Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹48.4 Cr
EMD Value
₹96.9 L
Closing Date
29 Oct 2025, 5:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer, CCP-II
VCV Gabar Singh Urja Bhawan UPCL, Dehradun
PKG B Undergrounding of HT and LT lines SsTapovan and Muni ki Reti on turnkey basis under Revamped Distribution Sector Scheme in Uttarakhand
2025_UPCLC_87656_1
CCP-II/8/2025-2026
Open Tender
Electrical Works
Turn-key
365 days
As per SBD
As per Tender
5 documents required · 5 mandatory
₹29,500
Yes
Executive Engineer (HQ), UPCL
₹96.9 L
Yes
Conference Hall, UPCL, Urja Bhawan
29 Sept 2025
29 Sept 2025
30 Oct 2025
29 Sept 2025
29 Oct 2025
29 Sept 2025
3 Oct 2025
BoQ_Ver3.0
Instructions to Bidders:- 1. All materials shall be as per technical specification of RDSS. Note:- 1.Any items and spare parts required for completion of work shall be borne by contractor at no extra cost and deemed to be inclusive in overall contract price quoted by contractor. PRICE SCHEDULE : Installation/Erection charges including Testing and commissioning (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
Name of the Bidder/ Bidding Firm / Company :
NUMBER #
33 KV UG Cable
33 KV New UG
33 KV UG TR-XLPE 4*(1Cx630) Sq mm Single Ckt.
19/33 KV (E) grade, Al conductor, Tr-XLPE insulated, Cu tape screened, armoured, PVC sheathed power cable : 1-core/ 630 Sqmm (Colour of Outer sheeth of Cable shall be different from 11 KV & LT cable as specified by UPCL)
CABLE LAYING : Laying, installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.5 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop.,back filling, removal of excess earth from site including earth compression. Cable dia including using motorised mechanical cable pullers, cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) rollers for cable support, Hydraulic jack for cable drum etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Laying and Pulling of 33kV (E) 1cx630mm2 TR-TR-XLPE Underground cable (Cable outer sheet colour as per voltage level decided by UPCL)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL. (New UG Line 1Cx630 Sqmm)
Laying and pulling of 1Cx630Sqmm cable (4 Run) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.5 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using motorised mechanical cable pullers, cable trench pullers (with Line tension Indicator) without open excavation in HDPE pipe:including provision of cable Labels(HDD method),back filling, removal of excess earth from site including earth compression,rollers for cable support, Hydraulic jack for cable drum etc. including cable marking & tagging, termination of cable on terminal gantry or RMU and final testing of HT cable
Laying and Pulling of 33kV (E) 1cx630mm2 TR-XLPE Underground cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply & Laying of HDPE Pipe PE 80/100 PN6 110 mm dia for HT cable at the depth not less than 1.5 meter (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.5 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) using conventional excavation method in HDPE pipe:including provision of cable Labels,back filling, removal of excess earth from site including earth compression
Laying and Pulling of 33kV (E) 1cx630mm2 TR-XLPE Underground cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply & Laying of High -Density Polythylene(HDPE) Pipe PE 80/100 PN6 110 mm Dia for 33 KV 1Cx630 Sq mm TR-XLPE Cable (colour of HDPE Pipe as per voltage level decided by UPCL) using conventional excavation method
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL. (New UG Line 1Cx630 Sqmm)
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 100 mm Dia
Laying and Pulling of 33kV (E) 1cx630mm2 TR-TR-XLPE Underground cable (Cable outer sheet colour as per voltage level decided by UPCL)
PG clamp T-Type (3 Bolt)
Termination kit for 33 KV Grade, 1-core, 630 Sq.mm, Al conductor, XLPE insulated, screened, armoured, PVC sheathed power cable, OUTDOOR / heat-shrinkable type including screen and armour earth kits, all accessories and lugs.
Straight through jointing kit for 33 KV Grade, 1-core, 630 Sq.mm, Al conductor, XLPE insulated , screened, armoured, PVC sheathed power cable, heat-shrink type including termite proofing SS mesh and all accessories
Design & construction of Joint Pit Chamber (1 no in 1 KM) for 33 KV cables : conforming to specifications / guidelines of PWD Uttarakhand and approval including supply of civil materials, reinstatement of road / footpath surface as per PWD Uttarakhand requirements. (Estimated quantities are for max dimensions upto 2000 mm (w) x 2000 mm (l) x (h) 1200 mm whereas actual dimensions subject to space availability and approvals) With Galvanised M.S. Channel 125x65x6 mm. (for frabrication of lid support mesh structure) works and Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for HDPE sheathed including soakpit
i) Excavation of earth in mixed soil
ii) Brick work 1:4
iii) MS bar 12 mm.
Fabrication of lid support mesh structure for Joint Pits using Galvanised M.S. Channel 125x65x6 mm.
Galvanised M.S. Channel 125x65x6 mm. (for frabrication of lid support mesh structure)
Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for PVC / HDPE sheathed cables .
Concrete route marker for HT cable having emboss " DANGER UPCL 33 KV CABLE BELOW" and directional arrows
33KV Incomer
33KV, 1250A, 3 Phase outdoor type VCB (SCADA Operated with Relay61850)
33KV Relay and Control Panel Inc Single T/F(SCADA Operated with Relay61850)
Dismantling of existing 33 KV CB & Control Panel.
33KV Outgoing
33KV, 1250A, 3 Phase outdoor type VCB (SCADA Operated with Relay61850)
33KV Relay and Control Panel FDR Single CKT(SCADA Operated with Relay61850)
Dismantling of existing 33 KV CB & Control Panel.
Replacement of Old Aged 11 KV VCBs/OCB to SCADA Enabled VCBs
Replacement of 11KV Incomer complete with CTs of ratio 800/400/5A
11 KV VCB I/C 500MVA, 800/400/5A, 24 V DC (SCADA Operated with Relay61850)
Dismantling of existing 11 KV VCB/OCB.
Replacement of 11KV Outgoing complete with CTs of ratio 400/200/5A
11 KV VCB FDR 350MVA, 400/200/5A, 24 V DC (SCADA Operated with Relay61850)
Dismantling of existing 11 KV VCB/OCB.
Replacement of 11KV Bus coupler with 11kV motorised Bus coupler
11 KV VCB 350MVA, Bus Coupler & bus riser, 24 V DC (SCADA Operated with Relay61850)
Dismantling of existing 11 KV VCB/OCB.
New 33 KV Bay With VCB's
990 KVA Compact Secondary Substation(CSS)
Supply, erection, testing and commissioning of Compact Secondary Substations (CSS) DRY TYPE including dismantling of existing DTRs.
Transformer 990KVA , LT I/C 2000amps, O/G - 5Nos x 400Amps, including supply & fixing of insulated mats (permanently) for all doors from where operation to be done & also including cable tagging with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
GI Fencing of size (3.5x3.5x2m) including CC columns approx (1 feet in ground & 2 feet above ground) including fixing of danger plate approved by UPCL with proper clamping arrangement on all walls of fencing & gravelling inside the fencing area complete in all respect for CSS & other HT electrical equipment.
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode, Bentonite , test link 450x450 MM C.I manhole chamber etc.
Supply and installation of GI earth strip 35x6mm for connection of earth point with the Earthing electrode in earthpit
CIVIL WORKS
Making of foundation and cable trench for 990 KVA CSS as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
Dismantling of old existing 100 KVA/160KVA/250KVA/400KVA/500KVA/630 KVA distribution transformer & Cartage of Dismantled Distribution Transformer and other accessories.
Locking Arrangement
Single Key Locking Arranagement of RMU (all doors, pads locks, interconnection points, fencing etc)
Sign Board 1 No. 4x3 feet made of MS sheet 14 Gauge(1.6mm thickness) with angle suport of (3"x3",6mm) and height of board 6 feet fromm ground level to bottom of board and length of angle to be buried in the ground 1.50 feet with 1 feet hole pass inside,painting on board ( enamel paint with red oxide base coat) to indicate Name of scheme.
630 KVA Compact Secondary Substation (CSS)
Supply, erection, testing and commissioning of Compact Secondary Substations (CSS) DRY TYPE including dismantling of existing DTRs.
Transformer 630KVA , LT I/C 1250amps , O/G - 4Nos x 400Amps, including supply & fixing of insulated mats (permanently) for all doors from where operation to be done & also including cable tagging with the help of paint & permanent cable taggers (Aluminium) & nomencl
GI Fencing of size (3.5x3.5x2m) including CC columns approx (1 feet in ground & 2 feet above ground) including fixing of danger plate approved by UPCL with proper clamping arrangement on all walls of fencing & gravelling inside the fencing area complete in all respect for CSS & other HT electrical equipment.
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode, Bentonite , test link 450x450 MM C.I manhole chamber etc.
Supply and installation of GI earth strip 35x6mm for connection of earth point with the Earthing electrode in earthpit
CIVIL WORKS
ature with the help of paint & embossing as approved by UPCL on panels.
Dismantling of old existing 100 KVA/160KVA/250KVA/400KVA/500KVA/630 KVA distribution transformer & Cartage of Dismantled Distribution Transformer and other accessories.
Locking Arrangement
Single Key Locking Arranagement of RMU (all doors, pads locks, interconnection points, fencing etc)
Sign Board 1 No. 4x3 feet made of MS sheet 14 Gauge(1.6mm thickness) with angle suport of (3"x3",6mm) and height of board 6 feet fromm ground level to bottom of board and length of angle to be buried in the ground 1.50 feet with 1 feet hole pass inside,painting on board ( enamel paint with red oxide base coat) to indicate Name of scheme.
Making of foundation and cable trench for 630 KVA CSS as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
11 KV 3 Way Ring main Unit (RMU) all complete works
Supply, erection, testing and commissioning of 11 KV 3 Way Ring Main Unit (RMU)
Supply. Erection , Testing and commissioning of 11kV 630A 21kA/3 sec Outdoor Motorised extensible type SF6 insulated RMU (3 Way) Compact Switchgear with 2No. incomer load break switch and 1No. VCB Module as outgoing with auxiliary power module and suitable to connect with FRTU including FPIs. (CCV) on DT from 250-1000KVA r (2No. load break switch for cable and cable out and 1no. VCB for trafo protection) (Including all complete works as making foundation and cable trench, GI fencing, chemical earthings and locking arraingment)
6.35/11 KV (E) grade, Al conductor, TR-XLPE insulated, Cu tape screened, armoured, PVC sheathed power cable : 3-core/ 300 sqmm (Colour of Outer sheeth of Cable shall be different from 33 KV & LT cable as specified by UPCL)
11 KV UG TR-XLPE 3x300 Sq mm Single Ckt.
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Laying and Pulling of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL. (SC)(New UG Line)
Laying and pulling of 11 Kv HT cable (SC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.2 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) without open excavation in HDPE pipe:including provision of cable Labels(HDD method),back filling, removal of excess earth from site including earth compression
Pulling and Laying of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply & Laying of HDPE Pipe 160 mm dia for HT cable at the depth not less than 1.2 meter (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Pulling and Laying of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Laying and Pulling of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 150 mm Dia
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.2 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) using conventional excavation method in HDPE pipe:including provision of cable Labels,back filling, removal of excess earth from site including earth compression
Termination kit for 11 KV Grade, 3-core, 300 Sq.mm, Al conductor, XLPE insulated, screened, armoured, PVC sheathed power cable, OUTDOOR (Heat-shrinkable type including including screen and armour earth kits, all accessories and lugs).
Straight through jointing kit for 11 KV Grade, 3-core, 300 Sq.mm, Al conductor, XLPE insulated , screened, armoured, PVC sheathed power cable, heat-shrink type including termite proofing SS mesh and all accessories
T-Connector (As per Cable current Capacity )
i) Excavation of earth in mixed soil
Design & construction of Joint Pit Chamber (1 nos in 1 KM) for 11 KV cables : conforming to specifications / guidelines of PWD Uttarakhand and approval including supply of civil materials, reinstatement of road / footpath surface as per PWD Uttarakhand requirements. (Estimated quantities are for max dimensions upto 2000 mm (w) x 2000 mm (l) x (h) 1200 mm whereas actual dimensions subject to space availability and approvals) With Galvanised M.S. Channel 125x65x6 mm. (for frabrication of lid support mesh structure) works and Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for HDPE sheathed including Soakpit
iii) Brick work 1:4
v) MS bar 12 mm.
viii) CC 1:1.5:3
Fabrication of lid support mesh structure for Joint Pits using Galvanised M.S. Channel 125x65x6 mm.
Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for PVC / HDPE sheathed cables .
Galvanised M.S. Channel 125x65x6 mm. (for lid support mesh structure)
Concrete route marker for HT cable having emboss " DANGER UPCL 11 KV CABLE BELOW" and directional arrows
6.35/11 KV (E) grade, Al conductor, TR-XLPE insulated, Cu tape screened, armoured, PVC sheathed power cable : 3-core/ 300 sqmm (Colour of Outer sheeth of Cable shall be different from 33 KV & LT cable as specified by UPCL)
11 KV UG TR-XLPE 3x300 Sq mm Single Ckt.
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
11 KV Dismantling of old conductor and accessories with opening of existing jumpering and making of bundle including Loading/Unloading Complete Work.
11 KV UG TR-XLPE 3x300 Sq mm Double Ckt.
Laying and pulling of 11 Kv HT cable (SC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.2 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) without open excavation in HDPE pipe:including provision of cable Labels(HDD method),back filling, removal of excess earth from site including earth compression
Pulling and Laying of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply & Laying of HDPE Pipe 160 mm dia for HT cable at the depth not less than 1.2 meter (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Pulling and Laying of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
11 KV Dismantling of old conductor and accessories with opening of existing jumpering and making of bundle including Loading/Unloading Complete Work.
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 150 mm Dia
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.2 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) using conventional excavation method in HDPE pipe:including provision of cable Labels,back filling, removal of excess earth from site including earth compression
Termination kit for 11 KV Grade, 3-core, 300 Sq.mm, Al conductor, XLPE insulated, screened, armoured, PVC sheathed power cable, OUTDOOR (Heat-shrinkable type including including screen and armour earth kits, all accessories and lugs).
Straight through jointing kit for 11 KV Grade, 3-core, 300 Sq.mm, Al conductor, XLPE insulated , screened, armoured, PVC sheathed power cable, heat-shrink type including termite proofing SS mesh and all accessories
T-Connector (As per Cable current Capacity )
i) Excavation of earth in mixed soil
Design & construction of Joint Pit Chamber (1 nos in 1 KM) for 11 KV cables : conforming to specifications / guidelines of PWD Uttarakhand and approval including supply of civil materials, reinstatement of road / footpath surface as per PWD Uttarakhand requirements. (Estimated quantities are for max dimensions upto 2000 mm (w) x 2000 mm (l) x (h) 1200 mm whereas actual dimensions subject to space availability and approvals) With Galvanised M.S. Channel 125x65x6 mm. (for frabrication of lid support mesh structure) works and Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for HDPE sheathed including Soakpit
iii) Brick work 1:4
v) MS bar 12 mm.
viii) CC 1:1.5:3
Fabrication of lid support mesh structure for Joint Pits using Galvanised M.S. Channel 125x65x6 mm.
Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for PVC / HDPE sheathed cables .
Galvanised M.S. Channel 125x65x6 mm. (for lid support mesh structure)
Laying and pulling of 11 Kv HT cable (DC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Dismantling of all types of HT Poles including accessories, Transportation to central store and handing over to UPCL
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL. (DC)(OH to UG)
New LT Line: Proposed Cabling Works for New DTR/CSS New LT Line with AB Cable
New LT line with Insulated ABC of 3x120+1x95+1x16 Sq.mm. for Plains
PCC Pole 8.5 Mtr
Suspension clamp assembly suitable for AB Cable with all fittings and S.S.strap
Dead end clamp assembly suitable for AB Cable with all fittings and S.S.strap
L.T. Insulation Piercing Connectors for energizing distribution kiosk/box & Jumpering
L.T. Insulation Piercing Connectors (16 sq.mm. - 16 sq.mm.) suitable for street light connection
Piercing connector 95 Sqmm.
Mid span jointing sleeves (120 Sq.mm.)
Mid span jointing sleeves (16 Sq.mm.)
Supply & Fixing of LT distribution boxes/kiosk on the LT poles including all clamps & material required for mounting, connections & sealing.
Insulated ABC of 3x120+1x95+16 Sq.mm.
1x35 mm2 TR-XLPE/PVC insulated Al. cable for energising the distribution boxes/ kiosks.
1x16 mm2 XLPE/PVC insulated Al. cable for energising the distribution boxes/ kiosks/Street light
LT Stay complete Annexure I-13
11 kV Galvanized Stay Set Complete 16ϕX1800 mm. with 2 no. turn-buckle, anchor plate (200x200x6mm) as per scope of work in SBD
GI Stay Wire 7/10 SWG
LT Stay Insulator as per SBD
Grouting with Cement Concreating ratio with 1:3:6
Stay Clamp (50x8mm) with Nuts, Bolts & warshers all galvanized
Rod type earthing of pole by MS earthing rod with welded Clamp 40X3mm, Bolts, Washers & Nuts complete .
8 SWG GI wire
Rod type earthing of pole by MS earthing rod 20ɸx2500mm with welded Clamp 40X3mm & GI wire 8 SWG (0.5 Kg) with Bolts Clamp, Washers & Nuts complete as per Drw. REC/RDSS/GEN/07 Annexure C37
Grouting with Cement Concreating ratio with 1:3:6
Stone pad (450x450x75 mm)
0.433 KV LT XLPE Underground Cable
LT line with 3.5x400 Sqmm XLPE Underground Cable (Double Ckt)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 400 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
Laying and installing, testing & commissioning of LT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open exca
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL.
Laying and pulling of LT cable (DC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
HDPE Pipe for LT cable of sizes 110mm (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in DWC Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
DWC Pipe of Suitable Size for LT Cable
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in Underground Road crossing, Nala crossings etc complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
DWC Pipe of Suitable Size for LT Cable
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as IS 1239 at Bridge &,culverts, crossings, at substations by side of bridges with support hangers, channels, angles, cable trays, fastners, bridge/piers complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
Dismantling of all types of LT Poles including accessories, Transportation to central store and handing over to UPCL
Dismantling of all types of LT ACSR Overhead Conductor & LT AB Cables including accessories etc, Transportation to central store and handing over to UPCL
Straight Through Joint LT Outdoor Type 3.5C x 400 sq. mm.
Concrete route marker for LT cable having emboss "DANGER UPCL LT CABLE BELOW" and directional arrows
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 400 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
LT line with 3.5x240 Sqmm XLPE Underground Cable (Double Ckt)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL.
Laying and pulling of LT cable (DC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 240 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
HDPE Pipe for LT cable of sizes 110mm (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 240 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in DWC Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
DWC Pipe of Suitable Size for LT Cable
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 240 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in Underground Road crossing, Nala crossings etc complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
DWC Pipe of Suitable Size for LT Cable
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 240 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as IS 1239 at Bridge &,culverts, crossings, at substations by side of bridges with support hangers, channels, angles, cable trays, fastners, bridge/piers complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
1.1KV LT armoured Power Cable 3.5x240sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Dismantling of all types of LT ACSR Overhead Conductor & LT AB Cables including accessories etc, Transportation to central store and handing over to UPCL
1.1KV LT armoured Power Cable 3.5x240sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Straight Through Joint LT Outdoor Type 3.5C x 240 sq. mm.
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 400 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
LT line with 3.5x150 Sqmm XLPE Underground Cable (Double Ckt)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL.
Laying and pulling of LT cable (DC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 150 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
HDPE Pipe for LT cable of sizes 110mm (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 150 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in DWC Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
DWC Pipe of Suitable Size for LT Cable
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 150 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in Underground Road crossing, Nala crossings etc complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
DWC Pipe of Suitable Size for LT Cable
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 150 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as IS 1239 at Bridge &,culverts, crossings, at substations by side of bridges with support hangers, channels, angles, cable trays, fastners, bridge/piers complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
1.1KV LT armoured Power Cable 3.5x150sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Dismantling of all types of LT ACSR Overhead Conductor & LT AB Cables including accessories etc, Transportation to central store and handing over to UPCL
1.1KV LT armoured Power Cable 3.5x150sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Straight Through Joint LT Outdoor Type 3.5C x 150 sq. mm.
LT protection (LT feeder pillars)
A-Type Panel for 630 KVA To 1000 KVA DTR (Annexture Y5)
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
FOR DT - 630KVA TO 1000KVA 1 No. Incomer - 2000Amps FP ACB 50kA LSIG 3Nos Outgoings - 400Amps TP MCCB 50kA & 2 No. 250 Amps TP MCCB 50KA
Supply, erection, testing and commissioning of LT cable heavy duty double compression termination Brass Glands and long barrel heavy duty AL Lugs including Provision of cale Armour Earting suitable for the following cable sizes:
1.1KV LT TR-XLPE Cable 3.5x400sqmm
1.1KV LT TR-XLPE Cable 3.5x240sqmm
Barrel Lugs
400 sq. mm. Long barrel Al Lugs for 3.5Cx 400 sqmm cable
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply and installation of GI earth strip 25x6mm for connection of earth point with the Earthing electrode in earthpit
Single Key Locking Arranagement of Panel (all doors, pads locks, interconnection points, fencing etc)
LT protection (LT feeder pillars)
Making of foundation and cable trench for LT A-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
FOR DT - 630KVA TO 1000KVA 1 No. Incomer - 2000Amps FP ACB 50kA LSIG 3Nos Outgoings - 400Amps TP MCCB 50kA & 2 No. 250 Amps TP MCCB 50KA
Supply, erection, testing and commissioning of LT cable heavy duty double compression termination Brass Glands and long barrel heavy duty AL Lugs including Provision of cale Armour Earting suitable for the following cable sizes:
1.1KV LT TR-XLPE Cable 3.5x400sqmm
1.1KV LT TR-XLPE Cable 3.5x240sqmm
Barrel Lugs
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply and installation of GI earth strip 25x6mm for connection of earth point with the Earthing electrode in earthpit
A-Type Panel for 160 KVA To 500 KVA DTR (Annexture Y6)
LT protection (LT feeder pillars)
FOR DT - 160KVA TO 500KVA 1 No. Incomer - 1000Amps FP ACB 50kA LSIG 2 Nos Outgoings - 400Amps TP MCCB 50kA & 2 No. 250 Amps TP MCCB 50KA
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
Supply, erection, testing and commissioning of LT cable heavy duty double compression termination Brass Glands and long barrel heavy duty AL Lugs including Provision of cale Armour Earting suitable for the following cable sizes:
A-Type Panel for 63 KVA To 100 KVA DTR (Annexure Y7)
1.1KV LT TR-XLPE Cable 3.5x400sqmm
1.1KV LT TR-XLPE Cable 3.5x240sqmm
Barrel Lugs
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply and installation of GI earth strip 25x6mm for connection of earth point with the Earthing electrode in earthpit
FOR DT - 63KVA TO 100KVA 1 No. Incomer - 250Amps FP MCCB 50kA LSIG 2 Nos Outgoings - 100Amps TP MCCB 50kA & 2 Nos Outgoings - 63Amps TP MCCB 50kA
1.1KV LT TR-XLPE Cable 3.5x150sqmm
B-Type Panel 160 KVA To 1000 KVA DT Feeders (Annexture Y9)
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
FOR DT - 630KVA TO 1000KVA 1 No. Incomer - 2000Amps FP ACB 50kA LSIG 3Nos Outgoings - 400Amps TP MCCB 50kA & 2 No. 250 Amps TP MCCB 50KA
A-Type Panel for 63 KVA To 100 KVA DTR (Annexure Y7)
1.1KV LT TR-XLPE Cable 3.5x400sqmm
1.1KV LT TR-XLPE Cable 3.5x240sqmm
400 sq. mm. Long barrel Al Lugs for 3.5Cx 400 sqmm cable
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply & Installation Of B Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
ABOVE 160KVA -1000KVA DT FEEDERS : 1 No. Incomer - 400Amps TP MCCB 50kA 3 Nos Outgoings - 400Amps TP MCCB 50kA
1.1KV LT TR-XLPE Cable 3.5x150sqmm
Making of foundation and cable trench for LT B-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
Supply, erection, testing and commissioning of LT cable heavy duty double compression termination Brass Glands and long barrel heavy duty AL Lugs including Provision of cale Armour Earting suitable for the following cable sizes:
A-Type Panel for 63 KVA To 100 KVA DTR (Annexure Y7)
1.1KV LT TR-XLPE Cable 3.5x400sqmm
Barrel Lugs
400 sq. mm. Long barrel Al Lugs for 3.5Cx 400 sqmm cable
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply & Installation Of B Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
B-Type Panel 63 KVA & 100 KVA DT Feeders (Annexture Y10)
FOR 63KVA & 100KVA DT FEEDERS : 1 No. Incomer - 250Amps TP MCCB 50kA 3 Nos Outgoings - 250Amps TP MCCB 50kA
C-Type Panel (Annexure Y11)
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
A-Type Panel for 63 KVA To 100 KVA DTR (Annexure Y7)
1.1KV LT TR-XLPE Cable 3.5x400sqmm
400 sq. mm. Long barrel Al Lugs for 3.5Cx 400 sqmm cable
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
Supply & Installation Of C Type Panel
Supply, erection, testing and commissioning of LT supply Service distribution Boxes for LT consumers complete with
CIVIL WORKS
50x5mm AL busbars for 3Phase + N, lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End) with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
Supply and installation of Spike earthing /Earthing Rod MS (20x2500mm) as per IS 3043 complete
Supply and installation of GI wire 5mm 6swg for connection of earth point with the earthing rod in earth pit
Making of foundation and cable trench for LT C-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
Service Cable
Laying Of 2x10sqmm Service Cables for 1 KM
Supply and Laying of LT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe, and refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
1.1KV LT XLPE Armoured Cable 2x10sqmm
Supply and Laying of 50mm HDPE Pipe for consumer service cables with bends & couplers, Sadling in open complete work in all respect
Making of foundation and cable trench for LT C-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
GI Pipe of suitable sizes for consumer service cables with bands & couplers
Laying Of 2x10sqmm Service Cables for 1 KM
Supply and Laying of LT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe, and refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
2x10 sq. mm. Long barrel Al Lugs
Laying Of 4x16 sqmm Service Cables for 1 KM
Making of foundation and cable trench for LT C-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
1.1KV LT XLPE Armoured Cable 4x16sqmm
Laying Of 2x10sqmm Service Cables for 1 KM
Supply and Laying of LT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe, and refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
4x16 sq. mm. Long barrel Al Lugs
Laying Of 3.5x95sqmm Service Cables for 1 KM
1.1KV LT XLPE Armoured Cable 3.5x95sqmm
1.1KV LT TR-XLPE Cable 3.5x95sqmm
3.5x95 sq. mm. Long barrel Al Lugs
Meter Box
Single Phase Polycarbonate meter box
3.5x95 sq. mm. Long barrel Al Lugs
Supply and Erection of Polycarbonate box for meter including dismantling of damaged / replaceable meter box for 1 Phase meter
Polycarbonate boxes for consumer energy meter 1-phase
Three Phase Polycarbonate meter box
Polycarbonate boxes for consumer energy meter 3-phase
UG Double Pole Required as per Site
33 KV UG Double Pole
Steel Tubular Poles 11 m long (STP 11.0 M, 410 MPa , SP-55) as per IS 2713 (Parts 1 to 3): 1980 (Bottom Portion hot dip galvanized) with MS Plate (300ɸx6)
33 KV Cross bracing Set 50x50x6mm with Belting angle of 50x50x6mm with clamps bolts & nuts all galvanized, as per SBD(for SP-55 pole)
PP of suitable size for Middle portion of STP-410, SP-55 Pole
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 150 mm Dia
33 kV top channel 125x65x6mm 3.2 mtr. Long with all fixing arrngement, bolts & nuts all galvanized (for DoublePole)
PP of suitable size for Top portion of STP-410, SP-55 Pole
33 KV lightening arrestor
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
33 kV Base channel 125x65x6mm 3.2 mtr. Long with clamp, nuts & bolt all galvanized for Cable GI pipe support
33 kV Polymer Pin Insulator complete
Rod type earthing of pole by MS earthing rod with welded Clamp 40X3mm, Bolts, Washers & Nuts complete .
8 SWG GI wire
33 kV Danger board with clamp Bolts & Nuts
Anti-Climbing Device (2.5mm dia (12SWG) galvanized barbed wire 3.5 m per pole) with top and bottam Clamp made of 50x8 mm strip with Nuts, Bolts & Warshers all galvanized for SP-55 Pole)
Rod type earthing of pole by GI earthing rod 20ɸx2500mm with welded Clamp 40X3mm & GI wire 8 SWG (0.5 Kg) with Bolts Clamp, Washers & Nuts complete as per Drw. REC/RDSS/GEN/07 Annexure C37
Stay complete (As per Annex-C-18)
LT Stay Insulator as per SBD
Grouting with Cement Concreating ratio with 1:3:6
Alluminium paint (Double Coat)
Red Oxide paints
Grouting with Cement Concreating ratio with 1:3:6
33 kV Galvanized Stay Set Complete 20ϕX1800 mm. with 2 no. turn-buckles, anchor plate (300x300x8mm) as per scope of work in SBD
Polycarbonate boxes for consumer energy meter 3-phase
Stay Wire 7/8 SWG
33 KV Cross bracing Set 50x50x6mm with Belting angle of 50x50x6mm with clamps bolts & nuts all galvanized, as per SBD(for SP-55 pole)
33kv Stay Insulator
11 kV Base channel 100x50x6mm 2.2 mtr. Long with clamps,nuts & bolt all galvanized for Cable GI Pipe Support
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 150 mm Dia
11 kV Polymer Pin Insulator complete
11 kV Danger Board with Clamp with N&B
9KV, 5KA Outdoor type Lighting Arrester Polymer.
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
33 kV Base channel 125x65x6mm 3.2 mtr. Long with clamp, nuts & bolt all galvanized for Cable GI pipe support
33 kV Polymer Pin Insulator complete
Rod type earthing of pole by MS earthing rod with welded Clamp 40X3mm, Bolts, Washers & Nuts complete .
8 SWG GI wire
11 KV UG Double Pole
LT Stay complete Annexure I-13
11 kV Galvanized Stay Set Complete 16ϕX1800 mm. with 2 no. turn-buckle, anchor plate (200x200x6mm) as per scope of work in SBD
11 kV top channel 100x50x6mm 2.2 mtr. Long with nuts & bolt all galvanized as per SBD specs(for SP-55 pole)
LT Stay Insulator as per SBD
Grouting with Cement Concreating ratio with 1:3:6
Alluminium paint (Double Coat)
Red Oxide paints
Grouting with Cement Concreating ratio with 1:3:6
BoQ_Ver3.0
Instructions to Bidders:- 1. Quoted rate for similar items must be same in each schedule. If any variation, then lowest rate of that item shall be considered for evaluation and award of Work. 2. All materials shall be as per technical specification uploaded with other tender documents. Note:- 1. Any items and spare parts required for completion of work shall be borne by contractor at no extra cost and deemed to be inclusive in overall contract price quoted by contractor. PRICE SCHEDULE: Plant and Equipment to be supplied. (This BOQ template must not be modified/replaced by the bidder and the same should be uploaded after filling the relevent columns, else the bidder is liable to be rejected for this tender. Bidders are allowed to enter the Bidder Name and Values only )
Name of the Bidder/ Bidding Firm / Company :
NUMBER #
33 KV UG Cable
33 KV New UG
33 KV UG TR-XLPE 4*(1Cx630) Sq mm Single Ckt.
19/33 KV (E) grade, Al conductor, Tr-XLPE insulated, Cu tape screened, armoured, PVC sheathed power cable : 1-core/ 630 Sqmm (Colour of Outer sheeth of Cable shall be different from 11 KV & LT cable as specified by UPCL)
CABLE LAYING : Laying, installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.5 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop.,back filling, removal of excess earth from site including earth compression. Cable dia including using motorised mechanical cable pullers, cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) rollers for cable support, Hydraulic jack for cable drum etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Laying and Pulling of 33kV (E) 1cx630mm2 TR-TR-XLPE Underground cable (Cable outer sheet colour as per voltage level decided by UPCL)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL. (New UG Line 1Cx630 Sqmm)
Laying and pulling of 1Cx630Sqmm cable (4 Run) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.5 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using motorised mechanical cable pullers, cable trench pullers (with Line tension Indicator) without open excavation in HDPE pipe:including provision of cable Labels(HDD method),back filling, removal of excess earth from site including earth compression,rollers for cable support, Hydraulic jack for cable drum etc. including cable marking & tagging, termination of cable on terminal gantry or RMU and final testing of HT cable
Laying and Pulling of 33kV (E) 1cx630mm2 TR-XLPE Underground cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply & Laying of HDPE Pipe PE 80/100 PN6 110 mm dia for HT cable at the depth not less than 1.5 meter (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.5 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) using conventional excavation method in HDPE pipe:including provision of cable Labels,back filling, removal of excess earth from site including earth compression
Laying and Pulling of 33kV (E) 1cx630mm2 TR-XLPE Underground cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply & Laying of High -Density Polythylene(HDPE) Pipe PE 80/100 PN6 110 mm Dia for 33 KV 1Cx630 Sq mm TR-XLPE Cable (colour of HDPE Pipe as per voltage level decided by UPCL) using conventional excavation method
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL. (New UG Line 1Cx630 Sqmm)
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 100 mm Dia
Laying and Pulling of 33kV (E) 1cx630mm2 TR-TR-XLPE Underground cable (Cable outer sheet colour as per voltage level decided by UPCL)
PG clamp T-Type (3 Bolt)
Termination kit for 33 KV Grade, 1-core, 630 Sq.mm, Al conductor, XLPE insulated, screened, armoured, PVC sheathed power cable, OUTDOOR / heat-shrinkable type including screen and armour earth kits, all accessories and lugs.
Straight through jointing kit for 33 KV Grade, 1-core, 630 Sq.mm, Al conductor, XLPE insulated , screened, armoured, PVC sheathed power cable, heat-shrink type including termite proofing SS mesh and all accessories
Design & construction of Joint Pit Chamber (1 no in 1 KM) for 33 KV cables : conforming to specifications / guidelines of PWD Uttarakhand and approval including supply of civil materials, reinstatement of road / footpath surface as per PWD Uttarakhand requirements. (Estimated quantities are for max dimensions upto 2000 mm (w) x 2000 mm (l) x (h) 1200 mm whereas actual dimensions subject to space availability and approvals) With Galvanised M.S. Channel 125x65x6 mm. (for frabrication of lid support mesh structure) works and Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for HDPE sheathed including soakpit
i) Excavation of earth in mixed soil
ii) Brick work 1:4
iii) MS bar 12 mm.
Fabrication of lid support mesh structure for Joint Pits using Galvanised M.S. Channel 125x65x6 mm.
Galvanised M.S. Channel 125x65x6 mm. (for frabrication of lid support mesh structure)
Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for PVC / HDPE sheathed cables .
Concrete route marker for HT cable having emboss " DANGER UPCL 33 KV CABLE BELOW" and directional arrows
33KV Incomer
33KV, 1250A, 3 Phase outdoor type VCB (SCADA Operated with Relay61850)
33KV Relay and Control Panel Inc Single T/F(SCADA Operated with Relay61850)
Dismantling of existing 33 KV CB & Control Panel.
33KV Outgoing
33KV, 1250A, 3 Phase outdoor type VCB (SCADA Operated with Relay61850)
33KV Relay and Control Panel FDR Single CKT(SCADA Operated with Relay61850)
Dismantling of existing 33 KV CB & Control Panel.
Replacement of Old Aged 11 KV VCBs/OCB to SCADA Enabled VCBs
Replacement of 11KV Incomer complete with CTs of ratio 800/400/5A
11 KV VCB I/C 500MVA, 800/400/5A, 24 V DC (SCADA Operated with Relay61850)
Dismantling of existing 11 KV VCB/OCB.
Replacement of 11KV Outgoing complete with CTs of ratio 400/200/5A
11 KV VCB FDR 350MVA, 400/200/5A, 24 V DC (SCADA Operated with Relay61850)
Dismantling of existing 11 KV VCB/OCB.
Replacement of 11KV Bus coupler with 11kV motorised Bus coupler
11 KV VCB 350MVA, Bus Coupler & bus riser, 24 V DC (SCADA Operated with Relay61850)
Dismantling of existing 11 KV VCB/OCB.
New 33 KV Bay With VCB's
990 KVA Compact Secondary Substation(CSS)
Supply, erection, testing and commissioning of Compact Secondary Substations (CSS) DRY TYPE including dismantling of existing DTRs.
Transformer 990KVA , LT I/C 2000amps, O/G - 5Nos x 400Amps, including supply & fixing of insulated mats (permanently) for all doors from where operation to be done & also including cable tagging with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
GI Fencing of size (3.5x3.5x2m) including CC columns approx (1 feet in ground & 2 feet above ground) including fixing of danger plate approved by UPCL with proper clamping arrangement on all walls of fencing & gravelling inside the fencing area complete in all respect for CSS & other HT electrical equipment.
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode, Bentonite , test link 450x450 MM C.I manhole chamber etc.
Supply and installation of GI earth strip 35x6mm for connection of earth point with the Earthing electrode in earthpit
CIVIL WORKS
Making of foundation and cable trench for 990 KVA CSS as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
Dismantling of old existing 100 KVA/160KVA/250KVA/400KVA/500KVA/630 KVA distribution transformer & Cartage of Dismantled Distribution Transformer and other accessories.
Locking Arrangement
Single Key Locking Arranagement of RMU (all doors, pads locks, interconnection points, fencing etc)
Sign Board 1 No. 4x3 feet made of MS sheet 14 Gauge(1.6mm thickness) with angle suport of (3"x3",6mm) and height of board 6 feet fromm ground level to bottom of board and length of angle to be buried in the ground 1.50 feet with 1 feet hole pass inside,painting on board ( enamel paint with red oxide base coat) to indicate Name of scheme.
630 KVA Compact Secondary Substation (CSS)
Supply, erection, testing and commissioning of Compact Secondary Substations (CSS) DRY TYPE including dismantling of existing DTRs.
Transformer 630KVA , LT I/C 1250amps , O/G - 4Nos x 400Amps, including supply & fixing of insulated mats (permanently) for all doors from where operation to be done & also including cable tagging with the help of paint & permanent cable taggers (Aluminium) & nomencl
GI Fencing of size (3.5x3.5x2m) including CC columns approx (1 feet in ground & 2 feet above ground) including fixing of danger plate approved by UPCL with proper clamping arrangement on all walls of fencing & gravelling inside the fencing area complete in all respect for CSS & other HT electrical equipment.
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode, Bentonite , test link 450x450 MM C.I manhole chamber etc.
Supply and installation of GI earth strip 35x6mm for connection of earth point with the Earthing electrode in earthpit
CIVIL WORKS
ature with the help of paint & embossing as approved by UPCL on panels.
Dismantling of old existing 100 KVA/160KVA/250KVA/400KVA/500KVA/630 KVA distribution transformer & Cartage of Dismantled Distribution Transformer and other accessories.
Locking Arrangement
Single Key Locking Arranagement of RMU (all doors, pads locks, interconnection points, fencing etc)
Sign Board 1 No. 4x3 feet made of MS sheet 14 Gauge(1.6mm thickness) with angle suport of (3"x3",6mm) and height of board 6 feet fromm ground level to bottom of board and length of angle to be buried in the ground 1.50 feet with 1 feet hole pass inside,painting on board ( enamel paint with red oxide base coat) to indicate Name of scheme.
Making of foundation and cable trench for 630 KVA CSS as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
11 KV 3 Way Ring main Unit (RMU) all complete works
Supply, erection, testing and commissioning of 11 KV 3 Way Ring Main Unit (RMU)
Supply. Erection , Testing and commissioning of 11kV 630A 21kA/3 sec Outdoor Motorised extensible type SF6 insulated RMU (3 Way) Compact Switchgear with 2No. incomer load break switch and 1No. VCB Module as outgoing with auxiliary power module and suitable to connect with FRTU including FPIs. (CCV) on DT from 250-1000KVA r (2No. load break switch for cable and cable out and 1no. VCB for trafo protection) (Including all complete works as making foundation and cable trench, GI fencing, chemical earthings and locking arraingment)
6.35/11 KV (E) grade, Al conductor, TR-XLPE insulated, Cu tape screened, armoured, PVC sheathed power cable : 3-core/ 300 sqmm (Colour of Outer sheeth of Cable shall be different from 33 KV & LT cable as specified by UPCL)
11 KV UG TR-XLPE 3x300 Sq mm Single Ckt.
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Laying and Pulling of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL. (SC)(New UG Line)
Laying and pulling of 11 Kv HT cable (SC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.2 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) without open excavation in HDPE pipe:including provision of cable Labels(HDD method),back filling, removal of excess earth from site including earth compression
Pulling and Laying of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply & Laying of HDPE Pipe 160 mm dia for HT cable at the depth not less than 1.2 meter (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Pulling and Laying of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Laying and Pulling of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 150 mm Dia
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.2 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) using conventional excavation method in HDPE pipe:including provision of cable Labels,back filling, removal of excess earth from site including earth compression
Termination kit for 11 KV Grade, 3-core, 300 Sq.mm, Al conductor, XLPE insulated, screened, armoured, PVC sheathed power cable, OUTDOOR (Heat-shrinkable type including including screen and armour earth kits, all accessories and lugs).
Straight through jointing kit for 11 KV Grade, 3-core, 300 Sq.mm, Al conductor, XLPE insulated , screened, armoured, PVC sheathed power cable, heat-shrink type including termite proofing SS mesh and all accessories
T-Connector (As per Cable current Capacity )
i) Excavation of earth in mixed soil
Design & construction of Joint Pit Chamber (1 nos in 1 KM) for 11 KV cables : conforming to specifications / guidelines of PWD Uttarakhand and approval including supply of civil materials, reinstatement of road / footpath surface as per PWD Uttarakhand requirements. (Estimated quantities are for max dimensions upto 2000 mm (w) x 2000 mm (l) x (h) 1200 mm whereas actual dimensions subject to space availability and approvals) With Galvanised M.S. Channel 125x65x6 mm. (for frabrication of lid support mesh structure) works and Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for HDPE sheathed including Soakpit
iii) Brick work 1:4
v) MS bar 12 mm.
viii) CC 1:1.5:3
Fabrication of lid support mesh structure for Joint Pits using Galvanised M.S. Channel 125x65x6 mm.
Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for PVC / HDPE sheathed cables .
Galvanised M.S. Channel 125x65x6 mm. (for lid support mesh structure)
Concrete route marker for HT cable having emboss " DANGER UPCL 11 KV CABLE BELOW" and directional arrows
6.35/11 KV (E) grade, Al conductor, TR-XLPE insulated, Cu tape screened, armoured, PVC sheathed power cable : 3-core/ 300 sqmm (Colour of Outer sheeth of Cable shall be different from 33 KV & LT cable as specified by UPCL)
11 KV UG TR-XLPE 3x300 Sq mm Single Ckt.
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
11 KV Dismantling of old conductor and accessories with opening of existing jumpering and making of bundle including Loading/Unloading Complete Work.
11 KV UG TR-XLPE 3x300 Sq mm Double Ckt.
Laying and pulling of 11 Kv HT cable (SC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.2 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) without open excavation in HDPE pipe:including provision of cable Labels(HDD method),back filling, removal of excess earth from site including earth compression
Pulling and Laying of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
Supply & Laying of HDPE Pipe 160 mm dia for HT cable at the depth not less than 1.2 meter (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Pulling and Laying of 11kV (E) 3*300mm2 TR-XLPE cable (Cable outer sheet colour as per voltage level decided by UPCL)
11 KV Dismantling of old conductor and accessories with opening of existing jumpering and making of bundle including Loading/Unloading Complete Work.
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 150 mm Dia
CABLE LAYING : Laying and installing, testing & commissioning of HT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using conventional excavation method and Laying the cable at the depth not less than 1.2 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. Cable dia including using cable trench pullers (with Line tension Indicator) and provision of cable Labels ,Protectin Tape (Tape Tile) etc. complete in all respect in the form original before digging. (All the required material to be provided by contractor) (As per approved drawing of UPCL )
Laying and installing, testing & commissioning of HT cable at the depth not less than 1.2 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using cable trench pullers (with Line tension Indicator) using conventional excavation method in HDPE pipe:including provision of cable Labels,back filling, removal of excess earth from site including earth compression
Termination kit for 11 KV Grade, 3-core, 300 Sq.mm, Al conductor, XLPE insulated, screened, armoured, PVC sheathed power cable, OUTDOOR (Heat-shrinkable type including including screen and armour earth kits, all accessories and lugs).
Straight through jointing kit for 11 KV Grade, 3-core, 300 Sq.mm, Al conductor, XLPE insulated , screened, armoured, PVC sheathed power cable, heat-shrink type including termite proofing SS mesh and all accessories
T-Connector (As per Cable current Capacity )
i) Excavation of earth in mixed soil
Design & construction of Joint Pit Chamber (1 nos in 1 KM) for 11 KV cables : conforming to specifications / guidelines of PWD Uttarakhand and approval including supply of civil materials, reinstatement of road / footpath surface as per PWD Uttarakhand requirements. (Estimated quantities are for max dimensions upto 2000 mm (w) x 2000 mm (l) x (h) 1200 mm whereas actual dimensions subject to space availability and approvals) With Galvanised M.S. Channel 125x65x6 mm. (for frabrication of lid support mesh structure) works and Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for HDPE sheathed including Soakpit
iii) Brick work 1:4
v) MS bar 12 mm.
viii) CC 1:1.5:3
Fabrication of lid support mesh structure for Joint Pits using Galvanised M.S. Channel 125x65x6 mm.
Duct sealing material / kit for duct dia 160 mm, sealing length upto 15 cm with expanding polyurethane filler or other sealant material suitable for PVC / HDPE sheathed cables .
Galvanised M.S. Channel 125x65x6 mm. (for lid support mesh structure)
Laying and pulling of 11 Kv HT cable (DC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Dismantling of all types of HT Poles including accessories, Transportation to central store and handing over to UPCL
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL. (DC)(OH to UG)
New LT Line: Proposed Cabling Works for New DTR/CSS New LT Line with AB Cable
New LT line with Insulated ABC of 3x120+1x95+1x16 Sq.mm. for Plains
PCC Pole 8.5 Mtr
Suspension clamp assembly suitable for AB Cable with all fittings and S.S.strap
Dead end clamp assembly suitable for AB Cable with all fittings and S.S.strap
L.T. Insulation Piercing Connectors for energizing distribution kiosk/box & Jumpering
L.T. Insulation Piercing Connectors (16 sq.mm. - 16 sq.mm.) suitable for street light connection
Piercing connector 95 Sqmm.
Mid span jointing sleeves (120 Sq.mm.)
Mid span jointing sleeves (16 Sq.mm.)
Supply & Fixing of LT distribution boxes/kiosk on the LT poles including all clamps & material required for mounting, connections & sealing.
Insulated ABC of 3x120+1x95+16 Sq.mm.
1x35 mm2 TR-XLPE/PVC insulated Al. cable for energising the distribution boxes/ kiosks.
1x16 mm2 XLPE/PVC insulated Al. cable for energising the distribution boxes/ kiosks/Street light
LT Stay complete Annexure I-13
11 kV Galvanized Stay Set Complete 16ϕX1800 mm. with 2 no. turn-buckle, anchor plate (200x200x6mm) as per scope of work in SBD
GI Stay Wire 7/10 SWG
LT Stay Insulator as per SBD
Grouting with Cement Concreating ratio with 1:3:6
Stay Clamp (50x8mm) with Nuts, Bolts & warshers all galvanized
Rod type earthing of pole by MS earthing rod with welded Clamp 40X3mm, Bolts, Washers & Nuts complete .
8 SWG GI wire
Rod type earthing of pole by MS earthing rod 20ɸx2500mm with welded Clamp 40X3mm & GI wire 8 SWG (0.5 Kg) with Bolts Clamp, Washers & Nuts complete as per Drw. REC/RDSS/GEN/07 Annexure C37
Grouting with Cement Concreating ratio with 1:3:6
Stone pad (450x450x75 mm)
0.433 KV LT XLPE Underground Cable
LT line with 3.5x400 Sqmm XLPE Underground Cable (Double Ckt)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 400 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
Laying and installing, testing & commissioning of LT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open exca
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL.
Laying and pulling of LT cable (DC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
HDPE Pipe for LT cable of sizes 110mm (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in DWC Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
DWC Pipe of Suitable Size for LT Cable
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in Underground Road crossing, Nala crossings etc complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
DWC Pipe of Suitable Size for LT Cable
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as IS 1239 at Bridge &,culverts, crossings, at substations by side of bridges with support hangers, channels, angles, cable trays, fastners, bridge/piers complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
Dismantling of all types of LT Poles including accessories, Transportation to central store and handing over to UPCL
Dismantling of all types of LT ACSR Overhead Conductor & LT AB Cables including accessories etc, Transportation to central store and handing over to UPCL
Straight Through Joint LT Outdoor Type 3.5C x 400 sq. mm.
Concrete route marker for LT cable having emboss "DANGER UPCL LT CABLE BELOW" and directional arrows
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 400 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
LT line with 3.5x240 Sqmm XLPE Underground Cable (Double Ckt)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL.
Laying and pulling of LT cable (DC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 240 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
HDPE Pipe for LT cable of sizes 110mm (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 240 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in DWC Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
DWC Pipe of Suitable Size for LT Cable
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 240 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in Underground Road crossing, Nala crossings etc complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
DWC Pipe of Suitable Size for LT Cable
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 240 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as IS 1239 at Bridge &,culverts, crossings, at substations by side of bridges with support hangers, channels, angles, cable trays, fastners, bridge/piers complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
1.1KV LT armoured Power Cable 3.5x240sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Dismantling of all types of LT ACSR Overhead Conductor & LT AB Cables including accessories etc, Transportation to central store and handing over to UPCL
1.1KV LT armoured Power Cable 3.5x240sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Straight Through Joint LT Outdoor Type 3.5C x 240 sq. mm.
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 400 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
LT line with 3.5x150 Sqmm XLPE Underground Cable (Double Ckt)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Making of Trench using conventional excavation method at requisite depth as per Approved Drawing by UPCL.
Laying and pulling of LT cable (DC) for cable loop using RCC Slab protection Layer and digging using coventional method including soft sand cushioning 75 mm below and 75 mm above cable,warning tape including cable marking and tagging,supply of all civil material, labour and T&P as per IS 1255 :1983 or latest amendments(as per site require ment)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 150 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
HDPE Pipe for LT cable of sizes 110mm (with colour coding of HDPE pipe as approved by UPCL in order to differentiate other voltage cables laid in other pipes) including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends
1.1KV LT armoured Power Cable 3.5x400sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 150 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of LT cable at the depth not less than 0.8 meter as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in DWC Pipe,back filling, removal of excess earth from site including earth compression,refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
DWC Pipe of Suitable Size for LT Cable
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 150 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in Underground Road crossing, Nala crossings etc complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
DWC Pipe of Suitable Size for LT Cable
1.1 KV Grade XLPE Al. Conductor, PVC Sheathed, Armoured Cable 3.5C x 150 sq. mm. (for main LT cable) (Colour of Outer sheeth of Cable shall be different from 33 KV & 11 KV cable as specified by UPCL)
Laying and installing, testing & commissioning of B-Class Heavy duty GI pipe as IS 1239 at Bridge &,culverts, crossings, at substations by side of bridges with support hangers, channels, angles, cable trays, fastners, bridge/piers complete in all respects including long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends and refilling the trench etc as required
1.1KV LT armoured Power Cable 3.5x150sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Dismantling of all types of LT ACSR Overhead Conductor & LT AB Cables including accessories etc, Transportation to central store and handing over to UPCL
1.1KV LT armoured Power Cable 3.5x150sqmm (with Colour coding as approved by UPCL in order to differentiate with other voltage cables)
Straight Through Joint LT Outdoor Type 3.5C x 150 sq. mm.
LT protection (LT feeder pillars)
A-Type Panel for 630 KVA To 1000 KVA DTR (Annexture Y5)
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
FOR DT - 630KVA TO 1000KVA 1 No. Incomer - 2000Amps FP ACB 50kA LSIG 3Nos Outgoings - 400Amps TP MCCB 50kA & 2 No. 250 Amps TP MCCB 50KA
Supply, erection, testing and commissioning of LT cable heavy duty double compression termination Brass Glands and long barrel heavy duty AL Lugs including Provision of cale Armour Earting suitable for the following cable sizes:
1.1KV LT TR-XLPE Cable 3.5x400sqmm
1.1KV LT TR-XLPE Cable 3.5x240sqmm
Barrel Lugs
400 sq. mm. Long barrel Al Lugs for 3.5Cx 400 sqmm cable
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply and installation of GI earth strip 25x6mm for connection of earth point with the Earthing electrode in earthpit
Single Key Locking Arranagement of Panel (all doors, pads locks, interconnection points, fencing etc)
LT protection (LT feeder pillars)
Making of foundation and cable trench for LT A-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
FOR DT - 630KVA TO 1000KVA 1 No. Incomer - 2000Amps FP ACB 50kA LSIG 3Nos Outgoings - 400Amps TP MCCB 50kA & 2 No. 250 Amps TP MCCB 50KA
Supply, erection, testing and commissioning of LT cable heavy duty double compression termination Brass Glands and long barrel heavy duty AL Lugs including Provision of cale Armour Earting suitable for the following cable sizes:
1.1KV LT TR-XLPE Cable 3.5x400sqmm
1.1KV LT TR-XLPE Cable 3.5x240sqmm
Barrel Lugs
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply and installation of GI earth strip 25x6mm for connection of earth point with the Earthing electrode in earthpit
A-Type Panel for 160 KVA To 500 KVA DTR (Annexture Y6)
LT protection (LT feeder pillars)
FOR DT - 160KVA TO 500KVA 1 No. Incomer - 1000Amps FP ACB 50kA LSIG 2 Nos Outgoings - 400Amps TP MCCB 50kA & 2 No. 250 Amps TP MCCB 50KA
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
Supply, erection, testing and commissioning of LT cable heavy duty double compression termination Brass Glands and long barrel heavy duty AL Lugs including Provision of cale Armour Earting suitable for the following cable sizes:
A-Type Panel for 63 KVA To 100 KVA DTR (Annexure Y7)
1.1KV LT TR-XLPE Cable 3.5x400sqmm
1.1KV LT TR-XLPE Cable 3.5x240sqmm
Barrel Lugs
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply and installation of GI earth strip 25x6mm for connection of earth point with the Earthing electrode in earthpit
FOR DT - 63KVA TO 100KVA 1 No. Incomer - 250Amps FP MCCB 50kA LSIG 2 Nos Outgoings - 100Amps TP MCCB 50kA & 2 Nos Outgoings - 63Amps TP MCCB 50kA
1.1KV LT TR-XLPE Cable 3.5x150sqmm
B-Type Panel 160 KVA To 1000 KVA DT Feeders (Annexture Y9)
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
FOR DT - 630KVA TO 1000KVA 1 No. Incomer - 2000Amps FP ACB 50kA LSIG 3Nos Outgoings - 400Amps TP MCCB 50kA & 2 No. 250 Amps TP MCCB 50KA
A-Type Panel for 63 KVA To 100 KVA DTR (Annexure Y7)
1.1KV LT TR-XLPE Cable 3.5x400sqmm
1.1KV LT TR-XLPE Cable 3.5x240sqmm
400 sq. mm. Long barrel Al Lugs for 3.5Cx 400 sqmm cable
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply & Installation Of B Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
ABOVE 160KVA -1000KVA DT FEEDERS : 1 No. Incomer - 400Amps TP MCCB 50kA 3 Nos Outgoings - 400Amps TP MCCB 50kA
1.1KV LT TR-XLPE Cable 3.5x150sqmm
Making of foundation and cable trench for LT B-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
Supply, erection, testing and commissioning of LT cable heavy duty double compression termination Brass Glands and long barrel heavy duty AL Lugs including Provision of cale Armour Earting suitable for the following cable sizes:
A-Type Panel for 63 KVA To 100 KVA DTR (Annexure Y7)
1.1KV LT TR-XLPE Cable 3.5x400sqmm
Barrel Lugs
400 sq. mm. Long barrel Al Lugs for 3.5Cx 400 sqmm cable
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
EARTHING FOR LT FEEDER PANELS
Locking Arrangement
Supply and installation of Chemical earthing station as per IS 3043 complete with GI earthing electrode ,Bentonite, . Conductor upto test link, test link,earthing chamber, 450x450 mm C.I. Manhole /Precast CC chamber etc.
CIVIL WORKS
Supply & Installation Of B Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
B-Type Panel 63 KVA & 100 KVA DT Feeders (Annexture Y10)
FOR 63KVA & 100KVA DT FEEDERS : 1 No. Incomer - 250Amps TP MCCB 50kA 3 Nos Outgoings - 250Amps TP MCCB 50kA
C-Type Panel (Annexure Y11)
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
A-Type Panel for 63 KVA To 100 KVA DTR (Annexure Y7)
1.1KV LT TR-XLPE Cable 3.5x400sqmm
400 sq. mm. Long barrel Al Lugs for 3.5Cx 400 sqmm cable
240 sq. mm. LT Long barrel Al Lugs for 3.5C x 240 sqmm cable
Supply & Installation Of C Type Panel
Supply, erection, testing and commissioning of LT supply Service distribution Boxes for LT consumers complete with
CIVIL WORKS
50x5mm AL busbars for 3Phase + N, lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End) with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
Supply and installation of Spike earthing /Earthing Rod MS (20x2500mm) as per IS 3043 complete
Supply and installation of GI wire 5mm 6swg for connection of earth point with the earthing rod in earth pit
Making of foundation and cable trench for LT C-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
Service Cable
Laying Of 2x10sqmm Service Cables for 1 KM
Supply and Laying of LT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe, and refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
1.1KV LT XLPE Armoured Cable 2x10sqmm
Supply and Laying of 50mm HDPE Pipe for consumer service cables with bends & couplers, Sadling in open complete work in all respect
Making of foundation and cable trench for LT C-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
GI Pipe of suitable sizes for consumer service cables with bands & couplers
Laying Of 2x10sqmm Service Cables for 1 KM
Supply and Laying of LT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe, and refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
2x10 sq. mm. Long barrel Al Lugs
Laying Of 4x16 sqmm Service Cables for 1 KM
Making of foundation and cable trench for LT C-Type Panel as per manufactrer recommendation and aprroved drawing by UPCL including supply of all civil materials,Complete
1.1KV LT XLPE Armoured Cable 4x16sqmm
Laying Of 2x10sqmm Service Cables for 1 KM
Supply and Laying of LT cable as per the code of practice for installation and maintenance of power cables as per IS 1255 :1983 or latest amendments using open excavation method in HDPE Pipe, and refilling the trench etc as required complete work in all respect (with Desired length of loops as approved by UPCL).
vation method, laying the cable at the depth not less than 0.8 meter in open trench, proper dressing of trench with bricks and sand works. Making RCC slab for protection of cable loop,back filling, removal of excess earth from site including earth compression. as required complete in all respect.(with Desired length of loops as approved by UPCL). (All the required material to be provided by contractor)
Supply & Installation Of A Type Panel lockable door arrangement self locking arrangement & pad locking arrangement for single key lock.complete with hardware and mounting arrangement as per site requirement: Also including cable tagging (Both End)with the help of paint & permanent cable taggers (Aluminium) & nomenclature with the help of paint & embossing as approved by UPCL on panels.
4x16 sq. mm. Long barrel Al Lugs
Laying Of 3.5x95sqmm Service Cables for 1 KM
1.1KV LT XLPE Armoured Cable 3.5x95sqmm
1.1KV LT TR-XLPE Cable 3.5x95sqmm
3.5x95 sq. mm. Long barrel Al Lugs
Meter Box
Single Phase Polycarbonate meter box
3.5x95 sq. mm. Long barrel Al Lugs
Supply and Erection of Polycarbonate box for meter including dismantling of damaged / replaceable meter box for 1 Phase meter
Polycarbonate boxes for consumer energy meter 1-phase
Three Phase Polycarbonate meter box
Polycarbonate boxes for consumer energy meter 3-phase
UG Double Pole Required as per Site
33 KV UG Double Pole
Steel Tubular Poles 11 m long (STP 11.0 M, 410 MPa , SP-55) as per IS 2713 (Parts 1 to 3): 1980 (Bottom Portion hot dip galvanized) with MS Plate (300ɸx6)
33 KV Cross bracing Set 50x50x6mm with Belting angle of 50x50x6mm with clamps bolts & nuts all galvanized, as per SBD(for SP-55 pole)
PP of suitable size for Middle portion of STP-410, SP-55 Pole
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 150 mm Dia
33 kV top channel 125x65x6mm 3.2 mtr. Long with all fixing arrngement, bolts & nuts all galvanized (for DoublePole)
PP of suitable size for Top portion of STP-410, SP-55 Pole
33 KV lightening arrestor
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
33 kV Base channel 125x65x6mm 3.2 mtr. Long with clamp, nuts & bolt all galvanized for Cable GI pipe support
33 kV Polymer Pin Insulator complete
Rod type earthing of pole by MS earthing rod with welded Clamp 40X3mm, Bolts, Washers & Nuts complete .
8 SWG GI wire
33 kV Danger board with clamp Bolts & Nuts
Anti-Climbing Device (2.5mm dia (12SWG) galvanized barbed wire 3.5 m per pole) with top and bottam Clamp made of 50x8 mm strip with Nuts, Bolts & Warshers all galvanized for SP-55 Pole)
Rod type earthing of pole by GI earthing rod 20ɸx2500mm with welded Clamp 40X3mm & GI wire 8 SWG (0.5 Kg) with Bolts Clamp, Washers & Nuts complete as per Drw. REC/RDSS/GEN/07 Annexure C37
Stay complete (As per Annex-C-18)
LT Stay Insulator as per SBD
Grouting with Cement Concreating ratio with 1:3:6
Alluminium paint (Double Coat)
Red Oxide paints
Grouting with Cement Concreating ratio with 1:3:6
33 kV Galvanized Stay Set Complete 20ϕX1800 mm. with 2 no. turn-buckles, anchor plate (300x300x8mm) as per scope of work in SBD
Polycarbonate boxes for consumer energy meter 3-phase
Stay Wire 7/8 SWG
33 KV Cross bracing Set 50x50x6mm with Belting angle of 50x50x6mm with clamps bolts & nuts all galvanized, as per SBD(for SP-55 pole)
33kv Stay Insulator
11 kV Base channel 100x50x6mm 2.2 mtr. Long with clamps,nuts & bolt all galvanized for Cable GI Pipe Support
Supply and laying of B-Class Heavy duty GI pipe as IS 1239 at Underground Road crossing, Nala crossings etc complete in all respects including Bell Mouth, long bends,short bends, couplers etc to ensure proper safety of cables & to avoid damage at ends, bends .GI Pipe 150 mm Dia
11 kV Polymer Pin Insulator complete
11 kV Danger Board with Clamp with N&B
9KV, 5KA Outdoor type Lighting Arrester Polymer.
150 sq. mm. Long barrel Al Lugs for 3.5C x 150 sqmm cable
33 kV Base channel 125x65x6mm 3.2 mtr. Long with clamp, nuts & bolt all galvanized for Cable GI pipe support
33 kV Polymer Pin Insulator complete
Rod type earthing of pole by MS earthing rod with welded Clamp 40X3mm, Bolts, Washers & Nuts complete .
8 SWG GI wire
11 KV UG Double Pole
LT Stay complete Annexure I-13
11 kV Galvanized Stay Set Complete 16ϕX1800 mm. with 2 no. turn-buckle, anchor plate (200x200x6mm) as per scope of work in SBD
11 kV top channel 100x50x6mm 2.2 mtr. Long with nuts & bolt all galvanized as per SBD specs(for SP-55 pole)
LT Stay Insulator as per SBD
Grouting with Cement Concreating ratio with 1:3:6
Alluminium paint (Double Coat)
Red Oxide paints
Grouting with Cement Concreating ratio with 1:3:6
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.11 MB
Guildlines_MoP.rar
Additional Documents • 12.73 MB
BOQ_104039.xls
BOQ • 0.67 MB
Tender_Specs_SBD_B.rar
Tender Documents • 26.16 MB
Technical_UPCL_RDSS.rar
Tender Documents • 24.00 MB
AprovedVendorList.pdf
Additional Documents • 0.03 MB
PKG_B_PQR.xls
Tender Documents • 0.05 MB
PreBid_Link.pdf
PDF • 0.05 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .