Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹65.2 LAccepted-AOC KRISHNAKRIPA KOTTARAKARA | ₹65.2 L Quoted ₹66.3 L | L1 | Accepted-AOC L1 Accepted |
| 2 | L2₹69.9 LRejected-AOC | ₹69.9 L | L2 | Rejected-AOC L2 Rejected |
| Sl No | Description | Qty | Unit | DSK ELECTRIC POWER L2 | K K Associates L1 |
|---|---|---|---|---|---|
| 1.00Electrification | |||||
| 1.00 | 1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC
insulated copper conductor single core cable in surface / recessed medium class PVC conduit,
with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS
PVC insulated copper conductor single core cable etc as required.Group C | 12 | point | 1,700 ₹20,400 | 1,600 ₹19,200 |
| 1.00 | OD297555/2024-2025:Supply, installation, testing and commissioning of pre-wired 1800 lumen round/ square surface mount fitting made of die-cast aluminium, having efficacy not less than 110 l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea and giving connection with required length of 16/0.2mm 3core copper conductor flex wire conforming to ISS ar extending the original wiring and giving connections as required. | 97 | each | 2,100 ₹2.0 L | 2,000 ₹1.9 L |
| 1.00 | OD18280/2025-2026:Supply conveyance, installation, testing and commissioning of 1000 lumen round/square (1ft x 1ft) recessed fitting made of diecast aluminium, having efficiency not less than 110l/w, pf greater than 0.95, THD less than or equal to 10% directly on ceiling and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required.(Cree/Osram/lumilled/Nichea or equalent make) | 91 | each | 1,800 ₹1.6 L | 1,680 ₹1.5 L |
| 1.00 | OD304484/2025-2026:Supply ,installation, testing and commissioning of 700lm pressure die cast housing Bulk head with IP65 protection & IK 08 having efficacy not less than 105lm/W and giving connection with 3 core flex wire as required. | 33 | each | 1,000 ₹33,000 | 1,000 ₹33,000 |
| 1.00 | OD304487/2025-2026:Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no's blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% including remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut and bolts , washers, temperature rise equal to 75 deg Celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required: | 33 | each | 3,150 ₹1.0 L | 3,100 ₹1.0 L |
| 1.01 | 1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm | 50 | metre | 110 ₹5,500 | 105 ₹5,250 |
| 1.01 | 1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm | 30 | metre | 207 ₹6,210 | 200 ₹6,000 |
| 1.01 | 1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm | 40 | metre | 158 ₹6,320 | 155 ₹6,200 |
| 1.01 | 1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm | 20 | metre | 305 ₹6,100 | 300 ₹6,000 |
Updated dates
Tender Value
₹65.3 L
EMD Value
₹50,000
Closing Date
28 Feb 2026, 6:00 pmClosed
Chief Electrical Engineer
Office of the Chief Electrical Engineer PWD Electrical Wing Public Office Thiruvananthapuram
GENERAL Health Department Annual Plan 2023 24 Implementation of Plan scheme Developing Super Specialty Facilities Various electrical works in Super Specialty Block 4th floor A A Rahim Memorial District Hospital Kollam General Electrical Work
2026_PWD_836909_1
PWD/BLDG/TR/3148/2023_6_1_1
Open Tender
Electrical Works
240 days
Kollam
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,760
₹50,000
Yes
7 Apr 2026
17 Feb 2026
3 Mar 2026
17 Feb 2026
28 Feb 2026
17 Feb 2026
17 Feb 2026 - 28 Feb 2026
Electrification
1.10.3:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD297555/2024-2025:Supply, installation, testing and commissioning of pre-wired 1800 lumen round/ square surface mount fitting made of die-cast aluminium, having efficacy not less than 110 l/w, pf greater than 0.95, THD less than or equal to 10%, Chip make Cree/Osram/lumilled/Nichea and giving connection with required length of 16/0.2mm 3core copper conductor flex wire conforming to ISS ar extending the original wiring and giving connections as required.
OD18280/2025-2026:Supply conveyance, installation, testing and commissioning of 1000 lumen round/square (1ft x 1ft) recessed fitting made of diecast aluminium, having efficiency not less than 110l/w, pf greater than 0.95, THD less than or equal to 10% directly on ceiling and giving connections with 16/0.20 mm 3 core PVC insulated and sheathed round copper conductor flex wire or extending the original wiring and giving connections as required.(Cree/Osram/lumilled/Nichea or equalent make)
OD304484/2025-2026:Supply ,installation, testing and commissioning of 700lm pressure die cast housing Bulk head with IP65 protection & IK 08 having efficacy not less than 105lm/W and giving connection with 3 core flex wire as required.
OD304487/2025-2026:Supply, installation, testing and commissioning of 1200 mm sweep BEE-5 star rated ceiling fan with brushless direct current motor (BLDC) , class of insulation B , 3 no's blades , 30 cm long down rod , 2no:s canopies, shackle kit, safety rope , copper winding, power factor not less than .9, service value (CM/M/W) minimum 6.00, Air delivery minimum 210 cum/min,350 RPM (tolerance as per IS :374-2019, THD less than 10% including remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut and bolts , washers, temperature rise equal to 75 deg Celsius ( maximum) , insulation resistance more than 2 Megaohm , suitable for 230V,50 Hz, single phase AC supply , earthing etc., complete as required:
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.6:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.15:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 2.5 sq. mm
1.17.21:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.17.22:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 4 sq. mm
1.17.24:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 4 sq. mm
90.6.4.54:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.10.00 sq.mm 4 Run
90.6.4.63:Supply and drawing 650/1100 V grade FRLS PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.16.00 sq.mm 4 Run
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
90.10.3.15:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )32A DP switch with indicator
90.10.3.32:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3 pin plug top with indicator
90.10.3.33:Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A 3pin Shuttered socket
1.27.1:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.27.5:Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm)
1.32:Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
2.3.2:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way, Double door
90.11.1.14:Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43)
2.10.1:Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral),240 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
2.15.3:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
2.13.1:Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
OD304977/2025-2026:Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 100 milli Amperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps
OD304471/2025-2026:Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & shall conform to relevant IS. Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc. , detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc. shall not be used for the fabrication of panel assembly. The measurements will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc. Supply and fabrication of MV panel board using 2.00mm CRCA sheet, powder coated (excluding base frame)
90.14.2.1:Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
90.14.3.1:Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet
90.14.4:Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC)
90.14.5:Supply and fabrication conveyance and installation of angle iron frame work for wall mounting panel board
90.14.6:Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
90.14.7:Supply and providing copper earth bus in the panel board
90.14.10.17:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.320A/400A, 50/55 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.14:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.250A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
OD295294/2025-2026:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required. 320/400A, 4 pole, MCCB with Isolation Duty.
90.14.10.12:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.160A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.11:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 35/36 kA (Ics=100%Icu), 4 pole, current limiting type MCCB with microprocessor based release with overload setting of 50 - 100% having adjustable OL & SC
90.14.10.3:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.16 A-100A, 16 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL
OD307310/2025-2026:Supply, conveyance and fixing the following types & current rated control gears & switchgears conforming to IS 13947 suitable for 440 V, 50 Hz, AC supply in the existing panel assembly as required.125A, 4 pole, current limiting type MCCB with Isolation duty
OD257828/2022-2023:Supply and providing spreader/terminal adapter kit extended terminal for 4 pole MCCB of rating 320A(8 pcs)
OD304466/2025-2026:Supply and providing spreader/terminal adapter kit extended terminal for 4 pole MCCB of rating 160A to 250A(8 pcs)
OD304469/2025-2026:Supply and providing spreader/terminal adapter kit extended terminal for 4 pole MCCB of rating 125A(8 pcs)
OD304470/2025-2026:Supply and providing spreader/terminal adapter kit extended terminal for 4 pole MCCB of rating 100A(8 pcs)
OD265215/2025-2026:Supply and Installation of 325A 4 Pole Power Contactors-Type MCX 41 with 2 NO, 2NC add on block conforms to IS/IEC 60947-4-1 & IEC 60947-4-1 in the existing panel.
OD265216/2025-2026:Supply and Installation of 255A 4 Pole Power Contactors-Type MCX 34 with 2 NO, 2NC add on block conforms to IS/IEC 60947-4-1 & IEC 60947-4-1 in the existing panel.
OD297347/2025-2026:Supply , conveyance , installation , testing and commissioning of Control Relays Auxiliary Contactors, , 2NO + 2NC (Make L&K India MXO AC 22E or equivalent)
OD297348/2025-2026:Supply , conveyance , installation , testing and commissioning of Add On Auxiliary Contactor Block , Coil voltage 24V DC, MO0 , 2NO + 2NC (Make L&K India MO0 or equivalent)
OD297349/2025-2026:Supply installation and testing AC / DC converter unit. 230 V AC to 24V DC
OD297350/2025-2026:Supply, conveyance and fixing 4 C/O relay MY4N-GS DC24 with Base PYF14A-N, Coil Supply 24VDC (MAKE :OMRON or equivalent )
OD297351/2025-2026:Supplying and fixing 16 amps rating, 250V DC volt miniature circuit breaker suitable in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double pole
OD297352/2025-2026:Supplying and fixing 6 amps rating, 130V DC volt miniature circuit breaker suitable in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
OD297353/2025-2026:Supplying and drawing 2 Core Shielded Signal Data Transmission Cable in the existing surface / recessed steel/ PVC conduit as required. (0.50 Sqmm X 1 Pair RS-485 Modbus UNARMD Cable)
OD297354/2025-2026:Supply, conveyance , fixing and testing of Single phase preventer SPP 3phase. Make :GIC SM301 or equivalent
OD297355/2025-2026:Supply and providing Multi function meter to read: Volts, Amps, PF, F, THD,W, Wh, VA, VAh, Var, Varh,Runhrs,Onhrs,Interupts, Preloaded Demand & Import /Export,Min/Max Monitoring with Date/Time stamping,Calibration LED & heart beat LED for communication status 3 phase accuracy class 1 with RS485 communication Port ( Make: Schneider Electric EM6400NG Class-1 with RS485 Port or equal)
OD297356/2025-2026:Supply and installation of Aluminium anodized semi oval type legend plate with inscription of ON/ OFF/ FORWARD/ REVERSE/ START/ STOP/ UP/ DOWN/ R PHASE/ Y PHASE/ B PHASE/ TRIP/ OPEN/ CLOSE/ LEFT/ RIGHT/ MOTOR ON/ MOTOR OFF/ ACCEPT/ RETRACT/ RESET/ EMERGENCY/ EMERGENCY ON/ EMERGENCY OFF/ PUMP RUNNING/ PUMP OFF/ EMERGENCY STOP
OD297357/2025-2026:Supply , conveyance and installation of DIN RAIL 35MMX7.5MM , SLOTTED DIN MOUNTING RAIL (MCB CHANEL)
OD297358/2025-2026:Supply and fixing 25x25 mm open slot cable management system in existing panel for control wiring laying
OD297359/2025-2026:Supply and fixing 50x50 mm open slot cable management system in existing panel for control wiring laying
OD297360/2025-2026:Supply, conveyance and fixing 4 sq mm Screw Clamp Type Polyamide Feedthrough Terminal Block (Pack of 100Nos)
OD297361/2025-2026:Supply and fixing Panel mounting type hooter with cut out dimensions of 96 x 96 mm
OD297364/2025-2026:Supply and providing Red, Green, Black, Yellow, Orange colours LED indicators, AC/DC 22.5mm cut out dia-
OD297363/2025-2026:Supply and providing Blue colour LED indicator lamp, AC/DC, 22.5 cm cut out dia-
OD297365/2025-2026:Flush head Push Button with 1 NO Block
OD297366/2025-2026:Flush head Push Button with 1 NC Block
OD271328/2025-2026:Supply, Installation, Testing and commissioning of 150/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT as required
OD257833/2022-2023:Supply, Installation, Testing and commissioning of 250/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT as required
OD258019/2022-2023:Supply, Installation, Testing and commissioning of 400/5 A, 5 VA, accuracy class 1, Resin Cast Metering CT as required.
OD257997/2022-2023:Supply and fixing Emergency Push Button with MS Box and giving connection etc as required.
OD304488/2025-2026:Supply and providing Danger 415 V, 150 x 100 mm aluminium anodised legend plates in the existing panel board as required.
OD304489/2025-2026:Supply and providing Bus bar chamber, 100 x 40 mm aluminium anodised legend plates in the existing panel board as required.
OD304490/2025-2026:Supply and providing Cable alley, 100 x 40 mm aluminium anodised legend plates in the existing panel board as required.
OD307294/2025-2026:Supplying and fixing 2A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
OD307295/2025-2026:Supply and providing Class A (2mm thick )Elastomeric insulating mat conforming to IS 15652/2006 with maximum use voltage is 3.3 KV .
OD257835/2022-2023:Painting letters or figures of the follwing sizes with enamel paint as identfication mark to SB, DB, panel board etc as required. 2.5 cm, 4 cm, 5 cm height.
90.14.11.5:MCCB AccessoriesSupply and fixing 100 - 200A earth fault module of MCCB with builtin CBCT.
90.14.11.6:MCCB AccessoriesSupply and fixing 250 - 400A earth fault module of MCCB with builtin CBCT.
90.14.11.12:MCCB AccessoriesSupply and fixing shunt release for all voltage range up to 630A.
90.14.11.14:MCCB AccessoriesSupply and fixing rotary handle, Direct type (including BUC handle with door interlock ) in the existing MCCB of rating up to 250 A
OD274328/2025-2026:Supply and installation of DIN Rail Surge Protection Device (4+0) Class B&C/ Type 1&2 with Total Impulse current-50 KA (10/350µ sec) & Total Max Discharge current 200KA (8/20µ sec), Voltage protection level <1.5 kV .The Surge Protection Devices should have TOV safefail for 120 Min : 442 V. Health Status Indication in all catridges.Total Response time <25 nano seconds. Protec T1 (4+0) or Equivalent
OD274329/2025-2026:Supply and installation of DIN Rail Surge Protection Device (4+0) Class B+C/ Type 1+2 with Total Impulse current-10 KA (10/350µ sec) & Total Max Discharge current 200KA (8/20µ sec), Voltage protection level <1.5 kV .The Surge Protection Devices should have TOV safefail for 120 Min : 442 V. Health Satus Indication in all the catridges.Total Response Time <25 nano seconds. Protec T2 (4+0) or Equivalent
OD304454/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required.1.50sq mm wire single run
OD304453/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 2.50sq mm wire single run
OD304452/2025-2026:Carrying out control wiring for panel with normal meters and indication lamps alone with 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 for interconnecting the control devices/equipments including providing suitable size insulated sockets at the termination points or soldered properly,providing numbering ferules for the proper identification of the wiring, keeping the wiring firm by suitable tie/tie mounts/PVC duct etc as required. 4.00sq mm wire single run
OD274321/2025-2026:Supply & laying of one number PVC insulated and PVC sheathed armoured copper power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required. 4 core 1.5 Sq.mm
OD294493/2025-2026:Supply, laying and clamping of 1 no. 1.5 sqmm 4 core PVC/ XLPE insulated armoured control cables with copper conductors for working voltages up to and including 1100 V conforming to IS 1554 part I 1988 for PVC and IS 7098 Part I for XLPE with the cables, spacing of clamps with factory made clamp not exceeding 60cms, making good the damages , colour washing etc. as required.
OD315562/2025-2026:Supply & laying and clamping of one number 2.5 sqmm 12 core PVC/ XLPE insulated armoured control cables with copper conductors for working voltages up to and including 1100 V conforming to IS 1554 part I 1988 for PVC and IS 7098 Part I for XLPE 12 core 2.5 Sq mm with factory made clamp
OD304447/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x35 sqmm (clamped with 1mm thick saddle)
OD304446/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x95 sqmm (clamped with 25x3mm MS flat clamp)
OD304445/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x120 sqmm (clamped with 25/40x3mm MS flat clamp)
OD304451/2025-2026:Supply and laying of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor armoured power cable of 1.1 KV grade conforming to IS1554(part I)/1988 for PVC & IS7098 (part I )/1988 for XLPE of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. 3.5x185 sqmm
OD304444/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 3.5x185 sqmm (clamped with 25/40x3mm MS flat clamp)
OD304443/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 4x10 sqmm (clamped with 1mm thick saddle)
OD304442/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 4x16 sqmm (clamped with 1mm thick saddle)
OD304439/2025-2026:Supply ,laying and fixing of one number PVC insulated and PVC sheathed / XLPE Aluminium conductor power cable of 1.1 KV grade conforming to IS 1554/(part I)/1988 for PVC & IS 7098/(part I)/1988 for XLPE of following size on wall surface as required. 4x25 sqmm (clamped with 1mm thick saddle)
9.1.21:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 35 sq. mm (32mm)
9.1.22:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm)
9.1.24:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 95 sq. mm (45mm)
9.1.25:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)
9.1.27:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.29:Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
90.12.9.4:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench77/63 mm or nearest size
5.4:Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD304437/2025-2026:Providing and drawing 2.00 mm (14 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
OD304435/2025-2026:Providing and drawing 2.65 mm(12 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
OD304434/2025-2026:Providing and drawing 3.15 mm (10 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
OD304433/2025-2026:Providing and drawing 4.0 mm (8 SWG) copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
90.16.2.3:Supply and laying of the following sizes of B class GI pipe laid 0.6 m below ground level including excavating trench of suitable size and refilling etc, as required.32 mm dia G.I pipe ( medium class)
OD304432/2025-2026:Providing and fixing 25 X 3 mm copper strip on surface or in recess for connection using copper saddles ,Al alloy/cadmium plated iron screws,40mm long PVC fastener as required.
OD304431/2025-2026:Supplying and laying 25 mm X 3 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50mm)
90.16.5.1:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.00 mm (14 SWG)
90.16.5.2:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.2.65 mm (12 SWG)
90.16.5.3:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.3.15 mm (10 SWG)
90.16.5.4:Supply of superior quality copper earth socket for the following size of earth conductor including crimping etc. as required.4.00 mm (8 SWG)
OD257980/2022-2023:Charges towards the preparation of necessary plan, scheme and other related papers for submission. A3 sheet first copy
OD257981/2022-2023:Charges towards the preparation of necessary plan, scheme and other related papers for A3 sheet additional copies
OD258006/2022-2023:Charges for dismantling the existing panel boards complete, making good the damages of walls and conveying the dismantled materials to section store.
Installation of UPS
OD306984/2025-2026:Supply, installation, testing and commissioning of 10 KVA, UPS having 30 minutes backup with Isolation transformer, suitable size of c10 tubular batteries & rack having the following specifications "a) 3 ph to 3 ph b) Input pf : 0.99 @ full load c) Output pf : 1 d) Input voltage range : 305V -485V with cut off e) THD : =94% g) Ambient Temperature : 0-40°C h) Generator Compatibility. i) Pure sine wave j) Battery over charge & under charge cut off. k) 3 year warranty. l) Bypass arrangement. m) Indications : Digital indications of Input V & A, output V & A, Battery charge, Temperature m) EN/IEC 620401 for General Safety compatibility n) EN/IEC 620402 for Electromagnetic Compatibility. o) EN/IEC 620403 for Performance p) EN/IEC 620404 for Environmental Compatibility q) battery : Exide / Panasonic or equivalent "
OD307100/2025-2026:Supply, installation, testing and commissioning of 20 KVA, UPS having 30 minutes backup with Isolation transformer, suitable size of c10 tubular batteries & rack having the following specifications "a) 3 ph to 3 ph b) Input pf : 0.99 @ full load c) Output pf : 1 d) Input voltage range : 305V -485V with cut off e) THD : <= 3% f) Overall Efficiency : =94% g) Ambient Temperature : 0-40°C h) Generator Compatibility. i) Pure sine wave j) Battery over charge & under charge cut off. k) 3 year warranty. l) Bypass arrangement. m) Indications : Digital indications of Input V & A, output V & A, Battery charge, Temperature m) EN/IEC 620401 for General Safety compatibility n) EN/IEC 620402 for Electromagnetic Compatibility. o) EN/IEC 620403 for Performance p) EN/IEC 620404 for Environmental Compatibility q) battery : Exide / Panasonic or equivalent "
OD311283/2025-2026:Supply,installation,testing and commissioning of 5 kg Clean agent fire Extinguisher Modular type of following sizes suitable for below ceiling built in 1 piece with body and bottom. Mild steel body with pressure gauge refillable device and safety release device, Brass valve suitable for B and C classes of fire complete with charge of HFC 236FA/FE36(it is a blend of Hydro Fluoro carbon and organic detossificant essence P 26). The extinguisher shall have pressure gauge for indication inside pressure with heat sensitive glass bulb 68 degree with brass forged nozzle and sheet thickness shall not less than 2mm
Installation of DG
18.8.7:Providing, laying, testing and commissioning of C class heavy duty GI pipe conforming to IS 1239, i/c welding ,fittings, like elbows, tees, flanges, tapers, nuts ,bolts ,gaskets etc., and fixing the pipe on the wall , ceiling with suitable clamp or support frame and painting with two or more coats of synthetic enamel paints of required shades complete as required. 100 mm
OD299810/2025-2026:Supply, conveyance and filling of good grade Diesel fuel.
OD271744/2025-2026:Supply and providing cladding for 100mm dia B class GI exhaust pipe using 50mm thick glass wool /mineral wool /rock wool density not less than 120Kg/m3 and aluminium cladding (0.6mm thick).
14.1:Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
14.7:Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required.
14.11:Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
OD307307/2025-2026:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth level Thermo - Mechanically Treated bars of grade Fe-500D or more(CIVIL WORKS specification code no:5.22.6)
Lightning protection
OD59672/2025-2026: Supply and fixing of fully solid 2 meter air terminal with accessories:Air terminals as per IEC - 62305 part-3 16mm rod tapered to 10 mm dia aluminium rod : Meets the requirement of VDE0185/305(IEC 62305) : semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. Includes clamp made of SS 304 tested to lightning current tested with VDE 0185-305 (IEC 62305) H/100KA , made of single piece sheet without welds. With stone base for high level of stability.
OD59674/2025-2026:Supply and fixing of fully solid 4 meter air terminal with accessories:Air terminals as per IEC - 62305 part-3 16mm rod tapered to 10 mm dia aluminium rod : Meets the requirement of VDE0185/305(IEC 62305) : semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. Includes clamp made of SS 304 tested to lightning current tested with VDE 0185-305 (IEC 62305) H/100KA , made of single piece sheet without welds. With multiple stone base for high level of stability.
OD169871/2025-2026:Supply and fixing 8mm solid aluminium round conductor with suitable Stainless steel conductor holder for concrete building meets the requirement of VDE0185/305(IEC 62305) conductor to be (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. With Metallic holder for parapet and heavy approx 1kg polyamide base for non drill area: With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder. Conductor holder @ 1 meter distance. All cross and stright joints at terrace part to be hot dip galvanized and tested in accordance with IEC 62561 including H/100kA , loosening torque test , electrical resistance and static mechanical test etc. Expansion piece to be provided wherever necessary. Should be tested as per IEC 62561 including Electrical resistance, resistivity, Tensile , cyclic test from International/National accredited lab Horizontal run-Parapet application Drillable Areas
OD169786/2025-2026: Supply and fixing 8mm solid aluminium round conductor Should be tested as per IEC 62561 including Electrical resistance, resistivity, Tensile , cyclic test from International/National accredited lab with suitable Stainless steel conductor holder: For down conductor/vertical run on wall/ concrete building Meets the requirement of VDE0185/305(IEC 62305) conductor to be (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. Conductor Holder to be Stainless steel Metallic holder including M8 Screw to connect the conductor holder. Conductor holder @ 1 meter distance. Vertical Run Drillable Areas
OD311291/2025-2026:Supply and fixing 8mm solid aluminium round conductor Should be tested as per IEC 62561 including Electrical resistance, resistivity, Tensile , cyclic test from International/National accredited lab with suitable Stainless steel conductor holder: For down conductor/vertical run on wall/ concrete building Meets the requirement of VDE0185/305(IEC 62305) conductor to be (E-AlMgSiO5 corresponds to DIN 48801) With 50 sq.mm cross sectional area. Conductor Holder to be Stainless steel Metallic holder including M8 Screw to connect the conductor holder. Conductor holder @ 1 meter distance. Horizontal run- concrete terrace application Non-Drillable Areas
OD169787/2025-2026:Supply and fixing of Expansion piece with connector: For equalising temperature related length changes. Necessary on conductors length over 20 meters. Made of round conductor Rd 8-Alu. Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip steel. Connection component should be tested for minimum Lightning current carrying capacity - H/100 kA . Conforms to the requirements according to DIN VDE 0185-305 (IEC 62305).
OD169792/2025-2026:Supply and providing test Joint , Bi metallic type with intermediate plate , made of SS 316. It should be tested for minimum Lightning current carrying capacity - N/100 kA. Suitable to connect 8mm round conductor and 10mm CU bonded conductor. Tested to IEC 62561 requirement All connection component sample to be submitted prior for approval . Test joint to be enclosed in enclosure Internal dimensions of minimum: 176x135x67 mm.
OD298044/2025-2026:"Providing and laying copper coated steel solid round conductor 10mm diameter from earth electrode directly in ground as required. copper coated steel, high corrosion resistant. Meets the requirement of (IS/IEC 62305) copper coating thickness of 100microns Should be tested and use exclusively for lightning protection earthing system and ring equipotential bonding. After test link needs to be routed inside Heavy duty conduit to avoid touch potential till ground level. Approved lab test certificate required
OD169836/2025-2026:Providing and fixing of Outdoor Glass Fibre Reinforced Polycarbonate Enclosure having minimum inner dimension of 75mm x 75 mm x 50 mm. Abox I 40 or Equivalent
OD298087/2025-2026:Supply and laying 10mm Copper bonded round conductor from earth electrode directly in ground for ring/direct test joint connection. Copper bonding to be minimum 100 micron coating. Should be tested to IEC 62561 requirements. Should be tested for Electrical resistance after salt mist cyclic test etc from International/National accredited lab , Connection component/Connectors to be SS and should be tested for minimum Lightning current carrying capacity - N/50 kA
OD298088/2025-2026:Providing and fixing of maintenance free Earthing system comprises of molecularly bonded copper of 99.9% purity on low carbon steel of min 3048mm length (10 feet), having a diameter of 20mm with copper bonding thickness of 250 microns as per UL 467. The Rod has to be either continuous or with self-coupling peg & bore arrangement with fault current withstand capability of 30 KA rms value for 1 second and I peak of 76 KA. The rod must be having corrosion test, peel off test for uniform coating, 180 degree bend test with out peeloff of copper bonding. Exothermic welded Clamp for clamping as suggested as per NBC 2016. Ordinary Stainless steel/Copper alloy universal clamps are not recommended. For self coupling peg & bore arrangement rod needs Impact point on the bottom rod for easy insertion. Earth enhancing mineral compound is used for improving the soil conductivity. The material shall be mineral inert to sub soil and shall not pollute the environment and non corrosive to earth rod. The material should have a resistivity less than 0.2 Ωm. It should be free from hazardous substances. The mineral compound is required to have minimum 17.5 Kg of the total composite. The compound should be chemically inert and needs to submit Govt approved Indian labs test certificate. FRP Earth electrode inspection chamber FRP Earth electrode inspection chamber with weight bearing capacity of 60KN. The dimension shall be 290mmx 290mmx 209mm. Govt approved Indian labs test certificate required.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
techsummary_1409157.pdf
finsummary_1409157.pdf
aoc.pdf
finance_1409157.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.05 MB
SBD.pdf
Tender Documents • 3.16 MB
MOM.pdf
Tender Documents • 0.38 MB
BOQ_1409157.xls
BOQ • 0.42 MB
Download all tender documents and submit your bid