Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹7.9 LAccepted-AOC | 1 | Accepted-AOC L1 OFFER | |
| 2 | 2₹8.4 L+₹45,750 (5.77%)Rejected-AOC | 2 | Rejected-AOC L2 OFFER, hence not awarding the contract |
Tender Value
₹10 L
EMD Value
₹25,000
Closing Date
23 Aug 2024, 2:00 pmClosed
HOU (TP)
Office of HOU (TP), TP Unit, KMML
Erection, installation, testing and commissioning of new MDBs for catering power to TERC/FTH/Society buildings of TP unit.
2024_KMML_682285_1
TP/ELE/MSDS/2024-25
Open Tender
Electrical Works
Supply and Service
90 days
TP UNIT, KMML
As per the tender document
2 documents required · 2 mandatory
₹1,770
₹25,000
TP UNIT, KMML
12 Nov 2024
25 Jul 2024
26 Aug 2024
25 Jul 2024
23 Aug 2024
1 Aug 2024
1 Aug 2024
Erection, testing & commissioning of Main Distribution Board at new oxygen plant MCC as per the technical specification. Installation including transportation from central stores (Approx: 300 mtrs), leading, mounting, leveling and assembling of PDB panel of dimension 2700 mm (Length) X 1875 mm (height) X 800 mm (depth) consisting of incoming ACB's and outgoing MCCB's as per the SLD attached. The panel shall be double earthed as per standards from the nearest earth grid. The MDB panel and GI strips for earthing shall be supplied by KMML. Necessary transportation facilities and material handling for positioning of PDB panel shall be arranged by the contractor.
Erection, testing & commissioning of Tubewell DB at panel room near ATM as per the technical specification. Installation including transportation from MSDS (Approx: 150 mtrs), leading, mounting, leveling and assembling of DB panel of dimension 2050 mm (Length) X 2150 mm (height) X 400 mm (depth) consisting of incoming and outgoing MCCB's as per the SLD attached. The panel shall be double earthed as per standards from the nearest earth grid.The additional base channels each, may be impeded and leveled with the existing ground for mounting the new PDB panel. The DB panel and GI strips for earthing shall be supplied by KMML. Necessary transportation facilities and material handling for positioning of DB panel shall be arranged by the contractor.
Dismantling the existing DB near ATM of dimension 900 (L) X 400 (W) X 1750 (H) mm after disconnection/de-glanding the power cables and earth flat without damage.Disconnection and removal of existing AYFY power cables without any damage, includes, 3.5 X 240/120/70/50/16 sq mm AYFY power cables. These cables after disconnection shall be properly tagged with outgoing feeder for the easy termination to the new DB. The DB near ATM shall be dismantled and transported to the central store/location shown by the concerned engineer.
Laying, dressing and clamping of following power cables along the cable trays/wall/supports/cable trenches/utility pipe ducts crossing the national highway by using Al clamps, GI nuts and bolts as per scope of work. Cable shall be supplied by KMML. Clamping materials, GI nuts and bolts shall be supplied by contractor. 3.5 X 300 sq. mm XLPE Al conductor
Glanding and termination of following power/control cables using DC glands/lugs including supply of cable glands, lugs, aluminium crimping sockets, nuts & bots as per scope of work. Gland earthing as per standards shall be done by the contractor. 3.5 x 300 sq.mm XLPE Al cable
Connection of following cables from existing DB near ATM from the existing trays/ structures/ racks/ columns etc and rerouting the cables to new feeders after proper clamping by using Al clamps, GI nuts and bolts as per scope of work. The existing glands shall be reused, however new aluminium crimping sockets shall be supplied by contractor for the termination works (4 sockets/run) . Removal & rerouting shall not be measured separtely 3.5 x 240 sq.mm XLPE
3.5 x 120 sq.mm XLPE cable
3.5 x 50 sq.mm XLPE cable
3.5 x 70 sq.mm XLPE cable
4 x 4/16 sq.mm XLPE cable
Supply of all materials and casting of earth pits using 1200 X1200 X 12 mm CI plate electrodes as per IS 3043-1987 and drawing attached. This work includes excavation, backfilling, filling of charcoal and salt of required quantity has to be put in the pit. Providing necessary frame around the pit, providing CI pit cover, supply & installation of funnel for watering, measurement of earth pit resistance and painting & numbering as per the scope of the work. The value of earth resistance of the earth pit to be taken before connecting to the earth grid in presence of concerned engineer supervising the work. The earth pit CI cover should be at a height of 200 mm from the ground. The required GI strip for fabrication shall be supplied by KMML. The earthing of PDB and tubewell DB and all accessories shall be done as per standards. All other materials required for the work shall be supplied by the contractor. All civil works related to casting of earth pit shall be carried out by the contractor. Cement shall be supplied by KMML.
Laying and clamping of GI earth strips 75/65/40X10/8/6 mm along trenches/walls including excavation (depth 70 cm, approximately 100 mtr), backfilling of the trench & connect to the nearest earth pit/earth grid. Welded joints shall be covered with jute & bitumen. 75/65/40X10/8/6 mm GI earth strip shall be supplied by KMML. All other materials required shall be supplied by the contractor. The area shall be refilled, leveled and plastered as before after laying earth strips.
Fabrication and erection of new cable supports throughout the length of existing stockade/structures, MS structurals, brackets for cable laying and for fabrication of new base channels for mounting PDB and Tubewell DB complete. All the supports and structures shall be properly cleaned and painted with two coats of epoxy grey paint over one coat of epoxy primer as per scope of work. The paint shall be Shalimar/Berger/Asian/Nerolac brand and shall be supplied by the contractor. The required MS items shall be supplied by KMML.
Excavation of cable trench to carry the power cable at a depth of 1 meter and width of 0.4 meter. The cable shall run along the trench and the trench shall be back filled with sand and brick. Cable marker as per standard in checkered plate shall be done at every 2 meter and shall be installed by doing proper civil PCC foundations. The cable marker shall engrave all details regarding the cable. Sand, Bricks are all under the scope of the contractor
Supply of hot dip galvanized wire rope of diameter 6 mm for pulling of 1.1 kV grade XLPE insulated PVC sheathed steel armoured aluminiun conductor of size 3.5 x 300 square mm through the utility pipes laid under NH 66. The galvanized wire rope shall be permanently laid inside pipe ducts for future cable pulling works.
Casting of civil PCC foundation for footings(approx 30 nos) for cable tray supports at a depth of 70 cm below the ground level and 20 cm above the ground level. Size of the PCC shall 30 x 30 x 90 cm. One end of the 3 mtr long MS channel box ( 2 x 100 x 50 mm ISMC) shall be empeded in the PCC straight for supporting power cables. Required quantity of cement shall be supplied by KMML, The other required materials shall be supplied by the contractor
Preparation of electrical drawings and approval from electrical inspectorate for new installation as per scope of work.
MICRON ELEC-TECH (BID ID -1913162)
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .