Loading…
Loading…
Tender Value
₹30 L
EMD Value
₹40,000
Closing Date
18 Jun 2026, 6:00 pm
Executive Engineer, RANDER DIVISION
Laying of underground cable network with terminations in the area of DGVCL under all scheme for Rander T-1 Sub division under Rander Division and if required work to be carried out at other sub division under Rander Division
311550
DGVCLDRND/0114/06/2026 Approved Date: 05-06-2026
Open
Electrical - All
Surat
3 documents required · 3 mandatory
₹1,180
SURAT
₹40,000
5 Jun 2026
5 Jun 2026
5 Jun 2026
18 Jun 2026
5 Jun 2026
Schedule-B for ARC for Erection and labour work of supply, laying, testing & commissioning of 11/22 KV Underground XLPE cable (XLPE cable will be
supplied by DGVCL) with cable end termination & straight through jointing kit (To be supplied by contractor) on ARC basis under All Scheme for
Rander T-1 sub division under Rander division and if required work to be carried out at other sub division under Rander Division.
Sr. No. Item Code Description Unit FY 2024-25
Labour charge for excavation of cable trench of 400mm width x 1200mm depth, in any
1 9925000001 type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm Meter
additional width shall be considered i.e. half trench length is to be considered)
Labour charge for excavation of cable trench of 600mm width x 1200mm depth, in any
2 9925000002 type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm Meter
additional width shall be considered i.e. half trench length is to be considered)
Labour charge for excavation of cable trench of 400mm width x 1500mm depth, in any
3 9925000003 type of soil for laying of cable of size up to 240 mm2 (For additional cable 200 mm Meter
additional width shall be considered i.e. half trench length is to be considered)
Labour charge for laying of 11kV / 22 kV XLPE Cable of size up to 240 mm2 & preparation
of sand layer 100mm thick, in the cable trench & covering the cable with 150 mm dia
(Inner), thickness 25 mm, 1.0 meter long RCC half round muffs and providing and fixing
4 9925000004 of 4inch width yellow colour polyethylene tape with printing "CAUTION ELECTRIC CABLE Meter
BELOW" at 0.75 m depth from ground surface after laying cable in trench. This will
provide indication that electric cable is passing underground so as to protect cable from
mechnical injuries, refilling the same, as per Instruction of Engineer in Charge (EIC).
Labour charge for horizontal drilling using Auger machine without damage to surface
road at max 2.0 mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D.
8.5mm thickness H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS certification
5 9925000005 and laying of 11KV/22KV XLPE cable of size up to 240 mm2 in HDPE pipe, as per Site Meter
Condition (excluding cost of pipe). The detail map obtained from HDD machine and excell
sheet(hard and soft copy) indicating the respective depth and distance from adjacent
landmark for each segment for HDD is must required to be submitted. HDD to be carried
out at depth 1.5 mtrs to 2.0 mtrs as per site conditions and as per instruction of EIC.
Labour charge for horizontal drilling manually without damage to surface road at max
mtrs depth & putting of 6.11 kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness
H.D.P.E. pipe confirms to IS 4984-1987(3rd revision) and BIS certification and laying of
6 9925000006 11KV/22KV XLPE cable of size up to 240 mm2 size, as per Site Condition (excluding cost of Meter
pipe). The detail map and excell sheet(hard and soft copy) indicating the respective depth
and distance from adjacent landmark for each segment of cable to be submitted. Drilling
to be carried out at depth Minimum 1.2 mtrs to 2.0 mtrs as per site conditions as per
instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5 mm thickness H.D.P.E. pipe
7 9925000007 confirms to IS 4984 and BIS certification for laying of underground 11KV / 22KV XLPE cable Meter
up to 240 mm2 size.
Labour work for RCC concreting on disputed location and repairing of damage portion of
8 9925000008 road crossing for the work carried out for roads crossing as well as concreting & muffing CMT
of ploes including all materials (1:2:4)
Sr. No. Item Code Description Unit FY 2024-25
Providing & fixing concrete stone route marker of 300 mm width x 150 mm thick x
mm height embedded in earth at least 300 mm below & 350 mm above ground level
respectively at distance approx 50 meters along the length of cable. The RCC concreting
(1:2:4)(all necessary maeterials will be in bidder's scope) of route marker is to be carried
out 300 mm width x 150 mm thick x 300 mm below ground level as per instruction of
9 9925000009 EIC. The route marker should be with name of company with approved yellow colour- No.
DGVCL. The distance from marker to cable and cable depth with feeder name etc.,
marked with arrow sign is to be painted on it.The route marker is to be fixed at location
near to any fixed permanent location (not necessary to fix exact on top of cable) as per
instruction of EIC.
Erection of D.P. (double pole) structure using 9 / 11 Mtr. RSJ pole with cable connection
arrangement along with fitting of necessary fabrication for 11KV cable including
10 9925000010 excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting & No.
muffing of poles)
Erection of Single pole structure using 9 / 11 Mtr RSJ pole with cable connection
arrangement along with fitting ofnecessary fabrication for 11KV/22 KV cable including
11 9925000011 excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting & No.
muffing of poles)
Erection of D.P. (double pole) structure using 8.0 Mtr. PSC pole with cable connection
12 9925000012 arrangement along with fitting of necessary fabrication for 11KV cable including No.
excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting &
muffing of poles)
Erection of Single pole structure using 8.0 Mtr PSC pole with cable connection
arrangement along with fitting ofnecessary fabrication for 11KV/22 KV cable including
13 9925000013 excavation of pit & refilling of earth as per instruction of EIC. (Exclusive of concreting & No.
muffing of poles)
Labour charge for erecting of 11kV / 22 kV XLPE cable of size up to 240 mm2 on DP
14 9925000014 Structure with fixing of 02 Nos polymer cleats on top and middle part.Polymer cleats, Per Job
nut bolts etc. fixing material to be provided by contractor.
Providing & fixing of 6.11kg/cm2 , class-4,Green color, 110mm O.D. , 8.5mm thickness
H.D.P.E. pipe confirms to IS 4984 and BIS certification on the erected DP structure for
the mechanical protection of cable by inserting the cable inside HDPE pipe. The HDPE pipe
15 9925000015 shall be erected in such a way that 300mm shall be below the ground level and the rest Per Job
2700 mm shall be supported on the DP Structure with 01 No Polymer cleat.All
materials including polymer cleat and Nut bolt to be provided by contractor.
Providing and fixing of pipe type earthing from 80 mm dia class-B GI pipe with pit to be
16 9925000016 filled with salt & coke and construction of chamber as per DGVCL Drg. No. dg /100 for DP No.
and cable. The earthing pit should be joined with cable by G.I. strip of size 1” width &
mm thick. All material GI pipe, Coke, Salt etc will be supplied by bidder.
Supply & fixing of heat shrink type end terminations (outdoor) for upto 11kV 3C x
mm2 size XLPE cable as per DGVCL technical specification
Supply & fixing of heat & shrinkable end terminations (outdoor) for upto 22 kV 3C x
mm2 size XLPE cable as per DGVCL technical specification)
19 9925000019 Supply & fixing of heat shrink type end terminations (indoor) for upto 11kV 3C x 185 mm2 No.
size XLPE cable as per DGVCL technical specification)
Supply & fixing of heat & shrinkable end terminations (indoor) for upto 22 kV 3C x
mm2 size XLPE cable as per DGVCL technical specification
21 9925000021 Supply & fixing of heat shrinkable straight through joint for upto 11kV 3C x 185 mm2 size No.
XLPE cableas per DGVCL technical specification.
22 9925000022 Supply & fixing of heat shrinkable straight through joint type for upto 22kV 3C x 185 mm2 No.
size XLPE cable as per DGVCL technical specification
Labour charge for excavation of 2100mm long x 1200mm wide x 1200 mm deep joint pits
23 9925000023 for installation of 11kV / 22kV Straight through joints as per instruction of engineer-in- No.
charge & covering the cable with 150 mm dia (Outer), thickness 25 mm, 1.0 meter long
RCC half round muffs & refilling same as per instruction of EIC .
Providing and fixing of insulating bus bar, made from 11KV/22KV XLPE cable after removal
of semi conducting layer and applying of PVC heat shrinkable anti-tracking core insulating
tubing (1.1KV), on both end terminal using Aluminium long barrel heavy duty up to 240 sq
24 9925000024 mm lugs, Aluminium bus connector. Taping with PG- clamp for bus conductor as per No.
drawing and as per instruction of EIC. The Alluminium lugs and PG clamp shall be covered
with 11KV/22KV HT insulating tapes.(11KV/22KV XLPE cable will be in scope of DGVCL
while all other materials will be in bidder's scope)
Sr. No. Item Code Description Unit FY 2024-25
25 9925000025 Testing of cable at various points and commissioning the feeder as per instruction of No.
engineer-in-charge.Test result shall be submitted by contractor with bill.
Preparation and submission of 6 (six) copies, of complete layout drawings with GIS
26 9925000026 mapping as per actual cable routing showing road crossing, HDPE pipe sleeving, jointing Set
locations, markers etc.
Providing and fixing of Sign Board at junction point Made out of 2 mm aluminium sheet
size 750x300 mm (2.5 x 1ft) rectangle, as per design, pre treated with phosphate process
and acid etching coated with one coat of epoxy primer and two coats of best quality
paints, refloctrorised with Hi-Intensity retro – reflective sheeting as per the latest and
27 9925000027 frame fabricated from suitable size iron angle. The Sign Board is to be fixed on the base No.
prepared from channel and bracing angles which is grouted by means of cement
concreting of 1:2:4 for size of 300 mm dia x 800 mm height (500 mm to be grouted in
ground). The details to be displayed on sign board will be given by In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing and fixing of Sign Board (Danger Board) on Distribution Transformer Centers
Made out of 2mm aluminium sheet size 300x300mm (1x1ft) as per design, pre treated
with phosphate process and acid etching coated with one coat of epoxy primer and two
28 9925000028 coats of best quality paints, refloctrorised with Hi-Intensity retro-reflective sheeting as per No.
the latest and frame fabricated from suitable size iron angle. The Sign Board (Danger
Board is to be fixed at the location as per instruction of In-charge Engineer.
(a) Hi intensity Micro prismatic Grade
Providing & fixing of aluminium tag of size 250 mm (L) x 75 mm (W) from 3 mm aluminium
sheet along with 1.0 mm dia aluminium binding wire for fixing of aluminium tag near end
29 9925000029 termination joint at DP structure for identifyng the cable. The details of feeder i.e. 11 / 22 No.
KV with feeder name shound be punched on the tag by letter punch of size 16 mm as per
instruction of In-charge Engineer.
30 9925000030 Supply & fixing of heat shrink type end terminations (outdoor) for 11kV 3C x 240 mm2 No.
size XLPE cable as per DGVCL technical specification
31 9925000031 Supply & fixing of heat & shrinkable end terminations (outdoor) for 22 kV 3C x 240 mm2 No.
size XLPE cable as per DGVCL technical specification)
Supply & fixing of heat shrink type end terminations (indoor) for 11kV 3C x 240 mm2 size
32 9925000032 XLPE cable as per DGVCL technical specification) No.
33 9925000033 Supply & fixing of heat & shrinkable end terminations (indoor) for 22 kV 3C x 240 mm2 No.
size XLPE cable as per DGVCL technical specification
34 9925000034 Supply & fixing of heat shrinkable straight through joint for 11kV 3C x 240 mm2 size XLPE No.
cableas per DGVCL technical specification.
35 9925000035 Supply & fixing of heat shrinkable straight through joint type for 22kV 3C x 240 mm2 size No.
XLPE cable as per DGVCL technical specification
Installation, Testing and commissioning of 11 KV,630 A SCADA Compatible, RRL type-
36 9925000038 Way RMU including Two numbers of earthings as per Drawing (material is in bidder's No.
scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 11 KV,630 A SCADA Compatible, RRLL type-
37 9925000039 Way RMU including Two numbers of earthings as per Drawing (material is in bidder's No.
scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA Compatible, RRL type-3
38 9925000040 Way, RMU including Two numbers of earthings as per Drawing (material is in bidder's No.
scope) and as per DGVCL Technical specification.
Installation, Testing and commissioning of 22KV,630 A SCADA Compatible, RRLL type-4
39 9925000041 Way, RMU including Two numbers of earthings as per Drawing (material is in bidder's No.
scope) and as per DGVCL Technical specification.
Construction of plinth for 11KV, RRL type- 3 Way (i.e Two numbers of Isolator & One
40 9925000042 number of Breaker) Ring Main Unit as per DGVCL's technical specification mentioned in No.
drawing no: Drg. 11kv-01. All required material will be supplied by contractor.
Construction of plinth for 11KV, RRLL type- 4 Way (i.e Two numbers of Isolator & Two
41 9925000043 number of Breaker)Ring Main Unit as per DGVCL's technical specification mentioned in No.
drawing no:Drg. 11kv-02.All required material will be supplied by contractor.
Sr. No. Item Code Description Unit FY 2024-25
Construction of plinth for 22KV, RRL type- 3 Way (i.e Two numbers of Isolator & One
42 9925000044 number of Breaker) Ring Main Unit as per DGVCL's technical specification mentioned in No.
drawing no: Drg. 22kv-01. All required material will be supplied by contractor.
Construction of plinth for 22KV, RRLL type- 4 Way (i.e Two numbers of Isolator & Two
43 9925000045 number of Breaker)Ring Main Unit as per DGVCL's technical specification mentioned in No.
drawing no:Drg. 22kv-02.All required material will be supplied by contractor.
Modifications e.g.Providing and fixing of Terminal protectors i.e. Re-use able boot (HT
Side 11/22KV, LT Side 1.1KV) including 11/22 KV insulating taps and L.T.(1.1 KV) insulating
taps ,Busbar, Tapping from Bus Bar (11/22 KV XLPE cable) through P.G. Clamp for H.T.
Jumper to D.O. Fuse to bushings of Transformer Center, providing & Fixing of jumper
and providing & fixing of Heat Shrinkable Anti Tracking Core Insulating Tubing (Insulation
Level 11/22 KV) in H.T. jumper , Clamping arrangement of cable support frame on both
side of existing Over Head type Distribution Transformer to utilize in Under Ground cable
network as per drawing & as per instruction of Engineer incharge. All live parts i.e. PG-
Clamp, connections of D.O.fuses, HT bushings etc . shall be covered with fixinng of 11/22
44 9925000046 KV HT insulating tapes. ( 11/22 KV XLPE cable will be in scope of DGVCL while all other No.
materials will be in bidder's scope ) .
45 9925000047 Laying of any size of 11/ 22 KV XLPE /PILC Cable in redaymade trench or in open space Per Mtr
46 9925000060 Labour charges for Lying of O/H XLPE cable pole to pole KM
47 9925000064 Supply of 150 mm dia (Inner), thickness 25 mm, 1.0 meter long RCC half round pipe No.
In Words :-- Thirty Lakh Rupees Only
Executive Engineer (O&M)
DGVCL,Rander Division
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Draft Letter_rander-1 inquiry.pdf
2. Rander T-1 SDN Bid Document -.pdf
3. Rander T-1 SDN Detail Tech Specification.docx
DOCX
4. Schedule-b for ug all Sub division.pdf
5.Reference Bid Drawing.pdf
6 .UG CABLE TENDER IMP POINTS.pdf
Download all tender documents and submit your bid