Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹78.4 LAccepted-AOC | L1 | Accepted-AOC lowest | |
| 2 | L2₹80.1 L+₹1.7 L (2.18%)Rejected-AOC NAMOPARA PURULIA | PURULIA | PURULIA | WEST BENGAL | 723101 | L2 | Rejected-AOC 2nd lowest | |
| 3 | L3₹80.8 L+₹2.3 L (2.99%)Rejected-Finance KALYANESWARI PASCHIM BARDHAMAN WEST BENGAL | KALYANESWARI | PASCHIM BARDHAMAN | WEST BENGAL | L3 | Rejected-Finance 3rd lowest |
Tender Value
Refer Docs
EMD Value
₹1.7 L
Closing Date
25 Nov 2022, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
The Executive Engineer, PMD,PHE.Dte
Office of the Executive Engineer Purulia Mechanical Division,PHE.Dte Ranchi Road,Purulia.
Supply, Delivery and installation of Centrifugal pumping machineries, MCC Panel with others allied works for Augmentation of Kotshila w/s scheme under PMD, PHE Dte. in the District of Purulia.
2022_PHED_419229_7
15/ EE/PMD/PHED OF 2022-2023
Open Tender
MECHANICAL
Item Rate
60 days
Purulia
Please refer Tender documents.
6 documents required · 6 mandatory
₹1.7 L
Yes
23 Mar 2023
4 Nov 2022
28 Nov 2022
4 Nov 2022
25 Nov 2022
4 Nov 2022
Amount
PART A
Supply, delivery at site multistage Centrifugal Pumping machinery suitable for dry pit installation capable of discharge against total head complete with pump motor set with tyre type coupling and M.S. fabricated channel base etc. as per following specifications: Capacity: 152.8 m3/hr, Head: 78 mtr, Pump casing: CI Pump shaft: SS, Impeller: Bronze Speed: 2901 rpm, Testing: as per IS 9137. (Make:- Kirloskar/CG/ KSB/WPIL) [ MOC, Test certificate, warranty certificate along with characteristics curve to be produced at the time of delivery] (Materials should be supplied after taking approval from department.) (All routine test to be performed in presence of EIC before delivery) Including supply and delivery of channel base frame, Coupling, Tyre coupling guard and with foundation bolts ETC. (for centrifugal pump motor set)
Supply and delivery at site of horizontal foot mounted squirell cage induction motor of suitable rating for driving the pump mentioned above. Power supply: 415V+ 10%, 50Hz + 5%, 3ph, Duty-S1, TEFC, IP55, Class-‘F’ temp rise limited to class ‘B’, connection DOL Motor power should be 15% - 20% over than pump input power at duty point i.e. Motor should be 55KW/73.7HP approximately.) Ambient temp. 50 C Speed: 2901 rpm as sync (Make:- Kirloskar/CG/KSB) (Materials should be supplied after taking approval from department.) (All routine test to be performed in presence of EIC before delivery.)
supply delivery at site & storage following valve, dimension & materials are as per preferred table of ISS. 200 mm dia sluice valve with PN 1.0 suction side as per IS:14846 spindle of IS 6603 gr12 cr12 (All routing test including high pressure test to be performed in presence of EIC before delivery.)
200 mm dia MS dismantling joints PN 1.6 rating with Rubber Compression Ring and adjustable follower flanged complete assembled unit with galvanized stud and nuts.
150 mm dia swing check type NRV with PN 1.6 delivery side IS:5312(PART-1) (All routing test including high pressure test to be performed in presence of EIC before delivery.)
150 mm dia sluice valve with PN 1.6 for delivery site as per IS:14846 spindle of IS 6603 gr12 cr12 (All routing test including high pressure test to be performed in presence of EIC before delivery.)
150 mm dia MS dismantling joints PN 1.6 rating with Rubber Compression Ring and adjustable follower flanged complete assembled unit with galvanized stud and nuts.
Supply, delivery & storage of Burden type pressure gauge, 150mm cast AL dial along with DN15 FI impluse line with valve (0-10kg) Make: Fibag/G L Guru.
200 mm dia sluice valve with PN 1.6 for common header as per IS:14846 spindle of IS 6603 gr12 cr12 (All routing test including high pressure test to be performed in presence of EIC before delivery.)
200 mm dia swing check type NRV with PN 1.6 delivery side IS:5312(PART-1) (All routing test including high pressure test to be performed in presence of EIC before delivery.)
Supply delivery of 200 mm dia. Electromagnetic flow meter shall be Microprocessor based with advance diagnostic capabilities & HART communication protocal with have digital memory, with Transmitter display with Power supply : 100~264 V AC, 50Hz Power supply through cvt, Cable length 10mtr, Cable entry " 1/2" NPTF, Language : English, Temp Limiptation : -20~60°C and satisfactory of following specification as SOQ.
200 mm dia MS dismantling joints PN 1.6 rating with Rubber Compression Ring and adjustable follower flanged complete assembled unit with galvanized stud and nuts.
Supply, delivery & storage at site MS pipe, MS flanges, bends, specials, bolts & nuts, gasket, all mechanical joints at the end of common header etc as required to make the installation complete in all respects up to the satisfaction of EIC. DN-200, E.R.W pipe thickness 7.1mm for suction header for 2nos pump (heavy type). (as per site requirement) (materials should be supplied as per requirement of site, no extra material bill be received by the department.)
DN-150, E.R.W pipe thickness 5mm for delivery header for 2nos pump (heavy type). (as per site requirement) (materials should be supplied as per requirement of site, no extra material bill be received by the department.)
DN-200, E.R.W pipe thickness 7.1mm for common delivery header for 2nos pump (heavy type). (as per site requirement) (materials should be supplied as per requirement of site, no extra material bill be received by the department.)
Supply delivery and storage at site of De-watering pump with all equipments with operational level controller float switch, motor, pipe line and accessories as per requirement. Power rating 1.1KW outlet size 50mm, Discharge capacity-(0.3-8 lits/s), Head-( 16-4 mtr), Supply voltage 220/240V, Single phase, 50Hz.
Supply and delivery at site of 70 sq mm PVC Insulated 3 core 1.1KV, XLPE insulated Ar. Al. conductor cable as per IS : 7098(PART-1_/1554(PART-1) 1988. (Materials should be supplied as per requirement of site, no extra materials will be received by the department.) (Make-Havells/Gloster/Polycab/Finolex) (For centrifugal pump)
Supply and delivery at site of 1.1KV grade 6 sq mm XLPE insulated 3 core aluminium armoured cable as per IS 7098 (PART-1_/1554(PART-1) 1988. (Materials should be supplied as per requirement of site, no extra materials will be received by the department.) (Make-Havells/Gloster/Polycab/Finolex) (For De-watering pump pump)
Providing, HOT crane 2 Ton capacity with 6m lift as per required, as per IS3832 of 6m travel, 6.5m span as per IS807 complete with gantry grider and square rail make (SAIL/TATA), tested to 25% over load carrying. (MOC, Test certificate, warranty certificate along with to be produced at the time of delivery) (Materials should be supplied after taking approval from department.) (All routine test to be performed in presence of EIC befor delivery)
Installation testing and commissioning of HOT crane 1 ton capacity, De-watering pumping machineries and centrifugal pumping machinery Pump motor base foundation , with new suction line, delivery line, common header, pipe support, reducer, enlarger, expansion joint, valve support, earthing materials, cable tray, saddle, ladder etc. as required. Laying of cable, connection with MCC panel as per direction of EIC & IE rules to complete net finishing of the whole installation. Rate is including hire charges of generator, welding set, fuels, lubricants & gland to complete the job as per relevant IS. Double earthing should be provided in all euipments (including MCC Panel and all pump motors.) connected with 400 + 10% volt and single earthing should be provided in rest of all equipments. (Including connection of common header with the rising main by necessary all erection materials, pipe support, reducer, enlarger, expansion joint, valve support. (Any item or accessories not considered in the specification but required to complete the entire installation and operation shall have to be supplied and installed. No extra charge shall be provided for this purpose).
Excavation of soil for installation of Earth Electrode and filling & ramming. For Morrum Soil
Earthing with 50mm dia G.I pipe 3.64mm thick 3.04mtr long and 1 x 4 swg. G.I with (4mtrs long)13mm dia x 80mm long GI bolts, double nuts,double washers including supplying and fixing 15mm dia G.I pipe protection (1mtr long)to be fitted with bitumen and salt partly under the ground level and partly above the ground level driven to an average depth of 3.65mtr below the ground level and restoring the surface duly rammed.As per direction of EIC.double earthing to be done for each pole. By ISI- Medium GI Pipe
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos.12 mm dia holes on the GI pipe
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required
Painting with proper colour code as per IS standard the whole installation by anti corrosive paint after applying suitable primer and necessary surface preparation.
Trial operation, maintenance and guarding of the entire installation of MCC, Centrifugal pumping station, electrical system, chlorination system, dewatering punp, submersible pumps, cable, lighting system as per direction of EIC on 24 hours basis including guarding for the data of commissioning inluding supplying of sundries, lubricants as required as per direction of EIC [ 02 nos. (two) operator in pump house].
Internal lighting (New Pump house, Chlorine room) Supplying and fixing of double door 2+8 way SPN MCB distribution board with IP-42/43 protection, concealed in wall after cuttin the wall and mending good the damages to original finish incl. inter connection with suitable size of copper wire and neutral line & provisional of earth attachment.
Supplying and fixing 240/415 V, MCB of Breaking capacity 10kA & characteristics on din rail of existing DBs and necessary connection. (Legrand/ABB/Hevells) a. 6A SP MCB (o/g)
b. 16A DP MCB (Two room)
c. 32 DP MCB (DB i/c)
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in suitable size PVC casing-capping (Precision make) with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, incl. necy. fittings etc. to light/fan/call bell point with Modular type switch (Brand approved by EIC) fixed on Modular GI / PVC switch board with top cover plate on wall incl. mending good damages to original finish. [PVC casingcapping and Switch board both on surface] a. Average run 8 mtr
b. Indicator Modular type
Supplying and fixing of 16A Modular type 6 pin plug socket
Supplying and fixing of 16A Modular type switch (yard lighting/16A plug socket)
supply delivery and fitting fixing of LED battan 20W tube light on wall as per direction of EIC.
Supply and fixing 240 V 300mm Exhaust fan (Heavy duty) with luver shatter after cutting hole on wall with mending good damages and complete connection as per direction of EIC. (Mame:CG/Havells)
Supply and delivery and fitting fixing of the following items 01 nos. of pump house celling fan250 V48" SWAP including necessary distribution wiring from existing prit in 1.1 KV grade 3x1.5sqmm (for phase neutral and earth connection for individual point )with single core stander FR PVC insulated and unsheathed copper wire for suitable size PVC casing -capping(Precision make),incl. necy. PVC clips, fittings etc. to fan with piano key type switch ( anchor make ) fixed on sheet steel fabricated switch board with 3 nos. "ph. , N" copper bar for wire connection with Perspex /Bakelite top on wall incl. necy. connection and making earthing attachment and mending good damages to building works for each point. with necessary colour code as per IS standard of cable for wiring ). (PVC casing capping and switch board both on surface). Made: Crompton/Havells
Supply fitting fixing LED street light luminaries(model BRP 409 74watt LED,make-philips)fitting complete with all fixing items and pole, clamp etc. as per direction of EIC.
PART B
Supply & delivery at site alone front and rear lockable hinged door access type MCC panel with made of 2mm thick CRCA sheet steel enclosed indoor floor mounted, dust & vermin proof, equivalent IP-54 degree of protection, powder coated pointed with soft rubber gaskets, Electrolytic grade thinned copper Bus bar(1A/mm will be max.), cubical type with front & rear lockable hinged door MCC with TPN electrolytic grade L.T. panel on FRP insulators, detachable gland plate at bottom & suitable for installation on cable trenches complete with Copper bus bar of suitable size with all switchgear and others item ( As per SOQ) duly wire up with necessary earthing protection and completed the job as per direction of EIC. Details as per SOQ attached with the NIET
Installation and commissioning of above mentioned MCC panel by making required size masonary cable trench width 1.15 mtr and length as per MCC depth 0.75 mtr and necessary foundation complete brick work, plaster, punning, with supplying required no. compression gland, socket, cable lug, STEEL CHEQUERED PLATE-5mm thick. MCC load should bear by C channel 50mm x 100mm x50mm on cable trench, length of C channel as per MCC as cross member length minimum 1.15mtr as required nos, 50 x50 equal angle for CHEQUERED PLATE support. Double earthing provide by 50mm x 6mm GI stripe for earthing connection etc. by expert electrician and electrical supervisor to complete the job upto satisfaction of EIC. Including all electrical connections to MCC panel with all pumps and from transformer LT line. (MCC panel foundation should be make after taking foundation drawing approval from department,)
Add GST @ 18%
Add CESS @ 1%
COMBINE ENTERPRISES
SUNRISE ENGINEERING CORPORATION
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .