Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.2 LAccepted-Finance | ₹5.2 L | L1 | Accepted-Finance L1 |
| Sl No | Description | Qty | Unit | Hi Elect Enterprises L1 |
|---|---|---|---|---|
| 1.00Replacement of 30 kVA UPS | ||||
| 1.00 | OD241116/2025-2026:Supply, installation, testing, and commissioning of a continuous duty, true online configuration with double conversion 3-phase online UPS System of 30 kVA with an input isolation transformer. The model shall have the capability to enhance UPS capacity/redundancy by operating the UPS in N+X Parallel Redundant Configuration (PRS configuration) and shall have the capability of independent or common battery bank operation of the UPS when operated in PRS. The UPS system shall be of indoor type (IP20) with input isolation transformer surge protection system, input PF > 0.99, input THDi < 5% without the use of any external filters, double conversion with input voltage range 320V to 460V @ full load, 50Hz, output voltage 240/400V 3-phase + Neutral + Ground with output variation limit of +/- 1%. It shall be 100% generator compatible, with efficiency > 94% and unity output power factor (30 kVA = 30 kW), and including all accessories, etc., as required. The UPS shall have zero ms transfer time from mains mode to battery mode and battery mode to mains mode, and automatic bypass built-in with transfer time < 1ms, and shall have manual maintenance bypass provisions, cold start capability, and serial communication interface RS232 port. The system shall have IGBT rectifier and inverter, suitable for operation in 0-40°C ambient temperature with a noise level < 65 dB at 1m distance. The UPS control panel shall be a color graphic LCD display for indication of UPS status, metering, battery status, alarm/event log, and advanced operational features, including audible alarms. The system shall comply with IEC/EN 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, CE, BIS, ROHS, and relevant IS standards. All relevant type test certificates shall be provided, and the UPS system shall include a minimum warranty of 3 years for UPS .Make of UPS: Legrand-Numeric/ Riello/ Delta/ Eaton or equivalent make. | 1 | each | 5,03,000 ₹5,03,000 Lowest |
| 1.00 | OD241115/2025-2026:SITC of 12V, 26 AH heavy-duty maintenance-free Lead Acid Battery in the existing 30kVA UPS battery panel, including connecting the battery using copper connecting cable. | 4 | each | 5,000 ₹20,000 Lowest |
| 1.00 | OD82015/2026-2027:Supply and fixing ofSelf-adhesive vinyl sticker for lettering and figures of sizes and colour selected by the Engineer in charge for the identification mark to fan, ALl UPS , SB, DB, panel board , fire etc as required | 9,000 | sqcm | 0.1 ₹900 Lowest |
Tender Value
₹5.3 L
EMD Value
₹13,135
Closing Date
30 Jul 2026, 6:00 pmClosed
Assistant Executive Engineer
Assistant Executive Engineer,PWD Electrical sub division,Tvpm
GENERAL-Installation of 1 no 30kVA UPS in MSB MCH TVPM-SITC of 1 no. 30kVA UPS in place of damaged one in Multy Specialty Block of Govt.MCH Tvpm-General Electrical Work
2026_PWD_860472_2
ESDT/ET-58/2026-27
Open Tender
Electrical Works
Item Wise
60 days
PWD Electrical sub division Thiruvananthaouram
please refer tender documents
6 documents required · 6 mandatory
₹1,160
₹13,135
5 Sept 2026
24 Jul 2026
1 Aug 2026
24 Jul 2026
30 Jul 2026
24 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Replacement of 30 kVA UPS | |||||
| 1.001 | OD241116/2025-2026:Supply, installation, testing, and commissioning of a continuous duty, true online configuration with double conversion 3-phase online UPS System of 30 kVA with an input isolation transformer. The model shall have the capability to enhance UPS capacity/redundancy by operating the UPS in N+X Parallel Redundant Configuration (PRS configuration) and shall have the capability of independent or common battery bank operation of the UPS when operated in PRS. The UPS system shall be of indoor type (IP20) with input isolation transformer surge protection system, input PF > 0.99, input THDi < 5% without the use of any external filters, double conversion with input voltage range 320V to 460V @ full load, 50Hz, output voltage 240/400V 3-phase + Neutral + Ground with output variation limit of +/- 1%. It shall be 100% generator compatible, with efficiency > 94% and unity output power factor (30 kVA = 30 kW), and including all accessories, etc., as required. The UPS shall have zero ms transfer time from mains mode to battery mode and battery mode to mains mode, and automatic bypass built-in with transfer time < 1ms, and shall have manual maintenance bypass provisions, cold start capability, and serial communication interface RS232 port. The system shall have IGBT rectifier and inverter, suitable for operation in 0-40°C ambient temperature with a noise level < 65 dB at 1m distance. The UPS control panel shall be a color graphic LCD display for indication of UPS status, metering, battery status, alarm/event log, and advanced operational features, including audible alarms. The system shall comply with IEC/EN 62040-1, EN/IEC 62040-2, EN/IEC 62040-3, CE, BIS, ROHS, and relevant IS standards. All relevant type test certificates shall be provided, and the UPS system shall include a minimum warranty of 3 years for UPS .Make of UPS: Legrand-Numeric/ Riello/ Delta/ Eaton or equivalent make. | - | each | - | - |
| 1.002 | OD241115/2025-2026:SITC of 12V, 26 AH heavy-duty maintenance-free Lead Acid Battery in the existing 30kVA UPS battery panel, including connecting the battery using copper connecting cable. | - | each | - | - |
| 1.003 | OD82015/2026-2027:Supply and fixing ofSelf-adhesive vinyl sticker for lettering and figures of sizes and colour selected by the Engineer in charge for the identification mark to fan, ALl UPS , SB, DB, panel board , fire etc as required | - | sqcm | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
finance_1458389.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.04 MB
BOQ_1458389.xls
BOQ • 0.30 MB
mom.pdf
Tender Documents • 12.68 MB
sbd.pdf
Tender Documents • 1.63 MB
sc.pdf
Tender Documents • 0.15 MB
nit.pdf
Tender Documents • 0.02 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .