Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.3 LAccepted-AOC KHATA NO 254 529 KHASRA NO 364 2 MIN PREET NAGAR A GALI NO 2 HARERI ROAD OPP STAR STUDIO HERARI SANGRUR | SANGRUR | SANGRUR | PUNJAB | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹34.7 L+₹69,605 (2.05%)Rejected-Finance 50 SARASWATI VIHAR SINGHAWALA AMBALA CITY | AMBALA CITY | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹35.5 L+₹1.5 L (4.38%)Rejected-Finance | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹38.3 L+₹4.3 L (12.6%)Rejected-Finance | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹46.0 L+₹12.0 L (35.3%)Rejected-Finance RAJKOT ROAD AIR FORCE STATION HALWARA 141106 PUNJAB | HALWARA | LUDHIANA | PUNJAB | 141106 | L5 | Rejected-Finance Other than lowest |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
28 Sept 2021, 6:00 pmClosed
GE (AF) Halwara
GE (AF) Halwara
REPAIR REPLACEMENT OF LT ELECTRIC SYSTEM AND EARTHING INFRASTRUCTURE IN TECH AREA AT AF STATION HALWARA
2021_MES_471939_1
GE/HAL-42/2021-22
Open Tender
Civil Works
Item Rate
273 days
GE (AF) Halwara
MES ENLISTED CONTRACTORS CLASS D CATEGORY b i
8 documents required · 8 mandatory
₹500
Yes
GE (AF) Halwara
₹70,000
Yes
14 Oct 2021
1 Sept 2021
30 Sept 2021
1 Sept 2021
28 Sept 2021
14 Sept 2021
Amount
Taking up/down worn out/damaged/unserviceable PVC insulated underground cable armoured, heavy duty with aluminium conductors of any size, 1100V grade from trench/duct/pole/wall/pipes/roof tops etc. complete including taking out sand cushioning and brick protection etc all as specified and directed. Note:- Excavation and earth work shall be measured and paid separetely.
Supply, laying and connecting, LT UG cable XLPE insulated, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor laid in trenches/on poles/walls/in ducts/passing through pipes etc including jointing materials such as cable glands, lugs etc of size 300Sqmm 3.5 core complete all as specified and directed. Note : Epoxy cable Joints shall be measured and paid separately
All as per Srl item No 2.00 above but of 240 sqmm 3.5 core.
All as per Srl item No 2.00 above but of 185 sqmm 3.5 core.
All as per Srl item No 2.00 above but of 150 sqmm 3.5 core.
All as per Srl item No 2.00 above but of 120 sqmm 3.5 core.
All as per Srl item No 2.00 above but of 95 sqmm 3.5 core.
All as per Srl item No 2.00 above but of 70 sqmm 3.5 core.
All as per Srl item No 2.00 above but of 50 sqmm 3.5 core.
All as per Srl item No 2.00 above but of 35 sqmm 3.5 core.
All as per Srl item No 2.00 above but of 25 sqmm 4 core.
All as per Srl item No 2.00 above but of 16 sqmm 4 core.
All as per Srl item No 2.00 above but of 16 sqmm 2 core.
All as per Srl item No 2.00 above but of 10 sqmm 2 core.
Excavation in trenches in soft or loose soil, not exceeding 1.5 metre deep and not exceeding 1.5 metre wide and getting out complete all as specified and directed. Notes : (i) Payment for excavation shall be made for one time in case the new cable is laid in the same trenches .
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed.
Removing surplus excavated soil to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and as directed.
M&L for brick protection with sub class "B" bricks (old size) laid dry, flat in trenches over cable with longest dimension perpendicular to the axis of the cable complete all as specified and directed specified .
Material & labour for sand cushioning in trenches and well ramming in layers with 8 cm below and 15 cm above the cable with fine dry sand for cable protection and complete all as directed and specified
S&F in replacement 40mm bore GI tubing light grade as in cable protection pipe including all fittings complete all as directed.
S&F in replacement 50mm bore GI tubing light grade as in cable protection pipe including all fittings complete all as directed.
S&F in replacement 80mm bore GI tubing light grade as in cable protection pipe including all fittings complete all as directed.
M&L for boring under road/path/hard standing to pass the HT / LT UG cables upto 80mm dia pipe with the own arrangements of T&P complete all as specified and directed.
M&L for heat shrinkable straight through joint for LT XLPE UG cables suitable for cable of size 300 Sqmm 3.5 core aluminium complete all as specified and directed.
M&L for heat shrinkable straight through joint for LT XLPE UG cables suitable for cable of size 185 to 240 Sqmm 3.5 core aluminium complete all as specified and directed.
M&Lfor heat shrinkable straight through joint for LT XLPE UG cables suitable for cable of size 70 to 150 Sqmm 3.5 core aluminium complete all as specified and directed.
M&L in replacement for feeder pillars box factory made-out door type made out of MS sheet (CRCA) of thickness not less than 3mm of size 75x75x45cm with aluminium bus bar strip 4 Nos of 600 Amps rated suitable for 1100 volt (LT) mounted of LT porcelain insulator front opening door two leaf braced with hinged,mounted on 4 Nos of angle iron 50x50x6mm duly welded with box and grouted in PCC block of size 30cmx30cmx15cm in concrete 1:2:4 type B-1 Top of box MS sheet duly bent in/slope,tapper with projection of 30mm on all side,weather/vermin proof with high quality of rubber beeding on panel door,cable entry arrangements at bottom includes earthing terminals 2 Nos at both side and painted with two coats of smoke grey stove enameled paint over a primer coat including providing MCCB, 4 pole,fixed type 400Amps, 36 KA rating-01 No complete all as directed by Engr-In-Charge.
Cleaning, scrapping, preparing the old painted steel surface of any description and applying two coats of synthetic enamel paint over one coat of red oxide primer to HT/LT panel of any size complete all as specified.
M&L in repairs for Earthing with galvanised steel earth plate electrode of size 60cmX60cmX6.00mm thick buried directly in ground (earth pit not less than 2.25m deep below the ground level) with top edge of the plate no less than 1.5m bellow normal ground level surrounded from all sides by 15cm thick and packed layer of charcol dust and common salt filling in alternatie layers and electrode connected by galvanised iron strip 32mmx6mm by means of bolts, nuts and washers connected to test termination point protected by 40mm bore GI pipe light grade and GI pikpe light grade 20mm bore for watering and inlcuding funnel, wire mesh, RCC pit cover and PCC chamber with PCC 1:2:4 type B-1 including necessary excavation and earth work in soft/loose soil, returning filling, disposal of surplus soil to a distance not exceeding 50mtr all as specified and shown in Electrical Plate No 3 of SSR Part-I and testing complete all as specified and directed. Note : (a) The unit rate shall include for GI water pipe, protection pipe wire mesh, funnel, excavation, RCC pit cover, PCC. Test point, GI strip 32x6mm from top of earth plate upto 5 mtr. (b) PCC pit shall be provided at least 1.5m away from the earth pit and extra cost of additional length of water pipes and fixing junction, elbow etc shall be deemed to be included in the unit rate. (c) RCC pit cover shall be precast of RCC 1:2:4 tyupe B-1, 80mm thick reinforced with XPM weighing not less than 4 Kg/sqm.
S&F in replacement MCB 63A TPN complete all as specified and directed.
S&F in replacement MCCB 63 A 4 pole 25KA with adjustable thermal & fixed magnetic setting lcs=100% of icu complete all as specified and directed.
S&F in replacement MCCB 100 A 4 pole 25KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed.
S&F in replacement MCCB 160 A 4 pole 25KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed.
S&F in replacement MCCB 200A 4 pole 36KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed.
S&F in replacement MCCB 250 A 4 pole 36KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed.
S&F in replacement MCCB 315A/320A 4 pole 36KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed.
S&F in replacement MCCB 400 A 4 pole 36KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed.
S&F in replacement MCCB 630 A 4 pole 36KA with adjustable Thermal & fixed magnetic setting lcs =100% of icu complete all as specified and directed.
S&F Alluminium Thimbles of sizes 6 Sqmm to 35 Sqmm conductor complete all as specified and directed.
S&F Alluminium Thimbles of sizes 50 Sqmm to 160 Sqmm conductor complete all as specified and directed.
S&F Alluminium Thimbles of sizes 185 Sqmm to 300 Sqmm conductor complete all as specified and directed.
S&F Alluminium Thimbles of sizes 400 Sqmm to 600 Sqmm conductor complete all as specified and directed.
Supply only LT tape rolls (Minimum 100 mtr each role) complete all as specified and directed.
S&F in repairs Formula ACB 1250 Amp MDO microprocessor release 50 KA 4 pole rear rotatable terminals LSIG release EK1LSIG MDO type including under voltage release, overload, short circuit, ground fault protection also including in release complete all as specified and directed by Engr-in-Charge. Make ABB Cat Part No FA1 Formula Air VCB or equivalent in Schneider Cat Part No NW Series/Seimens Cat Part No 3WL Series/Legrad cat Part No DMX'3.
S&F cable route indicator showing MES/LT UG cable 1100 volts and route of cable with arrow made of CI in suitable eleptical shape and fixed with MS rod 12mm dia, 70cm long (all words embossed) and embeeed in block of PCC 1:3:6 type C-2 using 40mm graded stone aggregates of size 60cmx30cmx30cm in ground complete all as specified and directed.
R N Enterprises
LAIQ RAM VERMA
JASSI TRADERS
M/S SANGA SINGH AND CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .