Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 CrAdmitted-Finance | ₹1.9 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.2 Cr+₹22.9 L (11.8%)Admitted-Finance | ₹2.2 Cr+₹22.9 L (11.8%) | L2 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Arken Solutions Pvt. Ltd L2 | MONITOR ENGINEERING WORKS L1 |
|---|---|---|---|---|---|
| 1.00 | 415V main incoming PCC panel | 1 | set | 21,12,060 ₹21,12,060 | 17,00,000 ₹17,00,000 Lowest |
| 2.00 | 415V aux PCC-1 panel | 1 | set | 36,53,310 ₹36,53,310 | 27,00,000 ₹27,00,000 Lowest |
| 3.00 | Supply Installation Testing and commissioning of 415V aux PCC-2 panel as per tender specification and drawing | 1 | set | 16,71,980 ₹16,71,980 | 11,50,000 ₹11,50,000 Lowest |
| 4.00 | Supply Installation Testing and commissioning of 415V Control Panel as per tender specification and drawing | 1 | set | 35,820 ₹35,820 Lowest | 3,75,000 ₹3,75,000 |
| 5.00 | Supply Installation Testing and commissioning of Timer Panel as per tender specification and drawing | 1 | set | 1,01,150 ₹1,01,150 Lowest | 2,55,000 ₹2,55,000 |
| 6.00 | EPCC P7 panel | 1 | set | 1,48,380 ₹1,48,380 Lowest | 4,75,000 ₹4,75,000 |
| 7.00 | EPCC P9 panel | 1 | set | 1,00,690 ₹1,00,690 Lowest | 2,05,000 ₹2,05,000 |
| 8.00 | EPCC P10 panel | 1 | set | 83,430 ₹83,430 | 75,000 ₹75,000 Lowest |
| 9.00 | EPCC EP10 panel | 1 | set | 77,430 ₹77,430 | 70,000 ₹70,000 Lowest |
| 10.00 | EPCC EP11 panel | 1 | set | 1,11,970 ₹1,11,970 Lowest | 1,15,000 ₹1,15,000 |
Tender Value
₹2 Cr
EMD Value
₹4 L
Closing Date
15 May 2023, 3:00 pmClosed
PD,BARC(V)
BARC main site ,Atchutapuram ,Visakhapatnam.
Power supply extension and Internal Electrification of HFRR Assembly shop building and MSBRD facility at BARC main campus, Atchutapuram near Visakhapatnam , A.P.
2023_BARC_748742_1
BARCF-V/ESS-V/2023/07
Open Tender
Electrical Works
Item Rate
240 days
BARC main site, Atchutapuram, Visakhapatnam.
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹4 L
16 Jun 2023
11 Apr 2023
16 May 2023
11 Apr 2023
15 May 2023
29 Apr 2023
12 Apr 2023 - 26 Apr 2023
Amount
415V main incoming PCC panel
415V aux PCC-1 panel
Supply Installation Testing and commissioning of 415V aux PCC-2 panel as per tender specification and drawing
Supply Installation Testing and commissioning of 415V Control Panel as per tender specification and drawing
Supply Installation Testing and commissioning of Timer Panel as per tender specification and drawing
EPCC P7 panel
EPCC P9 panel
EPCC P10 panel
EPCC EP10 panel
EPCC EP11 panel
EPCC EP12 panel
EPCC EP13 panel
600 X 600 LED Surface mounted lighting fixture.
300 X 300 LED Surface mounted lighting fixture
22W LED Batten Type Surface mounted lighting fixture.
40W LED Batten Type Surface mounted lighting fixture.
12W LED Round Type Surface mounted lighting fixture
5W LED Surface mounted mirror lighting fixture
120W LED Highbay Lighting Fixture
1200mm sweep BLDC Ceiling fan with regulator & safety wire.
200mm diameter PVC Exhaust fan with automatic shutter.
12 inch diameter metal exhaust fan with metal louvers.
15 inch diameter metal exhaust fan with metal louvers.
18 inch sweep industrial grade wall mounted circulator fan.
Supply of nominal insulating mat 2.5 mm +/- 10% thick and 1 m width conforming to IS 15652: 2006 and meeting the requirement of IS: 5216 (Part 1, 2 &3), IS 8437, IEC-479 Pub-1 & as per of IS: 15652 and suitable for class - B upto 11 kv, Make -Electromat or equivalent OEM
40 mm dia Earth electrode with earth pit
GI strip of 50mm X 6 mm.Strip. Installation of GI strip to be done along cable tray and on the wall. Connection of GI strip with cable tray with nut and bolts, distribution board is be done by nut and bolts. Installation along wall includes Insulator to be installed on wall at every 1 meter length of gap of strip. Bending of GI strip and taking out through hume pipe and connecting to earthing pit is included in the scope of work. Cost of Insulator and nut bolt, lugs is included in quoted rate.
MS item includes various sizes of L angle, C channel, metal sheet of various thickness. These items will be used for various purposes like creating support structure for the cable trays, checkered plates for covering the trenches. Fabrication including Cutting , welding , Red oxide painting and enamel paint, cost of welding rod is to be included in quoted rates.
150mm width Cable Tray.
300mm width Cable Tray.
450mm width Cable Tray.
TPN DB of 8way with acryllic door
Cable end box suitable for TPN DB of 8 way
SPNDB of 12 way
6 /10/16 amp SP C type
16 amp DP C type
16 amp 4P B type MCB
32 amp 4P C type MCB
63 amp 4P C type MCB
40 amp 2P RCCB of 30 ma sensitivity
6/16 Amp universal socket
6 Amp 1 modular Switch with indication light
1 modular weather proof (IP55) switch box & adaptor with pvc membrane containing 1 number of switch. (Equivalent to Legrand IP55 Plexo box with PVC membrane.)
6 Amp 1 modular 2 way switches
16 Amp 1 modular Switch with indication light
16 Amp starter for controlling of AC points
1 module/2 module cover plate with frame
3 module cover plate with frame
4 module cover plate with frame
6 module cover plate with frame
1 module / 2 module plastic surface box
3 module plastic surface box
4 module plastic surface box
6 module plastic surface box
Point wiring with 1.5 sq mm wire. Each wiring circuit consist of phase wire, neutral wire, earth wire. The average length of each wire(i.e. phase, neutral & earth) is (5±2) meter individually. Wiring in same flush box is not consided to be separate wiring point
Point wiring with 1.5 sq mm wire. Each wiring circuit consist of phase wire, neutral wire, earth wire. The average length of each wire(i.e. phase, neutral & earth) is (15±5) meter individually. Wiring in same flush box is not consided to be separate wiring point
Point wiring with 1.5 sq mm wire. Each wiring circuit consist of phase wire, neutral wire, earth wire. The average length of each wire(i.e. phase, neutral & earth) is (30±7) meter individually. Wiring in same flush box is not consided to be separate wiring point
Point wiring with 1.5 sq mm wire. Each wiring circuit consist of phase wire, neutral wire, earth wire. The average length of each wire(i.e. phase, neutral & earth) is (50±10) meter individually. Wiring in same flush box is not consided to be separate wiring point
Point wiring with 2.5 sq mm wire. Each wiring circuit consist of phase wire, neutral wire, earth wire. The average length of each wire(i.e. phase, neutral & earth) is (20±5) meter individually. Wiring in same flush box is not consided to be separate wiring point
Point wiring with 2.5 sq mm wire. Each wiring circuit consist of phase wire, neutral wire, earth wire. The average length of each wire(i.e. phase, neutral & earth) is (10±3) meter individually. Wiring in same flush box is not consided to be separate wiring point
Point wiring with 2.5 sq mm wire. Each wiring circuit consist of phase wire, neutral wire, earth wire. The average length of each wire(i.e. phase, neutral & earth) is (6±2) meter individually. Wiring in same flush box is not consided to be separate wiring point
Point wiring with 4 sq mm wire. Each wiring circuit consist of phase wire, neutral wire, earth wire. The average length of each wire(i.e. phase, neutral & earth) is (25±5) meter individually. Wiring in same flush box is not consided to be separate wiring point
Point wiring with 3C x 1.5 sq mm Tough Rubber Sheathed cable of average length (30+/-5) meter. Installation to be done at highbay height of 13 meter.
Point wiring with 3C x 1.5 sq mm Tough Rubber Sheathed cable of average length (6+/-2) meter. Installation to be done at highbay height of 13 meter.
Point wiring with 3C x 1.5 sq mm Tough Rubber Sheathed cable of average length (25+/-5) meter. Installation to be done at highbay height of 8 meter.
Point wiring with 3C x 1.5 sq mm Tough Rubber Sheathed cable of average length (6+/-2) meter. Installation to be done at highbay height of 8 meter.
25 mm MS conduit with 1.6 mm thickness
metallic junction box for interconnection of conduit of 25 sq mm
Metallic flexible pipe of 25 sq mm along with rolling flexible PVC rolling tape. The metallic flexible pipe to be connection to metallic junction boxes with metallic clamp. The cost of clamp is included in this quoted rate
PVC Casing and caping of 1 inch width along with all related accessories like elbow bends, t bends, all press fit bends. Prices of accessories to be included in the quoted price.
100mm X 100mm PVC box
3.5 C x 400 Sq.mm ,1.1kV xlpe extruded insulation, Aluminium cable, with FRLS sheath, round armoured
3.5 C x 120 Sq.mm ,1.1kV xlpe extruded insulation, Aluminium cable, with FRLS sheath, round armoured
3.5 C x 50 Sq.mm ,1.1kV xlpe extruded insulation, Aluminium cable, with FRLS sheath, round armoured
4C x 16 sq mm 1.1 kv, xlpe extruded insulation, copper cable, with FRLS sheath, round armoured
12C x 2.5 sq mm 1.1 kV, PVC extruded insulation, copper cable, with FRLS sheath, round armoured
End termination 3.5 C x 400 Sq.mm ,1.1kV xlpe extruded insulation, Aluminium cable
End termination 3.5 C x 120 Sq.mm ,1.1kV xlpe extruded insulation, Aluminium cable
End termination 3.5 C x 50 Sq.mm ,1.1kV xlpe extruded insulation, Aluminium cable
End termination 4 C x 16 Sq.mm ,1.1kV xlpe extruded insulation, copper cable
End termination for 12C x 2.5 sq mm copper cable
2250 VA inverter of 24 volt input & 230 V output
250 AH Battery
Supplying, lowering, laying approved 300 mm dia RCC pipes (Class NP2) of IS:458 with necessary collars, laid to correct grade & levels at 1m depth, including cutting to lengths, jointing with hemp yarn & cement mortar 1:1, caulking the joints, & finishing, curing, testing all as per directions of Engineer-in-charge. Cost including excavation upto depth of 1200mm , materials and labour, including hoisting, placing in position by manual or mechanical means and as directed by the Engineer-in-charge including testing of joints etc.
Providing and laying in position cement concrete of 1:3:6 (1 cement, 3 coarse river sand/crushed stone sand,6 graded stone aggregate of maximum size 20mm) including consolidation, finishing, curing, etc.
Earth work excavation
Physical protection of LT cable
Metal sheet box with dimensions (200mmX200mmX100mm). The (200mmX200mm) face of the box shall be openable. The box shall have provisions of knockout of cable glanding with fixing arrangement on wall using nut & bolts. The box shall be made up of seven tank treated, powder coated, oven baked, 3mm thick sheet.
Supply and Installation of 16 sqmm copper flexible single core wire with flame retardent, PVC compound, green colored insulation.
Supply, installation, testing and commissioning of white PVC trunking body of section 150 mm X 50 mm. The body should be able to partitioned into two 65 mm sections. The rate of body joints to be included in the quoted rates.
Supply, installation, tesing and commissioning of white PVC Partitions Separations. These are used to do partitioning in item no. 25.1
Supply, installation, testing and comissioning of white PVC flexible snap on covers of width 65mm to be installed over item no. 25.1. The rate of cover joints to be included in the quoted rates.
Supply, installation, testing and comisssioning of white PVC End Caps to be applied on terminals of item no. 25.1
Supply, installation, testing and comisssioning of internal angles to be used to provide curvature to bus trunking system at the corners. The cost of partition angles to be included in the quoted rates.
Supply, installation, testing and comisssioning of external angles to be used to provide curvature to bus trunking system at the corners. The cost of partition angles to be included in the quoted rates.
Supply, installation, testing and comisssioning of flat angles to be used to provide curvature to bus trunking system at the corners. The cost of partition angles to be included in the quoted rates.
Front adapter plate of 6 module for item no 25.1 to accommodate item nos 25.9 and 25.10 of legrand make or similar
6/16 universal shuttered socket 2 module to be installed in bus trunking system
Switch-20A-Single Pole-1way with indicator-1 module to be installed in bus trunking system
Arken Solutions Pvt. Ltd
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.55 MB
EARTHINGDRAWING2.pdf
Tender Documents • 0.11 MB
BOQ_787209.xls
BOQ • 0.33 MB
Tenderdocumentvolume1072023.pdf
Tender Documents • 2.81 MB
LETTERTRANSMITTAL072023.pdf
Tender Documents • 0.75 MB
FORMSATOH072023.xls
Tender Documents • 0.06 MB
Technicalspecification072023.pdf
Tender Documents • 1.10 MB
Cablelayingdrawing1.pdf
Tender Documents • 0.19 MB
FORMOFAGREEMENT072023.pdf
Tender Documents • 0.59 MB
Detailedpricebid072023.pdf
Tender Documents • 0.65 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .