Executive Engineer STD Sopore
Amargarh
Development/ Upgradation of 33kV lines of various Divisions of KPDCL-STD Sopore by way of Augmentation of 33Kv Dolipora line (Villgam Grid to Dolipora) from 100sqmm to 200sqmm and stabilization from Dolipora to Magam under SASCI
2026_PDD_332322_1
STDS/37 of 2026-27
Open Tender
Electrical Works
Turn-key
120 days
Kupwara/Dolipora/Magam/Vilgam
Please refer Tender documents.
5 documents required · 5 mandatory
₹3,002
Executive Engineer STD Sopore
₹2.7 L
27 Nov 2026
27 Nov 2026
23 Dec 2026
27 Nov 2026
21 Dec 2026
30 Nov 2026
27 Nov 2026 - 30 Nov 2026
180 days
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | Supply, Installation, Testing and Commissioning | - | - | - | - |
| 1.02 | Supply, Carriage upto site (including Loading/Unloading), Laying ,Stringing, Tensioning & Binding of ACSR Conductor, (200 Sqmm ACSR Conductor-Panther) as per approved drawings/standards | 8 | Km | - | - |
| 1.03 | Supply, Carriage upto site (including Loading/Unloading),Testing and Erection of Steel Tubular Pole, 11 Mtr. Long Pole(ST-410 SP-56) with planting depth of 1/6 th of the height of the pole, (11 mtr. Long ) as per approved drawings/standards | 190 | No. | - | - |
| 1.04 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of GI Channel/ GI V X Arms/Extension Top/Angle Iron/Flat/Belting Angle/Anti Skidding Clamps/Fuse plates of various sizes including clamps as per approved drawings/standards | 6,900 | Kg | - | - |
| 1.05 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of PG/T Clamps suitable for 200 Sqmm ACSR as per approved drawings/standards | 72 | No. | - | - |
| 1.06 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of PG/T Clamps suitable for 100 Sqmm ACSR as per approved drawings/standards | 124 | No. | - | - |
| 1.07 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 33kV Polymeric composite Pin Insulator 36kV, 10kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm (reputed make)as per approved drawings/standards | 474 | No. | - | - |
| 1.08 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of 33kV Polymeric composite Disc Insulator 36kV,min failing load 70kN, Lighting Impulse 170kV Positive and 180kV Negative, creepage distance 900mm with disc fitting (reputed make) as per approved drawings/standards | 192 | No. | - | - |
| 1.09 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Galvinized Nuts and Bolts as per approved drawings/standards | 190 | Kg | - | - |
| 1.1 | Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip 25x3mm as per approved drawings/standards | 190 | No. | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.22 MB
BOQ_1128205.xls
BOQ • 0.30 MB
SBD37.pdf
Tender Documents • 0.20 MB
GTPandDrawings.pdf
Tender Documents • 8.95 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .