Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.2 LAccepted-AOC B 106 1ST FLOOR GAUTAM BUDDHA NAGAR NOIDA DELHI DELHI 201301 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | ₹19.2 L | L1 | Accepted-AOC L1 |
| 2 | L2₹25.6 L+₹6.4 L (33.3%)Rejected-Finance BUILDING NO FLAT NO A 80 DDA SHED OKHLA INDUSTRIAL ESTATE PHASE 2 NEW DELHI OKHLA INDUSTRIAL ESTATE PHASE 2 NEW DELHI DELHI 110020 | SOUTH EAST DELHI | DELHI | 110020 | ₹25.6 L+₹6.4 L (33.3%) | L2 | Rejected-Finance L2 |
| 3 | L3₹25.8 L+₹6.6 L (34.5%)Rejected-Finance 1001 SHIVALIK ABAISE 100 FEET ROAD OPP ANANDNAGAR APARTMENT PRAHALADNAGAR AHMEDABAD AHMEDABAD GUJARAT 380015 | AHMADABAD | GUJARAT | 380015 | ₹25.8 L+₹6.6 L (34.5%) | L3 | Rejected-Finance L3 |
| 4 | L4₹25.8 L+₹6.7 L (34.8%)Rejected-Finance RAR 107A GROUND FLOOR RAJENDRA ARIHANT TOWER B 1 COMMUNITY CENTRE JANAKPURI NEW DELHI 110058 | NEW DELHI | WEST DELHI | DELHI | 110058 | ₹25.8 L+₹6.7 L (34.8%) | L4 | Rejected-Finance L4 |
| 5 | L5₹27.1 L+₹8.0 L (41.5%)Rejected-Finance Y 51 GROUND FLOOR OKHLA INDUSTRIAL AREA PHASE 2 OKHLA NEW DELHI DELHI 110020 | SOUTH EAST DELHI | DELHI | 110020 | ₹27.1 L+₹8.0 L (41.5%) | L5 | Rejected-Finance L5 |
| Sl No | Description | Qty | Unit | Nexus Fire And Security Systems L4 | DOSHI ELECTRIC ENGG. CO. L6 | CENTRE TAP ENGINEERING L3 | advent electric technologies pvt. ltd. L5 | DSS Electric Corporation LLP L1 | Nexpo Power Solutions Private Limited L2 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00Design, Installation, Testing & Commissioning of Aerosol-based fire suppression system for protection of critical areas that shall be electrically actuated including supply of UL/EN approved aerosol generators. The housing shall be constructed of stainless steel shell and sealed with non-permiable membrane. The units shall have passed salt spray corrosion testing as per NFPA/UL/EN/KIWA/UL2775 as part of their listing. The aerosol generator shall be potassium-based, non-toxic and providing effective fire suppression while being environmental friendly with zero Ozone Depletion Potential and Zero Global Warming potential, CFC & HFC-Free. Agent shall be listed by the US EPA under the SNAP program, that shall be non- toxic and marked with the green label. Aerosol generators shall be listed by Underwriter's Laboratory (UL)/EN subject to UL-2775 covering Fixed Condensed Aerosol System as per NFPA 2010. The room flooding must be designed as per UL/EN density of Aerosol less than 110 g/cu. mtr. for Class A, B & C fires as per NFPA 2010. The aerosol generator should have self life of atleast 15 years. The system shall comply with relevant standards including NBC 2016, NFPA 2010, complete with all necessary accessories and works required for satisfactory operation. Note : Number of Aerosol uni, design software for a given dimension of room duly approved by manufacturer (OEM) shall be submitted prior to starting of the works. Fire Suppression System for following rooms and given approximate volume.The gas Supression should be integrated with the Exsisting Conventioanl Type Fire detection and Alarm system of Ravel make with Fire Alarm panel of Model RE-102. | |||||||||
| 1.10 | DVOR- EQUIPMENT ROOM (Approx Room volume 81 cum.) | 1 | Job | 3,08,357 ₹3,08,357 | 4,73,630 ₹4,73,630 | 3,50,000 ₹3,50,000 | 4,02,781.2 ₹4,02,781.2 | 1,71,000 ₹1,71,000 Lowest | 2,60,700 ₹2,60,700 |
| 1.20 | DVOR- UPS ROOM (Approx Room Volume 20 cum.) | 1 | Job | 1,27,127 ₹1,27,127 | 1,04,600 ₹1,04,600 | 1,50,000 ₹1,50,000 | 1,86,145 ₹1,86,145 | 75,000 ₹75,000 Lowest | 1,32,750 ₹1,32,750 |
| 1.30 | DVOR- ELECTRICAL ROOM (Approx Room Volume 20 cum.) | 1 | Job | 1,27,127 ₹1,27,127 | 1,04,600 ₹1,04,600 | 1,50,000 ₹1,50,000 | 1,86,145 ₹1,86,145 | 75,000 ₹75,000 Lowest | 1,32,750 ₹1,32,750 |
| 1.40 | DVOR- WORK AREA (Approx Room Volume 56 cum.) | 1 | Job | 2,24,308 ₹2,24,308 | 2,92,880 ₹2,92,880 | 2,50,000 ₹2,50,000 | 2,97,643.2 ₹2,97,643.2 | 1,12,750 ₹1,12,750 Lowest | 2,84,850 ₹2,84,850 |
| 1.50 | LOCALIZER- EQUIPMENT ROOM (Approx Room Volume 70 cum.) | 1 | Job | 4,04,223 ₹4,04,223 | 3,66,100 ₹3,66,100 | 3,50,000 ₹3,50,000 | 3,61,634.6 ₹3,61,634.6 | 1,71,000 ₹1,71,000 Lowest | 3,64,800 ₹3,64,800 |
| 1.60 | LOCALIZER- ELECTRICAL CUM UPS ROOM (Approx Room Volume 65 cum.) | 1 | Job | 3,33,308 ₹3,33,308 | 3,39,950 ₹3,39,950 | 3,50,000 ₹3,50,000 | 3,61,634.6 ₹3,61,634.6 | 1,71,000 ₹1,71,000 Lowest | 3,45,600 ₹3,45,600 |
| 1.70 | GLIDE PATH- EQUIPMENT ROOM (Approx Room Volume 70 cum.) | 1 | Job | 3,72,705 ₹3,72,705 | 3,66,100 ₹3,66,100 | 3,50,000 ₹3,50,000 | 3,61,634.6 ₹3,61,634.6 | 1,71,000 ₹1,71,000 Lowest | 3,64,800 ₹3,64,800 |
| 1.80 | GLIDE PATH- ELECTRICAL CUM UPS ROOM (Approx Room Volume 65 cum.) | 1 | Job | 3,33,308 ₹3,33,308 | 3,39,950 ₹3,39,950 | 3,50,000 ₹3,50,000 | 3,61,634.6 ₹3,61,634.6 | 1,71,000 ₹1,71,000 Lowest | 3,45,600 ₹3,45,600 |
| 2.00 | Supply, installation testing & commissioning of Conventional agent release control panel with battery back up for 30 minutes in alarm condition having UL/EN/CE Certified approval. Panel shall be of 02 zones with necessary manual release switch, zone indication, fault indication, alarm display. Quoted rate shall include necessary battery & interconnections. | 8 | Nos | 36,705 ₹2,93,640 | 80,000 ₹6,40,000 | 30,000 ₹2,40,000 | 24,000 ₹1,92,000 Lowest | 95,000 ₹7,60,000 | 35,000 ₹2,80,000 |
Tender Value
₹38.3 L
EMD Value
₹1.1 L
Closing Date
13 Jul 2026, 6:00 pmClosed
Asst. General Manager (Engg-Electrical)
Airports Authority of India, Rajahmundry Airport, Madhurapudi Post, Rajahmundry-533102
SITC of Fire Suppression for DVOR, ILS and Unmanned CNS Installations at Rajahmundry Airport
2026_AAI_281783_1
AAI/RJY/ENGG(E)/NIT-04/2026-27
Open Tender
Electrical Works
Item Rate
90 days
Airports Authority of India, Rajahmundry Airport.
Please refer Tender Document
18 documents required · 18 mandatory
₹1,180
₹1.1 L
1 Sept 2026
23 Jun 2026
15 Jul 2026
23 Jun 2026
13 Jul 2026
23 Jun 2026
23 Jun 2026 - 2 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Design, Installation, Testing & Commissioning of Aerosol-based fire suppression system for protection of critical areas that shall be electrically actuated including supply of UL/EN approved aerosol generators. The housing shall be constructed of stainless steel shell and sealed with non-permiable membrane. The units shall have passed salt spray corrosion testing as per NFPA/UL/EN/KIWA/UL2775 as part of their listing. The aerosol generator shall be potassium-based, non-toxic and providing effective fire suppression while being environmental friendly with zero Ozone Depletion Potential and Zero Global Warming potential, CFC & HFC-Free. Agent shall be listed by the US EPA under the SNAP program, that shall be non- toxic and marked with the green label. Aerosol generators shall be listed by Underwriter's Laboratory (UL)/EN subject to UL-2775 covering Fixed Condensed Aerosol System as per NFPA 2010. The room flooding must be designed as per UL/EN density of Aerosol less than 110 g/cu. mtr. for Class A, B & C fires as per NFPA 2010. The aerosol generator should have self life of atleast 15 years. The system shall comply with relevant standards including NBC 2016, NFPA 2010, complete with all necessary accessories and works required for satisfactory operation. Note : Number of Aerosol uni, design software for a given dimension of room duly approved by manufacturer (OEM) shall be submitted prior to starting of the works. Fire Suppression System for following rooms and given approximate volume.The gas Supression should be integrated with the Exsisting Conventioanl Type Fire detection and Alarm system of Ravel make with Fire Alarm panel of Model RE-102. | |||||
| 0.0 | DVOR- EQUIPMENT ROOM (Approx Room volume 81 cum.) | 1 | Job | - | - |
| 0.9 | DVOR- UPS ROOM (Approx Room Volume 20 cum.) | 1 | Job | - | - |
| 0.0 | DVOR- ELECTRICAL ROOM (Approx Room Volume 20 cum.) | 1 | Job | - | - |
| 0.9 | DVOR- WORK AREA (Approx Room Volume 56 cum.) | 1 | Job | - | - |
| 0.0 | LOCALIZER- EQUIPMENT ROOM (Approx Room Volume 70 cum.) | 1 | Job | - | - |
| 0.0 | LOCALIZER- ELECTRICAL CUM UPS ROOM (Approx Room Volume 65 cum.) | 1 | Job | - | - |
| 0.0 | GLIDE PATH- EQUIPMENT ROOM (Approx Room Volume 70 cum.) | 1 | Job | - | - |
| 0.0 | GLIDE PATH- ELECTRICAL CUM UPS ROOM (Approx Room Volume 65 cum.) | 1 | Job | - | - |
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.08 MB
TenderDocument281783.pdf
Tender Documents • 10.78 MB
BOQ_328819.xls
BOQ • 0.27 MB
CORRIGENDUM1.pdf
PDF • 0.59 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .