Executive Engineer, Electrical (R&B) Division, surat
SITC of a DG Set for Court Building at Valod Di. Tapi.
352775
Online Notice No 13 of 2026-27
Open
Electrical Works
Works
Surat
7 documents required · 7 mandatory
₹900
Executive Engineer, Electrical (Rand B) Division, Surat.
₹17,000
7 Oct 2026
7 Oct 2026
7 Oct 2026
21 Oct 2026
7 Oct 2026
Name of work : SITC of a DG set for Court Building at Valod,Di-Tapi
SR. Qnty. Unit DESCRIPTION TENDER Amount
1 1 Ea Supply, Installation, Testing and Commissioning (SITC) of Silent Type 1198279.00
Diesel Generating (DG) Set(s) of prime power rating (kVA) as
specified, complete as a packaged system, conforming to CPCB IV+ (or
better) emission norms, and complying with all applicable statutory
requirements, codes and standards including (but not limited to) IS
4722:1968, IS 13364 (Part 2) and BS 5514 (latest
editions/amendments). The DG set shall be suitable for 415 V ±10%,
Hz ±5%, 3-phase, 4-wire operation at 0.8 lagging power factor,
RPM, for tropical conditions, and shall be capable of delivering 10%
overload for one (1) hour after twelve (12) hours of continuous
operation (ISO 8528), unless otherwise stated by the OEM. The scope
shall include complete accessories, interconnections, foundations/anti-
vibration arrangements, exhaust system, acoustic enclosure, earthing (as
required), consumables for first commissioning, and all works necessary
to render the installation fully functional and compliant, as directed by
the Engineer-in-Charge (EIC).
Factory testing shall be carried out with fuel and load bank at
power factor and the DG set shall be offered for inspection prior to
dispatch. The DG set shall be provided with a durable QR code/label
fixed on the enclosure/control panel, linking to a document repository
containing (as a minimum) approved GA drawings, wiring diagrams,
foundation and installation details, OEM catalogues, operating &
maintenance manuals, factory test reports, type test certificates (where
applicable), warranty certificate, geo-tag of manufacturing location, and
rating plate data as per relevant IS/BS/ISO requirements. The
OEM/Contractor shall provide a Remote Monitoring System (RMS)
with minimum one (1) year connectivity (SIM/data plan/server access as
applicable), including dashboard access, user ID/password, and data
download facility. RMS shall, at minimum, capture and report: DG
status (Auto/Manual/Off), start/stop events, kW/kVA/kVAR, V/I/Hz,
PF, run hours, fuel level, battery voltage, alarms/trips with time stamp,
and GPS/location (where supported). All licences/subscriptions required
for the stated period shall be included in the quoted price.
(A) Diesel Engine:
Turbocharged, 4-stroke, water-cooled, multi-cylinder diesel engine,
suitably rated for the specified DG set prime rating at site conditions,
complete with dynamically balanced flywheel, heavy-duty engine
mounting, and electric starting arrangement. The engine governing shall
be electronic (isochronous/droop as per OEM standard) and shall
comply with ISO 8528/BS 5514 requirements for steady-state speed
regulation. Engine shall be complete with dry type air cleaner with
restriction indicator, lube oil cooler (if required), radiator/cooling
package (as applicable), and all sensors/switches required for
protections and annunciation. The engine shall be capable of 10%
overload for one (1) hour after twelve (12) hours continuous operation
and shall be suitable for continuous duty under tropical ambient
conditions. The offered engine model shall be CPCB IV+ compliant and
shall be supplied with complete emission control/after-treatment system
(including DEF/urea dosing where applicable) along with all
accessories, tanks, pumps, heaters and controls required for compliant
operation. The supply shall include first fill of lubricating oil, coolant
and consumables required for initial commissioning and testing. All
fasteners, couplings, guards, hoses and standard/recommended
accessories required for safe and reliable operation shall be included
and shall be subject to inspection/approval by the EIC.
(B) Engine-Mounted Instrumentation/Control Panel:
Engine-mounted instrument/control panel shall be microprocessor
based, with LCD/LED display, event log and alarm/trip annunciation,
complete with all wiring, harnesses and terminations.
Indications/protections shall include (minimum) the following and any
additional protections recommended by the OEM: (i) Start/Stop key
switch and/or push buttons with emergency stop; (ii) Output breaker:
suitably rated 4-pole ACB/MCCB/MCB as applicable, with minimum
25 kA rupturing capacity (or as per fault level at site, whichever is
higher), with shunt trip where required; (iii) Jacket water/coolant
temperature – indication and high temperature alarm/trip; (iv) Lube oil
pressure – indication and low pressure alarm/trip; (v) Lube oil
temperature (where provided) – indication/alarm; (vi) Battery charging
indication, battery voltage indication and charging failure alarm; (vii)
Engine speed (RPM) indication and overspeed trip; (viii) Engine
running hours meter (non-resettable); (ix) Fuel level indication and low
fuel alarm; (x) Fail-to-start / crank fail alarm; (xi) Under/over frequency
and under/over voltage protection (alternator side) as applicable; (xii)
Common alarm and common trip indication with potential-free contacts
for BMS/remote annunciation. All meters/indications shall be of proven
industrial quality and the panel shall be wired, ferruled and labelled.
The contractor shall submit wiring diagrams, protection settings and
datasheets for approval prior to dispatch/installation. (C)
Synchronous, brushless alternator of appropriate kVA rating, 415 V, 3-
phase, 50 Hz, 1500 RPM, 0.8 lagging PF, continuous duty, dynamically
balanced rotor, self-cooled, self-excited and AVR regulated. Enclosure
shall be SPDP, minimum IP23. Insulation shall be Class H with suitable
tropicalization; temperature rise shall be within limits of the applicable
standard. The alternator shall comply with IS 13364 (Part 2), IS
and/or BS 2613 (latest), as applicable. Voltage regulation with AVR
shall be within ±1.0% (steady state) or OEM standard whichever is
better. The alternator shall be capable of 10% overload for one (1) hour
after twelve (12) hours of continuous operation. Harmonic distortion
shall be suitable for non-linear loads; alternator shall be equipped with
appropriate AVR features (e.g., soft start, UFRO) and shall be suitable
for motor starting duties typical to the installation. Terminals shall be
brought out to a terminal box with adequate space for termination and
shall include earthing terminals. All routine/type test certificates (as
applicable) shall be submitted for acceptance.
(D) Base Frame & Foundation: Engine and alternator shall be mounted
on a suitably designed, fabricated MS channel base frame with
stiffeners, lifting arrangement and coupling guard, duly painted/treated
for corrosion protection. The set shall be installed on an adequately
designed cement concrete foundation/pedestal with anchor bolts,
pockets, grouting and anti-vibration mounts (AVMs) / spring isolators
as per OEM recommendations and site conditions. Vibration levels shall
be within OEM permissible limits. The contractor shall be responsible
for alignment, levelling, tightening torque and re-check after load trial,
complete in all respects. (E) Fuel Tank: In-built/base fuel tank
fabricated from minimum 3 mm thick MS sheet, duly leak-tested,
complete with filling arrangement, vent, drain, cleaning opening, level
indication and isolation valve(s). The capacity shall be adequate for
minimum eight (8) hours continuous operation at full load. Fuel piping
between tank and engine shall be MS ‘C’ class pipes of suitable
diameter with compatible flexible connections (where required),
complete with all valves, clamps, supports, unions and fittings. Any
additional safety provisions required by local fire
authority/UGVCL/competent authority (such as double wall/bunding,
flame arrestor, etc.) shall be provided within the quoted scope.
(F) Exhaust System: Heavy-duty residential type exhaust silencer
suitable for CPCB IV+ installation (with DEF/after-treatment system
wherever applicable) along with exhaust piping of required length,
bends, supports and flexible bellow, complete with rain cap, drain
arrangement and all accessories. Exhaust piping shall be thermally
insulated/lagged and cladded where required to ensure personnel safety
and to limit heat radiation inside the DG room/enclosure. The complete
exhaust arrangement shall be designed such that engine exhaust back
pressure remains within OEM permissible limits and shall comply with
applicable statutory and safety requirements.
(G) Starting System: 12 V / 24 V DC electric starting system (as per
OEM design) comprising starter motor(s), battery charger/alternator
charging arrangement, relays, cabling and terminals, complete with
maintenance-free batteries of suitable Ah capacity to ensure minimum
three (3) consecutive cranking attempts. System shall include battery
isolator and indication of charging healthy/failure. All battery
interconnections shall be with crimped lugs, insulated sleeves and
proper supports, complete in all respects
(H) Acoustic and Weatherproof Enclosure: Acoustic enclosure shall be
factory-fabricated, weatherproof and corrosion protected, suitable for
outdoor installation, with minimum IP65 protection (or better) for the
enclosure body. Enclosure design shall provide adequate fresh air intake
and hot air discharge for engine radiator and alternator cooling such that
the internal temperature rise remains within OEM limits at full load.
Provision shall be made for safe access/maintenance including lockable
doors, viewing window (where provided), emergency stop access, and
cable entry glands. Noise level of the complete DG set with enclosure
shall not exceed 75 dB(A) measured at 1.0 m distance in free field
conditions, in accordance with applicable CPCB requirements. The
enclosure shall comply with CPCB IV+ (or better) requirements and
other applicable local rules/regulations. All louvers, acoustic
infill/insulation, fasteners and sealing arrangements shall be of fire-
retardant/industrial grade as per OEM standard. Any deviation from the
specified noise/IP requirements shall be treated as non-compliance
unless explicitly approved by the EIC in writing.
Erection, testing, commissioning and satisfactory performance
demonstration shall be carried out as per site requirements and as
directed by the Engineer-in-Charge. The scope shall include pre-
commissioning checks, insulation resistance tests, no-load and load
trials, safety/protection checks, and performance test on load bank
(where directed) with submission of test records.
The contractor shall provide initial consumables including first fill of
diesel fuel (minimum up to 80% of fuel tank capacity), lubricating oil,
coolant, etc. required for commissioning and the specified tests. The
bidder/OEM shall provide comprehensive warranty/guarantee for the
complete DG system (engine, alternator, control panels, RMS, enclosure
and all accessories) for a minimum period of two (2) years from the date
of commissioning/handing over, whichever is later, covering defects in
materials and workmanship. During warranty, all
spares/repairs/replacements and visits required to maintain the DG set
in serviceable condition shall be carried out at no additional cost. All
necessary statutory approvals, inspections, testing and certification from
the Electrical Inspector/competent authority (including provision,
testing and sealing of energy meter(s) wherever applicable) shall be
arranged and obtained by the contractor within the quoted scope and
time, at no extra cost. Required O&M manuals, as-built drawings,
warranty certificates and training to operating staff shall be provided
prior to handing over.
Note: The DG set specifications shall comply with the latest CPCB
guidelines/notifications and all applicable local rules/regulations
prevailing as on the last date of tender submission applicable local
rules/regulations prevailing as on the last date of tender submission(L)
Continuous rating of 100 KVA ,BHP not less than 126 BHP
2 1 Ea AMF Panel: 121201.01
Free standing floor mounted IP 42 automatic mains failure control
panel including auto by-pass, suitable for KVA as below for silent
type DG set complete with relays, timers, set of CTs for metering &
protection and energy analyser to indicate currents, phase and line
voltages, frequency, power factor, KWH, Kilo Volt Ampere
Reative Hour (KVARH), KVA (Phase & Total), KW (MFM) &
provision for overload, short circuit, restricted earth fault, under
frequency, all complete and inter locking and communication/
Ethernet /RS485/SNMP port open protocol for BMS integration
including suitable software, the panel shall be of DG Set. as per
approved by Engineering in charge and including the following:
1. Suitable numbers and appropriate capacity 4 ACB/ MCCB with
electronic release for O/C & E/F and shunt trip. (Icu=100%Ics) (Not
below 25KA Breaking Capacity at 415Volts), (Total Three Breakers)
2. Auto/Manual/Test/Off selector switch
3. Protection for under and over voltage phase reversal (2 nos
Over voltage relay, 2 Nos. reverse power relay and 2 Nos. under
voltage relay).
4. 3 Sets of current transformers 15 P 10 accuracy for protection and
15 VA class-I for metering
5. Energy analyser unit to indicate current, Voltage( L- N & L_L), kW,
kVA (Phase & Total), Frequency, KWH, PF.
6. LED Indicating lamps for load on mains and load on set
7. Fuse/ MCB for instruments
8. Battery charger, complete with transformer/ rectifier, D.C. voltmeter
and ammeter, selector switch for trickle, off and boost and current
9. Control/Signal/Multi core/Communication Cables between DG Set
and AMF Panel upto 20 Mtr
10. Main supply failure monitor
11. Supply failure timer
12. Restoration timer
13. Control unit with three impulse automatic engine start/stop and
failure to start lockout.
14. Impulse counter with locking and reset facility.
15. ON/OFF/Control circuit switch with indicator 16. Audio/Video
annunciation for
(i) High water temperature
(ii) Low lubricating oil pressure
(iii) Engine over speed
(iv) Engine fails to start (v) Full
load/maximum load warning
16. Protection for over/under Frequency, Loss of AC sensing, Over
Current, Unbalancing load with suitable number of relays and
17. Maintenance notification based on Engine Run Hour & due
18. Load Management through PLC to achieve auto opening and
closing of incomer breakers, bus coupler switching of essential panel
, interlocking providing signal to AMF Panel for load status and
AMF shall give command to DG Set to auto start / auto stop
depending upon load status and requirement etc. and necessary
hardware and software required to perform the operation shall be
provided by the contractor including all control wiring. (C) AMF
Control Panel for100 kVA/125 KVA3 phase DG Set
3 6 Ea Supplying & erecting earth pit of minimum bore dia.150mm size 4591.46
approved make Earthing Electrode consisting Pipe-in-Pipe Technology
as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipes
having Outer pipe dia of 50mm having 80-200 Micron galvanising,
Inner pipe dia of 25 mm having 200-250 Micron galvanising,
connection terminal dia of 12mm with constant ohmic value surrounded
by highly conductive compound with high charge dissipation suitable
for following type of applications with chamber and heavy duty cover.
(A)(approved make OEM has to submit test certificate including value
of earth resistance of installation duly stamped and signed by agency
and officer Incharge has to ensure the value of earthing resistane
mentioned in test Certificate) & having back filling compound of (B)
Inner chemical (CCM Compound)- Resistivity:- 0.2 ohm / meter testing
as per IEC 62561-2017, Voltage drop:- < 1 volt at no load & dry form,
Sulphar content:- <2%(C) Back fill Compound :- Earthing compound
should be capable to retain moisture for long time Necessary test report
must be submitted by Agency. (a) For Electrical Installation up to 440V
Length of pipe - 1 Mtr
Back filling compound - 1 Nos Bag of 15 Kg
4 6 Ea Providing and erecting Approved make Four pole moulded case circuit 6790.23
breaker having breaking capacity ICU of 25 KA. at 415 V,having
normal current rating up to 25 A to 100A. with Fixed thermal &
magnetic release suitable to work on A.C. supply 50 Hz. with all
internal connections, spreader tinned copper & complete erected in
existing 16 G.M.S. housing.ICS=100% of ICU only Cat III
5 1 Ea Providing and erecting Approved make Four pole moulded case circuit 17843.67
breaker having breaking capacity ICU of 35 KA. at 415 V. having
Normal current rating 200A.with variable Thermal & magnetic release
suitable to work on A.C.supply 50 Hz. with all internal connections,
spreader tinned copper & complete erected in existing
G.M.S.housing ICS=100% of ICU only Cat III
6 4 Ea Providing & erecting 240 V MCB double pole switch for motor & 362.59
inductive load (C Curve) having 10 KA breaking capacity & confirms
to IS : 8828 in existing box having following capacity(B) 40 Amp.
7 4 Ea Providing & erecting 415V MCB Four Pole Switch for Lighting Load 702.96
(B curve) having 10KA breaking capacity & confirms to IS :8828 in
existing box having following capacity(b)40 Amp. Cat.III [3-10-4]
8 1 Ea Supplying & erecting approved make Four Pole 415V change over 12241.20
switch interior for panel mounting with operating mechanism A.C.23
duty confirming to IS for (D)200A
9 1 RnM Supplying and erecting triple pole & neutral 440V / 500V panel 3202.71
Tr mounting Copper Busbars with four equal Nos. of electrolyte bus
having current density not more than 1.6 Amp. / sq.mm (Rated current /
cross section area) duly wrapped with colour insulating tape for phase
sequence of following current carrying capacity, erected with necessary
bus bar supports /insulators, main cable socket to each bar, erected in
existing cubical panel with necessary connections.(B) Suitable for
10 2 Sq Providing & erecting weather proof, dust & vermin proof, floor 11466.53
Mtr mounted front operated outdoor type double door cubical panel board
necessary IP-54 and above protection as per approval from engineer
incharge made from 14 SWG thick CRC M.S. sheet for outer body &
doors, 16 SWG thick CRC M.S.sheet for internal partitions with
necessary accesories , supporting angles/ flats channel including
cutting, bending, drilling, welding, riveting with internal partitions &
cable alley as per requirements & instruction of engineer-in-charge with
erection of supplied switch gears, BUSBARS, suitable size of inter
connecting PVC copper wire / copper-aluminium strips, rubber
grommets, rib, bakelite control fuses/MCB for measuring instruments,
earth bus & earth bolts, foundation flange - bolts-base Plates, sufficient
nos. of hinged doors, handles with locking arrangement and rubber
gasket,heavy duty end terminal connection,danger notice
board,necessary ventilation,earthing strip complete. The Panel shall be
painted with epoxy powder coating. (The rates excludes the cost of
switchgears, bus bars, inter connecting mains & Copper Aluminium
strips, meters, Fuses etc. The dimension shall be measured excluding
base beams) The panel shall be supplied with following approved
manufacturers with following size.(A) locally fabricated panel board (i)
with 350 mm depth
11 1 Ea Supplying and erecting approved make single phase servo controlled 6454.91
voltage stabilizer suitable for input voltage range 180/25OV. And
output voltage range 225/235V. A.C. complete erected. (A)1.0 kVA
12 1 Ea Supplying and erecting approved make panel mounting type Digital 1275.63
Voltmeter having 3 digits LED display, 0 to 750 AC Volts range
erected on existing panel board with all connection, wiring etc .with
manufacturers calibration certificate
13 1 Ea Supplying and erecting approved make panel mounting type Digital 1558.43
Ammeter having 3 digits LED display, external CT operated,
calibrated for 0 to 1000 Amps suitable to operate on 500 Volt AC
erected on existing panel board with all connection, wiring etc .with
manufacturers calibration certificate.
14 2 Ea Supplying and erecting Ammeter / Voltmeter selector switch for 3 317.14
phase AC Supply 500 V on existing panel board with necessary
15 3 Ea Providing & erecting L.T. Current Transformer with bar primary 50/5 274.72
to 1000/5 ratio 15 VA burden erected in existing CRCA box duly
secured with insulating materials connected to the meter
16 3 Ea Supplying and erecting approved make suitable panel indicator LED 43.43
type lamp, lens cover, complete erected with necessary connections.
17 10 Kg Providing , erecting , fabricating the M.S. structure as per requirement 77.77
on site incorporating proper size of M.S. angles,square,round, flats,
bars, channels, sections complete with cutting, welding, grinding &
finishing duly painted with one coat of red oxide with erection on site
as per direction of engineer in charge with necessary grouting,
cementing, plastering & finishing complete.
18 50 Mtr Providing and erecting required size Copper strip for earthing of H.T. 794.87
OCB / ACB/ Transformer, LT panel board, Motors etc. using copper
19 4.2 Cu Providing cement concrete. foundation or for concrete filling in 1:3:6 4511.67
mtr ratio with 20 to 25 mm stone metal duly plastered with necessary curing
for pole muffing or any other purpose.
20 1 Ea Providing and erecting Approved make Four pole moulded case circuit 17843.67
breaker having breaking capacity ICU of 35 KA. at 415 V. having
Normal current rating 200A.with variable Thermal & magnetic release
suitable to work on A.C.supply 50 Hz. with all internal connections,
spreader tinned copper & complete erected in new 16 G.M.S.housing
ICS=100% of ICU only Cat III
21 80 Mtr Providing and erecting FRLS-XLPE(IS:7098)(I)-88 ISI armoured cable 589.84
multistrand Aluminium conductor for 1.1 kV. to be laid on wall with
necessary clamps or in existing trench / pipe of following size of cables
(E) 3 1/2 core 95 Sq. mm ( 50 Sq. mm 1/2 core)
22 75 Mtr Making trench in soft soil of suitable width of 90 cm deep for laying 55.55
cable or locating the fault all over the run and back filling the same and
making the surface as normal ground.
23 75 Mtr Providing & laying approved make Double walled corrugated pipes 62.62
(DWC) of polyethylene(conforming to IS 14930 II )with necessary
connecting accessories of same material at required depth in existing
trench for laying of cable. below ground / road surface for enclosing
cable(A)50 mm outer dia
24 4 Ea Providing and, fixing heavy duty flange type brass double compression 131.30
type cable gland with rubber ring for PVC insulated armoured cable
complete with out going tails, insulating tape etc for following size of
cables.(D) 3 & 1/2 core 95 Sq. mm
25 4 Ea Solder less crimping type Aluminium lugs conforming to IS suitable for 20.20
cable of following size evenly crimped with high pressure tool &
connected to switchgear terminals with brass/cadmium plated nut bolts
in an approved manner. (D) 35/50 Sq.mm.
26 1 Ea SITC of Vertical Air Termination Solid aluminium with Base- 10 mm 9416.23
dia and 1000 mm long. Air Termination Base tested for conditioning,
Ageing Test & Lightning impulse current withstand test: 100 kA of
10/350µs waveform in an accredited Third party laboratory as per 6.3 &
6.4 of IEC 62561-1 2017 protocol with MAST 34mm dia 3000 mm long-
Cold Galvanized
27 85 Mtr SITC of 8 mm dia solid Aluminium Conductor for roof top mesh grid 299.97
and tested as per IEC 62561- 2 conducted in the Govt. accredited thirty
party laboratory to meet the requirement of IS/IEC 62305 with Required
Accessories - Aluminium Holding clamp at every 1 mtr distance,
Aluminium/SS cross splicer at every crossing of Alu. conductor,
Expansion piece with connectors at every 20 mtr distance, Aluminium
straight Splicer to connect conductors. All Accessories should be tested
as per IEC 62561-1 2018 Cl. 6.3 for conditioning & Ageing Test &
for Lightning impulse current withstand test: 100 kA of 10/350µs
waveform(Ageing & Electrical test ) conducted in a sequence manner &
tested in the Govt. accredited Third party laboratory to meet the
requirements of IS/IEC
28 2 Ea SITC of 14.2 mm dia 3 mtr long Earth electrode of High tensile steel 5992.33
electrode with 250 micron copper bonding & 1 bag of Carbon fill Based
environment friendly backfill tested as per IEC 62561-7 in NABL
accredited Laboratory and suitable stainless Steel double sided clamp.
Eco Friendly rust proof heavy duty weather proof Polyethylene Earth Pit
Chamber with following dimensions :254 mm dia (top), 330 mm dia
(bottom) & 260 mm (height).
Deputy Executive Engineer Executive Engineer
Electrical (R&B) Sub-Division Electrical (R&B) Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Schedule B DG set Court Valod.pdf
SBD Taluka court valod.pdf
SCHEDULE OF MAINTENANCE FOR GENSET.pdf
AMC New GR.pdf
Online Tender Notice No 13 of 2026-27.pdf
AMC for 10 years DG and AMF Panel.pdf
Special Condition for AMC.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .