Holes upto 50mm.to 75mm. deep at 150mm. centre to centre both ways shall be made with 12mm. diameter mild steel rod on the surface to facilitated saturation of the soil with the chemical emulsion. The work shall be carried out as per specification described in Para 6.4 of code IS-6313 (Part-II)-1981. (Mode of measurement will be per sq.m. of plan area of plinth treated).
Supplying & laying Polythene sheet (150gm/sqm.) over damp proof course or below flooring or roof terracing or in foundation or in foundation trenches. All floor, Roof & above including tie beam
Brick soling with picked jhama bricks including preparetion of bed as necessary with joints properly filled in and packed with powdered earth and including necessary cushion of similar material below the soling (and in between layers when more than one layer is used) completes as per direction. Single brick flat soling(thickness 75mm.).
Ordinary cement concrete (mix1:2:4) with graded stone chips (20mm nominal size) excluding shuttering & reinforcement if any, in ground floor as per relevent IS codes. Pakur variety.
Batch Mixed concrete of M 20 Grade with well Graded stone chips of 20 mm nominal size containing designed quantity of cement per Cu. M of Wet concrete produced in computerised batching plant under controlled condition using approved super plasticizer designing concrete mix following I.S 10262 and I.S. 456 transporting the mix with agitation in transit mixer to work site depositing the mix on a platform erected for the purpose at required level of concreting and then placing the mix in its final location of form work compacting and curing the same complete as per specification and direction of the Engineer-in charge including hire charges of computerised batching plant, transit mixer with all accessories vibrators etc. inclusive of all other incidental charges in this connection complete but excluding cost of hire charge of platform and its supporting staging which would be paid through separate item. Consumption of cement will not be less than 300 Kg of cement per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula.Pakur Variety.With approved concrete pump. - Ground Floor
Add extra over the rate of ground floor for basement and each additional floor above ground floor-1st Floor For 1st floor
For 2nd floor
For 3rd Floor
Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction. For work in foundation, basement and upto roof of Ground Floor/ upto 4 m. Tor steel Fe 500 (JSW/JSPL/SHYAM/SRMB/BMASL/ELECTROSTEEL/SSL).
For 1st floor
For 2nd floor
For 3rd Floor
Hire and labour charges for shuttering with centering and necessary staging upto 4 m using approved stout props and thick hard wood planks of approved thickness with required bracing for concrete slabs, beams and columns,lintels curved or straight including fitting, fixing and striking out after completion of works (upto roof of ground floor). (When the height of a particular floor is more than 4 m the equivalent floor height shall be taken as 4 m and extra for works beyond the initial 4 m ht. shall be allowed for every 4 m or part thereof)
25 mm to 30 mm shuttering without staging in foundation-GF
Steel shuttering or 9 to 12 mm thick approved quality ply board shuttering in any concrete work
Extra for works beyond the roof of ground floor per additional floor-1st Floor (i) upto 4th (per floor) and in basement. For 1st floor
For 2nd floor
For 3rd Floor
250 mm th. Autoclave aerated concrete block Work with size 625 mm x 250 mm x 125 mm- Grade-I, having drying Shrinkage less than 0.05% conforming to IS: 2185 (Part-3)-1984 made up of fly ash (conforming to IS: 3812-1981, with permissible loss on ignition upto 6% ), lime , cement and laid in Cement Mortar (1:6) complete in all respect as per direction & satisfaction of Engineer -in Charge . Ground Floor
For 1st Floor
For 2nd Floor
For 3rd Floor
125 mm thick Autoclave aerated concrete block Work with size 625 mm x 250 mm x 125 mm- Grade-I,having drying Shrinkage less than 0.05% conforming to IS: 2185 ( Part-3)-1984 made up of fly ash (conforming to IS: 3812-1981, with permissible loss on ignition upto 6%), lime , cement and complete in all respect as per direction & satisfaction of Engineer -in Charge . a) laid in Cement Mortar (1:6) -In Super Structure, Ground Floor.
For 1st Floor
For 2nd Floor
75 mm thick brick work with 1st class Bricks set in cement, sand mortar(1:4) in ground floor including H.B. netting in very alternate layers.
For 1st Floor
For 2nd Floor
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and dripourse, chiping, scaffolding / staging where necessary. Ground Floor With 1:6 cement mortar. 20 mm thick plaster. (excluding cost of chipping over concrete surface) Internal Plaster
For 1st Floor
For 2nd Floor
For 3rd Floor
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, noisng and dripourse, chiping, scaffolding / staging where necessary. Ground Floor With 1:6 cement mortar. 15 mm thick plaster. (excluding cost of chipping over concrete surface) External Plaster
For 1st Floor
For 2nd Floor
For 3rd Floor
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, noisng and dripourse, chiping, scaffolding / staging where necessary. . With 1:4 cement mortar. 10 mm thick plaster. all floor, Roof & above. Internal Plaster
For 1st Floor
For 2nd Floor
For 3rd Floor
Labour for Chipping of concrete surface before taking up Plastering work.
18mm. to 22mm. thick, kota stone slab set in 20mm thick (avg) cement mortar (1:4) in floor, stair & lobby including pointing in cement slurry with admixture of pigment matching the stone shade, including grinding &polishing as per direction of Engineer-in-charge to match with the existing work. [Slurry for bedding @ 4.4kg/Sq.m and pointing @ 2.0 kg/Sq.m]
Extra cost of labour for grinding Kota Stone Floor in treads and riser of Steps.
Supplying,fitting & fixing granite slab 15mm to 18mm thick in floor, lobby, stair, landing and treads etc. over 20mm (avg) thick base of cement morter (1:2) laid with white cement slurry @ 4.40Kg per Square meter before placing of granite and jointed with white cement slurry @ 2.0 Kg per square meter with necessary pigments and complete as per direction of Engineer-in-charge including cost of all materials, labours, curing and roughening of concrete surface complete. In ground floor (c) Area of each Granite slab above 1.00 Square meter.
Extra cost of labour for prefinished and premoulded Nosing to treads of steps, railing, window sill etc. of Kota Stone.
Supplying, fitting & fixing 1st quality Ceramic tiles in walls and floors to match with the existing work & 4 nos. of key stones (10mm) fixed with araldite at the back of each tile & finishing the joints with white cement mixed with colouring oxide if required to match the colour of tiles including roughening of concrete surface, if necessary or by synthetic adhesive & grout materials etc. With Sand Cement Mortar (1:4) 20 mm thick & 2 mm thick cement slurry at back side of tiles using cement @ 2.91 Kg/Sq.m & joint filling using white cement slurry @ 0.20kg/Sq.m. (A) Ground Floor (a) Area of each tile upto 0.09 Sq.m. (i) colour decorative. all floor, Roof & above.
For 1st Floor
For 2nd Floor
(B) Wall With Sand Cement Mortar (1:3) 15 mm thick & 2 mm thick cement slurry at back side of tiles using cement @ 2.91 Kg/Sq.m & joint filling using white cement slurry @ 0.20kg/Sq.m. (a) Area of each tile upto 0.09 Sq.m (i) Coloured decorative
For 1st Floor
For 2nd Floor
Supplying and laying true to line and level Double Charge Vitrified Tiles of approved brand conforming to IS 15622: 2006 (Group B I a) and tested as per IS 13630:2006 (relevant parts) [Non-modular sizes for tiles with Water Absorption (av.) ≤ 0.08 %] in floor, skirting etc. using polymerised adhesive of 6mm thick layer applied directly over finished artificial stone floor/Mosaic etc without any backing course and joints grouted with admixture of white epoxy grout materials of approved brand including spacer -2mm as directed and removal of wax coating of top surface of tiles with warm water and polishing the tiles using soft and dry cloth upto mirror finish complete including the cost of materials,Iabour and all other incidental charges complete as per direction of Engineerin-Charge. (Note: This work should not be executed without specific permission of Superintending Engineer) Ground Floor (size not less than 600mm x 600mm x 9.5mm thick)
For 1st Floor
For 2nd Floor
(a) M.S.or W.I. Ornamental grill of approved design joints continuously welded with M.S, W.I. Flats and bars of windows, railing etc. fitted and fixed with necessary screws and lugs in ground floor. (i) Grill weighing above 10 Kg./sq.mtr and up to 16 Kg./sq. mtr.
For 1st floor
For 2nd floor
Supplying fitting & fixing Collapsible gate with 40mm x 40mm x 6mm tee as top & bottom guide rail, 20mm x 10mm x 2mm vertical channels 100 mm apart in fully stretched position 20mmx5mm M.S. flats as collapsible bracings properly rivetted & washered including 38mm steel rollers including locking arrangements fitted & fixed in position with lugs set in cement concrete & including cutting necessary holes chasing etc. in walls floors etc & making good damages complete etc. (Add extra @ 1% for each addl. floor upto 4th floor and @ 1.25% for each addl. floor above 4th floor) 3rd Floor
Supplying, fitting and fixing steel rolling shutter profile type with 18 B.G . of approved type steel latche section 75mm wide, fitted with coil wire spring to necessiate the fitting of required Nos. of C.I. Pulleys on heavy type solid drawn seamless steel tube complete with locking arrangements both inside and outside specially builtup side guide channels including providing a hood for the steel rolling shutter in the room, painting two coats of approved aluminium paint over a coat of red lead primer complete.
Supplying fitting & fixing fiber reinforcement polymer(FRP) composite door shutters as per approved design with glass fiber reinforcement plastic moulded skins & a special sandwich core, so as to impart monolitaheic composite structure as per approved technology of Department of Science & Technology(DST) to satisfy IS:4020 door testing performance criteria. Ground Floor (i) 32mm thick
For 1st floor
For 2nd Floor
Supplying fitting & fixing fiber reinforcement polymer(FRP) composite door frame as per approved design with glass fiber reinforcement plastic moulded skins & a special sandwich core, so as to impart monolitaheic composite structure as per approved technology of Department of Science & Technology(DST) to satisfy IS:4020 door testing performance criteria. 66mmx90mm.
Supplying fitting & fixing frames for Fire resistant door shutters made of 1st class Malaysian Hardwood (densified to 810 kg/cum) and pressure treated with fire retardant chemicals in vacuum impregnation vessel under 160 psi pressure as per IS:401 and kiln seasoned to moisture below 15% as per IS:1141 of section 120 mm X 70 mm spray quoted with 2 coats of intumescent paint of minimum 200 micron, with single row of Brush- Type intumescent strip of size 10 mmx 4 mm affixed in the slit of the Frame for fire and smoke sealing, etc. complete as per direction of Engineer -in-Charge including a protective coat of painting at the contact surfaces of the frame excluding cost of concrete,Iron butt hinges and M.S clamp at Ground Floor.
Supplying & fitting of 55mm thick asbestos free - fire, heat and smoke resistant composite Fire check Door Shutter complying with fire performance- FD120 as per IS:3614 (part -II)-comprising of 2x8 mm Calcium cilicate boards over Chemically treated (with Fire retardant chemicals in pressure impregnation vessels under 160 psi pressure as per IS:401 and kiln seasoned to moisture below 15% as per IS:1141) internal timber (Malaysian Hard Wood, densified to 810 kg/cum ) frame work of 100 mm x32 mm with 32mm thick infill of ceramic fiber (density 128Kg/cum), vermaculite mix faced with 3 mm Fire retardant High Density fire board, internally lipped with hardwood beading, and pasted in Hydraulic Press under 25 MPa, spray coated with 2 coats of in-tumescent paint of minimum 300 micron, and with single row of Brush- Type intumescent strip of size 10 mm x 4 mm affixed on peripheral slit on all edges of shutter except bottom for fire and smoke sealing , without any external lipping including fitting ,fixing shutters in position but excluding the cost of hinges & other fittings as per direction of Engineer -in -charge complete in all respect in Ground Floor.
Supplying, fitting and fixing cast iron heavy type spiral staircase of approved design with 50 mm.dia. Stem and C.I. Steps 150 mm as per design 900 mm. high C.I, railing including necessary M.S. tie of suitable section embedded to wall with cement concrete (1:2:4) including cost of intermediate C.I. platform secured with necessary tie to stem and wall with cement concrete (1:2:4) including fixing the stem in ground with cement concrete (1:3:6) complete in all respect with all labour and materials. (Payment to be made on vertical height in between 1st step and top platform.) (b) With 1200 mm.dia. well
Wood work in door and window frame fitted and fixed in position complete including a protective coat of painting at the contact surface of the frame exluding cost of concrete, Iron Butt Hinges and M.S clamps. (The quantum should be correted upto three decimals). sal: malayasian. any floors. Roof & above. Note: Extra for Lifting Charges for each additional floor, i) Rs. 200/- per Cu.m (upto 4th floor)
For 1st Floor
For 2nd Floor
Supplying solid flush type doors of deluxe decorative (both side) quality, conforming to I:S 2202 timber frame consisting of top and bottom rail and side styles of well seasoned timber 65mm wide each and the entire frame fitted with 27.5mm wide battens places both ways in order to made the door of solid core and internal lipping with teak, mahogony or rose wood approved decorative veneers using phenol formaldehyde as glue etc. complete, including fitting, fixing the shutters in position but excluding the cost of hinges and other fittings in ground floor: 35mm thick shutters (single leaf).
Add extra over rate of ground floor for each addl. Storey F(1 to 6), B(11,12),F(10,11,12), G(7), G(13, 14,15,16,17,18), C(8,9,10,12), B(14 to 18), B(24 to 27), G(19,20), F(17, 18) (i) Upto 4th floor (First Floor)
For 2nd floor
Priming one coat on timber or plastered surface with synthetic oil bound primer of approved quality including smoothening surfaces by sand papering etc. (on timber surface)-Timber Surface
Priming one coat on steel or other metal surface with synthetic oil bound primer of approved quality including smoothening surfaces by sand papering etc.
Painting with best quality synthetic enamal paint of approved make & brand including smoothening surface by papering etc. including using of approved putty etc. on the surface, if necessary: on timber or plastered surface. With super gloss (hi gloss). Two coats (with any shade except white). Timber Surface
Painting with best quality synthetic enamal paint of approved make & brand including smoothening surface by papering etc. including using of approved putty etc. on the surface, if necessary: On steel or other metal surface: With super gloss (hi-gloss). (iv) Two coats (with any shade except white)
Supplying, fitting and fixing M.S. clamps for door and window frame made of flat bent bar, end bifurcated with necessary screws etc. by cement concrete(1:2:4) as per direction. (Cost of concrete will be paid separately) (b) 40mm X 6mm, 200mm Length
Iron butt hinges of approved quality fitted and fixed with steel screws, with IS Imark.
(viii) 100mm. X 75mm. X 3.50mm.
(vii) 100mm. X 58mm. X 1.90mm.
Anodised aluminium barrel / tower / socket bolt (full covered) of approved manufactured from extruded section conforming to I.S. 204/74 fitted and fixed with cadmium plated screws: (x) 300mm long x 12mm dia. bolt.
ii) Brass hasp bolt of approved quality fitted and fixed complete (oxidised) with 16mm dia rod with centre bolt and round fitting. (c) 300 mm long.
(A) Iron door ring of approved quality fitted and fixed with nut and washer complete. (ii) 75mm dia.
Acrylic Distemper to interior wall, ceiling with a coat of solvent based interior grade acrylic primer (as per manufacturer's specification) including cleaning and smoothning of surface. Two Coats
Applying Exterior grade Acrylic primer of approved quality and brand on plastered or concrete surface old or new surface to receive decorative textured(matt finish) or smooth finish acrylic exterior emulsion paint including scraping and preparing the surface throughly, complete as per manufacturer's specification and as per direction of the EIC. (a) Two Coat
For 1st Floor
For 2nd Floor
For 3rd Floor
Protective and Decorative Acrylic exterior emulsion paint of approved quality, as per manufacturer's specification and as per direction of EIC to be applied over acrylic primer as required. The rate includes cost of material, labour, scaffolding and all incidental charges but excluding the cost of primer. Two Coats. b) Premium 100% Acrylic Emulsion
For 1st Floor
For 2nd Floor
For 3rd Floor
Rrendering the Surface of walls and ceiling with White Cement base WATER PROOF wall putty of approved make & brand.(1.5 mm thick). The rate includes cost of material, labour, scaffolding and all incidental charges.
Godrej Hydraulic door closer fitted and fixed complete. Medium type.
Supplying, fitting & fixing UPVC pipes A- Type and fittings conforming to IS:13592-1992 with all necessary clamps nails, including making holes in walls, floor etc. cutting trenches in any soil through masonry concrete structures etc if necessary and mending good damages including joining with jointing materails (Spun Yarn, Valamoid/Bitumen/M-Seal etc) complete. UPVC Pipes: 160 mm. dia.
UPVC Fittings: Bend 87.5 160 mm. Dia.
Shoe 160 mm. Dia.
Plane Tee 160 mm. dia
M.S. structural works in columns, beams etc. with simple rolled structural members (e.g. joists, angle, channel sections conforming to IS: 226, IS: 808 & SP (6)- 1964 connected to one another with bracket, gussets, cleats as per design, direction of Engineer-incharge complete including cutting to requisite shape and length, fabrication with necessary bolting, metal arc welding conforming to IS: 816- 1969 & IS: 1995 using lectrodes of approved make and brand conforming to IS:814- 2004, haulage, hoisting and erection all complete. The rate includes the cost of rolled steel section, consumables such as electrodes, gas and hire charge of all tools and plants and labour required for the work including all incidental chages such as electricity charges, labour insurance charges etc. Payment to be made on the basis of calculated weight of structural members only in finished work as per IS specified weight. Payment for gusset, bracket, cleat, rivets, bolts and nuts may be make by adding the actual weight of such items with the weight of finished structural members or 7% of weight for finished structural members weighing not less than 22.5 Kg. / m. or 15 % of weight for finished structal members weighing less than 22.5 Kg. / m. may be increased allow for bracket, cleat, rivet, bolts and nuts etc. and no seperate payment being made for these items, as per direction of Engineer In Charge. The rates are considered for a height of erection 8m. / 2nd floor level from the ground. Add 1.5% extra over the rate for each additional floor or 4m. beyond initiial 8m. or part thereof. For built up sections / srtuctural members of specified sections weighing not less than 22.5 Kg./m -( Hose tower 5.725*6=34.35m)
Supplying, fitting and fixing single skin color coated trapezoidal profile for wall cladding, roof shall be made of 0.45 mm BMT (Base Metal Thickness) (0.50 mm TCT (Total Coated Thickness excluding paint), G550 (min 550 yield strength), of Zincalume metallic coating (ISI5965) with high Solar Reflectance Index (SRI) value for better colling as per thermatech technology, 1000-1015 mm effective cover width with five major corrugation, 28 mm high rib spaced at 203 mm c/c with subtle square fluting in the pan and the end rib shall have anti-capillary groove and return leg. The steel sheet shall be fastened with 40 micron zinc coated or 25 micron zinc-tin alloy coated, hex head, self-drilling screw as per IS 3566-2002 Class 3 fastener. The base steel shall be coated with zinc-alluminium alloy Zincalume (AZI50) (i.e. 55% Al, 43.4% Zinc, 1.6% Si) minimum of 150g/m2 coating total on both sides, pre-painted with colorbond XRW (xterior roofing, walling) paint system of 35 micron Super Durable Polyester paint (SDP) with stable inorganic pigment with no lead contents conforming ISI5965. The sheet shall be free from defects and have brand marking of the manufacturer giving product details on the back of the sheet at regular interval conforming genuinity of material. (i) in Roof (a) 0.5 mm thick Sheet.
Supplying,fitting & fixing of 2-Track / 3-Track Aluminium sliding Window of all Aluminium sections viz. window frame (top,bottom & side frame), shutter (top, bottom, side & interlock member) made of aluminium alloy extrusions conforming to IS 733-1983 & IS 1285-1975, annodised conforming to IS 1868-1983, fitted with all other accessories viz. PVC roller, EPDM gasket, maruti lock, screws etc. including labour charges for fitting & fixing of aluminium 2-track/3-track sliding window with fixing of glass (excluding cost of glass) all complete as per architectural drawings and direction of Engineer-in-charge. 10-12 Micron thickness Annodizing film Natural white For 2-Track window : Members for Bottom frame @ 0.875 Kg per Mtr. and for Top and Side frame @ 0.778 Kg per Mtr. and for shutter Bottom and Top member @ 0.472 Kg per Mtr., Style side member @ 0.493 Kg per Mtr. and Interlock member @ 0.612 Kg per Mtr. [Note : for estimate purpose construction wing may consider weight of 2- track Aluminium window @ 5.5 Kg per Sq.M.and 3-track Aluminium window @ 6.5 Kg per Sq.M]
Supplying best Indian sheet glass panes set in putty and fitted and fixed with nails and putty complete. (In all floors for internal wall & upto 6 m height for external wall) (ii) 4 mm thick
Iron catch hook of approved quality fitted and fixed to shutter and chowkat. (b) 6mm dia x 225mm long.
Anodised aliminium D-type handle of approved quality manufactured from extruded section conforming to I.S. specification (I.S. 230/72) fitted and fixed complete: (a) With continuous plate base (Hexagonal/ Round rod) (ii) 100 mm grip x 10 mm dia rod.
Supplying & laying 3mm thick pre-fabricated plastomeric water proofing membrane conforming to EN 12311-1 & ASTMD 5147, manufactured with atactic poly propylene (APP) modified premium grade asphalt , specially reinforced with non-woven polyester core with polyester reinforcement @160 gms per sqm & both faces covered with thermo-fusible polyethylene film /MineraL on top face over a coat of primer @ 0.40 lit/sqm of manufacturer's specification on smooth,clean dry surface prepared wherever required.Lap joint shall be provided of 75 mm in longitudinal & 100 mm in transverse direction and fused using LPG/Propane torch employing extra care ensuring full bondage, complete removal of entrapped air and sealing edges into grooves in appropriate manner as per direction of Engineer -in-charge all complete including materials,labour and applicable taxes. (Payment shall be made on the basis of finishedsurface area.). Membrane Property: Softening Point > 150 deg C, Cold Flexibility < -6 deg C, Tensile Strength, N/cm : 600 (longitudinal), 450 (transverse), Tearing Strength, N: 300 (longitudinal), 200 (transverse)
Artificial stone in floor, dado, staircase etc with cement concrete (1:2:4) with stone chips, laid in panels as directed with topping made with ordinary or white cement (as necessary) and marble dust in proportion (1:2) including smooth finishing and rounding off corners including raking out joints or roughening of concrete surface and application of cement slurry before flooring works using cement @ 1.75 kg/sq.m all complete including all materials and labour. In ground floor. 3 mm. thick topping (High polishing grinding on this item is not permitted with ordinary cement). Using grey cement (ii) 35 mm. thick
For LAND DEVELOPMENT Earth work in filling in foundation trenches or plinth with good earth in layers not exceeding 150 mm. Including watering and ramming etc. layer by layer complete. (payment to be made on the basis of measurement of finished quantity of work). With carried earth arranged by the contractor within a radius of 3 km. including cost of carried earth. (3065Sqm*0.3 = 920 Cum)
Panel (made of single plank) of door and window shutters to design as directed: In Ground Floor (Payment to be made on area of exposed new work). (In case of non-supply of single plank penal rate of reduction to a maximum of 30% will be made). (iii) 25mm thick panel of 30cm to 45cm width (a) 1st class best Indian teak
Applying Interior grade Acrylic Primer of approved quality and brand on plastered or cencrete surface old or new surface to receive Distemper/ Acrylic emulsion paint including scraping and preparing the surface throughly, complete as per manufacturer's specification and as per direction of the EIC. (In Ground Floor) (a) One Coat i) Water based interior grade Acrylic Primer
Sanitary & Plumbing Works and Tube well
Supplying, fitting and fixing shower of approved brand and make. Chromium plated round shower with revolving joint 100 mm dia with rubid cleaning system (Equivalent to Code No. 542(N) & Model - Tropical / Sumthing Special of ESSCO or similar brand). ( GF-3 + FF-3 + 2nd -2 = 8 nos )
Chromium plated Hand shower with Flexible Tube & fittings(Equivalent to Code No. Hsh-1937 & (Equivalent to Code No. 5037 & Model - Florentine of Jaquar or similar).).
Supplying, fitting and fixing bib cock or stop cock.
Chromium plated Bib Cock short body (Equivalent to Code No. 511 & Model - Tropical / Sumthing Special of ESSCO or similar brand). (GF-10 + F F-10.0+ 2nd Floor-4 = 24 nos )
Chromium plated Bib Cock long body with wall flange with aerator (Equivalent to Code No. 512 & Model- Tropical / Sumthing Special of ESSCO or similar brand) ((GF-1 + FF-1 +2nd Floor- 1 = 3 nos )
(b) (i) Chromium plated Stop Cock (Equivalent to Code No. 513(A) & 513(B) & Model- Tropical / Sumthing Special of ESSCO or similar. (GF-15+ FF-15+S.F- 4= 34 nos )
Supplying, fitting and fixing CPVC (Chlorinated Polyvinyl Chloride) pipes of approved make conforming to IS-15778: 2007 . with all necessary accessories, specials viz. socket, bend, tee, union, cross, elbo, nipple, longscrew, reducing socket, reducing tee, short piece etc. fitted with holder bats clamps, including cutting pipes, fitting, fixing etc. complete in all respect including cost of all necessary fittings as required,jointing materials in any position above ground. (Payment will be made on the centre line measurements of total pipe line including all specials. No separate payment will be made for accesories, specials. a) For Exposed Work CPVC Pipes Class-I,SDR-11 - 50 mm Connection between two tanks
Overflow-50mm- (3x2x1 + 3x15 ) + (6x11.50 +6x13.50) =201.0 m
Air pipe-50mm-( 3rd Floor -Part A-Main pipe from tank -4x1.0 +10+6x4.0 + Part-B- Main pipe from tank -2x1.0+ 12.0) = 52.0m
b) 40 mm Ground Floor - Part A (5.0x4 +10.0)=30.0m 1st Floor - Part A (5.0x4 +15.0 )=35.0m 1st Floor - Part B (15.0+6.0+8.0)= 29m Part B-Part -(2x15.0 +6.0+8.0) =58.0m TOTAL = 152m
c) 32 mm Ground floor - Part A (4x3+1) +Extra-20x1 + 1st Floor - Part- A (1+3+5) + Part -B (5x2+10)-2nd Floor -Part-B (2x5x2+ 2x10)= 102m
d) 25 mm Ground floor Part A (6x3+10 = 28.0m + Extra 25x1= 53m 1st floor - Part A 1+3+15=19.0 m Part-B -3x2+15 =21m 2nd floor Part B -2x3x2+2x15=42.0m TOTAL= 135m
e) 15 mm Ground floor Part A-6x2+12=24 +Extra 30x1= 54.0m 1st floor - Part A1+2.5+9.5=13.0 Part B -3x1+12=15.0m 2nd floor Part B -2x (3+1+12) = 30.0 Total = 112m
Supplying P.V.C. water storage tank of approved quality with closed top with lid (Black) - Multilayer. 2000 litre capaclity
Labour for hoisting plastic water storage tank. (ii) Above 1500 Litre upto 5000 litre capacity (2nd Fl)
a) Upto 1st story from GL.
b) Extra for each additional floor (2nd Fl).
Labour for punching hole in plastic water storage tank up to 50 mm dia. 2x4x4
Supplying, fitting and fixing stainless steel sink complete with waste fittings and two coats of painting of C.I. brackets. -2nd Floor-2.0 Total =2 nos Sink only - 630 mm x 550 mmx 180mm size
Supplying,fitting and fixing approved brand P.V.C. CONNECTOR white flexible, with both ends coupling with heavy brass C.P. nut, 15 mm dia. 600 mm long (GF-13 + FF-13+ SF & TF -3 = 29 nos )
Supplying,fitting and fixing approved brand 32 mm dia. P.V.C. waste pipe, with PVC coupling at one end fitted with necessary clamps. 1050 mm long (GF-9+ FF- 9+ SF- 3 = 21 nos
Supplying, fitting and fixing E.W.C. in white glazed vitreous chinaware of approved make complete in position with necessary bolts, nuts etc.
a) With 'P' trap
b) With 'S' trap
Supplying, fitting and fixing Anglo-Indian W.C. in white glazed vitreous china ware of approved make complete in position with necessary bolts, nuts etc. With 'S' trap (with vent) Ground Floor-5 nos
Supplying, fitting and fixing Anglo-Indian W.C. in white glazed vitreous china ware of approved make complete in position with necessary bolts, nuts etc. With 'P' trap (with vent) 1st Floor, 2nd Floor & 3rd Floor (4+2 = 6 )
Supplying, fitting and fixing Half round channel with or without outlet as required set in cement concrete (6:3:1) with jhama chips complete. 600 mm X 100 mm. White vitreous chinaware G.F (3.6x2+1.2x2+2.3x1+1.15x1 = 13.05 +F.F (3.6x2+1.2x2+2.3x1+1.15x1+2.6+1.5 = 17.15 + 2nd Floor (1.15x1+2.6+1.5 )= 5.25 Total = 36.0 m (A) Extra for item 13
i) Channel with outlet, stop end
ii) Channel with 'L' or 'T'
Supplying,fitting and fixing 32 mm dia. Flush Pipe of approved make with necessary fixing materials and clamps complete. - Polythene Flush Pipe (GF-4.0+ F.F-4.0 S.F -7.0 = 15 nos )
Supplying, fitting and fixing C.I. round grating. 100 mm (LS)
Supplying, fitting and fixing Flat back urinal (half stall urinal) in white vitreous chinaware of approved make in position with brass screws on 75 mm X 75 mm X 75 mm wooden blocks complete. 470 mm X 280 mm X 340 mm -G.F-6 +F.F -6 + 2nd & Floor- 2.0 = Total -14 nos
Supplying, fitting and fixing Squating plate with integral flushing in white vitreous chinaware of approved make in cement concrete (6:3:1) with jhama chips complete. (Payment of concrete will be paid seperately). 450 mm X 350 mm -G.F-1.0 +F.F-2.0 +2nd Floor--3 = Total -6 nos
Supplying, fitting and fixing liquid soap container. Cromium plated. (G.F -3.0 no +F.F-4 no + 2nd Fl-2 no= total-9 no)
Supplying, fitting & fixing Supplying, fitting and fixing porcelain soap tray of approved make. Recessed soap tray of size 150 mm X 150 mm (G.F -7.0+ F.F-8 no + 2nd Floor-3 no = 18 no )
Supplying, fitting and fixing bathroom shelf of approved make of size 580 mm X 150 mm (porcelain).( G.F -3+ F.F -3 + 2nd Floor -2 no= Total 8.0 nos
Supplying, fitting and fixing gun metal wheel valve o fapproved brand and make tested to 21 kg per sq. cm. (for water lines only). 50 mm dia.
40 mm dia.
25 mm dia.
Supplying, fitting and fixing best quality Indian make mirror 5.5 mm thick with silvering as per I.S.I. specifications supported on fibre glass frame of any colour, frame size 550 mm X 400 mm (GF- 3 +FF-4 + 2nd Floor -2 = 9 nos)
Supplying, fitting and fixing towel rail with two brackets C.P. over brass 25 mm dia. & 750 mm long(G.F- 3 +F.F-10 + 2nd Floor- 3 = 16 nos )
Constructing Inspection pit of inside measurement 600mm X 600mm X upto 600mm (depth) with 250 mm thick 1st. class brick work in cement mortar (1:4) on all sides, bottom of the pit consisting of 100 mm thick cement concrete (1:3:6) with stone chips over a layer of jhama brick flat soling,15 mm thick (1:4) cement plaster to inside walls and out-side walls upto G.L. and 20 mm.thick (1:4) plaster to bottom of the pit, providing necessary invert with cement concrete (1:3:6) with stone chips as per direction, neat cement finishing to entire internal surfaces, top of the pit covered with 100 mm thick R.C.C. slab (1:1.5:3) with stone chips and necessary reinforcements upto 1% and shuttering including 6 mm thick cement plaster (1:4) in all external surfaces of the slab and one 560 mm dia. R.C.C. manhole cover of approved make supplied, fitted and fixed in the slab with necessary fittings, necessary earthwork in excavation in all sorts of soil, filling sides of the pit with earth and removing spoils after work complete in all respect with all costs of labour and materials. A) With Pakur variety and with JSW/JSPL/SHYAM/SRMB/BMASL/ELECTROSTEEL/SSL steel
Construction of septic tank of different capacities as per approved drawing with 1st class brick work in cement mortar (1:4) including two 560 mm dia. R.C.C. manhole cover (heavy type) of approved make supplied, fitted and fixed in the 100mm thick R.C.C (1:1.5:3) top slab with necessary fittings, 20mm thick cement plaster (4 : 1) with neat cement finish to the internal surfaces and 15 mm thick cement plaster (4 : 1) to outside wall upto 200 mm below G.L floor finished with 25 mm thick grey artificial stone over 100 mm thick R.C.C (1:1.5:3) bottom slab including supplying, fitting and fixing all necessary specials, fittings, S.W. tees, C.I. foot rest etc. including excavation earth in all sorts of soil, shoring, bailing out and pumping out water as necessary, ramming, dressing the bed and refilling the sides of the tanks with earth, removing spoils, filling up the chamber with clear water, removing foreign materials from the chamber and including constructing attached inspection pit as per approved drawing and connecting all necessary pipes, joints etc. with internal plaster work and artificial stone flooring is to be done with admixture of water proofing compound @ 0.5% by weight of cement with all costs of labour and materials. Note:- (i) Finished level of Septic Tank should be 400 mm. from Ground Level. (ii) Height of 50 mm. Ventilation pipe &Mosquito proof mesh, should be follwed as per IS:2470,Part- I.Payment will be made separetly on the basis of actual height based on relevant I.S.Code. iv) For 50 users. A) With Pakur variety and with JSW/JSPL/SHYAM/SRMB/BMASL/ELECTROSTEEL/SSL steel
Construction of circular soak well 2.5 metre deep in all types of sandy soils with dry brick work upto 1.6 metre from the bottom having 150 mm intermediate cement brick work (1:4) band all round and cement brick work (1:4) upto 0.90 metre from top with 20mm thick cement plastering (1:4) to inside face upto the depth of cement brick work, 15mm thick cement plaster (1:4) on outer face from top of the well upto G.L. and 6 mm thick cement plaster (1:4) on top of the R.C.C. cover slab including filling bottom 1.00 metre of inside of the well with brick metal (50mm to 63 mm size) including R.C.C. cover slab of 100 mm thick with cement conc (1:1.5:3) with stone chips with necessary reinforcement and shuttering including one 560 mm dia. R.C.C. manhole cover (heavy type)of approved make supplied, fitted and fixed in the cover slab with necessary fittings, making nacessary arrangements for pipe connections, excavation of well including shoring, dewatering and removing the exess earth from the premises as per direction complete in all respect with all costs of labour and materials. With 250 mm thick dry brick work and 250 mm thick cement brick work (1:6) and 1.00m inside dia.( With JSW/JSPL/SHYAM/SRMB/BMASL/ELECTROSTEEL/SSL steel)
Supply of U.P.V.C. Pipes (B Type) & fittings conforming to IS-13592-1992 Single socketed 3m Length 110 mm dia. (internal) (5.3x6+0.65x11+2x2+3.5x2 +0.5x8 +0.6x8 +35+10+3.0) +10 + (0.5 x13 +3x 30 +2x36.0 = 285.0m
Fittings
Plain Tee-110mm
Door Tee (LH) & (RH)- 110 mm
Door Y (LH) & (RH) - 110 mm
Double Y with Door - 110 mm
Bend 87.5° - 110 mm
Door Bend (LH) & (RH) - 110 mm
W.C. Connector (450 mm long) W/lipring-75mm
Labour for fitting and fixing U.P.V.C. pipes for above ground work including cost of jointing materials etc. fitting and fixing all necessary specials, cutting pipes, cutting holes in walls or R.C. floor where necessary and mending good all damages excluding the cost of masonry or concrete... etc. Above ground 110 mm dia.
Supplying, fitting & fixing Cast iron P or S trap conforming to I:S 3989/1970 and 1729 / 1964 including lead caulked joint and painting two coats to the exposed surface with approved paint complete. ( Painting will however be paid seperately). 100 mm dia.
'P' Trap 1st Floor-8 nos + , 2nd Floor -8 nos = 16 nos
'S' Trap Ground Floor
Supplying, fitting and fixing 10 litre porcelain low-down cistern of approvedmakewitheither sideor bottominlet, sideoverflow, brackets complete with all internnal PVC fittings.
Ground Floor-4
1st Floor -4
2nd Floor-2 Total 10.0 nos
Supplying, fitting and fixing white vitreous china best quality approved make wash basin with C.I. brackets on 75 mmX75 mm wooden blocks, C.P.waste fittings of 32 mm dia.,one approved quality brass C.P.pillar cock of 15 mm dia.,C.P. chain with rubber plugof 30 mm dia., approved quality P.V.C.waste pipe with C.P. nut 32 mm dia.,900 mm long approved quality P.V.C. connection pipe with heavy brass C.P. nut including mending good all damages and painting the brackets with two coats of approved paint. 630 mm X 450 mm size - G.F-3 + F.F -4 + 2nd Floor-3 = Total -10 nos
Supplying, fitting and fixing in position CI manhole cover with rim -Round- 450mmx100mmx50Kg (approx)
TUBE WELL
Labour for boring through any type of soil for sinking tube well of required dia. with top enlargement by rig boring system (either by reserve circulation or by direct rotary method) including hire charges and labour for rig machine, tools and plants, staging, force pumping set and making arrangement for water required for boring etc. complete and lowering of pipes, strainers, blind pipes etc. complete. (b) For depth upto 250 metre for 150 mm dia. Tube well with top enlargement of 250 mm dia.(upto 50 metre).
(i) First 50 metre
(ii) Next 50 metre
(iii) Next 50 metre
(iv) Rest 170 metre
Supplying, fibre glass reinforced Epoxy resin slotted of 1 mm slot width in 6.1 m length of approved make and as per direction of the Engineer-in-Charge 150 mm nominal dia. 7.0 mm wall thickness
Supplying M.S.male / female adopter of approved make and brand for coupling of M.S. pipe and fibreglass strainers, as per direction of the Engineer - in - Charge. 150 mm
Supplying, fitting and fixing steel cutter piece upto 450 mm long with sockets. 75 mm
Supplying, fitting and fixing G.I. cap at top 300 mm
Supply of PVC pipes & fittings Schedule 80(medium duty) conforming to ASTMD-1785 and threaded to match with GI Pipes as per IS:1239 (Part - I). PVC Pipes 150 mm
Supply of E.R.W.M.S. (Electrical Resistant Welded M.S.) black pipe of TATA make (heavy quality) as per standard specification, 5 mm thick. 250 mm dia. (Internal)
Washing and developing tube well with air compressor pump and engine for 8 (eight) hours continuous pumping per day with necessary arrangements for testing the yield in gallons per hour with 'V' notch including hire and labour charges for all tools and plants and scaffolding as required. L.S.
Labour for making arrangement for showing verticality test including the cost for hire charges of tools and plants, scafolding, labour etc. all complete.
Collecting sample of water for bacteriological and chemical test from any depth at any time during execution of work including hire and labour charges for tools and plants and sterilising the equipments, paying all charges and fees, testing etc. complete in all respect as per direction.
Packing the annular space between the outside of the tube well pipes & strainers and the bore with pea size washed gravel of approved quality having size from 2 mm to 5 mm or the size approved by the Engineer-incharge including cost of all materials labour and equipment complete. Note: Initial 6 m. of Annular space between the housing pipe and the bore should not be shrouded with Pea size gravel to avoid contamination with surface water.
Packing annular space between the outside of the housing pipe and the bore with puddled clay balls of approved size as per direction of the Engineer-in-charge with cost of all materials and labour complete.
Geophysical investigation of the acquifer by electrologging system with all tools and plants as necessary including supply of necessary report
Internal Road
Earth work in excavation of foundation trenches or drains, in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading or stacking the spoils within a lead of 75 m. as directed. The item includes necessary trimming the sides of trenches, leveling, dressing and ramming the bottom, bailing out water as required complete. Depth of excavation not exceeding 1,500 mm. ( 1100sqm x 1m = 1100 cum)
Filling by Medium Sand (1100sqmX 0.5m = 550 Cum)
Granular Sub-base with Graded Material (Table:- 400-1) B. By Mix in Place Method : Construction of granular sub-base by providing graded material, mixing in Wet Mix Plant at OMC, carriage of mixed material to work site, spreading in uniform layers with Motor grader on prepared surface in proper grade and camber, compacting with vibratory power roller to achieve the desired density, including lighting, guarding, barricading, including cost of all materials, machinery, tools and plants and cost of quality control complete as per Clause 401 of Specifications for Road & Bridge Works of MoRT&H (5th Revision). Grading – III (1100sqm X 0.25m = 275 cum)
Water Bound Macadam Base Course (1100 sqm X 0.25 m = 275 Cum) Providing, laying, spreading and compacting stone aggregates of specific sizes to water bound macadam specification including spreading in uniform thickness, hand packing, rolling with vibratory roller 8-10 tonnes in stages to proper grade and camber, applying and brooming requisite type of screening / binding materials to fill up the interstices of coarse aggregate, watering including lighting, guarding, barricading and making necessary earthen bundh of one metre width on each side and preparing the bed by necessary cutting or filling, including cost of all materials and hire and labour charges of all men and machinery and compacting to the required density, as per Clause 404 of Specifications for Road & Bridge Works of MoRT&H (5th Revision). (iii) Grading-II Aggregate (53 mm to 22.4 mm) Using Stone Screening Type B (11.2 mm)-- By Mechanical Means
80 mm thick interlocking designer concrete paver block M-40 grade for medium-traffic zone & utility cuts on arterial roads etc. as per IS: 15658-2006 (over 20-40 mm medium sand bed on 250mm thk WBM/ WMM base course & 250 mm thk bound gnaular/ granular sub-base course & filling the interstices of blocks with fine sand by brooming & subsequent watering including cost of sand for sand bed but excluding cost of base, sub-base course & subgrade preparation.) complete as per direction of Engineer-in-Charge. Grey
Renovation of Existing Boundary Wall
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and dripourse, chiping, scaffolding / staging where necessary. Ground Floor With 1:6 cement mortar. 20 mm thick plaster. (excluding cost of chipping over concrete surface) (50mx2 =100Sqm + 210x1.5 =415sqm
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, noisng and dripourse, chiping, scaffolding / staging where necessary. Ground Floor With 1:6 cement mortar. 15 mm thick plaster. (excluding cost of chipping over concrete surface) External Plaster (50mx2=100Sqm+21x1.5=415 sqm
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, noisng and dripourse, chiping, scaffolding / staging where necessary. Ground Floor With 1:6 cement mortar. 10 mm thick plaster. (excluding cost of chipping over concrete surface) External Plaster - Gate Pillars (2.4x4x1.6=15.36 + Raising pillars 101x1x 1.5 + Coping 210x0.15x2+2x210x0.375+= 388 sqm
Protective and Decorative Acrylic exterior emulsion paint of approved quality, as per manufacturer's specification and as per direction of EIC to be applied over acrylic primer as required. The rate includes cost of material, labour, scaffolding and all incidental charges but excluding the cost of primer. Two Coats. Premium 100% Acrylic Emulsion
Applying Exterior grade Acrylic primer of approved quality and brand on plastered or concrete surface old or new surface to receive decorative textured(matt finish) or smooth finish acrylic exterior emulsion paint including scraping and preparing the surface throughly, complete as per manufacturer's specification and as per direction of the EIC. (a) Two Coat
Dismantling all types of masonry excepting cement concrete plain or reinforced, stacking serviceable materials at site and removing rubbish as directed within a lead of 75 m. For new gate -(12mx0.25x2.1m+9x0.25x2.1m + Coping-0.375x0.15x210 =23Cum
For construction of 04 nos boundary wall columns for installation of 2 new Gate-
Earth work in excavation of foundation trenches or drains, in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading or stacking the spoils within a lead of 75 m. as directed. The item includes necessary trimming the sides of trenches, leveling, dressing and ramming the bottom, bailing out water as required complete. Depth of excavation not exceeding 1,500 mm. (4x0.75x0.75x1.05 =2.4cum)
Filling in foundation or plinth by silver sand in layers not exceeding 150 mm as directed and consolidating the same by thorough saturation with water, ramming complete including the cost of supply of sand. (payment to be made on measurement of finished quantity) 4x0.75x0.3x0.75 = 0.68 cum)
Brick soling with picked jhama bricks including preparetion of bed as necessary with joints properly filled in and packed with powdered earth and including necessary cushion of similar material below the soling (and in between layers when more than one layer is used) completes as per direction. Single brick flat soling(thickness 75mm.). (4x0.75x0.754 =2.25 sqm)
Batch Mixed concrete of M 20 Grade with well Graded stone chips of 20 mm nominal size containing designed quantity of cement per Cu. M of Wet concrete produced in computerised batching plant under controlled condition using approved super plasticizer designing concrete mix following I.S 10262 and I.S. 456 transporting the mix with agitation in transit mixer to work site depositing the mix on a platform erected for the purpose at required level of concreting and then placing the mix in its final location of form work compacting and curing the same complete as per specification and direction of the Engineer-in charge including hire charges of computerised batching plant, transit mixer with all accessories vibrators etc. inclusive of all other incidental charges in this connection complete but excluding cost of hire charge of platform and its supporting staging which would be paid through separate item. Consumption of cement will not be less than 300 Kg of cement per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula.Pakur Variety.With approved concrete pump. -Gate Pillar + Raise of other pillars+coping+ Lintel
Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction. For work in foundation, basement and upto roof of Ground Floor/ upto 4 m. Tor steel Fe 500 (JSW/JSPL/SHYAM/SRMB/BMASL/ELECTROSTEEL/SSL).- For Gate Pillar+ Raise of other Pillers+ coping = 2.5% of 28.50= 6.0 MT
Hire and labour charges for shuttering with centering and necessary staging upto 4 m using approved stout props and thick hard wood planks of approved thickness with required bracing for concrete slabs, beams and columns,lintels curved or straight including fitting, fixing and striking out after completion of works (upto roof of ground floor). (When the height of a particular floor is more than 4 m the equivalent floor height shall be taken as 4 m and extra for works beyond the initial 4 m ht. shall be allowed for every 4 m or part thereof) Steel shuttering or 9 to 12 mm thick approved quality ply board shuttering in any concrete work - Gate Pillar(0.4x4x4x2.75 +0.3x4x4x0.75 = 25 Sqm +101x1.0x1.5 +0.225x2x110= 225.0
Priming one coat on steel or other metal surface with synthetic oil bound primer of approved quality including smoothening surfaces by sand papering etc.
Applying Exterior grade Acrylic primer of approved quality and brand on plastered or concrete surface old or new surface to receive decorative textured(matt finish) or smooth finish acrylic exterior emulsion paint including scraping and preparing the surface throughly, complete as per manufacturer's specification and as per direction of the EIC. (a) Two Coat
Painting with best quality synthetic enamal paint of approved make & brand including smoothening surface by papering etc. including using of approved putty etc. on the surface, if necessary: On steel or other metal surface: With super gloss (hi-gloss). (iv) Two coats (with any shade except white)
Supplying fitting and fixing 600 mm ( ±30 mm) diametre R.B.Tconcertina coils strtches (Reinforced Barbed Tape) Concertina fencing on wall top using concertina coils stretched to approx.6 meters length at site clipped with two nos. of horizontal R.B.T strands which will be tensioned and fixed with the vertical M.S angle iron posts by means of security fasteners (such as 'C' clips, R.B.T clips etc.)The rate is exclusive of the cost of posts
M.S. works in brackets made from flats, angles, tees etc. to sizes specialy bent, twisted, forged; making holes drilled and fitted to rafter of trusses with necessary bolts, nuts, washer or screws etc. (length of straight not less than 230 mm)- Bracket 50% Angle 65x65x6mm) -
Locking arrangement forJail typedoors includingsupplyingfitting and fixing in position complete as per approved design.
M.S. gate ofJail type as per approved design madeof strong M.S. frame work, intermediate stiffeners and round / square bars or angles. M.S. sheet (not less than 14 gauge) gussets, cleats etc. including necessary riveting, bolting, welding, lockingandhanging arrangements, fitting and fixing complete as per direction of the Engineer-in -charge. In ground floor-
Extra for supplying, fitting & fixing bottom roller including all labour 5% over item no 14
Supply fitting fixing in position rails on any surface
125 mm. thick brick work with 1st class bricks in cement mortar (1:4) in ground floor. 210x0.675=142 sqm
Dismantling R.C. floor, roof, beams etc. including cutting rods and removing rubbish as directed within a lead of 75 m. including stacking of steel bars. a) In ground floor including roof. -Existing Column(101x.25x.25x1.5)
Surface drain and Plinth Protection
Earth work in excavation of foundation trenches or drains, in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading or stacking the spoils within a lead of 75 m. as directed. The item includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as required complete (a) Depth of excavation not exceeding 1,500 mm.
Ordinary cement concrete (mix1:2:4) with graded stone chips (20mm nominal size) excluding shuttering & reinforcement if any, in ground floor as per relevent IS codes. Pakur variety.
Supplying & laying Polythene sheet (150gm/sqm.) in foundation or in foundation trenches.-w
Controlled Cement concrete with well graded stone chips (20 mm nominal size) excluding shuttering and reinforcement with complete design of concrete as per IS : 456 and relevant special publications, submission of job mix formula after preliminary mix design after testing of concrete cubes as per direction of Engineerin charge. Consumption of cement will not be less than 300 Kg of cement with Super plasticiser per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula. In ground floor and foundation, [using concrete mixture]. a) M-20 Grade i) Pakur variety[ upto plinth
Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction. (a) For works in foundation and upto roof of ground floor/upto 4 m (i) Tor steel/Mild Steel
Hire and labour charges for shuttering with centreing and necessary staging upto 4 m using approved stout props and thick hard wood planks of approved thckness with required bracing for concrete slabs , beams, m columns , lintels curved or straight including fitting , fixing and striking out after completion of works (upto roof of ground floor) 25 mm to 30 mm thick wooden shuttering without staging as per decision & direction of Engineer-In-Charge.
Brick work with 1st class bricks in cement mortar (1:6) upto plinth
Brick soling with picked jhama bricks including preparation of bed as necessary with brick joints properly filled in and packed with powdered earth and including necessary cushion of similar material below the soling (and in between layers when more than one layer is used) completes as per direction.(a) Single brick flat soling (thickness 75 mm.)
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and drip course, scaffolding/staging where necessary (Ground floor).[Excluding cost of chipping over concrete surface] (b) 20 mm thick plaster (i) With 1:6 cement mortar (External) Ground floor
Neat cement punning about 1.5mm thick in wall,dado,window sill,floor etc. NOTE:Cement 0.152 cu.m per100 sq.m
Internal Beautification
Earth work in excavation of foundation trenches or drains, in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading or stacking the spoils within a lead of 75 m. as directed. The item includes necessary trimming the sides of trenches, leveling, dressing and ramming the bottom, bailing out water as required complete. Depth of excavation not exceeding 1,500 mm. (60m X 0.85m X 0.65m =34 cum)
Filling in foundation or plinth by silver sand in layers not exceeding 150 mm as directed and consolidating the same by thorough saturation with water, ramming complete including the cost of supply of sand. (payment to be made on measurement of finished quantity) (60m X0.65m X 0.30m = 12Cum
Brick soling with picked jhama bricks including preparetion of bed as necessary with joints properly filled in and packed with powdered earth and including necessary cushion of similar material below the soling (and in between layers when more than one layer is used) completes as per direction. Single brick flat soling(thickness 75mm.). (60mx0.65m = 39Sqm )
Brick work with 1st class bricks in cement mortar(1:6). In foundation and plinth - 60m(5x0.15 +0.375x0.15+0.675x0.25)= 18 Cum
M.S.or W.I. Ornamental grill of approved design joints continuously welded with M.S, W.I. Flats and bars of windows, railing etc. fitted and fixed with necessary screws and lugs in ground floor.-60mx0.9mx 16kg= 864 Kg
Ordinary Cement concrete (mix 1:2:4) with graded stone chips (20 mm nominal size) excluding shuttering and reinforcement,if any, in ground floor as per relevant IS codes. foundation, basement all floor, Roof & above. (a)Pakur Variety -0.65x60x0.10 = 3.9 Cum
Priming one coat on timber or plastered surface with synthetic oil bound primer of approved quality including smoothening surfaces by sand papering etc.
Protective and Decorative Acrylic exterior emulsion paint of approved quality, as per manufacturer's specification and as per direction of EIC to be applied over acrylic primer as required. The rate includes cost of material, labour, scaffolding and all incidental charges but excluding the cost of primer. Two Coats. b) Premium 100% Acrylic Emulsion
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and drip course, scaffolding/staging where necessary (Ground floor).[Excluding cost of chipping over concrete surface] (b) 20 mm thick plaster (i) With 1:6 cement mortar (External) Ground floor (1.45 x 60 = 87.0sqm)
(a) M.S.or W.I. Ornamental grill of approved design joints continuously welded with M.S, W.I. Flats and bars of windows, railing etc. fitted and fixed with necessary screws and lugs in ground floor. (i) Grill weighing above 10 Kg./sq.mtr and up to 16 Kg./sq. mtr. (60x0.9=54 Sqm)
Painting with best quality synthetic enamal paint of approved make & brand including smoothening surface by papering etc. including using of approved putty etc. on the surface, if necessary: On steel or other metal surface: With super gloss (hi-gloss). (iv) Two coats (with any shade except white)
Supplying & laying Polythene sheet (150gm/sqm.) in foundation or in foundation trenches.- 60x.65= 39.0
Internal Electrification
PART-A (Internal E.I Work)
S & F 3 nos. 100 A. porcelain type kit kat fuses & 1 no. porcelain insulator based neutral link on 2 sqft. Size 19 mm thick water proof Plywood Board incli. S & F Plywood Board on wall. (Kit Kat Fuse Mk. Havell's / Standard) - N.S. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
S & F 415V. TPN SFU with sheet steel enclosure on angle iron frame on wall incl. S & F 3 nos. DIN type HRC fuse & necy. Connection as per GS. - (L & T / Siemens) - D -3/4a. 100 A.
S & F 415V. TPN on load front operated changeover switch with sheet steel enclosure on angle iron frame on wall incl. necy. connection as per GS. - (L & T / Siemens) - D -2/3a. 125 A.
Supplying and fixing double door vertical TPN MCB Distribution board for MCB incomer IP - 42 / 43 protection, on the angle iron frame on wall & mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Legrand / Siemens / Cabtree / L & T ). 8 Way -(D11/15)
Supplying and fixing 415V four pole MCCB of breaking capacity 25KA / 35KA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in existing DBs / enclosure and necessary connection. (Legrand / Siemens / Cabtree / L & T ). 100A 415V FP MCCB -(D8/10)
Supplying and fixing 240 / 415V MCB of breaking capacity 10KA & C characteristics on din rail of exiting DBs and necessary connection (Legrand / Siemens / Cabtree / L & T) i) 415V 40A. TP MCB (D6/7)
ii) 415V 6A-32A. TP MCB (D6/7)
iii) 415V 6A-32A. SP MCB (D6/7)
Supplying and fixing double door vertical TPN MCB distribution board for MCCB incomer with IP-42 / 43 protection, on angle iron frame on wall & mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Legrand / Siemens / Cabtree / L&T) 4 way (D11 / 15)
Supplying and fixing 415V four pole MCCB of breaking capacity 25KA / 35KA with fixed thermal and fixed magnetic / adjustable thermal and fixed magnetic setting in exiting DBs / enclosure and necessary connection. (Legrand / Siemens / Cabtree / L&T) 63A. 415V FP MCCB (D8/10)
Supplying and fixing double door Horizontal TPN MCB distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment, 4 Way (legrand / Cabtree / L&T) (D10/14)
Supplying and fixing double-door SPN MCB distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. 2+12 way enclosure (Legrand / Cabtree / L&T) (D9 / 13)
Supplying and fixing 240 / 415V MCB isolator on din rail of existing DBs and necessary connection. (Legrand / Siemens / Cabtree / L&T) i) 415V 40A FP MCB Isolator (D5 / 6)
ii) 240V 40A DP MCB Isolator
Distn. Wiring in 22 / 0.3 (1.5 sq.mm.) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Polycab / Havell's / KEI / RR Kabel) in 19 mm bore, 3mm thick polythen pipe (for horizontal & vertical run in wall and celing portion through prelaid polythen pipe) complete with all accessories embedded in wall to light/fan/call bell points with piano key type switch (Anchor make) fixed on sheet metal (16 SWG) switch board with bakelite/perspex (wall matching colour) top cover (3mm thick) flushed in wall incl. mending good damages to original finish (E10/3) i. Average mtr 9mtr
Distn. Wiring in 22/0.3 (1.5 sq.mm) single core stranded 'FR' insulated & unsheathed single core stranded copper wire (Polycab / Havell's / KEI / RR Kabel) in 19 mm bore, 3mm thick polythen pipe complete with all accessories embedded inwall to 240V 5A 3 Pin plug point incl. S & F 240V 5A 3 Pin flush type plug socket & piano key type switch (Anchor make) incl. S&F earth continuity wire, fixed on sheet metal (16 SWG) switch board with bakelite/perspex (Wall matching colour) top cover (3mm thick) flushed in wall incl. mending good damages to original finish on board (E10/4)
S&F PVC Rigid Conduit 'FR' (Precision Make) on Wall, ceiling with saddles and other accessories as required as per GS. - E16/7.
i. 20 mm dia
ii. 25 mm dia
S&F 19mm dia polythene pipe with 3mm thick complete with fittings as necessary under ceiling/beam, bound with S&F 22SWG GI binding wire as per GS. (Synchronizing with roof/beam casting work of building construction) E-2/1.
Cutting channel of 40 mm x 40 mm size on masonry wall incl. S&F 19 mm dia 3 mm thick heavy gauge polythene pipe as per GS. Incl. mending good damages to building works. - E2 / 3.
Supplying and laying 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Polycab / Havell's / RR kabel) of the following sizes in the prelaid Polythene pipe and making necessary connection as required. (E-9/1).
i. 2x2.5 sq.mm. + 1x1.5 sq.mm. as ECC (For P.P. & computer board point & for main line of Low bay lights)
ii. 3x1.5 sq.mm (for separate 6A. & others)
iii. 2x1.5 sq.mm. (for call bell points)
iv. 2x4 sq.,mm + 1x2.5 sq.mm. as ECC (for A.C.& IT work)
v. 2x10 sq.mm. + 1x6 sq.mm. as ECC (from TPN DB to SPNBDB)
vi. 4x10 sq.mm + 2x6 sq.mm. as ECC (from VTPN DB/Panel to TPN DB)
vii. 4x10 sq.mm. (from VTPN DB to Timer)
viii. 4x35 sq.mm. (from Meter to Normal Panel via cut outs) - N.S (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
Supply & fixing 240V, 2nso. 6A socket with separate 2 nos. 6A piano key type switch (Mk Anchor) on sheet metal switch board embedded in wall incl. S & F 175 x 100 x 65 mm MS (16 SWG) switch board with Ph, N,E, Bar and bakelite / perspex top cover of 3mm thick by brass screws after making housing for switch by cutting bakelite / persppex cover and making necessary connections as required. (E3/10, E5/14 & 15)
Supplying & fixing 240V, 20A, plug socket with separate 20A piano key type switch (Anchor) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16 SWG) switch board and bakelite / perspex top cover of 3mm thick by brass screws after making housing for switch by cutting bakelite / perspex cover and making necessary connections as required (E6/22)
Supply & fixing 240V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6A & 1 no. 20A piano key type switch, indicator (Mk Anchor) & 20A switch type SP MCB (Havell's) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16 SWG) switch board and bakelite / perspex top cpver of 3mm thick by brass screws after making housing for switch by cutting bakelite / perspex cover and making necessary connections as required (E7/26)
Supply and fixing 240V, 20A plug socket (Anchor) on sheet metal switch board incl. S & F 100x100x65mm MS (16 SWG) switch board and bakelite / perspex top cover of 3mm thick by brass screws after mking housing for switch by cutting bakelite / perspex cover and making necessary connections as required (E6 / 17 b)
S&F 240V, 20 / 25A, Modular type starter with 25A. Modular switch type DP MCB (C Curve) and 4 Module type switch board and 1 no. Blank Plate flushed in wall with top cover plate incl. necessary connection as per GS (Legrand / Cabtree) (E-19/17)
Supplying & fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall as per GS. - E-4/11.
i. 240 mm x 200 mm x 65 mm
ii. 200 mm x 150 mm x 65 mm
iii. 100 mm x 100 mm x 65 mm
iv. 150 mm x 100 mm x 65 mm
v. 300 mm x 200 mm x 65 mm
Supply & fixing bakelite / perspex top cover on existing inspection board by brass screws. - E-5 / 13.
i. 240 mm x 200 mm x 65 mm
ii. 200 mm x 150 mm x 65 mm
iii. 100 mm x 100 mm x 65 mm
iv. 150 mm x 100 mm x 65 mm
v. 300 mm x 200 mm x 65 mm
Finishing of the PVC insulated wire ends by socketing with pin / ring type copper sockets nd insulated tapes etc., including supplying sockets, tapes. - F-5/9.
i. 4 sq.mm.
ii. 2.5 sq.mm.
iii. 10 sq.mm.
iv. 35 sq.mm.
Supplying of 4 long twin LED Tube light fitting, complete with all accessories & 2 nos. 230V. 20W. T-LED Tubes of PC body. (Philips - TMC 501 2xT - LED 20W with two nos. LED tubes - MAS LED tube 1200 mm 18W865 T8, CG - Magik / Wipro / Bajaj, TWPP020 / KCCF020 - N.S. with 3 years warranty. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
Supplying of 4 long single LED Tube light fitting, complete with all accessories & 1 no. 230V. 20W. T-LED Tubes of PC body. (Philips - TMC 501 2xT - LED 20W with one no. LED tubes - MAS LED tube 1200 mm 18W865 T8, CG - Magik / Wipro / Bajaj, TWPP02PC / KCCF020 - N.S. with 3 years warranty.(S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
Fixing only single / twin Tube light with fitting complete with all accessories directly on wall and suitable size of MS fastener as per GS - C-2/14d.
Fixing only singl / twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 no. 20mm dia EI conduit (14 SWG) supports fixed with "L" type MS clamp whose one side fixed on ceiling with suitable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, "L" type (125mmx125mm) 6 mm thick and 25 mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20mm (1.5 sq.mm) flexible copper wire of 1.10 mt. length. (C-2/14).
Supply & fixing of box type fan clamp of 150mm dia & 80mm depth made of 16 SWG CRCA sheet with one end duly sealed by cover, properly welded, incl. S&F 12mm dia 600mm long MS rod duly bent by heat treatment at the centre position of rod to grip fan bobbin properly, incl. binding the rod and fan box with reinforcement by 22 SWG steel binding wire, incl. supplying & covering the box with alkathene sheet, placed in order to prevent concrete form entering the box (D-14/31).
Supply & fixing socket type fan regulator (step type) ( brand approved by EIC) on existing sheet metal switch board with bakelite / perspex top cover by screw incl. mking necessary connections etc. (E-6/18b)
Supply of ceiling fan of following size with complete accessories like blades, canopy, fork, rubber bush etc. (Orient (PSPO) / Crompton Aura) - N.S Gold model Avater). (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. (C3/21)
Supplying of following Heavy duty exhaust fan with blades & others accessories. (EPC / Crompton make) - N.S. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
i. 9" Heavy duty exhaust fan.
ii. 12" Heavy duty exhaust fan.
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter:
Supply & fixing GI sheet (20SWG) metal cowl with MS flat iron frame & GI wire mesh on wall with necessary bolts & nuts (6mm dia x 62 mm long) (D-14/33)
a) Supply 230V 9W pin type LED bulb (Philips, Magik / Wipro make) on holder - N.S with 3 years warranty. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
b) Fixing only lamp (C2/11)
Supplying & fiixng 240V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S & F HW board (D13/20a)
Supply LED mirror light fittings (Philips / Wipro / Magik /Bajaj) with 3 years warranty. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
a) Supply outdoor type LED bulkhead light fittings (Make- Philips - WT202W LED6S NW PSU S2 PC / Magik HWAR012C - N.S with 3years warranty.(S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
b) Fixing only bulkhead ceiling fitting on wall / ceiling by screws etc. (C2/13)
a) Supply LED Step lamp. (Philips / Legrand / Magik / Wipro) - N.S. with 3 years warranty. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
b) Fixing only pendent light fitting (Mirror light / Step lamp) Complete with lamp, shade and 24/0.2 mm (1.5 sq.mm) flexible copper wire incl. S&F pendent holder (C2/12)
S&F of 230V, 40W LED lowbay luminaries with all accessories on structure / surface including necessary connection as per GS & hanging arrangement as per direction of EIC (Make Magik PCCR045C / Philips / Wipro) - N.S with 3 years warranty. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
Excavation of soil for installation of Earth Electrode and filling & ramming. - Soft Soil. G1/1.
Supplying with 50mm dia Gi pipe 3.64mm thickx3.04 Mts. Long as per GS.- G 2.a. By ISI-Medium Gi pipe
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar as per GS- G-2/4.a.
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire on wall/floor as per GS-G-2/5.iv
S & Delivery of the following sizes 1.1 kv grade XLPE/PVC cable (Make: Havells/Universal/Polycab/RR Kebal)-N.S. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
2 Core x 10 sqmm.AI. Armoured cable.
4Core x 35 sqmm.AI. Armoured cable.
4 Core x 16 sqmm.AI. Armoured cable.
4 Core x 70 sqmm.AI. Armoured cable.
3 Core x 2.5 sqmm.Copper Unarmoured cable
Laying of cable on Wall/Surface incl. S & f Ms saddle with earthing attachement in 10 SWG GI (Hot Dip) wire ,making holes etc. as necy. Mending good damages and painting -F-1/2.
2 Core x 10 sqmm.AI. Armoured cable. With 1 no. 10 SWG GI wire
4 Core x 35 sqmm.AI. Armoured cable. With 2 nos. 10 SWG GI wire
4 Core x 16 sqmm.AI. Armoured cable. With 2 nos. 10 SWG GI wire
4 Core x 10 sqmm.AI. Armoured cable. With 2 nos. 10 SWG GI wire
3 Core x 2.5 sqmm.Copper Unarmoured cable
Supplaying and fixing compression type gland complete of following XLPE/PVC armoured cable as below. F-4/7.
2 Core x 10 sqmm.AI. Armoured cable.
4Core x 35 sqmm.AI. Armoured cable.
4 Core x 16 sqmm.AI. Armoured cable.
4 Core x 70 sqmm.AI. Armoured cable.
Finishing the end of following XLPE/PVC armoured cables as per GS incl. supplying and fixing solderless socket (Dowels make) etc. F-5/8.b.
2 Core x 10 sqmm.AI. Armoured cable.
4Core x 35 sqmm.AI. Armoured cable.
4 Core x 16 sqmm.AI. Armoured cable.
4 Core x 70 sqmm.AI. Armoured cable.
Supplying & fixing 40mm dia medium gauge GI Pipe (ISI-Medium) Protection with necessary fittings and jointing materials as required F-6/11.
S & F 3-ph. Timer controller in 2+14-way SPN-DB with 1 no front open hinged type door for providing incomming and outgoing copper wires and other accessories. The box having following accessories: a) 1 no. 230V 32A FP MCB, b) 1 no. 32 A 4 pole power contractor, c) 1 no. toggle switch, d) 1 no. timer clock, e) Indicating lamps etc. incl. suitable size of interconnecting wire (power line by 10 sq.mm. wire, control circuit by 1.5 sq.mm., indicating circuit by 1.5 sq.mm.) as required as per GS. - N.S. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
S&F 80mm dia x 1.5 mts. Long GI pipe (ISI-Medium) pole incl. S & F of 1 no. GI sole plate.(F6/11)
Erection of single steel tubular pole of length 1.5 M with / without sole plate & cap etc. in CC foundation (proportion and dimension indicated below), having 600x600x150 mm thick CC (4:2:1) base block below sole plate / pole with hard jhama metal including CC (6:3:1) muffing 0.30 mts. dia and 0.30 mts. above ground level including 3 mm thick neat cemented finish and GI earth bolt after making drilled holes etc. on pole & carriage of pole upto 1.6 km from store to work-site including filling up the excavated earth pit with shifted soil and ramming properly. (Size 0.6x0.6x1.70 mts.) (H1/1)
S/F single arm header fabricated with 100 mm dia GI pipe ( pole cap) of 10" height welded with 1.5 m long 40 mm dia GI pipe at an suitable angle incl. S / F nuts, bolts washer etc incl. painting as per GS - N.S. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
S&D 230V 90W LED street light fittings (Philips - BRP410 LED 091 CW HE MR PC S2 PSU GR / Magik Orion SPR090W / Wipro) - N.S. 3 years warranty. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
S&D 230V 72W LED street light fittings (Philips - BRP409 LED 074 CW HE MR FG S1 PSU GR / Magik Orion SPR072W / Wipro) - N.S. 3 years warranty. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
Fixing only LED street light fittings on pole incl. necessary connection as required as per GS - N.S. (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
Supply & fixing 200x150x100 mm GI waterproof type looping cable box on pole having 4 mm thick comprising of one 250V 16A kit-kat fuse unit, one NL on porcelain insulator as per GS incl. necessary connection & painting with anticorrosive paint as per GS - H-5/5.
S&laying 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core 3 x 1.5 sq.mm. copper wire as loop wire. (from loop box to fittings). E9/1.
S & F lightning conductor Air-terminal made of 15mm dia 1500 mm long Gi pipe (ISI Medium) having five prongs of 4 SWG GI (Hot Dip) at top with 85 mm dia 6 mm thick GI base plate at bottom incl. Necessary holes etc. duly grouted on the parapet etc. In CC mortar (4:2:1)-J-1/1.
S & F of SWG GI (Hot Dip) wire on parapet / Roof/Plinth/ Surface of wall for lightning condutor as required (For Horizental rins) with 40mm long GI staples spaced not exceding 1300 mm apart incl. mending good all the damages to the bulding works[J-1/2].
S & F of SWG GI (Hot Dip) wire on wall for the lightning condutor as required ( for vertical run) with staples (40 mm long ) spaced not exceeding 1 Mtr. apart incl. Mending good the damages to building works (excluding hire charges of scaffolding ) [J-1/3].
Making solderd joints between conductors , conductors and air terminals for 4 SWG GI (Hot Dip) wire incl. supply of jointing materials and painting with 2 (two) coats of bituminous paint . [J-1/5]
making solderd joints between conductors and down pipes/ other metalic objects for 14 SWG GI (Hot Dip) wire including supply of necessary 4 SWG GI (Hot Dip) wire , jointing materials and painting with 2 (Two) coats of bituminous paint . [J-1/6]
Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage , for LC installation , per storey of building per vertical run. [J-1/7]
Cutting cornices/ steps etc.including cutting recess in building etc. & supply & fixing 15 mm bore (ISI-Medium) GI pipe protection as below and mending good damages to the building works: Length above 0.5 Mtr (J1/4a).
Supply & fixing of testing joints by 20 mm x 3 mm thick GI (Hot Dip) strip 25mm long grouted on wall having clearance of 6 mm from wall for making connection with thimbles at the end of 7/10 SWG GI (Hot Dip) stranded wire and 4 SWG GI (Hot Dip) wire of vertical conductor and conductor from earth electrode complete with S & F thimbless, GI bolts , nuts check- nuts, spring washer etc.as required .[J-2/13]
S&F 230V, 40W LED post top type gate light on S&F 40 mm dia 2' length GI pipe grouted in pillar (Magix APBY040W/Philips/Wipro) after cutting the pillar and mending goods damages incl. Necessary connection with S&F suitable size Net guard on gate light . N.S. with 5 years warranty (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
Supply & installation of angle frame mounting rectangular shape Glow sign board size of (12'x4'x6'') fabricated with 25x25x6 mm Ms. Angle and 25x6 mm Ms. Flat front side of the board making arrangement for hinged type door with locking arrangement made with Ms. angle incl. provision for fixing the poly carbonate sheet facial approved colour (2 mm thick) with computerised lettering rigidly fixed on angle iron frame. The sign board should be by 10 nos.20W LED tube light (Make- Philips / Magix/ Havells) and incl. Necy arrangement & connection . Back side of the board should be covered with 14 SWG GI sheet to protect rain water. The sign board should be fixed on roof by 4 nos. 40x40x6 mm angle bar which will be fixed on wall by fust nuts. necessary nuts & bolts etc. & oainting as per direction of E.I.C The cost of transportation and scaffolding charges are included with the rate. The sign board must be inscripted as per the authority with biswa bangla logo as per direction of E.I.C- N.S (S.E.W.E.C. Estimate No: 44/WEC of 2022-2023)
Supply, installation, testing commissioning of Gong Bell of 30cms (12inch) size single phase220/250V AC.
SITC of Surge protection devices of 275VAC, 1P+1N, Type 2, 40KA.
PART-B (S.I.T.C of Split AC machines)
Supply of Split Air Conditioner fitted with Rotary Compressor: Cooling Capacity nominal (BTU/Hr):18000;Cooling Cap(Min) ; Min Room Dischrge Air Flow(Cf.m):777; Sheet Metal Body enclosed PCB; Star Rating : 03,410A refrigaren gas ( with or without Installation Kit of 12 fts.) Capacity 1.5 Ton - 3 nos. and 2 ton 1 no. [Make:Voltas/HItachi/O-General/Mitsubishi Electric/Daikin]. (Rate of Chief Engineer,Electrical, P.W.D Vide memo no 34/CEE/2020 dated 07.01.2020) Installation testing commissioning of newly supplied split AC Machine & dismantling and re-installation of existing AC machines including iron braket (power coated)for outdoor unit Supply of Copper Refrigeration pipe line for Suction(5/8"OD SD 0.7mm thick) line Supply of Copper Refrigeration pipe line for Liquid(1/2"OD HD 0.7mm thick) line Supply of 9mm thick Nitrile rubber insulation for above said pipes Supply, installation & commissioning PVC Drain pipe line (25mm OD HD 1mm thick) with insulation & supports & brackets (For 1.5Tr Conealed split AC)
PART-C (S.I.T.C of DG Set)
Supply, delivery at site foundation, commissioning of 415V, 50Hz, 30 KVA, 3 phase silent new DG set, comprising of Engine, alternator, seperate AMF panel, Base frame, Fuel tank, Battery, CPCB-II approved Engine & Acoustic Enclosure having following specifications :- (Rate of Chief Engineer, Electrical, P.W.D Vide memo no 34/CEE/2020 dated 07.01.2020)
Engine:-
Make: Cummins/ Caterpiller/ Volvo/ Ashok Layland*
Engine Type: 4 Stroke Diesel Engine
Rated Output: 42 BHP or Higher
Duty: PRIME*
Cooling: Water cooled with radiator*
Cylinder: 4
Aspiration: T.A.
Type of Governer: Electronic
Fuel Tank Capacity: Minimum capacity 65 Ltrs.
Fuel consumption at 75% rated Load with Radiator or Fan: 5.8 Ltr./ Hr. Or Less
Fuel consumption at 100% rated Load with Radiator or Fan:7.6 Ltr./ Hr. Or Less*
Overload capacity: 10% overload for one hour for every 12 hours continious running at full load or better*
Engine instrument Panel: Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls: Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Ehgine Water Temp. Warning/ Shutdown, Sensor failure Indicator, Engine overspeed indicator, Battery charging and low battery indicator
Exhaust Silencer: Residential Type
Starting system: 12V/24V starting system complete with starter motor, charging alternator with rectifier and cutout as per manufacture standard.
Battery: Lead Acid, Low Maintenance of SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning.
Alternator:-
Make: Stamford/ Leroy Somer/ Catepillar
Rating: 415V, 3 Ph, 50Hz, 30KVA, 1500rpm
Type: Brushless, self excited and self regulated
Insulation: Class H
Protection: Screen-protected drip proof with Min.IP-23 degree of protection
Voltage Regulation (max): + 1%
Winding connection: Star with Neutral
Total Distortion factor: Less then 3%
Total Harmonic distortion in output waveform: < 5%
AMF Panel:-
Cubical type floor mounted AMF panel made from 16 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 30 KVA DG set having following specification/ features.
i) 125A, 4P,MPR based MCCB with O/L, S/C, E/F protection & , U/V release etc.*
ii) In Built By-Pass switch for 125A capacity.*
iii) On-delay timer for load change over
iv) On-delay timer for engine shut off
v) Engine On-Off switch (Push button type)
vii) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set'and 'battery charger on'.
viii) Audio visual alarm for 'Low lubricating oil pressure ', 'High water temperature, Start failure', and DG over load'.
x) Microprocessor based relay with composite meter for digital display of following.
Generator voltage/AC Mains voltage
Generator Current in all phases
Frequency
Power Factor
Energy
Indication for alternator supply
Running time indications number of hours of operation and service intervals, service due indications
The AMF panel must be designed to ensure troble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
Acoustic Enclosure
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustict enclosure must be certified as per CPCB-II norms.
Base Frame
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
Installation work & Terms & Conditions
(i) Rate should be quoted inclusive of all applicable taxes and Duty etc.
(ii) All materials, equipments & accessories must conform to relavent IS /IEC specifications. The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer.
(iii) Nacessary manufacturer's test certificate for Desiel Engin, Alternator etc. Will have to submit in triplicate copy during delivery of the equipment.
(iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from competant Authority (As per CPCB-II).
(vi) The entire set must be warranted atleast 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier.
Extending the exhaust pipe with 100 mm. dia MS black pipe (Thickness 4 mm) including connection with the existing silencer attached with the flexible coupler and S&F flange, nuts, bolts & washers etc. & necessary fixing materials etc. as required from DG set upto 2.5 Mts high of the near higher installation with Asbestos rope / 2'' glass wool insulation and chicken net and Aluminium fol covering, with end cap with suitable high temperature painting.
S&F special type MS angle iron bracket support made of 40x40x6 mm. MS angle with flat iron clamp with nuts, bolts & washers etc. for 100 mm. dia MS black pipe. (Vertical Run).
Filling of HSD oil for initial refill with transportation.
Supply and delivery of best quality oil hand pump with 1" dia PVC flexible pipe (10 mtr. approx.)
Supply and delivery of 200 ltr. Capacity heavy gauge MS sheet barrel
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. Long With TATA-Medium GI pipe as per GS . [ 2(a)/G-1]
Connecting the equipment with 25mmx6mm galvanised MS hot dip flat on wall/floor as to GS. [5d/G-3]
Earth work in excavation of foundation trenches of drains, in all sorts of soil including removing, spreading or stacking the spoils within a lead of 75m as directed. The item includes necessary trimming the sides of trenches, levelling, dressing and ramming the bottom, bailing out water as required complete.( Depth of Excavation not exceeding 1500 mm ) [ Page- 1, Item no.- 2(a) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Earth work in filling in foundation trench or plinth with good earth in layers Board a) With earth obtained from excavation of foundation 1/5th of excavated earth [ Page 1, Item no.3(a) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Filling in foundation or plinth by silver sand in layer a) With earth obtained from excavation of foundation 1/5th of excavated earth [ Page- 2, Item no.- 4(A) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Single Brick flat soling of picked jhama bricks including ramming and dressing bed to proper level and filling joints with local sand [ Page- 14, Item no.1 of PWD Schedule of Rates, Volume-I of Building Works, 2017]
Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction.. A)For works in foundation and top of ground floor / upto 4 m i) Tor steel/ Mild steel SAIL/ TATA/RINL. [ Page- 43, Item no.40(a)(i)(I) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Ordinary cement concrete (mix 1:1.5:3) with graded stone chips (20 mm size) including shuttering and reinforcement, if any, in ground floor as per relevant IS codes ( Pakur variety ) [ Page 26, item no.10 of PWD Schedule for Building works with latest ammendmen ]
Brick work with 1st class bricks in cement mortar (1:4) In foundation and plinth. [ Page- 16, item no.-13(a)-(i) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Plaster (to wall, floor, ceiling etc.) of 10 mm thick with sand and cement with 1:4 cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and drip course, scaffolding/staging where necessary (Ground floor).[Excluding cost of chipping over concrete surface] [ Page- 189, item no.-1(ii)-(c) of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
Neat cement punning about 1.5mm thick in wall, dado, window sill, floor etc. NOTE: Cement 0.152 cu.m per 100 sq.m. [ Page- 192, item no.-15 of PWD Schedule of Rates, Volume-I of Building Works, 2017 ]
PART-D (S.I.T.C of Solar Photovoltic Panel)
Supply, Installation, Testing and Commissioning of on-grid Solar Photovoltaic Power Plant conforming to MNRE specifications as amended, consisting of C-Si Mono/C-Si Poly/ Mono PERC halfcut silicon solar cells, net metering facility, necessary protections, earthing, mounted on GI structure of suitable strength with incorporation of following components as required to complete the project successfully:- (Rate of Chief Engineer,Electrical, P.W.D Vide memo no 34/CEE/2020 dated 07.01.2020)
a) Solar Photovoltaic Module of capacity 330 Wp or above, manufactured in India, conforming to IS 14286/IEC 61215, IS/IEC 61730-Part-1, IS/IEC 61730-Part-2. Solar Photovoltaic Module conversion efficiency shall not be less than 19% PV modules used in solar power plants/ systems must be warranted for their output peak watt capacity, which should not be less than 90% at the end of 10 years and 80% at the end of 25 years. [Make: Vikram Solar/Adani/SOVA/Goldi Green/BHEL/PV Power Tech/Lubi/Nano/Maxx/Navitas/Navi Solar/Tata Solar/Panasonic/WAAREE]
b) Power Conditioning Unit (PCU) of 350-800 V or higher DC Input voltage range and 415 V AC, three phase, 4 wire, 50Hz +/- 2.5 Hz, output voltage suitable to generate AC Power with efficiency not less than 97%, total harmonic distortion less than 3% and suitable for ambient temperature from 0 to 50 degree C. The PCU shall adjust the voltage and frequency level to suit the Grid Voltage Frequency. [Make:ABB/Thea/Delta/Schneider/Sungrow/Power one/ SMA/ Solar Edge/Solis/Frontier/Growatt)
c) Data Monitoring System complete with accessories.
d) Fixing of Array junction box & Main junction box with IP 65 protection and termination arrangement for incoming and outgoing cable along with glands, lugs and other accessories etc. as required.
e) The proposed PV module panel frame structure shall be so fabricated as to be grouted on Roof top on its legs. The legs of the structure shall be fixed and grouted in the PCC/RCC foundation column made with 1:2:4 cement concrete. The foundation shall support SPV modules at a given orientation, absorb and transfer the mechanical wind speed of 120 KM/hr (minimum).
f) Conventional type Lightning protection of adequate quantity as per design, should be approved by EIC.
g) Surge voltage protection system as per guideline.
h) Connections & Interconnections by supplying & fixing of adequate size XLPE insulated copper conductor 1.1 kV grade armoured power and control cables(Make:RR Kabel/Polycab/Havells) between solar modules, main power cable to grid supply PCU unit along with supplying & fixing of necessary channel/conduit lugs and other accessories etc. as required.
Supply and installation of 125A, 415V, 50 HZ ATS with Cubical panel and necessary internal wiring.
PART-E (Source Of Electrical Power )
PART-F (EPBX System )
Supply & Installation of Digital EPABX with 4 PnT & 16 Extensions expandable upto 32 Extns. * 100% Non Blocking * 3 party conference * Caller Line Identification at each Extns. *Extn. to Extn. Call (Inter-Com). * Access to P&T Lines. * Call transfer/call pickup * Extension Privacy * High system reliability * Flexible feature programming * Loop Resistance:- 600 ohms. For Extensions & 1200 ohms. for P & T Line.Make: Projility (formally known as Siemens)/Syntel/ Neos/Matrix . 1 year onsite warrenty
SITC of cat 3 I/O with single module face plate & pvc back box, Make: D-link/Legrand/Molex
Supply & drawing of 2 Pair, Telephone cables (0.5 mm copper conductor) thru' 20 mm ISI marked pvc pipe with pvc clip, shuddle, necessary hardwares etc. Make- Finolex/polycab/havells.
Supply & Fixing of Telephone Instrument, make: BEETEL/LXTEL
20 Pair MDF with original Krone Module.
PART-G (CCTV )
SITC of IP 4MP IR Dome Camera (complete with perpetual license) with Motorized Varifocal lens having minimum technical specification: Image Sensor: 1/2.5” Progressive Scan CMOS; Min. Illumination: Color: 0.001 lux @(F1.6, ACG ON), 0 lux with IR; Shutter Speed: 1s to 1/100,000 s; Day & Night: IR Cut Filter; 3-Axis Adjustment Pan; Digital Noise Reduction: 3D DNR; WDR: 120dB; Focal length: 2.7 to 13.5 mm; View Angle:Horizontal FOV: 101.4° - 23.8°; Aperture: F1.6 - F3.3 with Auto focus; Lens Mount: Ø14; IR Range: 40 m or higher; Video Compression Main stream: S+265/H.265/H.264+/H.264/MJPEG; 3 streams, Video Bit Rate: 32 Kbps to 16 Mbps; Image Max. Resolution: 2592 X 1944, 50Hz: 25fps; Image Enhancement: BLC/3D DNR/HLC; Image Setting: Rotate mode, saturation, brightness, contrast, sharpness adjustable by client software or web browser; Day/Night Switch: Day/Night/ Auto/Schedule/Triggered by Alarm In; Alarm Trigger: Motion detection, video tampering, network disconnected, IP address conflict, illegal login, Protocols: TCP/IP, ICMP, HTTP, etc; Edge Analytics: line crossing, region entry/exit, intrusion, video blur;
Simultaneous Live View: Up to 6 channels; User/Host: Up to 7 users, 3 levels: Administrator, Operator and User; Interface: 1 RJ45 10M/100M self-adaptive Ethernet port, Audio:1 input, 12V DC, Built-in Micro SD/SDHC/SDXC slot up to 512 GB / H.265 encoding supports; Operating Conditions Temperature: -30 °C to +60 °C; Power Supply: 12 VDC, PoE (802.3af); ONVIF PROFILE S/T/G, SDK, CGI, P2P Including Centralised VMS Software License & Mounting Bracket for Camera (if required as per site). Material: Metal; Protection Level: IP67, IK10, Lightning Protection, Surge Protection and Voltage Transient Protection. REGULATORY: CE, FCC, UL/BIS. Certification: Quality Management, Environmental Management, Information Technonology Service Management, Information Security Management, Occupational Health and Safety Management, RoHS, Cyber Security. OEM should be in accordance with CMMI Level 5 compliance. Warranty: onsite comprehensive warranty with parts and service (Warranty Period up to 3 Years) (Make: . Make:Honeywell, Infinova, Panasonic, Hikvision, Alcon,Matrix)
SITC of SITC of IP 4MP IR Bullet Camera (complete with perpetual license) with Motorized Varifocal lens having minimum technical specification: Image Sensor: 1/2.8” Progressive Scan CMOS; Min. Illumination: Color: 0.001 lux @(F1.6, ACG ON), 0 lux with IR; Shutter Speed: 1s to 1/100,000 s; Day & Night: IR Cut Filter; 3-Axis Adjustment Pan; Digital Noise Reduction: 3D DNR; WDR: 120dB; Focal length: 2.7 to 13.5 mm; View Angle: Horizontal FOV: 101.4° - 23.8°; Aperture: F1.6 - F3.3 with Auto focus; Lens Mount: Ø14; IR Range: 70 m or higher; Video Compression Main stream:S+265/H.265/H.264+/H.264/MJPEG; 3 streams, Video Bit Rate: 32 Kbps to 16 Mbps; Image Max. Resolution: 2592 X 1944, 50Hz: 25fps; Image Enhancement: BLC/3D DNR/HLC; Image Setting: Rotate mode, saturation, brightness, contrast, sharpness adjustable by client software or web browser; Day/Night Switch: Day/Night/ Auto/Schedule/Triggered by Alarm In; Alarm Trigger: Motion detection, video tampering, network disconnected, IP address conflict, illegal login, Protocols: TCP/IP, ICMP, HTTP, etc; Edge Analytics: line crossing, region entry/exit, intrusion, video blur; Simultaneous Live View: Up to 6 channels; User/Host: Up to 7 users, 3 levels: Administrator, Operator and User; Interface: 1 RJ45 10M/100M self-adaptive Ethernet port, Audio:1 input, 12V DC, Built-in Micro SD/SDHC/SDXC slot up to 512 GB / H.265 encoding supports; Operating Conditions Temperature: -30 °C to +60 °C; Power Supply: 12 VDC, PoE (802.3af); ONVIF PROFILE S/T/G, SDK, CGI, P2P Including Centralised VMS Software License & Mounting Bracket for Camera (if required as per site). Material: Metal; Protection Level: IP67, Lightning Protection, Surge Protection and Voltage Transient Protection. REGULATORY: CE, FCC, UL/BIS. Certification: Quality Management, Environmental Management, Information Technonology Service Management, Information Security Management, Occupational Health and Safety Management, RoHS, Cyber Security. OEM should be in accordance with CMMI Level 5 compliance. Warranty: onsite comprehensive warranty with parts and service. (Warranty Period up to 3 Years) . Make:Honeywell, Infinova, Panasonic, Hikvision, Alcon,Matrix
SITC of PoE enabled, with PD: minimum 130 Watt Smart managed only, 1RU, GE Switch to be operated on 200- 240VAC, 50 Hz Supply, with perpetual license of OEM, having minimum technical specification: a) 8 x 10/100/1000Base-T Mbps PoE enabled host ports (Minimum); b) 2x 1GBase-F SFP uplink port; c) Forwarding performance/stacking bandwidth/ backplane speed (Minimum) of 14.9 Mpps; d) Fanless operation with operating temperature up to 50°C; e) DRAM and Flash RAM as per OEM; f) Software support with IPv4 routing (542 routes), multicast routing (IGMP) including necessary software license; g) Minimum switching capacity of 20 Gbps; h) Number of VLAN Supported: 32 (Minimum).; i) Total number of MAC Address: 8,000 (Minimum); j) Minimum Security: User privilege management and password protection, DoS attack defense, ARP attack defense, and ICMP attack defense, Binding of the IP address, MAC address, interface, and VLAN, Port isolation, port security, and sticky MAC, MFF, Blackhole MAC address entries, Limit on the number of learned MAC addresses, 802.1x authentication and limit on the number of users on an interface, AAA authentication, RADIUS authentication, HWTACACS authentication, and NAC, SSH v2.0, Hypertext Transfer Protocol Secure(HTTPS), CPU defense, Blacklist and whitelist; Access Security: DHCP Relay, DHCP Server,
DHCP Snooping, DHCP Security; k) Others: Applicable standards: IEEE 802.1p: CoS prioritization , IEEE 802.1Q: VLAN tagging, IEEE 802.1X: PortAccess Control, IEEE 802.3: 10BASE-T, IEEE 802.3u: 100BASE-T,IEEE 802.3ab: 1000BASE-T, IEEE 802.3z: 1000BASEX,IEEE 802.3af: Power over Ethernet, IEEE 802.3at: Power over Ethernet Plus, IEEE 802.3x: Pause Frames/Flow Control, IEEE 802.1D: Spanning Tree Protocol, IEEE 802.1s: Multiple instances of Spanning Tree Protocol (MSTP), IEEE 802.1w:Rapid reconfiguration of Spanning Tree Protocol, IEEE 802.3ad: Link Aggregation Control Protocol; l) REGULATORY: RoHS,WEEE, IEC 61000-4-2:2008, CISPR Class, ICES-003 Class A,UL,CSA 22.2,FCC,EN 300 386, CCC, ICES -003, CB. Make: Netgear/Zyxel/Cisco ,Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC of angular iron structure of 5mm thickness painted with redoxide anticorrosive paint for fitting multiple cameras including screws, nuts, bolts, plates etc as per direction of the EIC.
SITC of 10 TB Surveillance Hard Drive. Make: Seagate, WD, HP. Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC of best quality wireless Optical mouse with suitable battery Make: Logitech, HP, Lenovo
SITC of Commercial Full HD LED Display of 43" Indoor Type with following Configuration: Size (diagonally): 43", Panel Technology Vertical Alignment / IPS, Type: LED, resolution: 1920x1080, aspect ratio: 16:9, native contrast ratio: 1000:1 Or Better, brightness: 350 nits or more, Response time: 8 ms(Typ) or better, CONTINUOUS DUTY, Working Voltage AC 100-240V, 50Hz; Refresh Rate 50Hz or better operating temperature: 0°C- 40°C or better, Humidity: 20-80%, IP rating: IP 5x, , Built in Speaker (10W x 2) or better, Communication Interface Inputs ( viz. HDMI, USB 2.0, RS232,RJ 45) certification: CE FCC UL, BIS Including HDM1 Cable and with swivel fixing arrangement with All other Accessories as per site requirement. Make: Sony, Samsung, Panasonic, LG. Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC of HDMI Cable 5Mtr
SITC of CAT6, U/UTP, Outdoor Information Outlet with RJ45 adapter, backbox etc having minimum technical specification Outdoor type weatherproof boxes for camera cable connectors and base mounting I/O, IP 56/66. Ref. Make: R&M, Molex, 3C3, Legrand, Commscope, Belden, Derwiser. Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service except force majeure
SITC of PATCH CHORD Category 6 4-Pair, SF/UTP, Horizontal cable, 23 AWG solid bare copper conductors WITH RJ45 CONNECTOR AT BOTH END 1 MTR LENGTH Ref. Make: Molex, 3C3, Legrand, Commscope, Belden, Derwiser Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service except force majeure
SITC of CAT 6 U/UTP 24 Port Modular fully loaded patch Panel ISO 11801 AMD 1 Class EA TIA-568-C.2 Cat 6 ANSI/EIA1069-A IEC 60603-7 Ref. Make: Molex, 3C3, Legrand, Commscope, Belden, Derwiser Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service except force majeure.
SITC of WALL mounted Network Rack Cross Connect Equipments 12U Double Section Wall Mount (Minimum depth of 600mm) Rack with, Rack mount tray, Horizontal Cable Manager 2 Nos, Fan Housing Unit 90 CFM, PDU 6 Ports 1 No. and H/W front Panel (20 Nos/pkt) 2 pkt. Make: Make: Tata, Vertiv, Netrack, Valrack, Rittal, APW, MRS Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC of single Mode LIU, 24F, 1U Drawer shelf, Fully loaded with SC, OM3 Pigtails, Adapters, Splice Trays, Fiber Management Rings and Splice Slvees. Ref. Make: R&M, Molex, 3C3, Legrand, Commscope, Belden, Derwiser. Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service except force majeure.
SITC of OFC Joint and Closer including all accessories (Splicing, Pigtails, etc) as per sites requirements Ref. Make: Dlink, Tplink, 3M, ActiLink, Equivalent Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service.
SITC of 10Gb Duplex single mode 50/125 OM3 LSZH antirodent Armoured Fiber Patch Cable, SC-SC/ SC-LC/ LC-LC as per sites requirements - 3 MTR Ref. Make: Molex, 3C3, Legrand, Commscope, Belden, Derwiser Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service except force majeure.
SITC of 1GBase-F single Mode modular and field replaceable SFP module of same rating of Ethernet Switch and OEM Ref. Make: Cisco, Allied telesis, Cambium networks, Zyxel, Netgear Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service except force majeure.
SITC 600 VA (0.6/68 (KVA/VAH)) Line-Interactive UPS having minimum technical specification: 600VA /360 Watt Line Interactive Micro Processor Controlled UPS; Input Volt. Range: 140-300V (Full Load); Nominal Input Freq: 50Hz; Output Volt. Range: 230V +/- 10%(Batt. Mode); Output Freq. Range: 50Hz +/- 1%; Receptacle: 3 x Indian Socket; Internal Batt: 2 x 7AH/9AH; 90% Batt. Recharge: 4-6Hrs; Inverter Efficiency (%): >= 70%; Cold Start: Require; Operating Temp: 0-40*C; Surge Protection: Inbuilt; BIS Certification Require; Type Test Report; ISO 9001, ISO14001,OSHAS18001; Special battery terminal insulation cover and other accessories. Make: APC, DELTA, Eaton, Numeric, Orion; Make Battery: Amararaja- Quanta/Exide, Model: Tower Mount. Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC of Networking Horizontal armoured Cable, Antirodent,Antitermite 1000Base-T (Gigabit Ethernet), 100Base-T (Fast Ethernet), 10Base-T (Ethernet), 1-250 MHz (Minimum), Category 6, 4-Pair, U/UTP, 23 AWG solid bare copper conductors with FEP insulation,polyester separator, LSZH OUTER sheath COVER as to standard of ISO/IEC 11801 Ed. 2.0, EN 50173-1 and TIA/EIA 568C,(Make-Comscope/Belden/R&M) Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service except force majeure.
SITC OFSingle Mode ( 6 Core), Uni Tube, anti rodent, ELECTRO CROMIUM COROGATED STEEL TAPE ARMOURED, 6 Fiber, 50/125 Micron, type OS2; AS/ACIF S008; AS/NZS 3080,ITU-T REC G 652D,AS/NZS 3080; IEC 60332-1; suitable for use in direct burial, outdoor ducts and backbone cabling; Corrugated Steel Tape Armour -Thickness > 0.125mm; Loose tube material : Single PBTP Loose tube filled with water blocking Thixotropic gel; Jacket material: UV Stabilised Polyethylene (HDPE); Operating Temperature : -10 Degree C to +70 Degree C; Tensile Strength : 1000N; Crush Resistance : 2000N/10 cm. Make: R&M, Commscope, Belden Warranty 03 years onsite comprehensive OEM warranty with parts and service.
PART-H (LAN/WAN )
SITC of CAT6 Indoor Information Outlet with RJ45 adapter, STP die-cast Jack with dust cover, 180° cable exit faceplate and 4 "x 4" backbox.(Make-R&M, Commscope, Belden) Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service.
SITC of STP type CAT6 unloaded Patch Panel 8 port : 1U 24P Flat, Front portable labelling ; Individually removable patch panel ports; Removable cable management shelf; ANSI and metric hardware kit included; industry standard 110 punch down tool. Make: R&M, Commscope, Belden Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC of STP Information Outlet socket for the above patch panels. Make: R&M, Commscope, Belden. Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service.
SITC of PoE enabled, with PD: minimum 130 Watt Non-POE, 1RU, GE Switch to be operated on 200- 240VAC, 50 Hz Supply, with perpetual license of OEM, having minimum technical specification: a) 8 x 10/100/1000Base-T Mbps PoE enabled host ports (Minimum); b) 2x 1GBase-F SFP uplink port; c) Forwarding performance/stacking bandwidth/ backplane speed (Minimum) of 14.9 Mpps; d) Fanless operation with operating temperature up to 50°C; e) DRAM and Flash RAM as per OEM; f) Software support with IPv4 routing (542 routes), multicast routing (IGMP) including necessary software license; g) Minimum switching capacity of 20 Gbps; h) Number of VLAN Supported: 32 (Minimum).; i) Total number of MAC Address: 8,000 (Minimum); j) Minimum Security: User privilege management and password protection, DoS attack defense, ARP attack defense, and ICMP attack defense, Binding of the IP address, MAC address, interface, and VLAN, Port isolation, port security, and sticky MAC, MFF, Blackhole MAC address entries, Limit on the number of learned MAC addresses, 802.1x authentication and limit on the number of users on an interface, AAA authentication, RADIUS authentication, HWTACACS authentication, and NAC, SSH v2.0, Hypertext Transfer Protocol Secure(HTTPS), CPU defense, Blacklist and whitelist; Access Security: DHCP Relay, DHCP Server, DHCP Snooping, DHCP Security; k) Others: Applicable standards: IEEE 802.1p: CoS prioritization , IEEE 802.1Q: VLAN tagging, IEEE 802.1X: PortAccess Control, IEEE 802.3: 10BASE-T, IEEE 802.3u: 100BASE-T,IEEE 802.3ab: 1000BASE-T, IEEE 802.3z: 1000BASEX,IEEE 802.3af: Power over Ethernet, IEEE 802.3at: Power over Ethernet Plus, IEEE 802.3x: Pause Frames/Flow Control, IEEE 802.1D: Spanning Tree Protocol, IEEE 802.1s: Multiple instances of Spanning Tree Protocol (MSTP), IEEE 802.1w:Rapid reconfiguration of Spanning Tree Protocol, IEEE 802.3ad: Link Aggregation Control Protocol; l) REGULATORY: RoHS,WEEE, IEC 61000-4-2:2008, CISPR Class, ICES-003 Class A,UL,CSA 22.2,FCC,EN 300 386, CCC, ICES -003, CB. Make: Netgear/Zyxel/Cisco Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC of PATCH CHORD Category 6, 4-Pair,CAT6 SFTP Patch cord (0.2 Mtrs) - Conductor size: 24 AWG stranded; copper wire; Nom. O.D.: 5.9mm; Sheath: LS0H; Bend radius: 4X O.D; Operating temperature range: -25°C to +55°C; CSA FT1, IEC 60332- 1,IEC 61034; ISO/IEC 11801:2002/Amd 2:2010; Cat 6-, TIA-568.2-D Cat 6, EN 50173-1:2011 Class E, ETL Verified AS/CA S008:2020. Make: R&M, Commscope, Belden Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC of PATCH CHORD Category 6, 4-Pair,CAT6 SFTP Patch cord (2 Mtrs) - Conductor size: 24 AWG stranded; copper wire; Nom. O.D.: 5.9mm; Sheath: LS0H; Bend radius: 4X O.D; Operating temperature range: -25°C to +55°C; CSA FT1, IEC 60332- 1,IEC 61034; ISO/IEC 11801:2002/Amd 2:2010; Cat 6-, TIA-568.2-D Cat 6, EN 50173-1:2011 Class E, ETL Verified AS/CA S008:2020. Make: R&M, Commscope, Belden Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC of Networking Horizontal armoured Cable, Antirodent,Antitermite 1000Base-T (Gigabit Ethernet), 100Base-T (Fast Ethernet), 10Base-T (Ethernet), 1-250 MHz (Minimum), Category 6, 4-Pair, U/UTP, 23 AWG solid bare copper conductors with FEP insulation,polyester separator, LSZH OUTER sheath COVER as to standard of ISO/IEC 11801 Ed. 2.0, EN 50173-1 and TIA/EIA 568C, (Make-Comscope/Belden/R&M) Warranty: 03 (Three) years onsite comprehensive OEM warranty with parts and service except force majeure.
SITC of WALL mounted Network Rack Cross Connect Equipments 6U Double Section Wall Mount (Minimum depth of 600mm) Rack with, Rack mount tray, Horizontal Cable Manager 2 Nos, Fan Housing Unit 90 CFM, PDU 6 Ports 1 No. and H/W front Panel (20 Nos/pkt) 2 pkt. Make: Make: Tata, Vertiv, Netrack, Valrack, Rittal, APW, MRS Warranty 03 years onsite comprehensive OEM warranty with parts and service.
SITC 600 VA (0.6/68 (KVA/VAH)) Line-Interactive UPS having minimum technical specification: 600VA /360 Watt Line Interactive Micro Processor Controlled UPS; Input Volt. Range: 140-300V (Full Load); Nominal Input Freq: 50Hz; Output Volt. Range: 230V +/- 10%(Batt. Mode); Output Freq. Range: 50Hz +/- 1%; Receptacle: 3 x Indian Socket; Internal Batt: 2 x 7AH/9AH; 90% Batt. Recharge: 4-6Hrs; Inverter Efficiency (%): >= 70%; Cold Start: Require; Operating Temp: 0-40*C; Surge Protection: Inbuilt; BIS Certification Require; Type Test Report; ISO 9001, ISO14001,OSHAS18001; Special battery terminal insulation cover and other accessories. Make: APC, DELTA, Eaton, Numeric, Orion; Make Battery: Amararaja- Quanta/Exide, Model: Tower Mount. Warranty 03 years onsite comprehensive OEM warranty with parts and service.
PART-I (Computer & Accssories )
Supply and Installation of Slim Desktop PC, Operating System: Windows 11 Home & MSO 2021, Processor Name: Intel® Core™ i5-12400T (up to 4.2 GHz with Intel® Turbo Boost Technology, 18 MB L3 cache, 6 cores, 12 threads), Processor Family: 12th Generation Intel® Core™ i5 processor, Chipset: Intel® ADL H670, Memory: 8 GB DDR4-3200 MHz RAM (1 x 8 GB), Memory Slots:2 DIMM, Memory Note: Transfer rates up to 3200 MT/s. Storage: Hard Drive Description:512 GB SSD Expansion Features I/O Port Location: Front Ports, 4 SuperSpeed USB Type-A 5Gbps signalling rate; 1headphone/ microphone combo I/O Port Location: Rear Ports:4 USB 2.0 Type-A; 1 audio-in; 1 audio-out; 1 RJ-45; HP Serial Port Adapter Expansion Slots: 2 M.2; 1 PCIe x16; 1 PCIe x1 Video Connectors:1 VGA; 1 HDMI-out 1.4b Network Interface: Integrated 10/100/1000 GbE LAN Wireless: Realtek RTL8821CE-M 802.11a/b/g/n/ac (1x1) Wi-Fi® and Bluetooth® 4.2 combo Make :-(HP/ DELL/LENEVO or Equivalent make) Warranty:1 year (1/1/1) limited warranty includes 1 year of parts and labour. On-site repair. Terms and conditions vary by country. Certain restrictions and exclusions apply.
Supply and Installation of 20 inch Full HD LED Monitor (Make :-DELL/HP/LENEVO or Equivalent make)
Supply Deliver and Installation of Wired Keyboard and Optical Mouse Combo with Wired USB Desktop Keyboard (Black) (Make: -DELL/HP//LENEVO or Equivalent make)
Supply Deliver and Installation of 600VA/360W capacity UPS device for power backup of Computer set. (Make-As per choice of EIC)
Supply Deliver and Installation of Multi-function Monochrome Laser Printer (White, Grey, Toner Cartridge) (Make-HP or as per choice of EIC)
Pump and Accessories
Supply & installation of 7.5 H.P. (440V) 2900 R.P.M. monoblock submersible pump motor set (Make - Kirloskar.) by tools & tackles & manual labour. (Model No. - KOS-844+)
Supply and installation of 440 Volts 2900 R.P.M. 7.5 H.P. submersible pump motor set (Make - K.S.B.) Model No.- BPD 273/5A + UMAI 150 - 6/22 into the tubewell incl. errection of tripoid stand by co's own tools & tackles.
S&F of 200 mm dia round type M.S. well cover plate incl. cutting 50 mm dia holes in middle for passing column pipe and 1 No. 25 mm dia G.I. socket welded in corner for entry of cable.
S&F of 50 mm dia 600 mm long M.S. holding clamp for column pipe and pump including double nuts and bolts with washer also painting.
S&F 2.5 sq.mm. 3 core flat copper P.V.C. coated copper submersible motor cable (Make-Finolex).
S&F of G.I. pipe medium Quality (Make - TATA/Jindal) with necy. leak proof jointing materials.
a) 80 mm dia.
b) 40 mm dia.
S&F of 80 mm dia. G.M. Horizontal Check Valve (Make - Leader / I.S.I.).
S&F of 80 mm dia. G.M.G.M. Gate Valve CL - 1(Make - Leader / I.S.I.).
S&F of G.I. Hex Nipple.
a) 100 mm dia.
b) 80mm dia.
c) 40 mm dia.
S&F of G.I. Elbow.
a) 80 mm dia
b) 40 mm dia.
S&F of G.I. Socket.
a) 80 mm dia.
b) 40 mm dia.
S&F of G.I. Flange.
a) 100 mm dia.
b) 80 mm dia.
S&F of 100 mm dia. M.S. Steel Plug.
S&F of 100 mm dia. G.I. Reducing Tee.
S&F of 80 mm dia. G.I. short bend.
S&F of 40 mm dia.G.I. union.
S&F of Rubber insertion cloth upto 100 mm dia.
S&F of nuts & bolts with washer.
Charges for cutting & threading of G.I. pipe.
a) 80 mm dia.
b) 40 mm dia.
Charges for jointing 3 core, 2.5 sq.mm. flat P.V.C. submersible cable with S/F necy. Water insulating tape.
Charges for Cutting big hole through 12" wall & mending good the same after work.
Charges for cutting C.C. reservoir (10" dia) incl. brick gaurding in the same after work.
Assembling the Header upto 100 mm dia having multiple section incd. fixing the valves & requisite GI specials like flange, tee, short pice including cutting pipes, making threds with racket dice stock and refixing the same with all jointing materials as per direction of EIC.
Making pressure gauge arrangement incl. S&F 100 mm dia pressure gauge, G.M. valve and G.I. fittings complete.
Construction of brick piller approx size (300 mm × 300 mm × 1200 mm) height including plastering neat cement finishing for supporting the Header assembly as per direction of E.I.C.
Encasing the Tubewell with masonary brick work including neat cement complete charges for excavation of earth rammning with jhama brick around the 300 mm dia Tubewell (Size 1 mtr. X 1 mtr.x 1 mtr.).
Charges for cutting trench through any type of hard soil & refilling the same after work.
S&F of 415V, Fully - Automatic Star-delta Submersible pump controller (Type - MU-G15) having relay range 13 to 22A (Make - L&T) on angle iron frame on wall inclu. S&F Nuts & bolts etc.(Cat No - CS 94091SODO).
S/F of 440 V, 50 HZ, 63 AMP, TPN Main Switch on flat iron Frame on wall incl. necessary connection (Make - Havells/LT)
Painting the Header and exposed pipe line.
Transportation charges for carrying the pump motor set, G.I. pipes, fitting, valves and other accessories incl.tools & tackles from co's work shop to work site and back to co's work shop only tools & tackles.
Under Ground Reservoir
Earth work in excavation of foundation trenches or drains, in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading or stacking the spoils within a lead of 75 m. as directed. The item includes necessary trimming the sides of trenches, leveling, dressing and ramming the bottom, bailing out water as required complete. Depth of excavation not exceeding 1,500 mm.
Earth work in excavation of foundation trenches or drains, in all sorts of soil (including mixed soil but excluding laterite or sandstone) including removing, spreading or stacking the spoils within a lead of 75 m. as directed. The item includes necessary trimming the sides of trenches, leveling, dressing and ramming the bottom, bailing out water as required complete. Depth of excavation for additional depth beyond 1,500 mm. and upto 3,000 mm. but not requiring shoring. -
Supplying & laying Polythene sheet (150gm/sqm.) over damp proof course or below flooring or roof terracing or in foundation or in foundation trenches.
Ordinary cement concrete (mix1:2:4) with graded stone chips (20mm nominal size) excluding shuttering & reinforcement if any, in ground floor as per relevent IS codes. Pakur variety.
Controlled Cement concrete with well graded stone chips (20 mm graded nominal size) excluding shuttering and reinforcement with complete design of concrete as per IS : 456 and relevant special publications, submission of job mix formula after preliminary mix design after testing of concrete cubes as per direction of Engineerin charge. Consumption of cement will not be less than 300 Kg of cement with Super plasticiser per cubic meter of controlled concrete but actual consumption will be determined on the basis of preliminary test and job mix foumula. In ground floor and foundation. [using concrete mixture] M-25 Grade. Pakur variety. (Ref: P-25, it-6i PWD SOR)
Reinforcement for reinforced concrete work in all sorts of structures including distribution bars, stirrups, binders etc initial straightening and removal of loose rust (if necessary), cutting to requisite length, hooking and bending to correct shape, placing in proper position and binding with 16 gauge black annealed wire at every intersection, complete as per drawing and direction. For work in foundation, basement and upto roof of Ground Floor/ upto 4 m. Tor steel Fe 500 (JSW/JSPL/SHYAM/SRMB/BMASL/ELECTROSTEEL/SSL).
Hire and labour charges for shuttering with centering and necessary staging upto 4 m using approved stout props and thick hard wood planks of approved thickness with required bracing for concrete slabs, beams and columns,lintels curved or straight including fitting, fixing and striking out after completion of works (upto roof of ground floor). (When the height of a particular floor is more than 4 m the equivalent floor height shall be taken as 4 m and extra for works beyond the initial 4 m ht. shall be allowed for every 4 m or part thereof)
Steel shuttering or 9 to 12 mm thick approved quality ply board shuttering in any concrete work -
Brick soling with picked jhama bricks including preparation of bed as necessary with brick joints properly filled in and packed with powdered earth and including necessary cushion of similar material below the soling (and in between layers when more than one layer is used) completes as per direction.(a) Single brick flat soling (thickness 75 mm.)
Brick work with 1st class bricks in cement mortar(1:6). In foundation and plinth For Ramp
Filling in foundation or plinth by silver sand in layers not exceeding 150 mm as directed and consolidating the same by thorough saturation with water, ramming complete including the cost of supply of sand. (payment to be made on measurement of finished quantity) Do by-Fine Sand
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, nosing and dripourse, chiping, scaffolding / staging where necessary. Ground Floor With 1:6 cement mortar. 20 mm thick plaster. (excluding cost of chipping over concrete surface) Internal Plaster
Labour for Chipping of concrete surface before taking up Plastering work.
Plaster (to wall, floor, ceiling etc.) with sand and cement mortar including rounding off or chamfering corners as directed and raking out joints including throating, noisng and dripourse, chiping, scaffolding / staging where necessary. Ground Floor With 1:6 cement mortar. 15 mm thick plaster. (excluding cost of chipping over concrete surface) External Plaster
Artificial stone in floor, dado, staircase etc with cement concrete (1:2:4) with stone chips, laid in panels as directed with topping made with ordinary or white cement (as necessary) and marble dust in proportion (1:2) including smooth finishing and rounding off corners including raking out joints or roughening of concrete surface and application of cement slurry before flooring works using cement @ 1.75 kg/sq.m all complete including all materials and labour. In ground floor. 3 mm. thick topping (High polishing grinding on this item is not permitted with ordinary cement). Using grey cement. inside wall (i) 20 mm. thick
Tank Bot.l (iii) 35 mm. thick
Neat cement punning about 1.5mm thick in wall, dado, window sill, floor etc. NOTE:Cement 0.152 cu.m per100 sq.m.
Supplying, fitting and fixing in position FRP/GRP/COMPOSITE UV stabilizer Manhole Cover with high abrasion surface of 7mm top thickness with density of 2KG/m³ - approved make with rim of approved make (Heavy type) (i) 40 MT load bearing capacity round manhole cover provided with two lifter hooks fitted with matching frame of size Frame: 900 mm (36")
Providing and inserting nipples with approved fixing compound after drilling holes for grouting as per Technical specifications including subsequent cutting/removal and sealing of the hole as necessary of nipples after completion of grouting with Cement/Epoxy.
Sealing of crack / porous concrete with Epoxy Grout by injection through nipples complete as per clause 2803.1.
Epoxy bonding of new concrete to old concrete Constructio Joints
Applying epoxy mortar ( 10 mm nominal thick) over leached, honey combed and spalled concrete surface and exposed steel reinforcement complete as per Technical specification
(a) Applying 2 coats of bonding agent with synthetic multi functional rubber emulsion having adhesive and water proofing properties by mixing with water in proportion (1 bonding agent : 4 water : 6 cement) as per Manufacturer's specification [Cement to be supplied by the Department]
FIRE EXTINGUISHER
Providing & fixing 4.5 kg CO2 type Fire Extinguisher made out of Seamless Pipe Confirming to IS: 7285 and Wheel Type Valve Confirming to IS: 3224, including Wire Braided Hose of 1 Mtr. having working pressure of 180 Bar and Horn made of Polythene Fibre Glass along with powder coated wall bracket suitable for operating between -30°C to +60°C, fire rating -34 B. The Colour of extinguisher should be PO Red confirming to shade 538 of IS 5. The Complete Extinguisher should Confirm to IS: 15683 :2018. A label should be pasted on the body of the extinguisher showing: 1. Supplied by: HRBC 2. Date of manufacture: 3. Date of expiry / date of next filling: 4. Brand Name: (Minimax/Ceasefire/Safex/Fire Shield.)
Supplying, fitting, fixing of wll mounted Automatic fire extinguisher Launcher 06 kg A, B, C type powder base with dual heat technology fire suppresion system with CE certified, EN & IS (4306) Standard, PED certified, BSI approved Helium Leak Detection Tested. Epoxy powder coated can construction - Deep drawn & MIG welded working pressure - 15 BAR, Discharge lime - 15 sec. Gross Wt. 11.50 Kg. Dia. of shell 160.0 mm. Body Thickness 1.6 mm Squeeze Grip/Automatic Manual Squeeze grip, Automatic suppression system and Thrown inside the fire, hydrotratic Test Pressure - 35 Bar. EN 3 fire Ratings - 21A, 113B. WIth 5 years warranty (Inclusive all taxes, Freight charges & Fitting Fixing with spare accessories).
CAFS (compressed Air Foam System) Watermist fire estinguisher 50 litre trolley mounted Low Pressure Design 55a, Ivb, 1000v - Trolley Mounted Water Mist & Compressed Air foam (CAF) system - 50 Litre - Technology Water Mist & CAFS Fire Estinguisher with Low Pressure Dual Phase Technology (As per UIN EN 1866. 2007-10 Standards) Water container Capacity - 50 Litres. Water Cylinder working pressure - 05 to 12 bars. Water cylinder construction - Non corrosive Stainless Steel SS 316. Water Cylinder external paint - The paint should confirm to IS:5:2007 Shade 538. Operating working pressure (Not more than 11 bars. Air Bottle - certification - PESO (Petroleum and explosive safety organization). Total weight - Empty Filled - Not more than 54 KG (Empty). Not more than 15 KG (Water Bottle filled and Air bottle capacity - 6 litres/300 bar air bottle - construction - Seamless Mild Steel Cylinder. Operating temperature - Minimum +5 degree. Device operation - shall be suitable for both left and right hand operations. Fire extintion - suitability Class - A, Class - B. Live Electrical fires 1000V as per EN-3-7/IS-15683 (Tested for 36 kva) System Test. Electrical Test Certificate withdetails of test methods - Certification from ERDA as per IS 15683. Fire rating Certificates - Certification from NABL sccredialed Indian Lab as per EN3-7 2004 + A1:2007 Fire Rating Certificates for Class - A. Minimum A 55 Fire Rating Certificates for Class B - Minimum II B.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.21 MB
BOQ_2422914.xls
BOQ • 1.12 MB
Form2911.pdf
Tender Documents • 0.99 MB
Tender_Documents.pdf
Tender Documents • 4.20 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .