Tender Value
₹67.3 L
EMD Value
₹67,303
Closing Date
11 May 2026, 5:00 pmClosed
Superintending Engineer (CG), GIDC, Bharuch.
Supply installation, Testing & Commissioning of 9 Mtr. Hot dip galvanized octagonal streetlight poles with 90 watt LED luminaries streetlight fitting, centralized lighting load energy saver system panel &accessories with 05 years free maintenance guarantee period at Rajpipla-I Industrial Estate.
299147
E-Tender Notice No. 01 of 2026-27 Sr. No. 20
Open
Electrical Works
Works
Bharuch
2 documents required · 2 mandatory
₹2,832
Executive Engineer, GIDC, Ankleshwar
₹67,303
27 Apr 2026
27 Apr 2026
27 Apr 2026
11 May 2026
27 Apr 2026
Name of Work: Supply installation, Testing & Commissioning of 9 Mtr. Hot dip galvanized
octagonal streetlight poles with 90 watt LED luminaries streetlight fitting, centralized lighting load
energy saver system panel &accessories with 05 years free maintenance guarantee period at Rajpipla-
I Industrial Estate
Sr. Description Qty Unit Rate(Rs) Amount(Rs)
1 Supplying and erecting approved make 9 163 No. 15706.00
mtr Octagonal pole made from HR sheet
steel. The pole should be made as per IS.
and shall be coated with hot dip
galvanizing as per IS 2629/2633/4759,
suitable suspend local wind speed with
integral Junction box consist of terminal
plate of min 6mm Hylam sheet, standard
profile 35mmX7.5mm Din-Rail for MCB
Mounting, stud type terminal and
arrangement for cable termination to be
erected on foundation as per details given
by manufacturer considering site
requirement.9 Mtr. Long 70 mm Top X
155 mm bottom dia, 4 mm thickness with
260mmX260mmX16mm base plate, 4-
M24 Bolts and 750mm long J-Bolt.Approx
Pole weight 97 kg
2 Providing M-20 / 1:2:4 cement concrete 163 No. 1652.36
foundation for above item No. 1 & 70 %
PCC from bottom including excavation for
the pole of size 60 x 60 x 150 cms. Deep in
below ground level with plinth of 45 cms x
45 cms(or 45 cms dia x 45 cms) high upper
ground level with necessary curing and
finishing in approved manner and as per
drawing & including excavation and as per
instruction of Engineer Incharge.
3 P & F of Heavy Duty Flanged, Double 326 No. 47.47
Compression type Brass Cable Gland with
rubber ring suitable for 1 x 4.0 Core x
Sq. MM PVC Insulated Alu. Armoured
cable complete with outgoing tails,
insulating taps etc.
4 P & F of Solderless Crimping Type 1307 No. 15.15
Aluminium Lugs (4 Nos. per termination)
conforming to IS suitable for 1 x 4.0 Core
x 16 Sq. MM PVC Insulated Aluminium
Armoured cable tail complete erected with
insulating materials for each terminatio
5 Providing & erecting 240 V MCB double 163 No. 278.76
pole switch for lighting Load ( B Curve )
having 10 KA breaking capacity &
Signature of Contractor Executive Engineer (M&E)
confirms to IS : 8828 in existing box
having following capacity ( A ) 6 to
6 SITC of funnel type pipe earthing having 163 No. 602.57
1.50 Mtr. Long and 25 MM dia. Medium
Class Galvanised iron pipe with coupling
and buch burried in specially prepared
earth pit with salt & charcoal complete
with necessary double 8 SWG GI earth
wire - 0.8 Kg (2 x 3.5 Mtr. = 7Mtr.) laid
upto bolt fitted in pole for earthing .
(Earthing at each poles) as per drawing
7 SITC of Single Arm Decorative Bracket 163 No. 683.77
Providing and erecting street light pole
bracket comprising main B Class GI pipe
of 4.2 cm/require outside dia. complete
with suitable B Class G.I sleeve tubing of
approx. 45cms.length and suitable for
mm / 80mm. / require size pole top having
sufficient fasteners for fixing the brackets
and having spread of 1 mtr. length with
suitable rise as per site condition &
suitable welded stiffener reducer and
nipple with check nut complete painted
with one coat of Red oxide / PU base
primer and two coats of Aluminium / PU
paint. paint with following nos of arms., as
per site condition and as per drawing /
directed by Engineer Incharge. - (1 No. Per
St. Light Pole) (A) Single Arm Bracket
8 Supplying and erecting 90 Watt LED street 163 No. 5976.00
light fittings with fixed programmeable
micro processor based dimmable drive
High power White LEDs wattage of 3 Watt
and above assembled on single MCPCB,
efficiency more than 130 lm/w and
corrosion free High pressure die cast
aluminum housing with smooth finish
powder coated and heat sink extruded
aluminium with diffuser and Polycarbonate
optics/ lenses with company mark/name
engraved or embossed 120 to 300 V,Power
Factor more than 0.95, THD < 10 %, CCT
5000 K to 5700K,Uniformity ratio >0.45,
Luminaire efficiency> 100 lumens/watt .
LED driver efficiency > 85 %.CREE /
OSRAM / PHILIPS Lumileds / NICHIA /
SEOUL/ LG/BridgeLux (U.S.A.) make
LED used for luminaire. ( Fittings required
LM-79 & LM-80 certificates)-(A) Street
Signature of Contractor Executive Engineer (M&E)
Light (IP-66), Surge Protection -4KV and
10 KV non integral, Light must have
440VAC line supply protection. It should
withstand 48 hours for 440VAC line
supply.(Cat-III)
9 Providing & laying mains with 1.1 kV 2119 Mtr. 77.77
grade FR PVC insulated ISI Marked
Stranded Copper cable having Conductor
2 Wire 2.5 Sq. MM.,3 core round PVC
sheathed in exising pipe/ in street light pole
erected with 2.5 Sq. MM. copper
conductor FR PVC insulated stranded wire
of green colour for earth continuity. - (11
Mtr. per St. Light Fitting x 1 No. St. Light
Fitting = 11 Mtr.)
10 Providing, laying, testing & 4890 Mtr. 153.52
commissioning of 1 x 4.0 Core x 16 Sq.
MM, XLPE (IS: 7098 (i) - 88), ISI Mark,
Armoured, Multistranded, Aluminium
Conductor suitable for 1.1 kV grade to be
laid 90 Cms under ground or to be laid on
wall with necessary clamps or in existing
cable trench/ pipe at road crossing or on
floor and making the ground as per
original. - For Streetlight between two
poles & Service Connections.(35 Mtr. per
St. Light Pole)
11 Providing & laying of approved make 50 5216 Mtr. 62.62
MM Nominal OD Doubled Walled
Corrugated Pipes (DWC) of polyethylene
(conforming to IS 14930 - II) with
necessary connecting accessories like
coupler, Tee, L - Bow, etc. of same
material at required depth (90 cms)
including excavation for laying of cable
below ground/ road surface for enclosing
cable and back filling the same to make
ground as per original & as per instruction
of Engineer Incharge - for Streelight Cable
of 1 x 4 core x 10 Sq. MM and Service
cable of 1 x 4 core x 10 Sq. MM. (35 Mtr
Per Between two Pole)
12 Drilling the road without breaking the road 1229 Mtr. 616.10
surface(asphalt)for laying of cable for
feeding power supply by making up to
150mm dia.size of holes at both ends
13 Making trench in soft soil of suitable width 4890 Mtr. 55.55
of 90 cms deep for laying cable or locating
the fault all over the run and backfilling
Signature of Contractor Executive Engineer (M&E)
the same and making the surface as normal
14 Making trench in Hard Murrum / Tar Road 491 Mtr. 74.74
of suitable width of 90 cms or required
depth for laying any size of cable or
locating the fault all over the run and back
filling the same and making the surface as
15 Providing & laying of approved make 120 200 Mtr. 137.36
MM Nominal OD Doubled Walled
Corrugated Pipes (DWC) of polyethylene
(conforming to IS 14930 - II) with
necessary connecting accessories like
coupler, Tee, L - Bow, etc. of same
material at required depth (90 cms)
including excavation for laying of cable
below ground/ road surface for enclosing
cable and back filling the same to make
ground as per original & as per instruction
of Engineer Incharge - for Streelight Cable
of 1 x 4 core x 10 Sq. MM and Service
cable of 1 x 4 core x 10 Sq. MM.
16 SITC of 3 phase Smart 4G Timer, Supply 3 No. 100427.62
of lot based 4G Smart Streetlight Control
& Monitoring System having a Smart
Panel comprising of 3 Phase loT Streetlight
Smart 4G Timer with 16x2 LCD to display
RSSI, relay status, RTC time &
diagnostics., Controller works on 3-phase
& also on any available 1-Phase.,
Controller with 8-hour battery backup
during external power failure. External
power failure alert immediately to cloud.,
110-630 V AC @ 50-60 Hz 3 phase
operating range., Standby power
consumption <3W., Smart 4G Timer with
RS232 port for DLMS Energy meter.,
Smart 4G Timer must be compatible with
any make / brand of DLMS (RS232)
Energy Meter., DI: 4 Nos. (3
Contactor/Latch detection, 1 for Door
Sensor.)., DO: 3 Relays for Independent
control each phase (R, Y. B) with 1 extra
spare relay.. Smart 4G Timer with dual
SIM functionality for connectivity backup..
4G M2M SIM 3-Year communication
included., Local configuration via WiFi
BLE for maintenance or during force
majeure., GPS chip inbuilt of Smart 4G
Timer for auto location tracking &
astronomic schedule location.,
Signature of Contractor Executive Engineer (M&E)
programmable schedules., Astronomic
scheduling with monthly offsets.. Smart
4G Timer has inbuilt timer stores schedules
locally & also stores schedule execution
logs locally, syncs to cloud whenever
connected to cloud., Auto-scheduler
overrides manual operations., Monitoring
& alerts for MCB trips., Over/under
voltage, current, overload, power factor &
short circuit protections with alerts via
Dashboard, App, SMS, WhatsApp &
Email., Contactor / Latch chattering
protection & alerts, Smart 4G Timer with
neutral failure protection and alert., Bulit-
in Watchdog for anti-jamming.. Smart 4G
Timer must send Regular "heartbeat" on
software for CCMS status., Accelerometer
for tamper & panel movement detection &
alerts, Smart 4G Timer must be tested from
an NABL Lab for Surge Test @ 6 KV
(IEC 61000-4-5), ESD Test @ 4 KV (IEC
4), Conducted Emission @ 150 KHz-30
MHz (CISPR11), Damp Heat Test (40 Deg
C @ 95% RH) 2 cycles of 12+12 hours
(IS: 9000 (Part 5/Sec. 2): 1981 latest) with
all test passing criteria as "Temporary
degradation or loss of function or
performance which is self-recoverable".,
FOTA functionality required for upgrades.,
Smart 4G Timer sends & stores
online/offline data of controller & load for
lamp burn hours analysis., It stores &
syncs connectivity logs for configuration
of network connections & analytics.,
PANEL & SWITCHGEAR, The panel
includes a Class 1 DLMS energy meter
NABL approved with 1-2 months of stored
data of daily. hourly, monthly, load survey,
instantaneous, events, tamper data & with
power events stored in meter memory for
audit purpose.. Must monitor V. I. KWH,
KVA, PF, KVAH, etc., Panel made with
mm CRCA sheet with ground mountable
stand complete with gland plate,
waterproof glands, earthing bolt., IP55,
weatherproof panel with RAL7035
powder-coated.Smart 4G Timer must be
fitted on removable terminal sockets for
easy maintenance., Switchgear includes
Nos. 3 pole Contactor / Latch having
Signature of Contractor Executive Engineer (M&E)
minimum 50 A Load carrying capacity per
phase, all other switchgear & wires: 40 A
load carrying capacity., 1 Nos. 4P MCB
kA for Incomer & 6 Nos. 1P MCBs 10 kA
for Outgoing.. Phase-Wise Bypass MCBs
required.. 4P RCCB 100 mA., door sensor.
Also, provide lock & key facility.. Panel
mount outdoor antenna for GSM, GPS.,
Canopy design for draining down water.,
CCMS SMART SOFTWARE, OAuth
APIs for sending data to Government
clouds/software, etc., CCMS Web
dashboard with secure password & OTP
login., Hosted on trusted cloud, data
security, antivirus & attack protection.,
HTTPS,, AES256-bit encryption.,
Vulnerability Assessment and Penetration
Testing (VAPT) certificate for CCMS
Software., Streetlight management
software for load status, live analytics &
reports., Energy meter data tables (kW,
kWh, PF, I, V, etc.) available., Utility
monthly bill reconciliation & Class
accuracy reports for billing, energy
monitoring & auditing for streetlight load.,
Fault detection., Light fault 99% analysis
on dashboard using energy monitoring.,
WhatsApp integration.. Hierarchy-wise
reporting & alerts, GIS mapping of live
connected streetlight
control panels, poles & streetlights.,
MQTT protocol., Smartphone app with
local configuration & navigation.,
Monitoring & reporting of lighting
parameters.. Facility for media attachments
for site photos/videos/work
permits/checklists, etc. per Feeder Panel
for remote verification., Asset management
module for streetlight infrastructure data.,
Complaint/service task management with
history & escalation must be available.,
Android & IOS App for dashboard
analytics, graphs, energy data, alerts,
Years CCMS Web Software & Cloud
Server hosting subscription included
customizable user-friendly deshboard
Note: The Unit rates specified for various items to be executed as per Schedule "B" attached with the
Price Bid are excluding GST but inclusive all labours, materials, testing charges, equipment, all
Signature of Contractor Executive Engineer (M&E)
incidental charges involving in the work and as specified in the Mode of measurement & payment
of detailed specifications of items incl. all taxes, royalty, octroi, transportation cost etc. all as
applicable presently as to be enforced for future by any / all including Central/State Government
& Statutory bodies from time to time.
I / We agree to carry out the work at ______________________ % above the estimated tender rates
___________________________________________ should be written in figures and words.
I / We agree to carry out the work at ______________________ % below the estimated tender rates
___________________________________________ should be written in figures and words.
ESTIMATED AMOUNT ESTIMATED AMOUNT
Put to tender Rs. 6730299.54 Put to tender Rs.
Rupees in words: ___________ Rupees in words: _________________
1. (*) Please strike out whichever is not applicable. All work shall be carried out as per the
specifications of the GIDC or as directed.
2. All the columns in Schedule should be filled in ink and the total entries in the last column should
be struck by the contractor under his signature.
3. Rate quoted included clearance of site (prior to commencement of work & at, its close) in all
respect & hold good for the work under all conditions, site moisture, weather etc.
4. I/We have read the tender/general specifications/ conditions and I/We agree to follow same and
binding to me/us.
Bidders Signature Executive Engineer (M&E),
Signature of Contractor Executive Engineer (M&E)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Bank Guarantee.pdf
Modified schedule.pdf
Volume - I (PQ).pdf
Volume - II (Technical Specification).pdf
Price bid.pdf
B1 Agreement - Part 1.pdf
B1 Agreement - Part 2.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .