Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.1 CrAccepted-AOC DOOR NO 32 939C 1ST FLOOR CITY SCAPE BUILDING CHANGAMPUZHA NAGAR P O SOUTH KALAMASSERY ERNAKULAM KERALA 682033 | ERNAKULAM | KERALA | 682033 | ₹1.1 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹1.2 Cr+₹5.5 L (4.78%)Rejected-Finance N A | ₹1.2 Cr+₹5.5 L (4.78%) | L2 | Rejected-Finance Rejected being L2 |
| 3 | Rejected-Technical DOOR NO 42 2237 KRISHNA BEHIND ERNAKULAM MEDICAL CENTRE CENTURY CLUB ROAD VENNALA KOCHI 682028 | KOCHI | ERNAKULAM | KERALA | 682028 | - | - | Rejected-Technical Does not meets the criteria |
| 4 | Rejected-Technical | - | - | Rejected-Technical Does not meets the criteria |
Tender Value
Refer Docs
EMD Value
₹2.4 L
Closing Date
10 Apr 2021, 6:00 pmClosed
CE NW Kochi
Kattaribagh, Naval Base, Kochi-682004
SPECIAL REPAIRS TO EXISTING FIRE DETECTION AND ALARM SYSTEM AND FIXED FIRE FIGHTING SYSTEM AT INHS SANJIVANI, NAVAL BASE, KOCHI.
2021_MES_424454_1
890973
Open Tender
Civil Works
Item Rate
365 days
Kochi
As per NIT
7 documents required · 7 mandatory
₹1,000
GE NS Kochi
₹2.4 L
Yes
3 Jun 2021
22 Feb 2021
12 Apr 2021
22 Feb 2021
10 Apr 2021
27 Mar 2021
23 Feb 2021 - 4 Mar 2021
Amount
SCHEDULE 'A' B/R WORKS
Dismantling of floor/hearth or wall tiling including cement mortar bedding but not backing and roughening of slabs by hacking and removal of derbis from the premises complete all as specified and as directed by the Engineer-in-Charge.
Material and labour for Glazed ceramic coloured tiles in vertical surface 350X250X7mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match over backing coat of 10 mm thick in CM 1:3 complete all as specified and as directed.
Material and labour for Vetrified ceramic tiles of dark shade of size 600x600x10 mm thick with approved pattern and colour borders over cement screed 15 mm thick in CM 1:4 over 25 mm thick PCC 1:2:4 type B0 levelling course on RCC slab complete all as specified and as directed.
Material and labour for 18-20 mm thick Granite tiles approved colour over cement screed 15 mm thick in CM 1:4 over 25 mm thick PCC type B0 1:2:4 levelling course on RCC slab complete all as specified and as directed.
Material and labour for Chequered cement concrete tiles 30cmx30cmx25mm thick, set jointed and pointed in neat cement slurry in floors with grey cement and no pigment complete over 20 mm thick screed in CM 1:4 all as specified and as directed
Taking down cement plaster on brick/concrete walls including raking out joints, hacking for key, scrubbing down with water etc complete all as specified and as directed.
Material and labour for 10mm thick rendering in cement mortar 1:6 on fair faces of brick work/concrete finished even and smooth without using extra cement complete all as specified and as directed by the Engineer-in-Charge.
Material and labour for 5mm thick rendering in cement mortar 1:3 on fair faces of concrete ceiling surfaces finished even and smooth without using extra cement complete all as specified and as directed by the Engineer-in-Charge.
Material and labour for preparation of new plastered surfaces of walls and applying two coat of acrylic distemper over a coat of primer complete all as specified and as directed by the Engineer-in-Charge.
Material and labour for new plastered surfaces of ceilling and applying three coat of white wash complete all as specified and as directed by the Engineer-in-Charge.
Fixed Fire Fighting System:-Taking down old unserviceable GI tubing of size 150 mm complete all as specified and directed .
Taking down old unserviceable GI tubing of size 100 mm complete all as specified and directed .
Taking down old unserviceable GI tubing of size 80 mm complete all as specified and directed .
Taking down old unserviceable GI tubing of size 50 mm complete all as specified and directed .
Taking down old unserviceable Gate valve 50 mm complete all as specified and directed .
Taking down old unserviceable 150 mm dia CI Double flanged Non Return Valve complete all as specified and directed .
Taking down old unserviceable 100 mm dia CI Double flanged Non Return Valve complete all as specified and directed .
Taking down old unserviceable 80 mm dia CI Double flanged Non Return Valve complete all as specified and directed .
Taking down unserviceable 100mm Sluice Valve both end flanged complete, all as specified and as directed.
Taking down old unserviceable Hose Cabinet complete all as specified and directed .
Taking down old unserviceable Fire Delivery Hose 63mm dia complete all as specified and directed .
Taking down old unserviceable Hose reel Swining Wall Mounted 19mm dia 30 mtr long complete all as specified and directed .
Taking down old unserviceable Branch Pipe 63mm dia complete all as specified and directed .
Taking down old unserviceable Air Cushion Tank complete all as specified and directed .
Taking down old unserviceable Single Headed Fire Hydrant 63mm dia complete all as specified and directed .
Taking down old unserviceable Fire Brigade Inlet conncetion 4 way complete all as specified and directed .
Taking down old unserviceable Landing valve single headed 63mm dia complete all as specified and directed .
Taking down old unserviceable Pressure switch 25mm dia complete all as specified and directed .
Taking down old unserviceable Gun metal Aire releasevalve 50mm complete all as specified and directed .
Taking down old unserviceable Cable size 150 Sqmm 4 core complete all as specified and directed .
Taking down old unserviceable UG Cable size 16 Sqmm 4 core complete all as specified and directed .
Taking down old unserviceable earthing GI plate 4mm wire / 25 x 4 mm strip complete all as specified and directed .
Taking down old unserviceable control panel of main Pump and Jockey Pump with complete accessories all as specified and directed .
Supply and fixing Steel Water Tubing Heavy Duty Galvanised ISI marked with welding including all fittings like angle iron supports ,elbow, tee, flange, taper, nut, bolt, gasket etc fixed on walls/floors/ roof etc including fixing with clamps on wall for the wet riser including painting with approved two coats of synthetic enamel paint over a coat of suitable primer of required shade complete all as specifed and directed of following sizes :- Make: Jindal/Tata/Surya/Zenith
150 mm dia
100 mm dia
80 mm dia
50 mm dia
Supply and fix Gate Valve of size 50mm complete all as specified and as directed by the Engineer-in-Charge. Make:- Shakti/NVI/Zew/Atom
Supply and fix horizontal type Cast Iron Double Flanged Non return valve of approved quality confirming to IS 5312 with bolt, nuts, washers, 3mm thick insertion rubber gaskets complete all as specified and as directed of the following sizes:- Make:-Kirloskar/Bir/Leader/Karthar
150 mm dia
100 mm dia
80 mm dia
Supply and Fix 100mm dia horizontal type Sluice Valve, both end Flanged of approved quality conforming to PN 1.6 with bolts, nuts, washers, 3mm thick insertion rubber gaskets complete all as specified and as directed. Make:- AUDCO/C&R/INTERVALE/KARTHAR
Supply and fix fabricated Hose Cabinet made out of 18 gauge MS Sheet of size 800 x 600x 250mm with double door with 4mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white with lock two keys suitable for indoor use complete all as specifed and as directed. Make:- Friends/Capital Gains
Supply and fix fabricated Hose Cabinet made out of 18 gauge MS Sheet of size 800 x 600x 250mm with double door with 4mm thick glasses and door frame made of 16 gauge MS sheet painted fire red out side and brilliant white inside with lock two keys suitable for outdoor use complete all as specifed and as directed.Make:- Friends/Capital Gains
Supply and fix rubberized fabric reinforced rubber lined circular jacketted Fire Delivery Hose 63 mm dia (Red colour) treated against rot/mystex having 38 Kg/cm2 working pressure bearing IS-636 15 mtrs length with male and female coupling complete all as specified and as directed. Make:- Eversafe/Newage/SRI/Mahavir
Supply and fix Hose reel swinging wall mounted type comprising rubber hose 19mm dia 30m long high pressure double braided bearing, PVC shut off nozzle and 25mm gunmetal inlet valve confirming to IS-884 and connected to wet riser complete all as specified and directed. Make:- Eversafe/Newage/SRI/Mahavir
Supply and fix branch pipe 63 mm dia male instantaneous inlet threaded outlet fitted with hexagonal based nozzle of 20mm dia heavy duty confirming to IS-903 complete all as specified and directed. Make:- Eversafe/Newage/SRI/Mahavir
Fabricate, supply and connect Air Cushion tank (air vessel) 200mm dia 1200 mm height with dished top made out of 6mm thick MS plate sutable for floor mounting including 1 No 20mm dia wet riser including GI Tee of size 100 x 100 x 20 mm complete all as specified and as directed.
Supply and fix Fire Hydrant made out of gunmetal single headed with flanged inlet and 63mm female instantaneous outlet with 100 mm dia Steel water tubing heavy duty galvanised ISI marked stand post of 1M long including blank caps and chain bearing IS 5290 mark with flanged riser duck foot beand. 1No 100mm dia sluice valve PN 1.6 including bolts, nuts washers and gasket for flanged joints including painting and testing complete all as specified and as directed.Make:- Eversafe/Newage/SRI/Mahavir
Supply and fix Gun metal Fire brigade inlet connection 4 way including taking down unserviceable old one complete all as specified and as directed. Make:- Eversafe/Newage/SRI/Mahavir
Supply and fix Landing valve (internal hydrant) single headed gunmetal bearing ISI mark grade 63mm female instantaneous outlet complete with PVC blank cap and chain and having suitable flanges for 10mm dia wet riser including taking down unserviceable old one. Make:- Eversafe/Newage/SRI/Mahavir
Supply, erection, testing and commissioning of Pressure switch universal type complete all as specified and as directed.Make:-Danfoss/Indfoss/Honeywell
Supply, erection, testing and commissioning of Pressure gauge 4" dia, 0-14 Kg/cm2 rating complete all as specified and as directed. Make:-H Guru/Baumer/Mass
Supply, erection, testing and commissioning of Gun metal air release valve 50mm dia complete all as specified and as directed.
Supply and laying UG XLPE cable insulated, screened, PVC bedded with galvanised steel strip or wire armoured, 1100 volts grade with stranded aluminium conductor of size 150 Sqmm 3.5 core through medium grade PVC conduit of suitable size including all required accessories fixed with clamp & screw complete incl cutting chaees and making fod as per existing surface complete al as specified and as direced.Make:-Havells/Finolexx/Polycab
Supply and laying UG XLPE cable insulated, screened, PVC bedded with galvanised steel strip or wire armoured, 1100 volts grade with stranded aluminium conductor of size 16 Sqmm 4 core through medium grade PVC conduit of suitable size including all required accessories fixed with clamp & screw complete incl cutting chaees and making fod as per existing surface complete al as specified and as direced.Make:-Havells/Finolexx/Polycab
Material and labour for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm buried directly in ground to a depth not less than 2.25m below ground level with top edge of the earth plate at a depth not less than 1.5m below normal ground level surrounted from all side by 15 cm of thick and packed layers of charcoal dust and common salt ,filling alternate layers and electorde connected by using GI wire 4 mm dia (max -length of 7.5 mtrs )by means of bolts,nut and washer of GI and providing GI light grade pipe 15 mm dia as prrotection pipe for GI wire connected main controll board / test point and provided with GI pipe of light grade 20 mm bore for watering and including testing all as directed and shown in electrical plate No. 5 of SSR part -1 including testing on completion.
Material and labour for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm buried directly in ground to a depth not less than 2.25m below ground level with top edge of the earth plate at a depth not less than 1.5m below normal ground level surrounted from all side by 15 cm of thick and packed layers of charcoal dust and common salt ,filling alternate layers and electorde connected by using GI strip 25 x 4 mm (max -length of 7.5 mtrs )by means of bolts,nut and washer of GI and providing GI light grade pipe 15 mm dia as prrotection pipe for GI wire connected main controll board / test point and provided with GI pipe of light grade 20 mm bore for watering and including testing all as directed and shown in electrical plate No. 5 of SSR part -1 including testing on completion.
Material and labour for construction of brick masonary valve chambers of internal dimensions 1 mtrs x 1mtr x 1.2mtr (bottom PCC floor of the pit should be minimum 30 cms below the bottom surface valve flange to provide sufficent working space ), bottom floor of the pit be constructed in PCC (1:3:6) 15cms thick with 20mm stone aggregate, inner and outer exposed surfaces and bottom floor of the pit should be plstered in CM (1:4) 15mm thick. The sluice valve and other fittings should be housed in center of the pit. The vertices of the pit should be in right angle and champered. The top cover of the chamber will be made out of MS sheet min 5mm thick with angle iron frame made out of MS angle 50mm x 50mm x 6mm with galvanised steel hinges two nos and locking arrangements duly painted with two coats of water resistant synthetick enamelled paint over on coat of red oxide.
Overhauling and general servicing of Diesel Driven Pump set of 90 HP capacity ncluding replacement of engine oil of required quantity, oil filter, air filter and coolant top-up and refixing in position and pump side replacing of SS sleeve, gland packing, greasing etc and testing complete all as specified and directed.
Overhauling and general servicing of Electric Driven Pump set, 3 Phase, 415 volt, of 70 HP capacity by cleaning, varnishing, heating, assembling, refixing in position and pump side replacing of SS sleeve, gland packing, greasing etc and testing complete all as specified and directed.
Overhauling and general servicing of Electric Driven Pump set, 3 Phase, 415 volt, of 20 HP capacity by cleaning, varnishing, heating, assembling, refixing in position and pump side replacing of SS sleeve, gland packing, greasing etc and testing complete all as specified and directed.
Demolition of cement concrete(unreinforced) in ground floors and pavings n exc 15 cm thickness above or below ground level and disposal of debris complete all as specified and as directed by the Engineer-in-Charge.
Material and labour for 100mm thick plain cement concrete 1:3:6 type C2 (using 40mm graded stone aggregate), roofs, landings, balconies, canopies deck slabs and in floor slabs etc complete as specified.
Excavating in trenches not exc 1.5 m wide and not exc 1.5 m in depth for foundation etc. or for shafts, wells, cesspits,manholes, pier holes, etc. not exc 10 sqm on plan and not exc .5 m in depth and getting out soft/loose soil complete all as specified.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm for soft/loose soil all as specified and as directed by the Engineer-in-Charge.
Removing excavated material exc. 1.50 km but not exc. 5 km and depositing where directed complete all as specified and as directed by the Engineer-in-Charge.
Supply and spread dry riddled soil in trenches for cables cushioning all as specified and as directed by the Engineer-in-Charge. Note: Punned thickness shall only be measured.
Supply and laying reinforced precase concrete cable cover in trenches for cable protection, Class LV, Type I, flat size 250 mm x 150 mm x 40 mm complete all as specified and directed.
Fire Detection & Alarm System:-Taking down unserviceable Fire Alarm Control Panel complete all as specified and directed .
Taking down unserviceable Network Repeater Panel complete all as specified and directed .
Taking down unserviceable Multi sensor with heat and smoke combination detector complete all as specified and directed .
Taking down unserviceable old manual call paoint (Pull down/Break Glass type) complete all as specified and directed .
Taking down unserviceable control module for sounder cum strobes, complete all as specified and directed .
Taking down unserviceable Fault/Short circuit Isolator module complete all as specified and directed .
Taking down unserviceable FRLS cable size 1.5 Sqmm 2 core circuit Isolator module complete all as specified and directed .
Supply, installation, testing and commissioning of Network repeater panel with 600 characters LCD display & programmable QWERTY keypad and mapping minimum 20,000 points on network. The NPR shall act as an independent node communication on the peer to peer network and shall be dependent on the Fire panel CPU for operation. Failure of fire panel CPU shall not result in failure of NRP operation. There shall be options to connect printer directly to NRP. The Network repeater panel shall be UL listed and FM approved, complete all as specified and as directed. Make:- Notifier/Honeywell/Edward/Morley
Supply, installation, testing and commissioning of Addressable type multi sensor detector with heat and smoke combination detector complete all as specified and as directed.Make:- Notifier/Honeywell/Edward/Morley
Supply, installation, testing and commissioning of intelligent Addressable manual call point resettable type complete all as specified and as directed. Make:- Notifier/Honeywell/Edward/Morley
Supply installation, testing and commissioning of Control module including sounder cum strobes, complete all as specified and as directed. Make:- Notifier/Honeywell/Edward/Morley
Supply installation, testing and commissioning of intelligent analogue addressable Fault / Short circuit isolators modules for isolating shor / dewired /loose circuits with automatic re-setting arrangement complete all as specified and as directed.Make:- Notifier/Honeywell/Edward/Morley
Material and labour for laying FRLS copper cable of size 1.5 Sqmm 2 Core armoured multistranded drawn through in existing concealed conduit/above false ceiling in red colour with ISI marked complete all as specified and as directed . Make:- Finolex/Polycab/Havells
Material and labour for laying FRLS copper cable of size 1.5 Sqmm 2 Core armoured multistranded drawn through including new PVC conduit of suitable size concealed in wall where required and matching the existing surface complete all as specified and as directed . Make:- Finolex/Polycab/Havells
Supply, installation, testing and commissioning of Microprecessor based multi-loop, true peer-to-peer Networkable addressable fire alarm control panel with minimum 600 characters LCD display. 4000 events plus 1000 alarm log history events, QWERTY keypad for programming. The panel should be equipped with 6 numbers of loops considering 20% spare capacity in each loop. Each loop shall have a capacity of minimum 300 analog addressable devices with option for group device polling for faster responses. The panel shall work in degrade mode in case of CPU failure. Four access levels, flash EPROM, 24 volts AC power supply, automatic battery charger, 24 volts sealed lead acid batteries sufficient for 24 hours normal working and 30 mins in alarm condition. There shall be options on the FACP to connect external 3rd party printers. The MTBF (Mean time before failure) which signifies the reliability of the product) shall be minimum 20 years. The FACP and all accessories shall be UL listed and FM approved complete, all as specified and directed by the Engineer-in-Charge. Make:- Notifier/Honeywell/Edward/Morley
SKYLIGHT INNOVATIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .