Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance NEAR DOON INSTITUTE BHALLA FARM SHYAMPUR RISHIKESH DEHRADUN UK 249 204 | DEHRADUN | DEHRADUN | UTTARAKHAND | 249204 | Admitted-Finance |
| 2 | Admitted-Finance G 16 JAY COMPLEX BELOW UMA CO OP BANK NIZAMPURA VADODARA GUJARAT 390002 | VADODARA | VADODARA | GUJARAT | 390002 | Admitted-Finance |
| 3 | Admitted-Finance 4 A RUKSHMANI PARK SOCIETY OPP SAMA WATER TANK NEW SAMA ROAD VADODARA 390 008 | VADODARA | VADODARA | GUJARAT | 390008 | Admitted-Finance |
Tender Value
₹14.9 L
EMD Value
₹29,800
Closing Date
2 May 2024, 12:00 pmClosed
CWE AHMEDABAD
CWE AHMEDABAD
REPAIR/ REPLACEMENT AND MAINT OF HT OH LINE/ UG CABLE AND OTHER MISC WORKS HT WORKS FOR SECTOR A AND B UNDER GE (A) BARODA
2024_MES_649345_1
87245/E8
Open Tender
Civil Works
Item Rate
120 days
ARMY AREA BARODA
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (A) BARODA
₹29,800
Yes
10 May 2024
5 Apr 2024
3 May 2024
5 Apr 2024
2 May 2024
20 Apr 2024
Amount
Excavating in trenches not exceeding 1.5 meter wide and not exceeding 1.5 meter deep and getting out in soft/ loose soil complete all as specified and as directed.
Returning filling, in including spreading, watering and well ramming in layers not exceeding 25cm in soft/ loose soil complete all as specified and as directed.
Removing suplus soil to a distance not exceeding 50meter and depositing where directed at a level not exceeding 1.5 meter above the starting point complete all as specified and as directed.
Material and labour for sand cushioning for under ground cable with locally available sand for protection of cable 8cm before laying cable and 15cm deep over the cable including spreading and consolidations, complete all as specified and as directed. Note:- Punned thickness i.e. 18mm will be measured and paid.
Supply and laying in trenches dry well burnt locally available sub class 'B' bricks over sand cushioning for protection of cable complete all as specified and as directed.
Supply, laying, commissioning and testing in repairs of XLPE insulated, screened, PVC bedded, galvanise steel strip or wire armoured heavy duty electric power cable with aluminium conductor, 6.35/ 11 KV suitable for 11000 volts grade, cross-sectional area 95 sqmm 3core complete all as specified and as directed.
Material and labour for replacement of cable jointing kit for 11 kV grade (Earthed) HT cable for indoor termination cold shrinkable type complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following sizes complete all as specified and as directed by EIC.
(a) 50 to 95 Sqmm
All as per item 8 hereinbefore but outdoor type complete all as specified and as directed.
(a) 50 to 95 Sqmm
All as per item 8 hereinbefore but for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, straight through type complete all as specified and as directed.
Dismantling of unserviceable insulators of any type/ size and removal from site complete all as specified and as directed.
Supply and fixing of pin type, polymer type, vitreous white, brown or green insulators including galvanised mild steel spindle, two galvanised iron washers and one galvanised iton nut, 150mm height, 150mm dia including section of straps of 38 x 5mm size 20mm dia of bolts, nuts & washers for 11000 volts grade complete all as specified and as directed.
Supply and fixing of disc type insulator, polymer type, vitreous, white, brown or green insulators for working pressure 11000 volt of 145mm height 255mm dia ball and socket type two-in-series assembly for tension with tension clamp for conductors including bolts, nuts & washers complete all as specified and as directed
Dismantling of unserviceable air break gang operated switch 11000 volts grade from overhead HT line structure vertical/ horizontal mounted including insulators and operating mechanism complete all as specified and as directed.
Supply, installation, commissioning and testing 11 KV outdoor type Gang Operated Air Break Switch, 9 polymer type insulator, triple pole vertical type mechanically operated, mounted on polymer insulators and steel frame, with operating mechanism worked from ground level with 25mm dia GI pipe (medium grade) operating rod of suitable length for current rating upto 200 Amps with dropout fuse connected with new ACSR conductor complete all as specified and as directed. Note:- Quoted rate shall deem to be included cost of steel frame, GI pipe suitable length and drop out fuses.
Dismantling unserviceable explusion fuse assembly including insulators, 11000 volts grade from pole.
Supply and fixing explusion fuse single pole including insulators and drop out fuse 11000 volt grade of 25 to 50 Amps capacity complete. (Set of Three)
Dismantling unserviceable lightening arresotrs including insulators, 11000 volts grade from poles and removal from site. (Set of three).
Material and labour for detecting of fault of HT underground cable (any place any length any type/ size) with help of vehicle mounted cable fault locator including detecting exact location of cable fault and remove of cable for rectification complete all as specified and as directed.
Disconnecting and taking out existing HT 11 KV (VCB) from housing and cleaning, rubbing and overhauling the mechanical parts including greasing, oiling, replacement of unserviceable Trip coil, Breaker charging motor, gear pinion, roller switch, big gear checking of SF6 quality of vaccum interrupter, insulation resistances, static contact resistance and re-assembling the same after require and made the VCB serviceable including making all electrical connection and testing (IR value, Ratio test, polarity test) and connection verification of 11 KV current transformer (set of three) by PRIMARY INJECTION KIT and testing and calibration of relay (set of two over current and one earth fualt) by SECONDARY INJECTION KIT including all other functional tests of the VCB, C&R panel and CTs, PTs. Complete all as specified and as directed. Notes:- (i) All spares parts of VCB panel shall be measured and paid for separately under relevent item as supply only. (ii) The repair work and testing of VCB shall be carried out by the representative of OEM only.
Supply only breaker charging motor including gear assembly 220 volt AC of 11 KV VCB panel complete all as specified and as directed.
Supply, install, testing and commissioning of closing coil suitable for 11 KV HT VCB of make L& T 110V DC complete all as specified and as directed.
Supply, install, testing and commissioning of Triping coil suitable for 11 KV HT VCB of make L& T 110V DC complete all as specified and as directed.
Supply, install, testing and commissioning of Power Pack, 230V AC input, 110V DC output, 100VA suitable for 11 KV HT VCB of make L&T 110V DC complete all as specified and as directed.
Supply, install, testing and commissioning of 11 KV, indoor CT 100A/ 50A+1A ACC Class 5P ratio suitable for VCB of Make-ABB or equivalent model of make complete all as specified and as directed.
Supply, install, testing and commissioning of 11 KV, indoor PT 110 V suitable for SF6 VCB of Make-ABB or equivalent model of make complete all as specified and as directed.
Supply and fixing in repair 11 KV panel indicating lamp fitting RYB LED type suitable for 12/24 volt DC complete with base complete all as specified and as directed.
Supply and fixing in repair 11 KV VCB panel volt ampere frequency meter digital type suitable for 12/24 volt DC complete with base complete all as specified and as directed.
Supply, fixing and testing 11 KV bus insulator suitable for 11 KV SF6 VCB Panel complete all as specified and as directed.
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm x 600mm x 6mm buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edged of the plate not less than 1.5 metre below ground level connected to galvanized iron earth strip of size 32 x 6mm by means of bolt, nut, check nut and washer of galvanized iron or steel protected by galvanized iron pipe of 40mm bore medium grade, including. Funnel, 20mm dia bore galvanised iron pipe medium grade for watering, wire mesh, charcoal or coke and common salt in alternative layers all around the earth electrode compacted thickness 15 cm including. Excavation and earth work, PCC 1:3:6 type C-1, CI pit cover, including disposal of surplus soil to a distance not exceeding 50meter complete testing on completion, all complete as shown in electrical plate No. 3 of MES SSR Part-I. Complete all as specified and as directed. Note:- Cost of earth strip and GI protection pipe upto a distance 7.5 metre shall be included in the quoted rate.
Supply, fixing and testing 11 KV HT ceramic bushing of transformer 11 KV/ 433 volt indoor/ outdoor of various capacities complete all as specified and as directed by Engineer-in-Charge including taking out old bushing.
Supply, fixing and testing ceramic bushing LT side of transformer 11 KV/ 433 volt indoor/ outdoor of various capacities i.e. upto and including 350 KVA complete all as specified and as directed by Engineer-in-Charge including taking out old bushing.
Supply, fixing and testing bushing rod of brass both ends threaded including nut, check nut and washer LT side of transformer 11 KV/ 433 volt indoor/ outdoor of various capacities i.e. upto and including 350 KVA complete all as specified and as directed by Engineer-in-Charge including taking out old bushing rod.
Supply and fixing in repair gasket set of synthetic rubberized cork sheet 10mm thick for transformer top lid cover suitable for transformer of capacity upto 350 KVA complete all as specified and as directed.
Material and labour for painting of transformer after cleaning the body surface of transformer by rubbing with emery paper to remove oil strains, dust etc and applying two coat of heat resistance paint by spray paint including writing SM/ MES No and capacity of transformer of capacity upto 350 KVA complete all as specified and as directed.
Supply only transformer oil of approved quality as per IS No: 335-1993 low viscosity type having dielectric strength of 40-60 KV in 2.5mm gap for toping up complete all as specified and as directed.
Supply and fixing in replacement breather assembly complete with 250 grams silica gel suitable for any capacity/ model of transformer to air column of conservator tank complete all as specified and as directed.
Supply and fixing in replacement breather assembly complete with 500 grams silica gel suitable for any capacity/ model of transformer to air column of conservator tank complete all as specified and as directed.
Rewinding of LT/ HT coil, conforming to the orginal winding of the transformer of any make/ capacity with super enamelled DPC insulated copper wire/ strip of appropriate guage and turns and cutting and moving of burnt winding cleaning of core and drying in over after assembly including allied materials. Complete all as specified and as directed. Notes :- (i) Old retrieved materials shall be contractors property and necessary amount as per schedule of credit shall be deducted from contractor's dues. (ii) Rewinding work shall be carried out through OEM authorised representative. (iii) The repair work under each transformer shall be ordered by GE in writting after visual inspection on opening of transformer. (iv) Quoted rates shall be deemed to include cost of new gasket.
Material and labour for trimming/ cutting tree branches with clearing space upto 2 meter from the overhead conductor's any side, all around for HT distribution system complete all as specified and as directed. Note :- (i) Contractor shall take shut down from JE In Charge and proper enter into the shut down register at power house and complete the work within the time and clear the shut down from main power house after completion the work. (ii) The overhead line will be maintained for whole period of contract and the payment will be made on in final bill only. (iii) One span shall be corresponding to from one pole to next immediate pole. (iv) Tree/ branches shall be Govt property.
Dismantling and taking down old unserviceable PCC/ Steel poles complete all as specified and as directed.
Supply and errection steel tubular pole complete with cast iron base plate, final tapper plug, nuts bolts and screws as specified type 410 SP-55 (11 meter long) complete all as specified and as directed.
Material and labour for cement concrete 1:3:6 type C2 (using 40mm graded stone aggregate) as in foundation of pole complete all as specified and as directed.
Material and labour for PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) as in foudation filling and mass concrete for poles complete all as specified and as directed.
Material and labour for plain cement concrete (1:2:4) Type B1 (using 20mm graded stone aggregate) for coping of poles including necessary form work and finishing the exposed surface even and smooth without using extra cement complete all as specified and as directed at site.
Excavating in trenches 1.5m or part thereof in depth beyond the first 1.5m and getting out in soft/ loose soil complete all as specified and as directed.
Dismantling cross arms of MS channel or angle sections/ anti climbing devices complete all as specified and as directed.
Material and labour for structural steel work conforming to grade Fe-410S as in cross arms, bracing, supports, clamps and back plates fabricated from structural steel sections, including nuts, bolts, washers, welding, bending cold or hot drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat, one finishing coat of aluminium paint and epoxy coating sufficient for 11 KV insulation complete all as specified and as directed.
Supplying and fixing aluminium strip 40 x 6mm, fixing with screws, including making holes for cable/ thimbles as required complete all as specified and as directed.
Supply and fixing in replacement of HT jumper of 70 sqmm single core aluminium cable conductor including PG clamps, nut bolts, thimbles and washer required at site complete all as specified and as directed.
Material and labour for preparation of old painted steel and iron surfaces and painting to steel tubular poles of any height 9/11/13 meter, any type (double swan/ single swan) with two coats of synthetic enamel paint upto 1.5 meter height above form ground level (in yellow and black strips of 30 cm wide each) and applying two coats of aluminium paint above 1.5 meter height of poles including painting on cross arms, bracing, clamps etc and writing pole number with black synthetic enamel paint complete all as specified and as directed.
Material and labour for preparation of old painted steel and iron surfaces and painting to 4 pole structure PCC/ Steel poles of any height 9/11/13 meter, any type (double swan/ single swan) with two coats of synthetic enamel paint upto 1.5 meter height above form ground level (in yellow and black strips of 30 cm wide each) and applying two coats of aluminium paint above 1.5 meter height of poles and cross arms, bracing, clamps and writing pole number with black synthetic enamel paint complete all as specified and as directed.
Gayatri Associates
City Light
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .