Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.5 LAccepted-AOC BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹26.8 L+₹2.3 L (9.29%)Rejected-Finance 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | L2 | Rejected-Finance Higher Quoted Rate. | |
| 3 | L3₹33.3 L+₹8.8 L (35.7%)Rejected-Finance 14 BEPIN BEHARI GANGUALY STREET KOLKATA 700 012 | KOLKATA | KOLKATA | WEST BENGAL | 700012 | L3 | Rejected-Finance Higher Quoted Rate. | |
| 4 | L4₹33.8 L+₹9.3 L (37.9%)Rejected-Finance | L4 | Rejected-Finance Highest Quoted Rate. |
Tender Value
Refer Docs
EMD Value
₹57,200
Closing Date
30 Jul 2024, 12:00 pmClosed
SE, PWD, Kolkata Electrical Circle
P-16, India Exchange Place Extn.KIT Building, 2nd Floor, Kolkata-700073
Proposed new Integrated Science and Technology campus of University of Calcutta at Rajarhat-Construction of G plus 7 storied Bldg (Tower 4) and Construction of G plus 3 storied New Building (Tower 3)-SITC of Fire Detection and Alarm System.
2024_WBPWD_705878_1
PWD/SE/KEC/NIT-07/24-25
Open Tender
FIRE FIGHTING ORG
Item Rate
60 days
University of Calcutta, Rajarhat
Please refer Tender documents.
8 documents required · 8 mandatory
₹57,200
Office of the SE, PWD, Kolkata Electrical Circle
17 Dec 2024
3 Jul 2024
1 Aug 2024
3 Jul 2024
30 Jul 2024
16 Jul 2024
12 Jul 2024
Amount
SITC of Microprocessor based Intelligent, addressable fire alarm control panel (VDS / UL / FM / ULC approved) fully networkable having requisite numbers of loop with 20% spare capacity with each loop capable of taking requisite number of devices as per latest IS/NBC, 1/4 VGA display character alpha-numeric liquid crystal display.The panel shall be soft addressable type.The panel shall be able to give pin point location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered.The Panel should be able to store sufficient numbers of log events in its Memory as per recommended standards. IS / NBC. Shiuld have the provision for incorporating with BMS.
The panel shall have in built rectifier, provision for external & internal printer (if required ), Loop cards, L C D unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, in built Surge protection facility, integral SMF lead acid batteries with sealed cells of 24 V capable of running for 24 hours normal working and then be capable of operating the system for 30 minutes during Emargency condition, with integral battery charger complete as required.
The FACP shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS 485 bus.The FACP shall have provision for interfacing with the public address system and BMS (RS 485). The panel should have modbus output & ready to communicate with remote computer. The system must be preloaded with licenced software. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor). For G+7 building
For G+3 building
SITC of Analog Addressable Intelligent multisensor detector (VDS / UL / FM / ULC approved) with in built optical smoke sensors as well as additional heat detector sensor with decentralise intelligence, soft addressable Photothermal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices ( Numbers of addressable devices in a group will be as per latest recommended IS / NBC) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor) For G+7 building
For G+3 building
SITC of Addressable Heat Detector (Fixed temperature cum rate of rise) (VDS / UL / FM / ULC approved) with twist lockable removal base, built - in fault isolator, drift compensation feature etc including connections as per specifications complete as reqd and having IP as per recommended standard(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices (Numbers of addressable devices in a group will be as per latest recommended standards) without any additional cost). (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward / Secutron / Securiton/ Apollo / Morley / System Sensor). For G+7 building
For G+7 building
SITC of Addressable Manual Call Point (VDS / UL / FM / ULC approved) soft addressable type with in built fault isolator as per NFPA style 7 wiring complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward / Secutron / Securiton/ Apollo / Morley / System Sensor). For G+7 building
For G+3 building
SITC of Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd)complete with inbuilt isolator & IP65 base and ( VDS / UL / FM / ULC approved) approved. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor ). For G+7 building
For G+3 building
SITC of Addressable transponder/ Monitor Modules (VDS / UL / FM / ULC approved) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward / Secutron/ Securiton/ Apollo / Morley / System Sensor). For G+7 building
For G+3 building
SITC of Addressable Relay Modules (VDS / UL & FM approved) for switching / integration of Lift / AHU etc complete as required. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward / Secutron/ Securiton/ Apollo / Morley / System Sensor)
SITC of LED type Response Indicator (VDS / UL / FM / ULC approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo / Morley / System Sensor). For G+7 building
For G+3 building
SITC of Repeater Panel (VDS / UL / FM / ULC approved) which will act as an add-on device for remote display of FACP status information of the FDA operating front related to the detectors and decetors zones.Event messages are displayed via LED collective indicators and on the 2-Line LCD display with the associated detecors zone number and a programmable additional text. Each message is signalled via the built-in buzzer. The buzzer can be acknowledged by pressing a button. The requisite LCD indicator panel can be operated on as RS 485 bus. (Approved Make: Esser/Cerberus Pro/ Bosch/ Johnson Controls/ Notifer / Edward /Secutron/ Securiton/ Apollo /Morley/System Sensor)
SITC of Power supply 230 V AC to 24V DC with all other accessories. (Make: Reputed)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/RR Kable/Polycab) with 20 mm NB PVC rigid conduit pipe(Make: Precision /AKG/ATUL /VIP/ Universal /BEC/Polycab) on the surface of the wall.
TERMS & CONDITIONS
a.The Fire Alarm system shall comply with latest requirements of -- 1. National Fire Protection Association (NFPA) Standards. 2. IS 2189 3. NFPA 70 National Electric Code 4. NFPA 72 National Fire Alarm Code 5. local Statutory Regulations 6. Manufacturer Recommendation.
b. TESTS:1.The system shall be tested and commissioned by a qualified competent,trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system. 2. Before energizing the cables and wires, check for correct connections and test for short circuits, ground faults, continuity, and insulation and other tests as per above standards must be done.
c. Auto CAD Drawing of whole FDA system & submission of 5 set hard copy of drawing and soft copy (in Auto-CAD format) is to be submitted.
d. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
e. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
f. If any refurbished material is supplied and installed, penal action will be taken as per existing rules. (Rates should be inclusive of all taxes & duties)
Creative Projects
ASSOCIATED ELECTRICAL CONST CO. 1963 PVT.LTD
FIRE EXTINCT
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .