Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance D NO 58 22 34 9 PYDIMAMBA NILAYAM BUTCHIRAJUPALEM VISAKHAPATNAM 530 027 | VISAKHAPATANAM | ANDHRA PRADESH | 530027 | Admitted-Finance |
| 4 | Admitted-Finance D NO 9 947 66 DOCTORS COLONY SHIVAJI PLEM VISAKHAPATNAM 530017 | VISAKHAPATANAM | ANDHRA PRADESH | 530017 | Admitted-Finance |
| 5 | Rejected-Technical D NO 38 22 40 NEAR LAKSHMI NARASHIMA THEATER 104 AREA VISAKHAPATNAM 530007 | VISAKHAPATANAM | ANDHRA PRADESH | 530007 | Rejected-Technical Not enlisted in requisite category |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
25 Jan 2024, 6:00 pmClosed
Nitesh Kumar Singh, IDSE AEE(Civ)
AGE (I) R and D, NSTL Complex, Visakhapatnam 530027
8484 REPAIRS/REPLACEMENT AND MAINTENANCE TO U/S PARTS OF CENTRAL AC PLANTS OF VARIOUS BUILDINGS IN TECHNICAL AREA UNDER AGE (I) RnD, NSTL, VISAKHAPATNAM
2024_MES_635721_1
AGE I R AND D NSTL VIZAG 8484
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Visakhapatnam
class E, cat c(i)
7 documents required · 7 mandatory
₹500
AGE I R and D NSTL Visakhapatnam
₹30,000
Yes
20 Feb 2024
4 Jan 2024
27 Jan 2024
4 Jan 2024
25 Jan 2024
18 Jan 2024
Amount
M&L for cleaning/ servicing the cooling coil of 35 TR (2 x 35 TR) capacity plant at Manasi AHU of by air pressure method using air blower and cleaning the cooling coil with suitable cleaning agent, cleaning the AHU base tray completely and applying one coat of synthetic enamel paint inside the base tray, including greasing to AHU blower shaft bearing for smooth functioning, cleaning the AHU filter, replacement of unserviceable V belts etc. all as directed. Note:- V belts shall be measured and paid separately as 'Supply only' under respective items of this Schedule.
All as per Item No. 1 herein before but for 70 TR (3 x 35TR) capacity plant at C&G
All as per Item No. 1 herein before but for 260 TR / 280 TR capacity plant at Talwar / CNC
M & L for cleaning/ servicing of cooling tower, natural draught type/ FRP type of 35 TR (2x35TR) Capacity AC Plant at Manasi including cleaning of wooden/ PVC/ FRP louvers by scraping inside and outside, cleaning of water tank, cleaning and replacement of damaged/ choked nozzles, replacement of PVC pipe n. exc. 3 mtr in length; arranging, refixing in position of all louvers in correct manner and applying one coat of black bituminous paint inside and outside of water tank, cleaning of CT Fan blades, replacement of corroded nuts and bolts as per existing size including replacement of damaged/ broken louvers and unserviceable nozzles all as specified and as directed.
All as per Item No. 4 herein before but for 70 TR (3 x 35TR) capacity plant at C&G
All as per Item No. 4 herein before but for 260/ 280 TR capacity plant at Talwar / CNC
M & L for complete leak testing the entire central AC plant of any capcity up to 60TR per unit consisting of compressors, condensers, chillers, AHUs with connected chilled piping, expansion valves and all accessories by flushing out the refrigerant gas present in the system, pumping Nitrogen gas at requisite pressure, locating leak positions, rectifying the leaks, including pressure testing and holding the pressure for 48 Hrs for observation for any pressure drop in the system and flushing out the complete system on rectification of leaks if any, vacuumising & de-hydration the complete system with heavy duty vacuum pump and removal of moisture and other foreign particles from the system complete including checking of all safety controls and parameters, testing & commissioning of the AC plant after charging the refrigerant gas all as directed by the Engineer-in-Charge. [Note: Supply & charging refrigerant gas will be measured and paid separately]
M & L for complete leak testing the entire central AC plant of any capcity above 60TR and up to 140 TR per unit consisting of compressors, condensers, chillers, AHUs with connected chilled piping, expansion valves and all accessories by flushing out the refrigerant gas present in the system, pumping Nitrogen gas at requisite pressure, locating leak positions, rectifying the leaks, including pressure testing and holding the pressure for 48 Hrs for observation for any pressure drop in the system and flushing out the complete system on rectification of leaks if any, vacuumising & de-hydration the complete system with heavy duty vacuum pump and removal of moisture and other foreign particles from the system complete including checking of all safety controls and parameters, testing & commissioning of the AC plant after charging the refrigerant gas all as directed by the Engineer-in-Charge. [Note: Supply & charging refrigerant gas will be measured and paid separately]
M & L for de-scaling the condenser unit, shell and tube type of 35TR capacity by circulating the approved cleaning agent / diluted hydrochloric acid at the appropriate ratio depending up on the scale deposits till removal inside the copper tube by means of circulating the de-scaling chemical through condenser by pressure feeding method after disconnecting condenser water lines, opening the end covers, scraping/cleaning the condenser water tubing, removing the scales and refixing the dismantled part, end cover with 3mm thick rubber gasket set, re-connecting with the system etc. including minor repairs all as specified and as directed.
All as per Item No.9 herein before but of 130 TR capacity
All as per Item No. 9 herein before but of 140 TR capacity
M&L for Disconnecting electrically and mechanically mono-block pump set of 15 to 20 HP capacity of any make from the existing position by arranging dummy plates to suction and delivery line, removing from the existing position, opening up, varnishing to stator winding with class I varnish, heating/ baking the same, removal of damaged motor bearing, cleaning the rotor and re assembling the motor, cleaning the impeller of pump, supply & replacement of shaft bearings, gland rope, gland bolts &nuts, greasing the pump bearing, fixing back at original location with proper alignment, connecting and testing complete all as specified.
All as per Item No. 12 herein before but of 10 to 12.5 HP capacity
All as per Item No. 12 herein before but of 5 / 7.5 HP capacity
M & L for disconnecting/ Dismantlig (electrically & mechanically) 3 phase, 440 volts, 50 Hz electrical motor from the monoblock pump set of 20 HP capacity and shifting to workshop, opening the motor end cover, taking ou trotor, taking out burnt stator winding, cleaning the stator and rewinding the motor with appropriate gauge, weight and turns of super enamelled copper wire using proper insulating material, varnishing with Class-I varnish, heating/ baking, reassembling the motor completely and brought back to site, fixing back duly coupled with the pump in prope aignment, connecting and testing complete all as specified. Note: Insulation of wiondng shall be Class 'B' upto 7.5 HP and Class 'F' for 10 HP and above.
All as per Item No 15 here-in-before but of 10 HP Capacity
All as per Item No 15 here-in-before but of 5/7.5 HP Capacity
Supply only Wedge (V) Belts B - 134 for compressor & motor/ AHU & motor. [Make: Fenner/ Yule/ ContiTech]
Supply only Wedge (V) Belts B - 95 for compressor & motor/ AHU & motor. [Make: Fenner/ Yule/ ContiTech]
Supply only Wedge (V) Belts B-2253 LP /B87 for compressor & motor/ AHU & motor. [Make: Fenner/ Yule/ ContiTech]
S&F in repairs Single phase preventer Heavy duty relay for protection against single phasing, phase reversal condition, unbalance condition, with inbuilt timer working on 440V, 50Hz power supply complete all as specified and directed. [Make: Minilec 3NA-30-323 or equivalent in Siemens]
S&F Starter Push Button switch with 1 NO + 1 NC complete working on DC/ AC supply up to 16 Amps capacity by removing of the defective unit all as specified and as directed. [Make: L&T ESBEE/ Siemens]
S&F in repairs 4 pole contactors AC operated rating at 415 Volts, AC1 45 Amps rating with 2NO + 2NC auxiliary contacts with operatabe coil voltage 24 volts to 415 volts AC/DC with front/ side mounted Add On blocks as per site requirement. [Make: ABB/ Siemens/ Schneider/ legrad
All as per Item No. 24 herein before but of AC1 rating 30 Amps
All as per Item No. 24 herein before but of AC1 rating 60 Amps
S&F in repairs Thermal Overload relay, 18 to 42 Amps, direct mounted on contactors [TA42DU series of make: ABB or equivalent in GE/ scheider
S&F in repairs Thermal Overload relay, 22 to 80 Amps, direct mounted on contactors [TA75DU series of make: ABB or equivalent in GE/ scheider
Supply only Refrigerant gas 'R- 22' in manufacturer's sealed cylinder.
Supply only Refrigerant gas 'R- 134a' in manufacturer's sealed cylinder. Note for Sl. item No 29 & 30:- (i) Empty cylinder will be returned to contractor on completion of work (ii) Net weight of refrigerant gas shall be measured and paid under these items.
Supply only filling of compressor oil suitable for compressor of Make: Carrier all as directed by Engr-in-charge.
Supply only filling of compressor oil suitable for compressor of Make: Voltas all as directed by Engr-in-charge.
Supply and fixing of PCB board with flexible cards by replacing the damaged/ worn-out electronic components/ ICs with heat sinks, programming automation complete for Central AC plants of various capacities from 70 TR to 160 TR complete including testing and commissioning all as directed.
S&F in repairs pneumatic safety valve for condensers of central AC plants of capacity 35 / 130 / 140 TR. [Make: Castle/ Brassolite/ Henry]
S&F in repairs flow control limit switch/ sensor as per the existing make/ model complete all as specified and as directed. [Make: Castle/ Rapid controls/ Honeywell]
Supply and fixing of water pressure meter dial type up to 7 Kg/cm2 complete all as specified and directed. Make: Guru/Danfoss
Supply and fixing of temperature meter dail type with stop valve o to 30 degree cebntigrade with complete acessories by removing of the old unserviceable meter complete all as specified and directed. Make: H- guru / danfoss/ universal
Removal of the damaged HP cut out, supply and fixing of High Pressure cut out on the compressed / pressurised gas lines complete all as specified and directed.
Removal of the damaged LP cut out, supply and fixing of Low Pressure cut out on the compressed / pressurised gas lines complete all as specified and directed.
Removing of the defective unserviceable temperature sensor and supply and fixing of temprature sensor / thermostat controller along with necessary controll wiring and acessories. Make: Simens/ Honey well
Removing of the defective unserviceable humidity sensor and supply and fixing of humidity sensor/ controller along with necessary controll wiring and acessories. Make: Simens/ Honey well
Supply only HRC fuses suitable for Screw compressor control panel of capacity 130 TR suitable
Disconnection and removing the LT cable connection from the Air Circuit breakers of capacity up to 1600 Amps AC 440 volts from existing LT panel including Complete Servicing of ACB for smooth functioning and operation with repair/replacement of worn out parts such as Switches, Arcing contacts, Main contacts, Jaw contacts, tripping coil, charging motor, relays etc with new spare parts suitable for the existing ACB's make,specifications complete and refixing the same in original position, testing complete all as specified and as directed by Engineer in charge. Make of existing ACB's : C & S / Note:- (i) Spares required for servicing are measued and paid separately under relevant items.
Supply only Isolating Contacts 800/ 1600 A suitable for LT ACBs
Supply only shunt trip coil 230/ 440 Volts suitable for LT ACBs
Supply only UV coil 230/ 440 Volts suitable for LT ACBs
Supply only Rack-in Rack-out mechanism suitable for LT ACBs
Disconnection and removing the unserveciable MCCB & Supply and fix new MCCB with thermal-magnetic release Conforms to IS/IEC 60947-2 & IEC 60947-2 4 pole ,415 V ,400 A , 50 Hz , breaking capacity of 36 KA , complete all as directed by Engineer in charge. Make : scheinder, ABB,Legrand,Siemens,L&T
All as per item No 48 but of capacity 250 A , 36 KA
All as per item No 48 but of capacity 200 A , 36 KA
M&L for Preparation of old painted surface of scrapping of existing cooling tower & connected items by applying two coats of synthetic enamel paint over a coat of zinc chrome primer on existing complete all as specified and directed by Engr-in-charge.
M&L for Preparation of old painted surface of scrapping including valves, strainers etc and applying two coats of synthetic enamel paint over a coat of zinc chrome primer on existing pipe line surfaces complete all as specified and directed by Engr-in-charge.
M&L for disconnecting the existing rusted MS pipe line of any size from their existing position including all accessories complete all specified and directed by Eng in charge.
S&F MS pipe line of 125 mm size
S&F MS pipe line of 150 mm size
S&F in repairs gun metal Ball vales 15mm dia with screwed ends fixed complete all as directed. [Make: Leader/ Zoloto/ Lakshmi/ Sakthi]
All as per item 55 above herein before but 25 mm dia
S&F 25mm bore ball brass valves, high pressure, with polythene float and fly nut complete, screwed for iron pipe or brass ferrule and fixed in repairs. [Make: Leader/ Zoloto/ Lakshmi/ Sakthi]
Supplying and laying synthetic Rubber insulated mats 2 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m.
Tubes, 'light grade' galvanised of size 25 mm bore ,with all fitting and fixed complete to walls and ceilings or laid in floors.
Tubes, 'light grade' galvanised of size 40 mm bore ,with all fitting and fixed complete to walls and ceilings or laid in floors.
S&F of air filter with aluminium frame for HV AC AHU of 10 micron for AC plant 70 TR (2x35 TR) Capacity plant at Mansi ( filter size-610x610x50mm)
S&F of air filter with aluminium frame for HV AC AHU of 10 micron for AC plant 70 TR (3x35 TR) Capacity plant at C&G ( filter size-610x610x50mm)
S&F of air filter with aluminium frame for HV AC AHU of 10 micron for AC plant 260 TR Capacity plant atTalwari ( filter size-610x610x50mm)
S&F of air filter with aluminium frame for HV AC AHU of 10 micron for AC plant 280 TR Capacity plant at C&C ( filter size-610x610x50mm)
LAKSHMI SAI CONSTRUCTIONS
P VENKATA RAO
AR POWER INFRA PVT LTD
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .