Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.5 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹10.7 L+₹1.1 L (12.0%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹10.8 L+₹1.3 L (13.3%)Rejected-Finance 1 1E KHODAGONGE ROAD KOLKATA 700 010 | KOLKATA | KOLKATA | WEST BENGAL | 700010 | L3 | Rejected-Finance L3 |
Tender Value
Refer Docs
EMD Value
₹21,300
Closing Date
16 Jun 2025, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer, MD-I, EM, KMDA
OFFICE OF THE EXECUTIVE ENGINEER, MECHANICAL DIVISION-I. E-M SECTOR. KMDA, 59-NAZRUL PARK. ASHIWINI NAGAR. KOLKATA- 700159.
Repairing and overhauling of Pump set No. 1, 2 and 3 (Capacity- 270 m3/Hr, Head- 20 M, 980 RPM, Make- Wilo mather and platt, Model no-81268599/30), replacement of 1 no. Soft Starter set and allied works at RWPS, under Pujali municipality.
2025_KMDA_851328_1
KMDA/E-M/EE/MD-I/NIQ No.-02 of 2025-26 Dated- 20.05.2025
Open Tender
Miscellaneous Works
Item Rate
30 days
Pujali municipality.
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹21,300
28 Jul 2025
28 May 2025
18 Jun 2025
28 May 2025
16 Jun 2025
28 May 2025
Amount
Loading-unloading and transportation charges for bothway from the pump floor to workshop and back to pump house including loading and unloading of all the necessary pump components such as impeller, pump shaft, sleeves etc of Pump No.2 which has already been lifted and dismantled before by the existing agency under the scope of ongoing Operation and maintenance as per the direction of E.I.C.
Reparing & overhauling of pump no. 2, by dismantling all the pump components part by part for detection of fault, throughout inspection and checking for finding out all the damaged spare parts. Rectification / replacement of spare parts as necessary as per the direction of E.I.C. The details of the works are as follows:
Dismantling of thrust bearing , sleeves, bush, impeller assembly etc part by part for complete checking by pump experts, removal of greese and other foreign particles from each parts with the help of jute, emery paper and other necessary materials.
S.S Material deposition on intermediate & head shaft and removal of the excess material through turning operation to the required limit for necessary rectification of the shafts.
Replacement of Spherical Thrust Roller Bearing (SKF 29318 E)
Replacement of intermediate bearing bracket
Replacement of cutlass bush G.M
Replacement of stuffing box G.M bush.
Replacement of S.S muff coupling
Replacement of G.M Clamp( gland flange)
Replacement of G.M Gland
Replacement of shaft sleeve
Replacement of shaft key
Replacement of rubber bush for universal coupling
Fitting charge for all the replaceable spare parts
Balancing of the Impeller & shaft asssembly
Painting charge
Supply, delivery and fitting fixing of 1 no. ABB make Soft Starter at Raw water pumping station under pujali municipality as per direction of EIC. ( Model no: PSTX105-600-70)
Hire Charges of Diesel Generator set with suppling of oil and operator,Cable / Wire, Light etc.for emergency power supply at the time of fault detection of cable as per direction of the EIC.
Identification of cable routes and excavation of trenches (average width 500mm and depth 760mm) for extracting cables with dismantaling of artificial stone flooring / brickflat soiling / line concrete including earth cutting as required with precautions to ensure not to damage other utility services and removing dbries and stocking serviceable materials at site as per direction of the EIC.
Extraction of the cables including removal of pipes / bricks tiles etc and stacking the serviceable materials at site as per direction of the EIC. (Ref. KMDA/P-46/Iteam-11.8 )
Supply, delivery at work site of 1.1 KV grade PVC/ XLPE insulated Aluminium conductor, armoured cable as per direction of EIC. Cable size as mentioned below: i) 3.5 Core 150 sq mm. (MAKE: Gloster/Crystal/Havells)
Laying of two cables above 35 sqmm and upto 185 sqmm in an underground trench in single tier formation (horizontal), the trench size : 680 mm x 760 mm average depth, with brick protection on the top of each cable 8 (eight) Nos. bricks per Mtr. and 4 (four) Nos. bricks per Mtr. as separator between the bricks and cables and also trench to be filled up with shifted soil, levelling up and restoring surface duly rammed . (Cable Size: 1.1KV Grade,3.5 core 150sqmm)
Straight through Jointing of cable of different size by compound jointing kit including S&F ferrul, tapes and jointing materials.(Brand approved by EIC)
RANJAN ENTERPRISE (BID ID -6505355)
COSMOS CONSTRUCTION (BID ID -6544564)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .