| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.9 LAccepted-Finance | L1 | Accepted-Finance Selected | |
| 2 | L2₹16.3 L+₹37,586.91 (2.36%)Accepted-Finance SHAHDARA | DELHI | 110095 | L2 | Accepted-Finance Selected | |
| 3 | L3₹16.7 L+₹82,242.91 (5.17%)Accepted-Finance 2ND FLOOR SHAHEEN BAGH F 207 ABUL FAZAL ENCLAVE II JAMIA NAGAR OKHLA SOUTH DELHI 110025 | SOUTH EAST | DELHI | 110025 | L3 | Accepted-Finance Selected | |
| 4 | Not Admitted-Fee/PreQual/Technical C 344 GALI NO 2 BLOCK C WEST KARAWAL NAGAR DELHI 110094 | NORTH EAST | DELHI | 110094 | - | Not Admitted-Fee/PreQual/Technical Others-Affidavit not as per NIT |
Tender Value
₹17.2 L
EMD Value
₹34,483
Closing Date
24 Sept 2026, 3:00 pmClosed
The Executive Engineer (E)
The Executive Engineer (E), EMD South East, PWD, Thyagraj Sports Complex, New Delhi-11000
Servicing of substation and replacement of ACB, relay, contactor, faulty bus trunking etc at Sub Station and Workshop-1 in ITI Arab ki Sarai Nizamuddin New Delhi.
2026_PWD_298224_1
110/EE(E)/EMD South East/PWD/2026-27
Open Tender
Miscellaneous Services
Works
180 days
At Site
Please refer Tender documents.
15 documents required · 15 mandatory
₹0
₹34,483
25 Sept 2026
17 Sept 2026
24 Sept 2026
17 Sept 2026
24 Sept 2026
17 Sept 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Servicing of 630Amps, 3 Phase, 11 KV, HT VCB, complete with removal from HT panel, opening the required parts for servicing, checking, cleaning, testing & rectification of defects, oiling, greasing of moving gear assembly and arc contacts with CR-2 spray and cadmium solution i/c re-assembling, re-installation in HT panel, re-commissioning etc as reqd. | 3 | Nos | 8,142 | ₹24,426 |
| 2 | Servicing of 630/800 Amps capacity, 3phase, 415 Volt withdrawal type MV ACB complete with removal from panel board, opening/ dismantling the required parts for servicing, checking, cleaning, testing & rectification of defects, oiling greasing moving gear assembly and arc contacts with CR-2 spray and cadmium solution & checking & cleaning of LT panel board in respect of each LT breaker by opening of LT panel & CT’s chamber removing the dust with vacuum cleaner, checking, cleaning & decarbonizing the LT panel, fixed contacts of switchgear & CT’s with CTC/ CRC tightening of contacts & joints of bus-bar CT & PT connections, tightening of cable end termination replacement of burnt/ heated thimbles, nuts, bolts, LT tapping i/c testing, commissioning, re-assembling, reinstallation in panel board etc complete as reqd. | 3 | Nos | 2,375 | ₹7,125 |
| 3 | Testing and calibration of IDMT relay set having 2 Nos. O/L and one No. earth fault relay installed in the existing HT panel by secondary injection method, cleaning the contacts, resetting with required accuracy complete checking & setting of control wiring i/c refixing of the relay unit etc complete as reqd. | 3 | Nos | 1,696 | ₹5,088 |
| 4 | Supplying, Fixing, Testing and Commissioning of IDMT relay set having 2 Nos. O/L and one No. earth fault relay installed in the existing HT panel by secondary injection method, cleaning the contacts, resetting with required accuracy complete checking & setting of control wiring i/c refixing of the relay unit etc complete as reqd. | 3 | Nos | 26,370 | ₹79,110 |
| 5 | Serviceing and cleaning of LT panel, AMF panel, emergency panel, capacitor panel i/c MCCB, busbar, cable termination and check the all termination properly etc complete as reqd. | 1 | Jobs | 5,428 | ₹5,428 |
| 6 | Supplying, installation, testing and commissioning of 800A capacity, 4P Air Circuit breaker 50KA suitable for 415V and designed at 690V AC Supply system,3 phase, Insulation voltage (Ui)=1 kv, Impulse Voltage (Uimp)= 12 kv, 50 Hz, electrical draw out type, front operated with microprocessor-based LCD protection release for adjustable over current, adjustable short circuit, adjustable earth fault & instantaneous protection. The ACB shall havecs=Icu=Icw=100% for 1 sec. for short circuit breaking capacity, full rated neutral, zone selective interlocking with atleast required number of NO and NC switches. ACB shall also confirm to IEC 60947/part 2. Protection release shall have with inbuilt battery back-up. Pre-overload & over temperature protection with individual fault indicating LED's on release. New door as per new ACB's also to be mount as existing panel breaking should have electrical interlocking (Incomer and bus coupler) through under voltage release with proper wiring. Retrofitting to match the ACB with existing panel. Including dismantling of existing ACB complete as required. | 1 | Nos | 2,35,497 | ₹2,35,497 |
| 7 | Providing and fixing 400-420 Amp rating 4 pole contactor with 2 NO and 2 NC auxilliary contacts in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. | 1 | Nos | 72,254 | ₹72,254 |
| 8 | Supplying and fixing insulator in existing VCB/HT panel and connect properly to VCB etc complete as reqd. | 3 | Nos | 1,568 | ₹4,704 |
| 9 | supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: a) 240 sq. mm | 1 | Set | 17,414 | ₹17,414 |
| 10 | SITC of power-Pack 12/24volt (DC Power supply Unit) in existing HT Panel complete etc as required. | 1 | No. | 11,118 | ₹11,118 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.87 MB
BOQ_397603.xls
BOQ • 0.34 MB
tender.pdf
Tender Documents • 2.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .