SR EXECUTIVE ENGINEER
CIVIL MAINTENANCE DIVSION HPSEBL THALOUT
Supply installation testing and commissioning of Automatic water level sensor non-contact transmission Radar Ultrasonic at Barrage site of 3x42 MW Larji HEP
2026_HPSEB_134127_1
HPSEBL/LPH/CMD/DB-8/2026--011
Open Tender
Civil Works - Others
30 days
THALOUT
PLEASE REFER TENDER DOCUMENT
2 documents required · 2 mandatory
₹590
₹4,484
25 Apr 2026
11 Apr 2026
16 Apr 2026
11 Apr 2026
16 Apr 2026
11 Apr 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing & commissioning of Automatic water level sensor non-contact transmission (Radar/Ultrasonic) at Barrage site of 3x42 MW Larji HEP including armoured shielded instrumentation cable 1 sqmm, 100m length, display units, installation of canopy, protection panel etc. at site for safe installtion etc as required complete in all respect and direction of EIC. The Specifications as detailed below: Automatic Water Level Recorder should be capable of measurements over turbulent mountain streams using non-contact transmission (radar/RF type)
Measuring height range: 0 to 30 m (Sensor must be capable of measuring up to 50m)
Process Fitting & Beam Angle: Thread G2, Flange from DN 80; Beam Angle 5° or
better upto 16° at higher end.
Response Time: ≤1S
Frequency:24 GHz or better
Operating temperature: -40°C~70°C; Operating Humidity: 0 to 100 %
Process Pressure: -1 Bar~3 Bar
Resolution: 1mm
Accuracy: ±3 mm or better | - | Nos | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.36 MB
BOQ_198349.xls
BOQ • 0.22 MB
TENDERDOC011.pdf
Tender Documents • 0.78 MB
Download all tender documents and submit your bid