Superintending Engineer
ETC, Patharhiya Road, Mirzapur
Carriage of 132/33 KV, 20 MVA transformer (PME) make from 132 KV S/S Sarai Akil to 132 KV S/S Bhadohi and its installation at 132 KV S/S Bhadohi under ETD-IV, Varanasi.
2020_UPTCL_463979_1
05/2020-21/ETC/Mzp
Open Tender
Electrical Works
Fixed-rate
90 days
Bhadohi
As per tender specifcation
2 documents required · 2 mandatory
₹1,180
Executive Engineer, ETD
₹7,000
4 Jul 2020
30 Apr 2020
16 Jun 2020
30 Apr 2020
15 Jun 2020
30 Apr 2020
Amount
Following work is to be carried out at 132 KV S/S Bhadohi
Shifting/dragging of oil filled dismantled 20 MVA T/F from its location up to 20 meter distance including turning of tank if required, including all T&P and work required to complete the job satisfactorily at 132 KV S/S Sarai Akil
Additional shifting of 25 meter @ 5 meter/job at 132 KV S/S Sarai Akil, if required
Loading of 20 MVA transformer main tank, conservator tank, radiators, HV/LV side bushing and its other parts and accessories along with oil drums on the truck/trailer safety to avoid any type of damage at 132 KV S/S Sarai Akil
Packing of HV/LV/N bushing of transformer for safe carriage
Transportation of the transformer safely from 132 KV S/S, Sarai Akil to 132 KV S/S Bhadohi (distance approx 175 Km a side). Required insurance of the transformer during transit shall be done by the contractor on his own expenditure.
Unloading main tank, conservator tank, radiators, HV/LV/N bushing and its other parts and accessories of 20 MVA transformer from trailer along with T/F oil drum from the truck/Trailer safely to avoid any damage at 132 KV S/S Bhadohi
Shifting/dragging of oil filled 20 MVA, 132/33 KV T/F from its location to plinth up to 20 meter distance including turning of tank, if required, including all T&P and work required to complete the job satisfactorily at 132 KV S/S Bhadohi
Additional shifting of 10 meter@ meter/job at 132 KV S/S Bhadohi
Complete erection of gasket of 20 MVA T/F by erection of radiators, conservator tank, bushing with turrets (if available), connecting all pipe lines, erection of Buchholz relay for completing the work, erection of cooling fans, laying of cables and termination by making control cable connections of the fan, WTI, OTI and Buchholz relay OLTC to marshalling box etc with proper ferruling as per drawing, radiator, conservator tank and all other accessories work for completion of job, electrical connections of 20 MVA T/F
Centrifuging of complete 20 MVA T/F oil in T/F and Tank by connecting centrifuging pipes circulating the T/F oil through centrifuging machine to be provided by the contractor & taking the BDV & IR value of the oil periodically till the required value is achieved
Opening of cable termination from RTCC, Marshaling box, DP Panel of dismantled 20 MVA T/F & connecting the cable in erected 20 MVA to RTCC marshaling box, DM panel after re-ferruling and redressing
Laying & termination of new cable for 20 MVA T/F and OLTC panel to the control and relay panel, if required, as per site condition having sizes as gien below-
ii) 4x2.5 mm2
iii) 6x2.5 mm2
Connection to the existing earthing of erected 20 MVA T/F and OLTC, RTCC at two points using 75x10mm MS flat
Jumpering of the T/F from 132 KV HV side with single ACSR Panther conductor from 132 KV, 20 MVAT/F bay and 33 KV LV side with single ACSR Moose conductor from LV side of the T/F to 36 KV CT through 33 KV 10KA LA
Changing of CT ratio of all three 36 KV CTs of CTR 800-400/1-1A from 400A to 800A in primary side of CT’s
Installation of RTCC Panel at control room of sub-station and its electrical connection
Earthing of 20 MVA T/F Neutral bushing with using 75x10 mm MS flat run old laders its grouting, painting and making then connection delta with two points and other associated work (earthing electrode rod shall be provided by department free of cost) the above also includes painting of earthing strips with one coat of red oxide primer and two coat of bus green synthetic enamel paint
Complete earthing of erected 20 MVA T/F as per standard practice using 75x10 mm MS flat, main tank of the T/F, marshalling box, drive mechanism of cooling fan it shall be earthed as per standard practice (MS flat shall be provided by contractor)
TECNO SYNDICATE
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .