Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹49.7 L
EMD Value
₹99,420
Closing Date
7 Apr 2025, 6:00 pmClosed
GE (I) DM, Visakhapatnam
GE (I) DM, Visakhapatnam
OVERHAULING MAINTENANCE AND OTHER ALLIED WORKS OF HT VCBS AT OLD DOCKYARD AREA SUBSTATIONS AT NAVAL DOCKYARD VISAKHAPATNAM UNDER GE (I) (DM) VISAKHAPATNAM
2025_MES_700839_1
8264/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Naval Dockyard Visakhapatnam
As per tender documents
8 documents required · 8 mandatory
₹500
GE (I) DM, Visakhapatnam
₹99,420
Yes
19 Apr 2025
10 Mar 2025
9 Apr 2025
10 Mar 2025
7 Apr 2025
24 Mar 2025
Amount
Attending day to day complaints and call on repair for 24 Hrs of HT Switchgear Vacuum Circuit breaker of capacity 630A to 1250A with one Engineer , one electrician and one helper for all days including Holidays & Sundays for opening of covers, checking for any uncertainty and refixing the same to original position, re-connection of all existing cables, extended bus bars, after rectification & testing , closing the complaint by re-energising the feeder complete all as specified and as directed. Note: Replacement of defective parts shall be measured and paid separately.
Taking down HT Switch gear vaccum circuit breaker of capacity 630 Amps to 1250 Amps, 11 KV for carrying out following repairs, overhaluing, servicing, preventive maintenance and reflixing the same after carrying out repairs / overhauling complete all as specified and as directed. (a) Tripping off the breaker, rackout the breaker complete from the panel along with trolly for servicing / inspection/ overhauling. (b) Servicing / inspecting/ checking automatic safety shutter operation for service ability and replacement of spares if required. (c ) Servicing /inspecting / checking of busbar spout and circuit spout connections for RYB Phases and replacement of spares if required. (d) checking of breaker main mechanism assembly, fixed contacts and cuurrent carrying parts of the breaker, trolley, insulated asembly etc. (e) setting, reassembling, cleaning adjustment of fixed contacts main contact, acring contact and moving contact for proper setting of auxiliary contacts operatingg mechanism.
(f) Servicing / inspecting / checking of secondary socketd / busbar earthing plugs / earthing sockets and replacement of spares if required. (g) checking, setting and adjustment of rackin and rackout operation of the breakedr trolley. (h) Decarbonising of busbar and connected items. (j) Lubrication and greasing of all moving parts of the trolley, stopper bolt for proper operating. Note: (a) The rate quoted shall be deemed to be include for necessary T & P, Nuts, bolts, washers, gasket, insulation tape, HT Sleeve, monoplast compound to put in to the VCBs and paneles in serviceable condition, testing and commissioning (b) Replacement of defective parts of the VCB Shall be measured and paid separately.
Maintenance, servicing, cleaning of vacuum circuit breaker unit of 11 KV VCB panel of capacity 630 Amps to 1250 Amps, taking out from panel, cleaning of all parts with CTC and clean cloth, removal of carbon deposited inside the moving contacts, greasing of all moving parts of the VCB, checking of complete operating mechanism for proper functioning, reporting for any defective parts, complete all as specified and as directed. Note: Replacement of defective parts of the VCB shall be measured and paid separately.
Supply and fix including dismantling taking out unserviceable Buffer (For Opening Spring ) For 630 Amps to 1250 Amps Schneider make 11 KV VCB. All as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix including dismantling taking out unserviceable Buffer (For Closing Spring ) For 630 Amps to 1250 Amps Schneider make 11 KV VCB all as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABBt
Supply and fix single (Read-Blue) phase busbar spout suitable for 630 Amps to 1250 Amps VCB make complete all as specified and as directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix single (Y) phase busbar spout for 630 Amps to 1250 Amps VCB complete all as specified and as directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix CT Spout suitable for VCB 630 Amps to 1250 Amps complete all as specified and as directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply & fixing closing coil assembly 110 V DC to Schneider make 11KV VCB incl necessary connection testing complete including dismantling taking down unsv one complete all as specified and as directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fixing tripping coil 110 V DC to Schneider make 11KV VCB including necessary connection testing complete incl dismantling taking down unsv one complete all as specified and as directed.. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix including dismantling taking out unserviceable Service /Test Position Limit Switch 1NO+1NC For 630 Amps to 1250 Amps Schneider make 11 KV VCB complete all as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix including dismantling taking out unserviceable Breaker Wheel - CAST IRON, For 630 Amps to 1250 Amps Schneider make 11 KV VCB all as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix including dismantling taking out unserviceable spring charging Universal motor with gear box 220V AC For 630 Amps to 1250 Amps Schneider make 11 KV VCB all as spcified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix including dismantling taking out unserviceable vacuum interrupter of suitable for VCB of capacity 630 Amps to 1250 Amps all as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix including dismantling taking out unserviceable busbar supporting insulator for 630 Amps to 1250 Amps Schneider make 11 KV VCB all as specified and directed. Make :- Schneider or equivalent
Supply and fix including dismantling taking out unserviceable Rectifier unit (Monoblock) for spring charging motor For 630 Amps to 1250 Amps Schneider make 11 KV VCB all as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix Drive Beam suitable for 11 KV VCB 630 Amps to 1250 Amps all as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix including dismantling taking out unserviceable Isolating Contact for 630 Amps to 1250 Amps Schneider make 11 KV VCB complete all as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix Epoxy Body suitable for 11 KV VCB 630 Amps to 1250 Amps 2 complete all as specified and as directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix Shutter assembly for busbar / circuit spout suitable for 11 KV VCB 630 Amps to 1250 Amps all as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix space heater, 230V, 100 watt inside cable chamber including necessary connection, testing complete all as specified and as directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix including dismantling taking out unserviceable thermostat for space heater For 630 Amps to 1250 Amps Schneider make 11 KV VCB all as specified and directed. Make : - Schneider/Areva/L&T/Siemens/ ABB
Supply and fix including dismantling taking out unserviceable resin cast CT dual core of ratio 100-50/5A-5A/15VA core 1 metering, core 2 protection of breaking capacity 31.5KA with dimension 220x110x230 mm and hole to hole 110 mm for 800 to 1250 A Schneider make 11 KV VCB all as specified and directed. Make : Kappa/Esun/ Pragati/AE/ SCHENIDER/Plastofab Note : Contractor should visit the site for brackets size to mounting the CTs in 11 KV VCBs.
All as per item No 22.00 above, but 400-200/5A-5A/15VA 5P10
All as per item No 22.00 above, but 600-300/5A-5A/15VA 5P10
M&L for THERMOGRAPHIC TESTING of 11kV switch Boards with IMAGE INFRARED CAMERA to detect Hot spots, to avoid electrical failures and increase safety for all current-carrying devices. Visual and Mechanical Inspection to be done when load is applied to the system. Use & follow appropriate caution, safety devices, and personal protective equipment. Provide a report which includes the following: 1. Description of equipment tested. 2. Discrepancies if any.(HOT Spots). 3. Identify load conditions at time of inspection. 4. Provide photographs and/or thermo grams.
M&L for painting of outer surface of multiple section of complete VCB panel 11 KV size upto 2m x 1.8 x 0.8 in one substation using one coat of synthetic zinc paint after preparation of surface, providing protection cover to all metering equipment, panel meters, switchgears, cleaning of all meters and switch gears all as specified and directed.
Decarburizing/Buffering of copper Busbar complete from 11kV HT Bus bar chamber of each VCB panel including connecting Busbar from CT to main Busbar & spout. Servicing of support insulator by clean cloth and hot air blower/ vacuum cleaner, applying Backtol Red solution to the bus bar insulator , checking for any loose contact, refixing of all nuts & bolts by Stainless steel , refixing all covers ,replacement of defective parts, busbar sleeve and ensure proper decarburizing up to proper megger value , checking all the connections all as specified and directed.
Supply and fixing of complete PT set, including dismantling taking out complete unserviceable drawout type PT trolly set , PT of 100 VA, dual core of ratio 11KV/root3/110V/root3/100VA , Insulation class F, core 1 metering, core 2 protection. Make : Kappa/Esun/ Pragati/AE/SCHENIDER/Plastofab/AudioVision or approved by engineer-in-charge complete all as specified and as directed. Make : Kappa/Esun/ Pragati/AE/SCHENIDER/ Plastofab c Note : Contractor should visit the site for brackets size to mounting the PTs in 11 KV VCBs.
Supply and fix including dismantling taking out unserviceable HRC Fuse-Pt HT Side (VTF-11, 3A) For 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. Make-Schneider/AudioVision/ANNAND/ UNITY/BUSSMANN
M&L for maintenence/servicing of PT unit 11Kv / 110V by disconneting and taking out from panel mounted position, checking & cleaning of fixed and moving contact points, cleaning/ decarbonising of busbar connections, resin cast PTs using hot blower, CTC solution to the epoxy PT body, tightening of all nuts, bolts, washers, and refixing the same PT to original position, testing complete all as specified and directed.
Supply and fix PT Spout suitable for VCB Panel 800 to 2500 Amps , along with connected busbars/cables complete all as specified and as directed. Make : Kappa/Esun/ Pragati/AE/ SCHENIDER/ Plastofab
Supply and applying Si-COAT 570 RTV Silicone High Voltage Insulator Coating solution using an Sprayer to the 11KV Indoor VCB panel Cable chamber (4.5 Kg coating materials per panel) , testing complete all as specified and directed. Make:- CSL Silicones Inc. Canada
Supply and applying Si-COAT 570 RTV Silicone High Voltage Insulator Coating solution using an Sprayer to the 11KV Indoor VCB panel Bus bar chamber (4 Kg coating materials per panel) , testing complete all as specified and directed. Make:- CSL Silicones Inc. Canada Note for item Nos. 33.00 & 34.00 :- (i) Surface preparation: All insulation surfaces of the equipment to be coated shall be made free from dust, grease, oil and any other foreign material without damaging the surface. The surface of the equipment shall be made dry before application of the RTV coating. (ii) All the required materials, tools & tackles, testing equipment, consumables etc. for application of HVIC coating shall be in bidders’ scope
SIRI CONSTRUCTION (BID ID -3273745)
SREE LALITHA ENGINEERING ENTERPRISES (BID ID -3276913)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .