Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹12.8 LAccepted-Finance | 1 | Accepted-Finance 1 lowest | |
| 2 | 2₹14.1 L+₹1.3 L (10.4%)Accepted-Finance | 2 | Accepted-Finance 2 lowest | |
| 3 | 3₹15.6 L+₹2.8 L (22.1%)Accepted-Finance | 3 | Accepted-Finance 3 lowest | |
| 4 | Rejected-Technical 1ST FLOOR SIDHARTH TOWER BALTI KHARKHANA BYELNE S J ROAD ATHGAON GUWAHATI KAMRUP ASSAM 781001 | KAMRUP METRO | ASSAM | 781001 | - | Rejected-Technical No |
Tender Value
₹13.2 L
EMD Value
₹13,210
Closing Date
20 Feb 2023, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
SE, EWC, Bareilly
Katju Marg, Bareilly
Increasing capacity of 33/11kv s/s Harunagla from in district Bareilly
2023_MVVNL_774601_1
24/EWC(B)/2022-23
Open Tender
Electrical Works
Item Rate
90 days
Harunagla Bareilly
as per tender form
3 documents required · 3 mandatory
₹3,540
A/c No. 019205006347, IFSC Code ICIC0000192
₹13,210
23 Jun 2023
13 Feb 2023
20 Feb 2023
13 Feb 2023
20 Feb 2023
13 Feb 2023
Amount
Note - Any material/Labour required to complete the work (which is not covered in above) will be provided by the firm.
Loading, unloading and safe carriage of the following materials from any Electy. Store Center of Electricity store division of Bareilly zone.
M.S. Channel 125x65mm
M.S.Angle 75x75x8mm
MS Angles 50x50x6mm
MS Angle 65x65x6 mm
Rail Piece 90 Lbs
M.S.Channel 100X50X2240mm (Top channel & dropper)
M.S angle lron 65x65x6mm, (bracing)
ST Pole 11Mtr. Long
11KV Disc Insulator 45KN
Disc Fittings 45 KN
11KV Disc Insulator 70 KN
Disc Fittings 70 KN
Earthing complete
Stay Set 16X1800 mm complete
33 KV Lightening Arrestor
33 KV 400 A Bus Isolator
33 KV VCB 800A 750 MVA
Control pannel I/C for 33 KV Single T/F
Cost of 33 kv O/D CT CTR 200/100/1
11 KV VCB I/C CTR 600/300/5A 250 MVA 630 A
11 KV VCB O/G CTR 200/100/5A 350 MVA
33 KV 3x300 mm2 XLPE Cable
11 KV Cable 3x300 Sq. mm XLPE
11 KV Cables 3x185 Sq. mm XLPE
33 KV 3x300 mm2 C/J Kit O/D
11 KV Cable jointing Kit
Cost of ACSR Dog conductor
Earthing of indoor & outdoor equipments of Sub-Station after proper welding of joints and painting of earth strip above soil with proper clamp etc. as per RESPO approved drawing & resistance of earthing should be not more than 2Ω as per as per details given below. Firm have to submitted jointly signed resistance testing certificate of earthing.
Making of triangular bridge by using 32 mm MS round bar electrode , GI strip 50x6mm and GI Pipe 50 mm dia with providing of well type pipe earthing upto 15 Mtr. depth below ground level including welding etc. by boaring process at T/F neutral and T/F body including cost of GI pipe of size 40 mm dia 15 mtr. long of ISI mark(all the required material will be supplied by the contractor and dully checked by AE (Works).
Supply of GI strip of size 50x6mm for earthing of all newly erected structures and equipments in switchyard including cutting, fixing & proper welding with equipments. All LA will be seprately earth also as per RESPO norms. (All the required materials will be provided by firm and will be inspected by AE (Works) before installation.)
Construction of new transformer plinth of size 4.5x3.5 Mtr. for upto 10 MVA Transfomer having depth 0.5 Mtr. below ground level & 0.5 Mtr. above ground level. The work including excavation of foundation. base & concreting of foundation base of CC 1:6:12 ratio (cement, fine sand & brick ballast) first class brick work of cement morter of ratio 1:4 for masonry & lintring work of transformer plinth of RCC work of ratio 1:2:4 (cement, coarse sand and store grit of 20mm using MS Bars of 10mm dia(tor) for reinforcement of linter including cutting, bending & binding of MS bars of required plinth size & shape. The work also includes laying of 2 Nos. 3.5 Mts. long rail pieces after cutting in proper size & shape & fitting etc. The plinth will be made as per RESSPO/Approved drawing suitable for 10 MVA transformer & shall be plastered of walls of ratio 1:4 (cement & fine sand)/finished on top and sides of the plinth. (all material will be provided by firm).
Fabracation, erection and grouting of the following structures as per RESSPO/ Approved Drawing and its, plinth 30cm above ground leval as directed by the Engineer Incharge (All steel sections will be provided by Deptt).
33 KV Bus Isolator Structure
Lightening Arrestor Structure
33 KV VCB Structure
33 KV CT Structure
Fuse Set Structure
Post insulator Structure
Bus bar gantry
Installation of followig equipments on their respective structures including mechanical & electrical fixing after proper adjustment on their structure.
33 KV Bus side isolator (will be mounted on the above bus isolator structure)
33 KV Bus side isolator (will be mounted on the above bus bar gantry)
Lightening Arrestor
33 KV VCB complete
33 KV CT (03 Nos)
33 KV Fuse Set (will be provided by firm)
33 KV Post insulator (will be provided by firm)
24 V Battery set with charger ( To be provided by firm I.S.I. mark only of DC System with one float cum boost charger & battery set for 24V. System with 200A.H. Capacity with cabinet). Including 3 year guarantee.
Complete laying and termination of copper control cables (fire resistance) from 5 MVA power T/F, 33 KV VCB, 33 KV CT in the out door switch yard to the Transformer relay control panel inside the control room including cost of all materials and labour required for proper completion of works as per RESSPO drawings, including cost of testing of transformer, VCB, CT, relay pannel & proper relay settings as per requirement etc.
Laying of dog conductor alongwith cost of all required calmps and connectors etc. as per RESSPO Approved drawing of L.A., C.T., V.C.B., Bus Isolator etc.
Erection and grouting of double pole structure of PCC Poles including stays for 11KV out door feeders, complete in all respect as per RESSPO drawing along with grouting material about 3 meter 4" dia G.I. pipe along with required elbow shall be provided at D/P for power cable including provision of 02 Nos. feeders name plate on D/P. (All type of insulators, steel, stay set with wire, earthing rod, clamps, GI pipe & grouting material provided by the Firm except PCC pole).
Making of M.S. Angle Ladder type frame of Angle (75x75x8mm) & GI Strip (50x6mm) near power transformer for power cable with concreting of the same in the ground and proper clamping (50x6mm) of the same with transformer cable.
Making of M.S. Angle frame of (75x75x8mm) in L shape to connect T/F Neutral by flexible copper strip including cost of copper strip & will be connected to newly constructed well type earthing for Power T/F Neutral as per RESPO norms.
Laying of 11KV cable of different size from power T/F to control room I/C and control room to outside D/P. 11 KV Cable will be layed in brick trench constructed below 750mm to the ground level over the ganga sand. brick trench will be constructed by Ist class bricks covering three sides of cable, after laying 11 KV Cable brick trench will be filed by Ganga sand & then will be covered by bricks & backfill of soil over cable trench as per RESSPO norms.
Laying of 33KV 3x300mm cable from bus bar gantry to ladder near bus isolator of new 5 MVA Transformer. 33 KV Cable will be layed in brick trench constructed below 750mm to the ground level over the ganga sand. brick trench will be constructed by Ist class bricks covering three sides of cable, after laying 33 KV Cable brick trench will be filed by Ganga sand & then will be covered by bricks & backfill of soil over cable trench as per RESSPO norms.
Erection of 11 KV incoming and outgoing panel (with testing & setting of relays) in substation control room including grouting of Anchor bolts of panel and making of pocket for power cable to insert in panel from trench and complete filling of control room's tranches by river sand.
Erection & testing of 1 No. single T/F Control panel in substation control room including grouting of anchor bolts of panel and making of pocket for control cable to insert in panel from trench and complete filling of control room's tranches by river sand.
Termination of 11 KV 3x300sqmm size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of transformer to switch gear panels by providing suitable connectors.
Termination of 11 KV 3x185sqmm size XLPE cable by filling 11 KV heat shrinkable type cable boxes including proper connection with LV side of switch gear panels to double poles out side S/S by providing suitable connectors.
Termination of 33 KV 3x300sqmm size XLPE cable by filling 33 KV heat shrinkable type cable boxes including proper connection with both side of cable by providing suitable connectors.
Hoisting of 11 KV Cable on DP in GI Pipe.
Painting of the fabicated structures with one coat of red oxide primer and two coats of synthetic enamel alumm. Paint/green paint of ISI Mark alongwith earthing strip above ground level.
Shifting and dragging of 33/11 KV 5 MVA transformer from road side to its plinth alongwith its erection including fixing of all assessories and top-up of T/F oil.
Repairing and replacement of damage gasket, Bushing rod, Bushing .Breather,Silica gel etc by repalcement. (In case of old & used 5 MVA T/F)
Cenrifusing of transformer oil in case of old & used power transformer.
Providing of Rubber matting sheet 8/10mm of good quality as per standard specification.
M/S MEGHA ENTERPRISES
M/S SUPER ENGINEERING TRADERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .