Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC 0001D ATM HOUSE AIR FORCE NEENA THAPA GORAKHPUR UTTAR PRADESH 273008 UDYAM UP 32 0054752 | GORAKHPUR | UTTAR PRADESH | 273008 | ₹1.3 Cr | L1 | Accepted-AOC LOWEST QUOTED BIDDER |
| 2 | L2₹1.5 Cr+₹18.6 L (14.4%)Rejected-Finance HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | ₹1.5 Cr+₹18.6 L (14.4%) | L2 | Rejected-Finance NOT THE LOWEST QUOTED BIDDER |
| Sl No | Description | Qty | Unit | om sai enterprises L1 | UNITED ENGINEERING CORPORATION L2 |
|---|---|---|---|---|---|
| 1.00 | Supply, install, connect, test and commissioning of inverter type air conditioner Hi wall comprising of units Indoor & outdoor complete with cordless remote control unit, within built in air ioniser, Plasma filter for better indoor air quality, leakage detector etc with minimum 3 star rating and EER 3.2 of capacity 1.5 TR, inclusive of suction and discharge lines of suitable size and length of copper tube, necessary brazing and providing nitrile tubing over gas circulating copper tubes and neatly tying the ends with PVC insulating tape and mounting on suitable bracket, suitable drain pipe for disposal of waste water upto ground level and testing, neatly finishing the disturbed surfaces of walls to match with the surroundings complete all as specified and as directed.
Make -LG/Voltas/Carrier/Blue star/Daikin/Hitachi | 35 | Each | 43,000 ₹15,05,000 | 39,000 ₹13,65,000 Lowest |
| 2.00 | Supply, install, connect, test and commissioning of inverter type air conditioner Hi wall comprising of units Indoor & outdoor complete with cordless remote control unit, within built in air ioniser, Plasma filter for better indoor air quality, leakage detector etc with minimum 3 star rating and EER 3.2 of capacity 2 TR, inclusive of suction and discharge lines of suitable size and length of copper tube, necessary brazing and providing nitrile tubing over gas circulating copper tubes and neatly tying the ends with PVC insulating tape and mounting on suitable bracket, suitable drain pipe for disposal of waste water upto ground level and testing, neatly finishing the disturbed surfaces of walls to match with the surroundings complete all as specified and as directed.
Make -LG/Voltas/Carrier/Blue star/Daikin/Hitachi | 42 | Each | 53,000 ₹22,26,000 Lowest | 53,000 ₹22,26,000 Lowest |
| 3.00 | Supply, install, connect, test and commissioning of inverter type air conditioner Hi wall comprising of units Indoor & outdoor complete with cordless remote control unit, within built in air ioniser, Plasma filter for better indoor air quality, leakage detector etc with minimum 3 star rating and EER 3.2 of capacity 3 TR, inclusive of suction and discharge lines of suitable size and length of copper tube, necessary brazing and providing nitrile tubing over gas circulating copper tubes and neatly tying the ends with PVC insulating tape and mounting on suitable bracket, suitable drain pipe for disposal of waste water upto ground level and testing, neatly finishing the disturbed surfaces of walls to match with the surroundings complete all as specified and as directed.
Make -LG/Voltas/Carrier/Blue star/Daikin/Hitachi | 3 | Each | 93,000 ₹2,79,000 | 75,000 ₹2,25,000 Lowest |
| 4.00 | Disconnection and removing the BER refrigerator and Supply, install, connect, test and commissioning of refrigerator of capacity 310 Ltrs, double door single phase 240 volt, 50 Hz complete all as specified and as directed.
Make - Samsung/Voltas/Godrej | 5 | Each | 39,000 ₹1,95,000 | 36,500 ₹1,82,500 Lowest |
| 5.00 | Disconnection and removing the BER refrigerator Supply, install, connect, test and commissioning of refrigerator of capacity 280 Ltrs, single door single phase 240 volt, 50 Hz complete all as specified and as directed.
Make - Samsung/Voltas/Godrej | 2 | Each | 30,000 ₹60,000 Lowest | 34,500 ₹69,000 |
| 6.00 | Disconnection and removing the BER refrigerator Supply, install, connect, test and commissioning of refrigerator of capacity 210 Ltrs, single door single phase 240 volt, 50 Hz complete all as specified and as directed.
Make - Samsung/Voltas/Godrej | 1 | Each | 25,000 ₹25,000 Lowest | 32,000 ₹32,000 |
| 7.00 | Disconnection and removing the BER deep freezer and Supply, install, connect, test and commissioning of Metal Top Deep Freezer of capacity 310 Ltrs single phase 240 volt, 50 Hz complete all as specified and as directed.
Make - Voltas/Godrej/Blue star | 3 | Each | 30,000 ₹90,000 | 24,500 ₹73,500 Lowest |
| 8.00 | Disconnection and removing the BER deep freezer and Supply, install, connect, test and commissioning of Metal Top Deep Freezer of capacity 200 Ltrs single phase 240 volt, 50 Hz complete all as specified and as directed.
Make - Voltas/Godrej/Blue star | 1 | Each | 25,000 ₹25,000 | 21,500 ₹21,500 Lowest |
| 9.00 | Supply and fixing ceiling fan (BLDC) complete with accessories 230V SP 1200 mm sweep complete all as specified and as directed .
Make : Havell Cat Part No ES-50 Premium 5 star rating and equivalent in Bajaj/Usha/Orient | 300 | Each | 2,700 ₹8,10,000 Lowest | 3,400 ₹10,20,000 |
| 10.00 | S&F in replacement of dessert cooler of plastic body, electric fan driven (Single phase) having normal air flow capacity of min 4000 Cum/ hour complete with exhaust fan motor of 1400 RPM and submerisble water lifting pump and water tank capacity 70 Ltr complete all as specified and as directed. | 20 | Each | 12,000 ₹2,40,000 Lowest | 14,500 ₹2,90,000 |
Tender Value
₹1.4 Cr
EMD Value
₹2.2 L
Closing Date
1 Jan 2026, 6:00 pmClosed
CWE (AF) Secunderabad
CWE (AF) Secunderabad
SPECIAL REPAIRS / REPLACEMENT OF BER E/M EQUIPMENT AT AFS BIDAR
2025_MES_742925_1
85667/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) Bidar
As per NIT
9 documents required · 9 mandatory
₹1,000
GE (AF) Bidar
₹2.2 L
Yes
23 Jan 2026
4 Dec 2025
3 Jan 2026
4 Dec 2025
1 Jan 2026
25 Dec 2025
4 Dec 2025 - 23 Dec 2025
Supply, install, connect, test and commissioning of inverter type air conditioner Hi wall comprising of units Indoor & outdoor complete with cordless remote control unit, within built in air ioniser, Plasma filter for better indoor air quality, leakage detector etc with minimum 3 star rating and EER 3.2 of capacity 1.5 TR, inclusive of suction and discharge lines of suitable size and length of copper tube, necessary brazing and providing nitrile tubing over gas circulating copper tubes and neatly tying the ends with PVC insulating tape and mounting on suitable bracket, suitable drain pipe for disposal of waste water upto ground level and testing, neatly finishing the disturbed surfaces of walls to match with the surroundings complete all as specified and as directed. Make -LG/Voltas/Carrier/Blue star/Daikin/Hitachi
Supply, install, connect, test and commissioning of inverter type air conditioner Hi wall comprising of units Indoor & outdoor complete with cordless remote control unit, within built in air ioniser, Plasma filter for better indoor air quality, leakage detector etc with minimum 3 star rating and EER 3.2 of capacity 2 TR, inclusive of suction and discharge lines of suitable size and length of copper tube, necessary brazing and providing nitrile tubing over gas circulating copper tubes and neatly tying the ends with PVC insulating tape and mounting on suitable bracket, suitable drain pipe for disposal of waste water upto ground level and testing, neatly finishing the disturbed surfaces of walls to match with the surroundings complete all as specified and as directed. Make -LG/Voltas/Carrier/Blue star/Daikin/Hitachi
Supply, install, connect, test and commissioning of inverter type air conditioner Hi wall comprising of units Indoor & outdoor complete with cordless remote control unit, within built in air ioniser, Plasma filter for better indoor air quality, leakage detector etc with minimum 3 star rating and EER 3.2 of capacity 3 TR, inclusive of suction and discharge lines of suitable size and length of copper tube, necessary brazing and providing nitrile tubing over gas circulating copper tubes and neatly tying the ends with PVC insulating tape and mounting on suitable bracket, suitable drain pipe for disposal of waste water upto ground level and testing, neatly finishing the disturbed surfaces of walls to match with the surroundings complete all as specified and as directed. Make -LG/Voltas/Carrier/Blue star/Daikin/Hitachi
Disconnection and removing the BER refrigerator and Supply, install, connect, test and commissioning of refrigerator of capacity 310 Ltrs, double door single phase 240 volt, 50 Hz complete all as specified and as directed. Make - Samsung/Voltas/Godrej
Disconnection and removing the BER refrigerator Supply, install, connect, test and commissioning of refrigerator of capacity 280 Ltrs, single door single phase 240 volt, 50 Hz complete all as specified and as directed. Make - Samsung/Voltas/Godrej
Disconnection and removing the BER refrigerator Supply, install, connect, test and commissioning of refrigerator of capacity 210 Ltrs, single door single phase 240 volt, 50 Hz complete all as specified and as directed. Make - Samsung/Voltas/Godrej
Disconnection and removing the BER deep freezer and Supply, install, connect, test and commissioning of Metal Top Deep Freezer of capacity 310 Ltrs single phase 240 volt, 50 Hz complete all as specified and as directed. Make - Voltas/Godrej/Blue star
Disconnection and removing the BER deep freezer and Supply, install, connect, test and commissioning of Metal Top Deep Freezer of capacity 200 Ltrs single phase 240 volt, 50 Hz complete all as specified and as directed. Make - Voltas/Godrej/Blue star
Supply and fixing ceiling fan (BLDC) complete with accessories 230V SP 1200 mm sweep complete all as specified and as directed . Make : Havell Cat Part No ES-50 Premium 5 star rating and equivalent in Bajaj/Usha/Orient
S&F in replacement of dessert cooler of plastic body, electric fan driven (Single phase) having normal air flow capacity of min 4000 Cum/ hour complete with exhaust fan motor of 1400 RPM and submerisble water lifting pump and water tank capacity 70 Ltr complete all as specified and as directed.
Disconnection and removing the BER AC of capacity 1.5/2/3 Ton from the blgds/ Hangers from any height including copper piping between indoor and outdoor unit and depositing to MES store yard complete all as specified and as directed. Note for item No 4 to 11 : The old/unsv equipments is deposited to MES store yard.
Disconnection and removing the old unserviceable Copper Pipe and S&F copper pipe of 1/2" dia and connecting alongwith insulation sleeves between indoor and outdoor unit including necessary welding and brazing complete all a specified and as directed.
Disconnection and removing the old unserviceable Copper Pipe and S&F copper pipe of 1/4" dia and connecting alongwith insulation sleeves between indoor and outdoor unit including necessary welding and brazing complete all a specified and as directed.
Disconnection and removing the old unserviceable Copper Pipe and S&F copper pipe of 5/8" dia and connecting alongwith insulation sleeves between indoor and outdoor unit including necessary welding and brazing complete all a specified and as directed.
Disconnection and removing the old unserviceable wiring and M&L for sub main wiring with 2 runs of 4 sqmm, single core, PVC insulated, unsheathed FRLS, 1100 volts grade, multi stranded with copper conductor, drawn through and including suitable size of heavy duty PVC conduit pipe and accessories and one run of single core, PVC insulated, unsheathed FRLS, 1100 volts grade, multi stranded with copper conductor for earth continuity , concealed in surface / walls / floors / ceilings/ roofs etc.,including cutting grooves and chases and finished the surface with existing surface complete all as specified and as directed. Note :- Two runs of main copper conductor, one run of copper conductor for earth continuity and one run of conduit shall be measured as one unit length.
Disconnection and removing the old unserviceable copper cable and M&L for S&F PVC Insulated, PVC Sheathed, Multistranded Copper Cable 3 Core 2.5 Sqmm, ISI Marked, 1100 volts Grade and connecting to the unit along with necessary fixing materials complete all a specified and as directed Make :- Polycab / Finolex / Havells
Disconnection and removing the old unserviceable SPN enclosure and Supply & fixing single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp rating suitable for 1.5/2 Ton capacity complete all a specified and as directed.
Disconnection & removing the old/us stabilizer ans supply, install, connect, test and commissioning of voltage stabilizer of 3 KVA capacity for automatic operation, single phase naturally air cooled, indoor type & designed for input variation between 170V to 260V with output volatge stabilized at 230V with accuracy of ± 2.5% with high& low voltage cut out & time delay including electric connection complete all as specified and as directed. Note : The old/unsv stabilizer is deposited to MES store yard.
All as per item No-18 above but 4 KVA complete all as specified and as directed.
All as per item No-18 above but 5 KVA complete all as specified and as directed.
Supply, installation, testing and proving of micro processor based,air cooled type ductable split Air Conditioners with remote & all accessories. Scope includes copper piping, power cabling, suitable drain tray and Drain piping in consealed PVC casing, joining with existing ducts and suitable stands for out door units/Indoor units as per the given specifications complete all as specified and as directed. Scope :- Cooling capacity : Min.8.3TR Condenser & Evaporator Coil Matl : Copper Air flow : Min. 4400 CFM Power Supply : 3 Ph, 415V ±10%, 50Hz Compressor : Scroll / Reciprocating / Rotary Refregerent : Eco friendly Makes: VOLTAS / BLUE STAR / CARRIER / HITACHI / DIAKIN Each unit shall comprise of separate indoor and out door unit consists of following. (i) Indoor unit should be ceiling suspended ductable type which is having capacity delivery minimum 4400 CFM (ii) out door unit should consists of 8.3 TR Capacacity single / twin scroll compressor operated with co-friendly refigerant gas. (iii) safety devices; unit should be provided with all safety controls like LP / HP cutouts, overloads protection for all drives (over voltage under voltage protection), Phase failure protection, phase failure protection,phase reversal protection for compressor.
M&L for copper tubing for suction line of size 28 mm from indoor unit to outdoor unit including suitable insulation including taking down the old copper piping complete all as specified and as directed.
M&L for dismantling and transportation of the existing ductable AC of capacity 8.3 TR and depositing to MES store yard complete all as specified and as directed.
M&L for supply and installation, testing and balancing of Air distribution system consists of factory fabricated as per IS-655 galvanised iron sheet of zinc coating 120 grade as per IS-277 metal ducting 22 gauge with TDF flanges complete with 4.0 mm thick self adhesive neoprene rubber gasket, stiffeners, elbows , splitters , vanes, bolts, nuts and including provision of mild steel angle iron frames for fixing of ducts, supports duly painted with two coats of synthetic enamel paint over a coat of red oxide primer, complete all as specified and as directed.
Supply and installation, testing and commissioning Acoustic insulation of supply air ducting with 19mm thick closed cell electrometric nitrle rubber with density minimum 43kg/m3, anti - microbial with EPA approved and fire performance to pass, class - 1 as per BS 476 part-7 and class O as per BS 476 part 6 and use recommended adhesives/SR 505 grade Fevicol and covered with 7mm thick chemically treated woven glass cloth having density 205+/- 10gram / sqm and affixed using synthetic contact adhesive of approved make and covered with 24G aluminium cladding for all exposed ducts complete all as specified and as directed.
Supply and Installation of Thermal insulation of air ducting with with 15 mm thick Open cell Nitrile rubber Insulation of density minimum 43kg/m3, anti- microbial with EPA approved and fire performance to pass and suffixed using synthetic contact adhesive of approved make, complete all as per specifications and approved drawings complete all as specified and as directed.
AIR TERMINALS: S & F of supply / return / exhaust air diffusers / grilles / louvers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core complete all as specified and as directed. Make: Ruskin Titus, Zeco, Rola Star, Air Flow
Supply and lay cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3½ core complete all as specified and as directed. Note: Aluminium lugs and thimbles for end terminations is deemed to include in quoted rates.
All as per item No-30 above but 3.5 Core 35 Sqmm complete all as specified and as directed.
All as per item No-30 above but 3.5 Core 185 Sqmm complete all as specified and as directed.
Excavating in trenches in soft/l
oose soil n.exc 1.5 m wide and n.exc 1.5 m in depth for foundation etc or for shafts, wells, cesspits, manholes, pier holes etc n exc 10 sqm on plan and n.exc 1.5 m in depth and getting out as I soft/ loose soil complete all as specified and as directed
Returning filling in, including spreading levelling, watering and well ramming in layers n exc 25 cm complete all as specified and as directed.
Removing excavted material n exc 50 m and depositing where directed at level n exc 1.5 m above the staring point as soil complete all as specified and as directed.
Sand cushioning (dry sand) to under ground cable for cable protection in layers of 23cm thick (8 cm thick before laying of cable and 15cm thick after laying of cable) in trenches complete all as specified and as directed. Note:- Only puned layers shall be measured.
Supply and laying unreinforced pre cast concrete cable cover class LV type 1 flat size 250 x 150 x 40 mm for cable protection including taking down of old cable cover complete all as specified and as directed.
M & L for perforated cable tray of size 250 mm x 50 mm (WXH) of suitable length industrial type open slot cable reaceway special , cable management chgannel cord track to hide cable wire for run electric cable to further distribute with panel for necessary cable protection. Cable tray should be made out of min 2 mm thick rolled sheet should be fabricated and fabrication process shall include pressing, punching , slotting , drilling , welding extra including taking down existing cable tray complete all as specified and as directed.
M&L for dismantling and transportation of the existing package AC Plant of capacity 2x9.7 TR and depositing to MES store yard complete all as specified and as directed.
Disconnection & removing the BER submersible pump from open well and S&F submersible pump set of 30 HP, 415 volts, 50 Hz, 6 stage, Head range - 113 to 29 mtr, LPM - 0 to 1900, outlet size 100mm, Impeller material Stainless steel, protection class-IP-68, NRV material- Cast Iron, Shaft material- stainless steel complete all as specified and as directed.
Disconnection & removing the BER submersible pump from borewell and S&F submersible pump set of 10 HP, 415 volts, 50 Hz, 10 stage, Head range - 141 to 41 mtr, LPM - 80 to 480, outlet size 65mm, motor body stainless steel, Impeller material Noryl, Oil seal protection, NRV material- Cast Iron, Shaft material- stainless steel complete all as specified and as directed.
Disconnection & removing the BER centrifugal pump from pump house and S&F mono block centrifugal pump set of capacity 10 HP, inlet/outlet - 80/65mm, 415 volts, 50 Hz, RPM-3000, Head range - 10 to 36 mtr, Discharge - 23 to 9.6 LPS, Motor body Cast Iron, Impeller- Stianless steel, shaft stainless steel, sealing mechanical seal complete all as specified and as directed. Note : The old/unsv pumps of any description and capacity are deposited to MES store yard.
S&F in replacement of automatic star delta starter for submersible/centrifugal pump set of capacity 10 HP, three phase 11-18 Amp complete all as specified and as directed.
S&F in replacement of galvanized pipe, “Heavy class” including fittings 100 mm (4”) dia connecting to open well submersible pump set complete all as specified and as directed. Note :- (i) Each piece of pipe will be 2 or 3 mtr long and will have flanged ends for connection. (ii) The cost of material and labour for flanges, nut & bolt and washer is inculded in the quoted rate.
Provn of CPCB -4+ silent DG set approved Acoustic enclosure compoiste type for Generator set and complete technical drawings and manuals of AMF panel, DG will be provide with trouble shooting instructions.
PRICE SCHEDULE (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only)
Supply and installation of Accoustic Enclosed diesel engine driven generating set in incl minimum of 310 HP/1500 RPM water cooled multi cylinder and coupled with 250 KVA /200 KW 415 Volt 0.8 P.F(Lag) 50 Hz AC alternator,mounted on a common base frame, governing class (as ISO 8528 Part-V) G3, along with all std accessories i.e.fuel tank of cap 600 Ltr,floor mounted electric control panel, battery 24 Volt with leads exhaust silencer as per std scope of supply with AMF (Automatic on mains failure) panel type 415 Volts 3 phae 4 wire complete relay panel for noise level at 1 Mtr dBA< 75 (Gen set with canopy) acoustic enclosure housing and incl electrical battery starting volt 24 Volt complete all as specified and as directed including following standard accessories for 250 KVA DG Set. Make : Kriloskar Model: KG4-250WS1or equvalent. Note:- (i) The quoted rate shall deemed to include for breaking of floors/walls etc including digging of trenches for removing of cables of loops and connecting to the new panel boards/DG AMF panel and making good the disturbed surfaces to match with the existing surfaces. (ii) The cost of PCC work for DG foundation with plinth portection measured and paid separately (iii) The panel shall be fabricated from a reputed firm
Fuel (Services) Tank:- The fuel tank cap 600 Ltr and shall be built in type and include fuel level indicator fuel piping internally with necessary piping as recommended by the manufacturer from tank to engine and for over flow etc.,and supplying semi rotary pump hand driven manually operated suitable to pump diesel upto 10 feet height etc. complete all as specified and as directed.
(CPRI Approved).
AMF panel : Factory made microprocessed,cubical type, floor mounted totally enclosed with locking arrangement, with provn of self ventilation with wire mesh as per OEM etc. complete fabricated out of CRCA steel 14 SWG, over an angle iron base frame with removable side cover, hinged front and and rear panel doors for easy accessibility powder coated complete, Heat shrinkable LT BUS BAR for 3 PH and Neutral of rating 600 AMPS for phases and neutral , internal wiring with suitable size multistranded copper conductor cable and cable glands for external connection compelte suitable for 250 KVA DG set with bypass arangement including all LT switch gear of suitable capacity such as four pole contactors of suitable rating , MCCB' FOUR POLE and CTs,
The tools as per the manufacturer's list shall be provided by the contractor alongwith the set at no extra cost.
Unit rate quoted shall deemed include the LT UG cable/ Control cable of suitable rating / capacity from DG set to AMF panel, DIESEL OIL,LUB OIL , COOLANT FOR RADIATOR etc for smooth functioning of DG SET during PH I & PH I I complete testing and initial full tank filling of DIESEL, OIL after PH I & PH I I testing,topping of LUB OIL,COOLANT FOR RADIATOR etc required for commissioning and testing of DG set .
Inverter 100 W capacity of reputed make and LED 20 WATTS with all accessories with necessary connections and wiring from DG Set Battery.inside the acoustic enclosure.
Dismantling the earth chamber, Excavation and removing the u/s earthing materials along with u/s earth electrodes from the existing u/s earth pits and M&L for Earthing complete with copper plate electrode 600 x 600 x 3.15 mm thick burried ndirectly in ground ( earth pit not less than 2.25 m deep below ground level with top edge of the plate not lesss than 1.5 m below the normal ground level connected with copper strip 20 x 3 mm thick by means of bolts, nuts, check nuts and excavation & earth work in any type of soil, removing surplus soil to a distance not exc 50 m, with and including PCC chamber in PCC (1:2:4), type B using (20 mm graded stone aggregate ), mild steel frame made out ange iron of size 40 mm x 40mm x 3mm thick duly painted with two coats of synthetioc enamal paint with two coats of synthetic enamal paints over one coat of red oxide zinc chrome primer hinged with and including 6mm thicks CI cover with handle, watering arrengement with funnel internally secured with wire mesh with 20mm dia medium grade pipe for watering, 40mm dia light grade GI pipe for lead protection in and including alternate layer of charcoal dust and comman salt complete all as shown in electrical plat no. 3 connected to earthing test point all as specified and indicated including testing on completion complete all as specified and as directed. Note:- The earth resistance shall be not less than 5Ω, in case of resistance beyond the specified limit, the contractor shall provide additional earthing in parallel with the existing without any additional cost.
S&F in replacement Mild steel plates, plain or chequered, 5mm thick cut to shape and size to match with the existing duct of pump houses and painting the same with two coats of synthetic enamel paint over one coat of red oxide primer complete all as specified and as directed.
M&L for providing cement concrete type B1, 1:2:4 using 20 mm stone aggrigate in coping or chamfered on edges complete all as specified and as directed.
AC Alternator : The AC alternator (Generator) shall be designed for continuous operation at 1500 RPM for an out put of 250 KVA / 200 KW at full load for continuous rating & 10 % for over load for one hour at 0.8 ( lag ) PF including self excited and self regulating screen protected ,insulation class H, efficiency (at 100% load) 0.8pf lag is 94% as per standard IEC 60034-1standard panel with all accessories cable terminal box suitable size of glands earth terminal etc. complete all as per OEM specifications complete all as specified and as directed.
M&L for dismantling and transportation of old existing BER DG duly disconnecting in all respects and remove the same using crane without damaging existing structure and shifted to MES yard complete all as specified and as directed.
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.27 MB
85667TENDERPDF.pdf
Tender Documents • 0.70 MB
BOQ_831911.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .