Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.8 LAccepted-AOC NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | ₹21.8 L Quoted ₹23.7 L | L1 | Accepted-AOC Lowest bidder |
| 2 | L2₹24.6 L+₹88,422 (3.72%)Rejected-Finance | ₹24.6 L+₹88,422 (3.72%) | L2 | Rejected-Finance Unsuccessful Bidder |
Tender Value
₹25.6 L
EMD Value
₹51,200
Closing Date
27 Nov 2019, 6:00 pmClosed
CWE Tezpur
HQ CWE TEZPUR PO DEKARGAON DIST SONITPUR PIN 784501 (ASSAM)
REPAIR/REPLACEMENT OF TRANSFORMERS, VCBS, AND OTHER CONNECTED ITEMS AT NAA UNDER GE (N) TEZPUR
2019_MES_284562_1
CWE/TEZ(N)/T-24 of 2019-20
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (N) Tezpur
as per tender docs
8 documents required · 8 mandatory
₹500
GE (N) Tezpur
₹51,200
Yes
23 Jan 2020
30 Oct 2019
30 Nov 2019
30 Oct 2019
27 Nov 2019
13 Nov 2019
Amount
Dismantling and taking down existing unserviceable Gang operated switch from RCC / Steel tubular (Single/2Pole/3Pole/4Pole) pole structures complete all as specified and directed
Dismantling and taking down unserviceable Lightining arrestors complete all as specified and directed.
Dismantling and taking down rusted / corroded Cross arms any shape and size from PCC/ Steel Tubular Poles including nut bolts clamps complete all as specified and directed
Dismantling and taking down worn out Pin / Disc insulators 11 KV any shape and size from PCC/Steel tubular poles complete all as specified and directed
Dismantling and taking down disturbed GI Wire or cradles from the RCC/Steel Tubular poles Complete all as specified and directed
Dismanteling and taking down disturbed /rusted Overhead ACSR Conductor of any size from HT Poles and shifting to MES store yard all as specified and directed
Dismantling and taking down unserviceable stay assembly complete from PCC / Steel tubular poles complete all as specified and directed
Dismantling and taking up bend/rusted PCC/Steel tubular pole by breaking PCC ,staking at site or shifting to MES store yard. complete all as specified and directed
Dismantling and taking down unserviceable HT UG cable from pole or in trench all as specified and directed.
M&L for Cross-arms, Bracings, Supports, Clamps and Back Plates fabricated from Structural Steel Sections including Nuts, Bolts, Washer, welding, bending cold or hot, drilling holes for Bolts, in any shape or size as indicated/ directed and inclusive of two coats of Aluminium Paint over a coat of primer, complete all as specified and as directed
M & L for Switch Air Break Gang Operated for 11 KV grade, Triple Pole vertically mounted having 12 insulator and fitted on steel frame suitabe for, current rating 200 Amps, mechanically operated mechanism consisting of Operating Rod of GI Pipe 25mm bore (dia) ‘light grade’ of suitable Length worked From Ground Level and with Locking Arrangement Mild Steel Flat Iron Clamp 50x6mm including Expulsion Fuse, Single Pole, Channel type/ drop out type suitable as per Site requirement with Working Pressure 11 KV grade of capacity 50 to 100 Amps including taking down unserviceable Fuse , complete all as specified and as directed
Supply & laying HT XLPE Cable, insulated, screened, PVC bedded, Galvanised Steel Strip or Wire armoured, Electic Power Cable (heavy duty) with Aluminium Conductor, conforming to IS:7098 (Part II), 11 KV, ‘Earthed Grade, cross-sectional area 95 Sqmm 3 Core, laid in Pipe/ Ducts/ Trenches/ under Floor/under Road including Testing, complete all as specified and as directed. NOTE : Earthworks, Sand Cushioning, Bricks, GI Pipe, etc. will be measured and paid under appropriate Items.
Materials and labour for outdoor cable end termination joint cold shrink type suitable for 11 KV 50 to 95 sq mm 3 core HT XLPE 11000 volts heavy duty armoured cable complete all as specified and directed
Materials and labour for indoor cable end termination joint cold shrink type suitable for 11 KV 50 to 95 sq mm 3 core HT XLPE 11000 volts heavy duty armoured cable complete all as specified and directed
S&F of Lightning Arrester Expulsion type complete with all Fittings Transmission Class discharge capacity 65 KA suitablefor working pressure of 11000 Volts including earth strip , complete all as specified and directed
Dismantling and taking down any type of transformers indoor/outdoor,by disconnect HT & LT connections from plinth/ platform/ pole mounted and shifting to workshop for carry out repair (rewinding) works as directed and reinstall back in original location including re-connection of HT & LT supply system including testing complete all as specified and directed.for the following capacity.(Note spare items required for repair including rewinding will be measured and paid seperately under respective items of Sch. Note:- (a) Required tools & plant including lifting arrangement, transport etc shall be included in the rate quoted. (b) Any damage occurred during lifting/ transporting, the firm will be responsible to rectify such defect free of cost
(a) 50 KVA to 160 KVA
(b) 200 to 400 KVA
Draining out all the transformer oil, dismantling and inspection of transformer core and winding including taking out burnt out winding/insulation of LV / HV coils in the presence of the authorized rep.. Reassembling of core and winding, drying out in Heat chamber till specified IR values are obtained and providing new insulation materials, gasket, nuts , bolts, checking of leakages and rectifying the same by welding etc and conducting all tests as per IS 6792-1972 as specified, for transformer capacities 200 to 400 KVA complete all as specified and directed. Note: (i)Supply and fix of all materials required such as winding, LV/HV bushes, Silica gel breather etc will be measured and paid for separately (ii) While removal of the core care shall be taken not to spoil the transformer oil and required filtration including topping up shall be carried out, which shall be measured and paid under respective items of schedule.
All as per item No 17 above but transformer of capacity 50 to 160 KVA complete all as specified and directed
Materials and labour for replacement of silica gel of breather including providing silica gel as per the existing size / model complete all as specified and directed
Supply & fixing in replacement breather assly complete with first fill of silica gel all as specified and directed for 100KVA-400 KVA transformer as per existing make and size
Materials and labour for replacement of temperature gauge as per the existing size / model complete all as specified and directed
Materials and labour for removing the burnt out/ damaged LV bushes with porcelain insulator and replace with Brass LV bushes, nuts , check nuts, rubber washer etc complete as per the existing size / model, for transformers of capacity of 160KVA to 400KVA complete all as specified and directed
Materials and labour for removing the burnt out/ damaged HV bushes with porcelain insulator and replace with Brass HV bushes, nuts , check nuts, rubber washer etc complete as per the existing size / model, for transformers of capacity of 160KVA to 400KVA complete all as specified and directed
Dehydration / Filtration of transformer oil by using Filter Plant and till obtaining the oil dielectric strength 60 KV including topping up of transformer oil to the required level in various transformers located outdoor / indoor sub stations complete all as specified and directed. (Note :- Transformer oil for topping up will be measured and paid separately)
Supply and charging topping up of new low viscosity transformer oil from sealed drums confirming to IS 335-1993 Part-II after testing the correct dielectric strength up to 60KV duly de-hydrated complete all as specified and directed.
Material & labour for scraping of rusted paint from transformer & spray painting of Transformer with smoke grey synthetic enemalled paint over a coat of primer and writing on transformer Capacity ,Make,MES No all as specified and directed by GE/AGE.
Excavation in trenches, in soft / loose soil not exceeding 1.5m wide and not exceeding 1.5m in depth for foundation, etc or not exceeding 10 Sqm on plan and not exceeding 1.5m in depth for Pole, shafts, cesspits, manholes, pier holes, etc and getting out of soft / loose soil complete all as specified and directed
Excavating over areas, n exc 1.5 m deep and getting out in Soft/Loose soil, complete all as specified and as directed
Removing excavated soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed
Returning, Filling in including spreading, leveling, watering and well ramming in layers not exc. 25 cm thick in soils, complete all as specified and as directed
M&L Sand Cushioning (dry) in trenches/ducts for protection of UG Cables (below, above and around the UG Cable laid in Trenches) of 23 cm Spread thickness (8 cm in depth before laying the Cable and 15 cm in depth after laying the Cable) and consolidated (punned) upto 18 cm thickness, complete all as specified and as directed. NOTE : For the purpose of Payment, Punned thickness of Sand Cushioning only shall be measured and paid for
Material and labour for 40mm graded crush stone aggeregate spread around transformer all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover class HV, type - I, flat, size 300 x 180 x 40 mm all as specified and directed
Supply & fixing GI Pipe light grade 80 mm dia, ISI marked, of required length for protection of cables complete including necessary MS clamps, nuts, bolts and washers etc complete all as specified and directed.
Materials and labour for Stay assy complete with accessories as shown in electric plate No.1 stay rod 16mm incl taking down complete (loop type insulator stay clamps excavation & concrete measured separately) complete all as specified and directed
Supply and fix galvanized stay strand size 7/4mm incl taking down the unserviceable stay wire complete all as specified and directed
Materials and labour in replacement pin type porcelain , vitreous, white, brown or green insulator including one galvanized mild steel spindle, two G I washers and one G I nut, 150 mm height and 150 mm dia suitable for 11000 Volts grade complete all as specified and directed.
Material & Labour in replacement for Disc Insulator porcelain viterous, white/brown/green 145mm high and 255 mm dia ball and socket type for working 11000Volts complete all as specified and directed
Material and labour for cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate in foundations, filling and mass concrete for poles / stays complete all as specified and directed
Material and Labour for Plain cement concrete 1:3:6 type C1 using 20mm graded stone aggregate in cement mortar 1:4 for coping incl necessary formwork complete all as specified and directed
Material and Labour for Plain cement concrete 1:2:4 type B1 using 20mm graded stone aggregate in cement mortar 1:4 for coping incl necessary formwork complete all as specified and directed
Material and labour steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11 meters long) and applying two coats of aluminum paint over a coat of red oxide primer,the embeded portion shall be applied with two coats bituminous paint complete all as specified and directed. Note : PCC & Earth work will be measured and paid seperately
Material and labour for alluminium conductor steel reinforced (ACSR) of any size stringing properly on insulators on pole and binding with alluminium tape /binding with connectors, jumpers etc including dismantling and taking down old unserviceable ACSR conductor complete all as specified and directed.
Supply, stretching and fixing in position GI earth wire on poles for continuous earth wire and cradles hexagonal / rectangular fabricated out of 4 mm dia galvanised steel wire including stretching and proper binding inclduing taking down the existing & removing from site complete all as specified and directed
Material and labour for painting to steel tubular pole 9.00/11.0 metre long with two coats of synthetic enamel silver up to below 1.5M from Top edge and 1.50 metre height from ground level in 30 cm alternative black and red strips and remaining portion with alluminium paint incl numbering of pole numbers by stensils and MS frames like channel,clamps, angle, D-clamps etc with two coats of aluminium paint complete all as specified and directed
Supply and fix danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with M S Clamps, bolt and nut approved size for LT poles, 20x15cm size including taking out old unserviceable danger notice plate complete all as specified and directed
Materials and Labour for Earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge of the earth plate at a depth not less than 1.5M below normal ground level connected to galvanised steel strip 32 mm x 6mm by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 54 cm x 54 cm x 5 cm (Reinforced with 8 mm dia. TMT bars @ 150 mm, center to center both ways) with one handle for lifting made out of 8 mm dia. MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing light grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing complete all as shown on electrical plate No 3 of SSR Part-I (2009) complete as specified and directed.
Shifting of HT VCB 11 KV panel from MES Sub Station near DRL gate by disconnecting all incoming and out going control cables connections, dismanteling in to parts and re installation of VCB Pannel at Sub Station in Pump house NO-7 and connecting all controll cable connection and servicing of VCB pannel (such as oiling ,greasing and recalibration of relays for tripping.cost include all minor items) for its smooth functioning up to entire satisfaction of Garrison Engineer/Engr-in-Charge.All as specified and directed. Note : (a) Required tools & plant including lifting arrangement, transport etc shall be included in the rate quoted. (b) Any damage occurred during lifting/ transporting, the firm will be responsible to rectify such defect free of cost.
Cutting of green growth and wild grass by manual labour or by machine at electrical installation premises,around the pole,along the fencing,removing rubbish from the site of work and depositing where directed not exc 100 Mtr from the starting point. complete all as specified and directed. Note :- The item shall be operated maximum 4 times in the entire period of the contract and the measurement will be taken time separately as per the direction of the Engineer-in-Charge
Cutting and trimming of tree branches to clear the over head lines in the area of HT over head lines/feeders (including repairing and jointing of ACSR conductor if damaged during cutting of trees branches) and removal of trimmed branches of trees and depositing the same in waste bin inside the campus all as specified and directed ( Span length not more than 65 Mtr).
NOTES :- 1. For the items for which specifications not mentioned any where in the tender, the IRC specifications shall be followed. 2. Unless otherwise specified the rates for PCC shall deemed to include the cost of formwork shuttering etc., required for complete and proper execution of the work. Refer Schedule "A" notes for details.
M/S GOSWAMI ENGINEERING
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .